SPECIFICATION NO.
TI/SPC/PSI/CT/0515(05/2015)                Page 1 of 27
         TRACTION INSTALLATION DIRECTORATE
                    GOVERNMENT OF INDIA
                    MINISTRY OF RAILWAYS
                  TECHNICAL SPECIFICATION
                                 FOR
                  CURRENT TRANSFORMERS
                    i. 220 kV, 200 - 100/5A
                    ii. 132 kV, 400 - 200/5A
                    iii. 110 kV, 400 - 200/5A
                    iv. 66 kV, 800  400/5A
                              for
       RAILWAY AC TRACTION SUBSTATIONS
                        (MAY 2015)
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)
                               ISSUED BY
                Traction Installation Directorate
 R e s e ar c h De s i g n s & S t a n d ar d s O r g a n i s a t i on ,
                         M a n a k N ag ar ,
                       Lu c kn o w - 2 260 1 1 .
    SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)        Page 2 of 27
SPECI FICATION : T E C H N I C A L S P E C I F I C A T I O N F O R
   CURRENT TRANSFORMER FOR RAILWAY AC
           TRACTION SUBSTATIONS.
 SPECIFICATION No. TI/SPC/PSI/CT/0515(05/2015)
  Amendment     Amendment /Revision           Total pages      Date of
   Number                                 including drawings    Issue
                      Prepared By       Checked By     Approved By
  Signature
  Date
  Dsignation           SSE(TR)           DDTI(PSI)       DTI(PSI)
   SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)      Page 3 of 27
                               INDEX
  ITEM                         HEADING                     PAGE
  NO
  1.0     Scope                                               4
  2.0     Governing Specification                             4
  3.0     Service Conditions                                  5
  4.0     Traction Power Supply System                        5
  5.0     Rating and other Particulars                        6
  6.0     Type & General Construction                         8
  7.0     Bushing and Terminal Arrangement                    9
  8.0     Parts Fittings and Accessories                     10
  9.0     Painting                                           10
  10.0    Testing                                            10
  11.0    Technical data and drawings                        14
  12.0    Spares                                             16
  13.0    Erection Testing and Commissioning                 16
  14.0    Training of Indian Railways Engineers             16
  15.0    Warranty                                           16
  16.0    Packing and Shipment                               17
                         APPENDIXES
APPENDIX- A    General Arrangement at the Traction            18
               Transformer at Traction Sub-station
APPENDIX- B    Schematic Diagram showing the protection       19
               scheme
APPENDIX- C    Schedule of Guaranteed Performance,            20
               Technical and Other Particulars
                         ANNEXURES
ANNEXURE- A    Drawing & Details of Terminal Connectors       23
ANNEXURE- B    Format for Title of Drawings                   24
ANNEXURE- C    Details of 132 kV CT to be used in Mumbai      25
      SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)             Page 4 of 27
                   area
1.0   SCOPE
1.1   This specification applies to outdoor electrically exposed type Current
      Transformer for a nominal system voltage of 220 kV or 132 kV or
      110 kV or 66 kV for use in unattended Railway Traction Sub-station
      in any part of India together with associated. Electrical/Electronic
      measuring/indicating instrument and protective devices. It
      supersedes          Specification       No.         ETI/PSI/117(07/88),
      ETI/PSI/102(08/87), ETI/PSI/40(08/83), ETI/PSI/22(09/82) and
      ETI/PSI/55(09/79).
 1 . 2 The Current Transformer shall be complete with all parts, fittings and
       accessories including mounting frame work of steel, necessary for its
       efficient operation. All such parts, fittings and accessories shall be
       deemed to be within the scope of this Specification, whether
       specifically mentioned herein or not. The Current Transformer shall
       be of proven design.
2.0   GOVERNING SPECIFICATION:
 2.1 Assistance has been derived from the following Standards,
     specifications/codes of practices (latest version) in the preparation of
     this specification.
S.    Standards & Codes of          Applicable Rules.
No.   Practices
1.    IS:5          1978    Colours for ready mixed paints and
      (3rdRevisin)           enamels.
2.    IEC: 185-1966          Current Transformer.
3.    IS:335-1983            Specification for new insulating oil
4.    IS:1271-1958           Classification of insulating material for
                             electrical machinery and apparatus in
                             relation to their thermal stability in service.
5.    IS:1570 (Pt.V)         Specification of bolt, nut and spring
                             washer.
6.    IS:1576-1967           Solid press-board for electrical purposes.
7.    IS:2074-1979           Ready mixed paint, air drying red oxide
                             zinc chrome priming.
8.    IS:2099-1985           Bushing for alternating voltages above
                             1000 volts.
9.    IS:2705-1981           Specification for Current Transformers: -
                             PartI: General requirement.
                             PartII: Measuring Current Transformer.
                             Part-III: Protective Current Transformer.
10.   IS:2932-1974           Enamel synthetic interior
                                 (a) Under coating
                                 (b) Finishing
11.   IS:3024-1965           Electrical steel sheets (oriented with
                             amendment No. 1&2)
12.   IS:4201-1988           Application guide for Current Transformer.
13    IS:4253 (Part-II)-1980 Cork and rubber.
14.   IS:5561-1970           Electrical power connectors.
15.   IS:11322-1955          Method for partial discharge measurement
          SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)            Page 5 of 27
                                in in Instrument Transformers.
