SERIES DPT-R8-3W
AEROSENSE DIFFERENTIAL PRESSURE TRANSMITTER
                                                                                                  DPT
                                                                                         Aerosense
                                                                                          LOW PRESSURE DEVICES
                                     Image for DPT-R8-3W-D
               Zero-point adjustment                                                                             Technical data
                   Note! Supply voltage must be connected one hour before the                                    Service: Air and non-aggressive gases
                   0-point adjustment is carried out.                                                            Measuring element: Piezoresistive
                                                                                                                 Accuracy: 0.8%, or (1% <250 Pa)
                   1) Loose both tubes from the pressure inlets + and 
                                                                                                                 Measuring unit: Selectable by jumper (Pa, kPa, mbar,
                   2) Push zero button until the red led turns ON.                                               inchWC, mmWC, psi)
                   3) Wait until LED turns off and then install tubes again to the                               Response Time: 0.8 / 4 s selectable by jumper
                     pressure inlets.                                                                            Max pressure: 400 kPa
                     It is recommended to adjust the zero point every 12 months                                  Electrical interface:
                     during normal operation.                                                                     Supply voltage: 24 VAC or VDC  10%
                                                                                                                  Power consumption: <1.0 W (<1.5W with Iout 20mA)
                   * If the transmitter is equipped with automatic zero element the
                                                                                                                 Output signal:
                     manual push button adjustment is not required.                                              010 VDC, Load R minimum 1kor
                                                                                                                 420 mA, maximum load 500
                   Optional auto zero element                                                                    Materials:
                   AZ-calibration is a function in the form of an automatic zeroing circuit built into            Housing: ABS
                                                                                                                  Cover: PC
                   the PCB. The AZ-calibration electronically adjusts the transmitter zero at
                                                                                                                  Pressure connections: ABS
                   predetermined time intervals (every 10 minutes). The AZ-calibration
                   eliminates all output signal drift due to thermal, electronic or mechanical                   Connections:
                   effects, as well as the need for technicians to remove high and low pressure                   Electrical connections: 4 screw terminals, max 1.5 mm2
                   tubes when performing initial or periodic transmitter zero point calibration.                  Cable entry: M16
                                                                                                                  Pressure connections: Male 5,0 mm and 6,3 mm
                   The AZ adjustment takes 4 seconds. To avoid conict with the BAS system,                      Weight: 150 g
                   the output and display values will freeze to the latest measured value, after                 Dimensions: 90,0 x 71,5 x 36,0 mm
                   which the device returns to its normal measuring mode. Transmitters                           General ambient condition:
                   equipped with the AZ-calibration are virtually maintenance free.                               Temperature range:
                                                                                                                 - Operation -10+50C (-5+50C for  AZ model)
                                                                                                                 - Storage: -20+70C
                    Model                       Model                        Model
                                                                                                                 - Ambient humidity: 0 to 95% RH
                    DPT250-R8-3W                DPT2500-R8-3W                DPT7000-R8-3W
                    0-25 Pa                     100-0-100 Pa                0-1000 Pa                            Safety:
Measuring Ranges
                    0-50 Pa                     0-100 Pa                    0-1500 Pa                             Protection standard: IP54
                                                                                                                  Conformance: Meets the requirements for CE marking:
                    0-100 Pa                    0-250 Pa                    0-2000 Pa
                                                                                                                 - EMC directive 2004/108/EY
                    0-250 Pa                    0-500 Pa                    0-2500 Pa                            - Rohs Directive 2002/95/EY
                    25-0-25Pa                   0-1000 Pa                   0-3000 Pa
                                                                                                                 Optional Accessories:
                    50-0-50 Pa                  0-1500 Pa                   0-4000 Pa
                                                                                                                  Plastic Pressure Tips
                    100-0-100 Pa                0-2000 Pa                   0-5000 Pa
                                                                                                                  2m Tubes
                    150-0-150 Pa                0-2500 Pa                   0-7000 Pa
                   Add - D to end of Model with Display For e.g. DPT250-R8-3W-D
                   Add - AZ to end of Models with Auto-Zero facility For e.g. DPT250-R8-3W-AZ
                   Add - AZ - D to end of Models with Display and Auto-Zero facility For e.g. DPT250-R8-3W-AZ-D
Installation                    ZEROING: Press the bu on
                                                  LED: Turns ON
                                                  Zeroing
                                                                         Model DPT2500
                                                                                    100Pa     100Pa    250Pa    500Pa
                                                                         Jumper 1
                                                                         Jumper 2
                                                                         Jumper 3
                                                                                    1000Pa      1500Pa 2000Pa    2500Pa
                                                                         Jumper 1
                                                                         Jumper 2
                                                                         Jumper 3
                                                                         Model DPT7000
         Jumper 1                                                                   1000Pa     1500Pa   2000Pa   2500Pa
         Jumper 2                                                        Jumper 1
         Jumper 3                                                        Jumper 2
                                                                         Jumper 3
         Jumper 4
         Jumper 5                                                                   3000Pa     4000Pa   5000Pa 7000Pa
         Jumper 6                                                        Jumper 1
                                                                         Jumper 2
                                                                         Jumper 3
                                                                            0.8 s            4.0 s
Electrical Connection:                                        Jumper 4                                    Set response time
                                                                                        Select unit        Note: Measuring unit
0-10V    Output 010 V                                        Jumper 5                                     can be change
4-20mA   Output 420 mA                                                                                    pressing bu on when
24V      Supply 24 VAC or VDC                                 Jumper 6     Not in use                      Jumper 5 is placed.
GND      Ground                                                                                            Please remove
                                                                                                           jumper a er se ng.