16        RDSOs    Spec    No. Steel and stainless steel fasteners.
          ETI/OHE/18(04/84)
          with correction Slip
          No.6 (09/87)
17        RDSOs    Spec    No. Specification for hollow porcelain insulator
          ETI/PSI/70(11/84)     and bushings.
2.2        Any deviation from this specification proposed by the tenderer
           calculated to improve upon the performance, utility and efficiency
           of the equipment will be given due consideration, provided full
           particulars of the deviation with justification thereof are furnished.
           In such a case, the tenderer shall quote according to this
           specification and the deviations, if any, proposed by him shall be
           quoted as an alternative/alternatives. In case of any contradiction
           between       the     provisions   of     the     Indian    Standards
           Specification/Recommendation of IEC and this Specification the
           letter shall prevail.
3.0       SERVICE CONDITIONS:
3.1       The Current Transformer is intended for use in humid tropical
          climate in any part of India with the following atmospheric
          conditions:
     1.      Maximum ambient temperature of 45C
             air in the shed
     2.      Minimum temperature air in the 0 C
             shed
     3.      Maximum relative humidity       100%
     4.      Maximum wind pressure           200 kg/m2
     5.      Number of thunderstorm days per 85 days (Approx.)
             annum
     6.      Maximum no of dust storm 35 days
             days/annum
     7.      Average annual rainfall         1750 to 6250 mm.
     8.      Altitude                        Not exceeding 1000 m
3.2    The Current Transformer shall be subjected to vibrations on account
of trains running on nearby railway tracks. The amplitude of these
vibrations which occur with rapidly varying time period in the range of 15 to
70 ms lies in the range of 30 to 150 microns at present with the
instantaneous peak going up to 350 microns.
4.0 TRACTION POWER SUPPLY SYSTEM:
4.1 General scheme: The single phase, 50 Hz power supply for Railway
Traction at 25 kV is obtained from 220kV/132kV/110kV/66kV three phase
grid system through a step down single phase Traction Power Transformer,
The primary winding of which is connected to two phases of the three
phase effectively earthed transmission line network of the of the State
Electricity Board. In order to reduce the impedance on the three-phase grid
system, the two phases of three-phase transmission line are tapped in a
cyclic order for feeding the successive substations. The distance between
adjacent Sub-stations is normally 40 km and 80 km depending upon the
density of traffic, gradients in the section, etc.
         SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)           Page 6 of 27
4.1.1 One terminal of the 25 kV secondary winding of the Traction
Transformer is connected to the Overhead Equipment (OHE) and the other
equipment is solidly earthed and connected to the appropriate running rails.
The load current flow through the OHE to the locomotives and returns
through the rail(s) and earth to the Sub-station. Where Booster
transformers and Return conductors are used the Return current flows
through these and partly through the earth in the vicinity of the Sub-
station. Approximately midway between two adjacent Sub-stations, a dead
zone known as the Neutral Section or Phase Break is provided to
separate the different phases. The power to the OHE on one side of the
sub-station is controlled by a feeder circuit breaker while that for each track
is controlled by an interrupter. In case of a fault on the OHE, the feeder
circuit breaker isolates it. The incoming 220/132/110/66 kV supply voltage
may vary between 10% to -12.5% as per I.E. Rule No. 54. A schematic
diagram No. ETI/PSI/702-1 MOD D showing the general arrangement at
the Traction Transformer at the Traction Sub-station is at Appendix-A.
4.2 The Current Transformer shall be on the Primary side of the single
phase Traction Power Transformer for use with the following
Electrical/Electronic  measuring/indicating instruments/meters    and
protective devices/Relays: -
   a) Instantaneous Overcurrent Relay,
   b) Inverse Definite Minimum Time Lag Over Current Relay,
   c) Restricted Earth Fault Relay.
A panel/Digital type indicating Ammeters will also be connected to these
Current Transformers.
4.3 Operation of any of the protective devices/relays which serve as the
backup protective system for that on the 25 kV side of the Traction Power
Transformer shall trip the circuit breaker on the primary side of the
Transformer. A schematic diagram showing the protection scheme is at
Appendix  B.
5.0   RATING AND OTHER PARTICULARS
5.1(a) For other tan Mumbai area: The rating and other particulars of the
       Current Transformer shall be as follows:-
             i)Type:                         Single phase, oil filled natural
                                             air cooled, One core for other
                                             than Mumbai area.
             ii) No. of windings:            Primary  Two
                                             Secondary - One
             iii) System voltage:
   a.    Nominal system voltage, kV      220     132    110   66
   b.    Highest system voltage, kV      245     145    123   72.5
   iv) Rated primary/secondary Currents:
   a.    Nominal system voltage, kV          220    132   110  66
   b.       Highest system voltage, kV           245      145   123     72.5
   c.       Primary Current, Amp.                200-     400- 400-     800-
                                                 100      200   200     400
   d.       Secondary Current, Amp.              5        5     5       5
   v.       Rated Frequency, Hz                  50 Hz,   +/- 3%
   vi       Class of Insulation                  A
   vii      Rated Burden                         30 VA
        SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                 Page 7 of 27
   viii    Accuracy Class                         Other than Mumbai area -
                                                  5P to IS: 2705-1981(Part-
                                                  III)
   ix      Accuracy limit factor                  15
   x. Rated short time current:
   Nominal          Transformation Short  time               Short time current
   system           ratio          current rating             rating (Dynamic)
   voltage, kV                     (thermal)      for         kA.
                                   one second, kA
   220              200-100/5      31.5                       78.75
   132                400-200/5         31.5                  78.75
   110                400-200/5         31.5                  78.75
   66                 800-400/5         31.5                  78.75
   xi. Rated Insulation Level:
   a. Nominal system voltage,        220        132           110           66
         kV
   b. Rated one minute power         460        275           230           140
         frequency      withstand
         voltage, kV(rms)
   c. Impulse           withstand    1050       650           550           325
         voltage (1.2/50 micro,
         sec. wave shape),
         kV (peak)
   xii. Terminal Bushing:
   a. Nominal system voltage,        220        132           110           66
         kV
   b. Rated current, Amps.           800        800           800           800
   c. Minimum            creepage    6125       3625          2075          1813
         distance, mm
   xiii. Temperature rise:          See clause 10.1.2
   xiv. Rated overload:             150% of full load for 15 minutes.
   xv. Secondary winding resistance at 75 0C (Max.) 0.3 Ohms.
5.1(b) For ABT Metering: The rating and other particulars of the
       Current Transformer shall be as follows:-
             i)Type:                         Single phase, oil filled natural
                                             air    cooled,     One     core
                                             for ABT Metering.
             ii) No. of windings:            Primary  Two
                                             Secondary - One
             iii) System voltage:
   a.    Nominal system voltage, kV      220            132         110      66
   b.    Highest system voltage, kV      245            145         123      72.5
   iv) Rated primary/secondary Currents:
   a.      Nominal system voltage, kV             220     132         110        66
        SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)             Page 8 of 27
   b.       Highest system voltage, kV           245     145      123        72.5
   c.       Primary Current, Amp.                200- 400- 400- 800-
                                                 100     200   200   400
   d.       Secondary Current, Amp.              1       1     1     1
   v.       Rated Frequency, Hz                  50 Hz, +/- 3%
   vi       Class of Insulation                  A
   vii      Rated Burden                         30 VA
   viii     Accuracy Class                       For ABT Metering  0.2S
                                                 to IS: 2705-1981(Part-III)
   x. Rated short time current:
   Nominal          Transformation Short  time           Short time current
   system           ratio          current rating         rating (Dynamic)
   voltage, kV                     (thermal)      for     kA.
                                   one second, kA
   220              200-100/5      31.5                   78.75
   132                400-200/5          31.5             78.75
   110                400-200/5          31.5             78.75
   66                 800-400/5          31.5             78.75
   xi. Rated Insulation Level:
   a. Nominal system voltage,         220       132       110           66
         kV
   b. Rated one minute power          460       275       230           140
         frequency      withstand
         voltage, kV(rms)
   c. Impulse           withstand     1050      650       550           325
         voltage (1.2/50 micro,
         sec. wave shape),
         kV (peak)
   xii. Terminal Bushing:
   a. Nominal system voltage,         220       132       110           66
         kV
   b. Rated current, Amps.            800       800       800           800
   c. Minimum            creepage     6125      3625      2075          1813
         distance, mm
   xiii. Temperature rise:          See clause 10.1.2
   xiv. Rated overload:         150% of full load for 15 minutes.
   xv. Secondary winding resistance at 75 0C (Max.) 0.3 Ohms
5.1(c) For Mumbai area: The rating and other particulars of the
       Current Transformer shall be as refer Annexure -C:-
          6.0 TYPE AND GENERAL CONSTRUCTION:
      6.1    The current Transformer shall be suitable for mounting on
steel structures embedded in concrete foundations close to the circuit
breakers.
       6.2    The Current Transformer shall be of sealed type either filled
with inert gas or provided with metallic bellows above the cooling and
insulating oil. In case of inert gas filling, a pressure relief device shall be
provided.
      SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)             Page 9 of 27
      6.3    The core shall be built up of high permeability Cold Rolled
Grain Oriented (CRGO) silicon steel laminations conforming to IS: 3024, the
laminations being coated on both sides with suitable insulations capable of
withstanding stress relief annealing.
       6.4   Class A insulation immersed in oil shall be used. The Current
Transformer shall be supplied complete with insulating oil conforming to
IS:335 required for first filling.
6.5   The current transformer shall have a Single Core with wound
primary. The primary winding shall be split in two sections insulated from
each other and connected to terminals P1, P2, C1 & C2. It shall be possible
to change the transformation ratio by connecting C1 with C2 for series
configuration or P1 with C1 & P2 with C2 for parallel configuration. For
connecting these terminals in series or parallel configuration, suitable links
of adequate section made of copper flat shall be provided. The nuts and
checknuts used for connecting these links shall be made of copper. Only
copper conductor shall be used for primary and secondary windings.
      6.5.1 Normally no joints in the winding shall be allowed. Joints if
unavoidable shall be brazed with high silver alloy grade Ba Cu Ag6 of IS:
2927-1975 or electrically butt-welded.
       6.6   The secondary terminals of the Current Transformer shall be
housed in a weather proof terminal box of mild steel of thickness not less
than 1.6mm. The connection/disconnection of external cable to/from the
terminals         shall       be         easy     and         convenient.
The cables shall be of 4 sq. mm, sections 2 core PVC insulated and PVC
sheathed and their entry into the terminal box shall be through proper
cable glands fitted on the bottom of the terminal box. The cable glands
shall be supplied with the Current Transformer.
      6.6.1 Facilities for shortcircuiting the secondary terminal shall be
provided within the terminal box. The Current Transformer shall be
provided with a standard IOA test winding.
       6.7   All the bolted mechanical and electrical connections in the
Current Transformer will be tightened properly to prevent loosening in
service due to vibrations.
       7.0    BUSHING AND TERMINAL ARRANGEMENT:
       7.1     Out door type bushing shall conform to IS: 5621.The basic
insulation level shall have the appropriate value as given in clause 5.1(xi)
of this specification. The porcelain housing shall be capable of withstanding
all electrical and mechanical stresses that might be produced during the
operation of the Current Transformer under normal and short-circuit
conditions.
      7.2 The profile of porcelain shed shall be simple and free from the
ribs on the underside so as to avoid accumulation of dust and pollutants
and permit easy cleaning. The porcelain housing shall be of single piece
construction i.e. without joint in the porcelain body. The material of
clamping rings/ flanges used shall conform to MCI Grade BM-340 of IS:
2108 or to SGCI Grade: 400/12 of IS:1865 or to Aluminium alloy
Grade:4450 of IS:617. The mass of Zinc coating shall not be less that 1000
gm/mm2.
      SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)              Page 10 of 27
      7.3    Porcelain housing/support insulator used shall have creepage
distance as given in Clause 5.1(xii)-C.
       7.4   The bushing/housing terminal shall be provided with rigid type
connectors as per Research Designs & Standards Organisation (RDSO)
drawing No. ETI/PSI/11010 in Annexure  A suitable for connecting to
ZEBRA 28.62 mm ACSR conductor. The connector shall conform to IS:
5561 and its design shall be such so as to be connected to the equipment
terminal pad with a minimum of four 12 mm dia bolts, nuts and lock nuts
which shall all be of stainless steel conforming to IS: 1570(Pt. V) Grade 04
Cr. 17 Ni 12 Mo2. Each of these bolts shall also have a flat washer and
spring washer.
      7.5   The connectors and porcelain housing shall be procured only
from approved manufacturers.
      7.6     For equipment earthing, the steel supporting frame shall be
provided with two earthing terminals of adequate capacity to carry the
rated shot-circuit current safely. The earthing terminal shall be connected
to 50mm x 8 mm MS flat. The earthing terminal shall be provided with 17.5
+0.5mm dia. hole for fixing the earthing flat 0.4
      7.7 The approved source of porcelain housings are as under:
      (i) M/s Aditya Birla Insulator, Hallol & Rishra.
      (ii) M/s Insulators & Electricals Co. Mandideep, Bhopal.
      (iii) M/s Modern Insulators Ltd., Abu Road,
      (iv) M/s WSI, Chennai.
8.0   PARTS FITTINGS & ACCESSORIES:
8.1   Apart from the parts, fittings & accessories specifically detailed in the
foregoing clauses, the following shall be supplied with each Current
Transformer.
      (i)    Rating plate with diagram of connections and terminal
             markings.
      (ii)   Weatherproof terminal box.
      (iii)  Lifting lugs.
      (iv)   Pressure Release Device.
      (v)    Nitrogen gas filling valve and oil filling port.
      (vi)   Oil level gauge of prismatic glass.
      (vii) Adjustable arcing horns.
      (viii) Cable Gland (Brass Nickel plated).
      9.0     PAINTING
       9.1    All the steel surfaces which are in contact with insulating oil
shall be painted with heat resistant oil insoluble insulating warmish. All
steel surfaces exposed to weather shall be given on primer coat of zinc
chromate and two coats of gray paint to shade No. 631 of IS: 5. One coat
of additional paint shall be given at site by the manufacturer.
9.2   Fasteners.
       All fasteners of 12 mm diameter and less exposed to atmosphere
shall be stainless steel and those above 12 mm diameter shall be preferably
       SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)            Page 11 of 27
be of stainless steel or of mild hot dip galvanized to RDSOs specification
No. TI/SPC/OHE/FASTNERS/0120(03/2013).
10.0   TESTING
10.1 Once a purchase order is placed for supply of a Current Transformer
the designs and drawings shall be furnished to the purchaser/ Director
General (Traction Installation), Reseach Designs and Standards
Organisation, [DG(TI), RDSO] Lucknow, as the case may be, within the
period stipulated in the order. Only after all the designs and drawings have
been approved for prototype tests and a written advice given to that
affect, shall be successful tenderer/manufactuer take up manufacture of the
prototype of the transformer. It is to be clearly understood that any change
or modification required by the above authorities to be done in the
prototype shall be done expeditiously, not withstand approval having
already been given for the designs and drawings. Such change or
modification shall be incorporated in the drawings as indicated in clause
14.4.
(ii)   Prior to giving a call to the purchaser/DG(TI), RDSO, Lucknow, for
inspection and testing of the prototype, the successful tenderer/
manufacturer shall submit a detailed test schedule consisting of schematic
circuit diagrams for each of the tests and the number of days required to
complete all the tests at one stretch. Once the schedule is approved, the
tests shall invariably be done accordingly. However, during the process of
type testing or even later, the purchaser reserves the right to conduct any
additional test(s), besides those specified herein, on any equipment/ items
so as to test the equipment/item to his satisfaction or for gaining additional
information and knowledge. In case any dispute or disagreement arises
between the successful tenderer/manufactuerer and representative of the
purchaser/DG(TI) RDSO, Lucknow, during the process of testing as regards
the procedure for type tests and/or the interpretation and acceptability of
the results of type tests, it shall be brought to the notice of the
purchaser/DG(TI), RDSO, Lucknow as the case may be, whose decision
shall be final and binding. Only after the prototype transformer is
completed and ready in each and every respect, shall the successful
tenderer/manufacturer give the actual call for the inspection and testing
with at least 15 days notice for the purpose.
iii)   In the event of the tests not being carried through the completion at
the one stretch for any reason attributable to the successful tenderer/
manufacturer and it is required for the representative of the
purchaser/Director General (Traction Installation), Research Designs &
Standard Organisation, [DG(TI) RDSO], Lucknow, to go again or more
number of times to the works of the successful tenderer/manufacturer or
other place(s) for continuing and/or completing the tests on the
prototype(s) of the equipment, the successful tenderer/manufacturer shall
reimburse to the purchaser/DG(TI), RDSO, Lucknow, the costs for the
representative having to visit the works or other place(s) for the tests more
than once. The costs as claimed by the purchaser/DG(TI), RDSO, Lucknow,
shall be paid through a demand draft to the concerned Accounts Officer of
the Purchaser/DG(TI), RDSO, Lucknow, as shall be advised to the
successful tenderer/manufacturer.
iv)    The following type tests shall be carried out on the prototype current
transformer art the works of the successful tenderer/ manufacturer or at
the reputed testing laboratory in the presence of the representative of the
       SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                Page 12 of 27
Purchaser/DG(TI), RDSO, Lcuknow, in accordance with the relevant
specifications and as modified or amplified as under:
10.1.1 Visual inspections: It shall comprises
         (a)     Checking of the layout, terminal markings,             mounting
                 arrangement, labeling and any other items.
         (b)     Quality of painting and anti-rust treatment.
         (c)     Quality of workmanship and finish as well as provision of all
                 parts, fittings and accessories.
10.1.2           TEMPERATURE-RISE TEST:
             This test shall be carried out on the Current Transformer for
the higher rating fitted with approved terminal connector for fullload and
for overload specified in clause 5.1(xiv). The temperature rise under
specified overload shall not exceed the following values.:
         (a)     Winding      :        500C (Temperature rise       measurement
                                       by the resistance method).
         (b)     Insulating oil        : 400C (temperature rise measurement by
                                        thermometer)
         (c)     Terminal connector : 400C (temperature rise        measurement
                                      by thermometer)
         The above values are with reference to an ambient temperature of
         450C.
10.1.3 Impulse Voltage Test:
      The lightening impulse voltage withstand test shall be done on the
primary windings with test voltages specified in clause 5.1(xi).
10.1.4      Short-time current test:
        The short time thermal (rms) and dynamic (peak) current withstand
tests shall be done to verify the ability of the Current Transformer and the
terminal connectors fitted there to withstand the rated short-time current
specified in clause 5.1(x). The Current Transformer shall be deemed to
have passed the test if the conditions laid down in clause 7.6.3 of IS: 2705
(Pt. I) are satisfied.
10.1.5      Excitation test and plotting of magnetizing characteristics curves.
      The curve shall be drawn at least up to that point, where an increase
of 100% in voltage results in an increase of 50% in current.
10.2      TYPE TEST ON ACCESSORIES:
10.2.1 Porcelain Bushing
       The following tests shall be carried out on prototype unit of 52 kV or
72.5 kV or 123 kV or 145 kV or 245 kV (as the case may be) class bushings
in accordance with IS: 2099 and IS: 5621.
         (i)     Dry power-frequency withstand voltage test.
         (ii)    Wet power-frequency withstand voltage test.
         (iii)   Dry-lightening impulse voltage withstand test.
         (iv)    Thermal stability test.
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                Page 13 of 27
(v)      Temperature-rise test.
(vi)     Thermal short time current withstand test.
(vii)    Dynamic current withstand test.
(viii) Cantilever load withstand test.
(ix)     Measurement of partial discharge quantity (as per IS:6209)
(x)      Tightness test at flange or other fixing devices.
(xi)     Temperature cycle test.
10.2.2      Test on terminal connectors:
       The terminal connector shall be from the approved supplier of
RDSO. In case these are not from the approved suppliers of RDSO,
the following tests shall be carried out:
         (i)     Visual inspections and verification of dimensions.
         (ii)    Tensile test.
         (iii)   Resistance Test.
         (iv)    Temperature-rise test at normal and specified overload.
         (v)     Short- time current test.
         (vi)    Chemical analysis of materials used.
10.3 In addition to the above tests, all routine tests detailed in
clause 10.7 shall be carried out on the test unit.
10.4 If the prototype of a Current Transformer conforming to this
Specification has been approved for earlier supplies to Indian
Railways, the testing of prototype again may be waived provided that
no change in the design or material(s) used have been made.
10.5 Manufacturers type test certificates in respect of the tests
carried out on (a) porcelain housing and (b) terminal connector, as
per relevant IEC recommendations/IS specifications shall be
submitted by the successful tenderer for approval.
10.6 The tenderer may quote separately his charges for conducting
short-time current (thermal) and dynamic current withstand tests
described in clause 10.1.4, hereof. No charges shall be payable for
any other type and routine/acceptance test.
10.7     Routine tests/Acceptance tests.
      Every Current Transformer shall be subject to the following
tests at the manufacturers works as per IS: 2705 (Pt.I) and IS:
4322.
10.7.1 Verification of Terminal markings and polarity.
10.7.2 High voltage power-frequency tests on primary winding.
     The windings shall be subject to the following tests voltages:
a.      Nominal system 220             132         110         66
        voltage, kV
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)               Page 14 of 27
b.   Voltage to be 460               275          230          140
     applied between
     winding & earth,
     kV (rms)
c.   Voltage to be 2                 2            2            2
     applied between
     two sections of
     primary winding,
     kV (rms)
10.7.3 High voltage power-frequency withstand               test   on   the
secondary winding: 3 kV (rms) for one minute.
10.7.4 ACCURACY TESTS:
         The accuracy test shall comprise the following:-
         a) Current error & phase displacement at the rated primary
            current.
         b) Composite error at rated accuracy limits primary current.
10.7.5 Measurement of insulation resistance between primary
winding and secondary winding with a 2500 V Megger; and that
between secondary winding & earth with a 500 V Megger.
10.7.6 Measurement of secondary winding resistance and its
computation at 750C.
10.7.7     Measurement of partial discharge of windings.
10.8 Only after clear written approval of the results of the tests on
the prototype unit is communicated by RDSO/purchaser to the
manufacturer, shall be taken up bulk manufacture of the ordered
Current Transformers which shall be strictly with the same material
and process as adopted for the prototype. In no circumstances shall
material, other than those approved in the designs/drawings and /or
the prototype, be used for bulk manufacture on the plea that they
had been obtained prior to the approval of the prototype.
11.0     TECHNICAL DATA AND DRAWINGS:
11.1 The information furnished in Schedule of Guaranteed
Performance, Technical & other particulars (Appendix C) shall be
complete in all respects. If there is entry like shall be furnished later
or blanks are left against any item, the tenderer is not likely to be
considered such as omissions causes delay in finalising the tender.
Evidence in the form of type test reports for basic insulation level,
i.e. rated impulse withstand voltage test, rated power frequency
(wet) withstand test, rated power frequency (dry) withstand test,
temperature rise test and short time current withstand test on the
current transformer offered shall be furnished.
11.2 The tenderer shall specifically indicate in a statement attached
with his offer, his compliance with each clause and sub-clause of this
specification. A separate statement shall be attached with the offer
indicating reference to the clauses where the tenderer deviates
therefrom together with detailed remarks/justification. If either the
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                 Page 15 of 27
statement of compliance or statement of deviation is not attached
with the offer, it is not likely to be considered. If there are no
deviations, a NIL statement shall be attached.
11.3 The tenderer shall furnish the following drawings as per Indian
Railways standards in sizes of 210mm x 297 mm or any integral
multiplies thereof. A format of the title sheet is attached at Appendix
D.
       a)     Outline general arrangement giving               the     overall
              dimensions of current transformer.
       b)     Internal arrangement of Current Transformer including
              crosssectional views.
11.4   The tenderer shall also furnish the following information
       along with his offer-
       a) Excitation characteristic curve.
       b)    Manufacturers test certificates of :-
       (i) Winding wire (ii) Oil seal/gaskets (iii) insulating oil
       (iv) pressure release device.
       c) The tenderer shall furnish the detailed calculation and basis
           in support of the minimum knee point voltage.
            For calculations purpose the lead resistance may be
             presumed as 0.4 ohms.
11.5        The successful tenderer shall be required to submit for
            approval the following detailed dimensioned drawings as
            per Indian Railways standard in Annexure B (Title of
            Drawing) in sizes of 210mm x297mm or any integral
            multiples thereof-
            a)   General    outlines  drawings      showing    mounting
            arrangement, relative position of primary and secondary
            terminals, CT earthing and position of various parts, fittings
            and accessories.
            b) Cross-sectional view along with its internal details.
            c) Porcelain housing/bushing        including    its     clamping
            arrangement.
            d) Name and rating plate with the diagram of connections
            (both in English and Hindi).
            e) Details of primary terminals and links used for changing
            the transformation ratio.
            f) Secondary terminals and terminal box.
            g) Details of metallic bellow, if provided as well as its
            operation.
            h) Detailed part drawings for:-
            (i) Oil level gauge(ii) Nitrogen Gas filling valve(iii) Pressure
            release device(iv) Cable gland (v) Terminal connector (vi)
            Earthing terminals and (vii) Oil draining pipe with plug.
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)            Page 16 of 27
11.6     After approval, six copies of approved drawings along with
         two sets of reproducible prints shall be supplied to each
         consignee(s). Besides, two copies of drawings along with
         one set of reproducible prints shall be supplied to the
         Director General (Traction Installation), Research Designs &
         Standards Organisation, Lucknow (India).
11.7     The successful tenderer shall supply five copies of the
         instruction/maintenance    manual      for   the   Current
         Transformer to each consignee(s) and two copies to the
         Director General (Traction Installation), Research Designs
         and Standards Organisation, Lucknow (India).
12.0     SPARES:
         The tenderer shall furnish along with his offer a list of spare
         (with cost) recommended by him for maintenance of
         Current Transformer for a period of two year.
13.0     ERECTION TESTING AND COMMISSIONING:
13.1     The transformer shall be erected by the purchaser under
         the supervision of a competent engineer of the successful
         tenderer/manufacturer/supplier. The Current Transformer
         shall be subjected to the specified proving/pre-
         commissioning tests by the Railwayss Engineer at site and
         with which the successful tenderer/supplier/ manufacturer
         shall also be fully associated. For this purpose, prior
         intimation regarding the date and location of tests shall be
         given     by    the    purchaser     to    the     supplier/
         manufacturer/successful tenderer.
14.0     TRAINING OF INDIAN RAILWAYS ENGINEERS
14.1     The offer shall include the training of two Engineers of the
         Indian Railways free of cost at the manufacturers in India
         or abroad and at the maintenance depots/workshop on a
         railway system or other public utility where Current
         Transformers of similar/identical design are in operation.
         The total duration of training for each engineer shall be for
         12 weeks of which approximately 6 weeks will be at
         manufacturers works and 6 weeks on Railway system or
         other public utility. The cost of travel to the country of the
         manufacturer and back will be borne by the Indian
         Railways. Other details shall be settled at the time of
         finalizing the contract of the purchase order.
15.0      WARRANTY:
15.1     Each Current Transformer supplied against a purchase
         order/contract in which this specification is quoted,
         irrespective of origin (imported or indigenous), shall be
         guaranteed for trouble-free and satisfactory performance
         for a period of 24 months from the date of supply of or 18
         months from the date of commissioning at the sub-station
         on Indian Railways, whichever period is shorter. Details of
         warranty clause, the extant of responsibility and other
         relevant aspects shall be included in the purchase order or
         contract. The tenderer shall furnish detailed terms and
         conditions in this regard in his offer.
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)          Page 17 of 27
         The     successful   tenderer     shall  make      necessary
         arrangements for closely monitoring the performance of the
         Current Transformer through periodical (preferably once in
         two months during the warranty period) visits to the sub-
         station for on the spot detailed observations. Arrangement
         shall also be made for spare parts to be kept readily
         available with the manufacturer/supplier/ successful
         tenderer to meet exigencies warranting replacement so as
         to put back the Current Transformer in service without
         unduly long interruption of traction power supply.
16.0     PACKING AND SHIPMENT:
16.1     The Current Transformer shall be transported from the
         manufacturers works to the destination by rail, road or sea
         as determined in the contract/purchase order. The parts,
         fittings and accessories which are liable to damage during
         transit shall be separately packaged/crated and dispatched
         so as to reach destination along with the Transformer
         tanks. Any opening crated on the Current Transformer tank
         by the removal of any parts, fittings and accessories shall
         be closed by suitable blanking plates.
         A general packing list, for the various components of each
         Current Transformer shall be furnished. The packing has to
         be done properly so that no damage may be done during
         transit.
    APPENDIX  A
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)              Page 18 of 27
                                                    APPENDIX  B
        Schematic Diagram Showing the Protection Scheme:
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)          Page 19 of 27
             SUB-SECTOR      SUB-SECTOR   SUB-SECTOR
                          SECTOR
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                     Page 20 of 27
                                                          APPENDIX-C
SCHEDULE OF GUARANTEED               PERFORMANCE,         TECHNICAL         AND
OTHER PARTICULARS.
S.    Description                                         Unit        of
No.                                                       measurement
1.    Name of the manufacturer
2.    Country of origin
3.    Standard governing specification
4.    Manufacturers type designation
5.       (a) Nominal system voltage                       kV
         (b) Highest system voltage                       kV
6.       (a) Rated primary current                        Amp
         (b) Rated secondary current                      Amp
         (c) Rated transformation ratio
7     Rated burden                                        VA
8     Accuracy class
9     Rated accuracy limit factor
10    Current error at rated primary current              Percent
11    Phase displacement        at   rated        primary Minutes
      current
12    Complete error at rated accuracy limit percent
      primary current
13    Rated short-time current and duration
         (a) Thermal (Ith)                                kA (RMS)for one
                                                          sec.
                                                          kA (peak)
         (b) Dynamic (Idyn)
14    Temperaturerise of the windings
      (by resistance method) over an ambient
      temperature of 45 0C                                0
                                                              C
         (a) At rated current
         (b) At 100% overload for 5 minutes               0
                                                              C
15.   Partial discharge level                             pC
16.   Particulars windings
         a) Primary winding
            i)      Type
            ii)     No. of turns
            iii)    Current     density      at     rated Amp/mm2
                    current
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                      Page 21 of 27
                iv)       Size of conductor
                v)        Class of insulation
         b) Secondary windings:
                i)        Type
                ii)       No. of turns
                iii)      Current   density     at   rated
                          current
                                                             Amp/mm2
                iv)       Size of conductor
                v)        Class of insulation
                vi)       Resistance computed to 75 0C
                vii)      Insulating material used
                                                             Ohm
         c)       Rated insulation levels:
                i)        One minute power frequency
                                                     kV (rms)
                          withstand voltage
                ii)       Inter-section       withstand
                          voltage of primary windings.  kV (rms)
                iii)      Impulse withstand voltage          kV (peak)
17    Particulars of core:
         i) Type
         ii) Flux density.
              a) At rated primary current                    Tesla
              b) At 15 times rated primary current           Tesla
         iii) Thickness of steel laminations                 mm
         iv) Whether CRGO steel stampings are
             used ?
         v) Knee point e.m.f.
         vi) Exciting current to knee point
18.   Particulars of porcelain housing/bushing:
         (i) Specification to which it conforms
         (ii) Name of manufacturer
         (iii) Power frequency withstand voltage
               for one minute.
         (a) Dry
                                                             kV (rms)
         (b) Wet
                                                      kV (rms)
          iv)         Dry lightning impulse withstand
                                                      kV (peak)
                      voltage,   1.2/50  micro-second
                      wave shape.
          v)           Visible power frequency discharge kV (rms)
                       voltage.
          vi)          Creepage distance in air
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                    Page 22 of 27
                       a. Protected                      mm
                       b. Total                          mm
         vii)      Weight of      porcelain      housing Kgs.
                   /bushing
19    Overall dimensions:
         i)      Length                                  mm
         ii) Width                                       mm
         iii) Height                                     mm
20    Weights:
         (i) Total weight of copper used
              a) Primary winding                         Kgs.
              b) Secondary winding                       Kgs.
         (ii) Weight of core                             Kgs.
         (iii)(a) Quantity of insulating oil             Liter
                   b) Weight of insulating oil           Kgs.
          iv) Total weight                               Kgs.
21    Particulars of terminal connector:
         (i) Name of manufacturer
         (ii) Rated current                              Amp.
         (iii)         Temperature rise above an
                       ambient temperature of 45 0C
              a) At rated current
              b) At 150 percent of rated current for
                 15 minutes.
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)       Page 23 of 27
                                                 ANNEXURE- A
                Details of Terminal Connector:
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)      Page 24 of 27
                                                ANNEXURE- B
                   Format of Title Drawing:
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)            Page 25 of 27
                          ANNEXURE- C
1.0   SCOPE
      This part of specification cover design, manufacture, testing,
      inspection, packing and supply of 145 kV class outdoor,
      Current Transformer with CT ratio of 1200-800-400/5A to the
      Specification given below to be used in Mumbai area on 110
      kV side at Traction Sub-station with 30 MVA Transformers and
      required to be operated in parallel with adjacent Traction Sub-
      stations.
2.0   RATING AND OTHER PARTICULARS:
      i)      Type                     Single phase, oil filled natural
                                       air cooled outdoor.
      ii)     No. of cores             4
      iii)    System voltage
                 a) Nominal system 132
                    voltage , kV
                 b) Highest system
                                   145
                    voltage, kV
      iv)     Rated
              primary/secondary
              currents
                 a) Primary current,
                    Amp              1200
                 b) Secondary          5
                    current, Amp
      v)      CT ratio                 1200-800-400/5A
      vi)     Rated frequency          50 Hz,+/-3%
      vii)    Class of insulation      A
      viii)      a) Short       time 40
                    current    rating
                    (thermal) for 3
                    second, kA
                 b) Short       circuit 40
                    withstand current
                    (3 sec.), kA
                 c) Short       time
                    current    rating 100
                    (dynamic),     kA
                    (peak)
      ix)     Rated insulation level
                 a) One minute 50 275
                    Hz      withstand
                    voltage/induced
                    over-voltage, kV
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)                Page 26 of 27
                     (rms)
                  b) Impulse           650
                     withstand
                     voltage, positive
                     and      negative
                     polarity (1.2/50
                     microseconds
                     wave), kV (peak)
      x)       Minimum      creepage 4495
               distance of insulator
               (31 mm/kV), mm
      xi)      Temperature          rise 50 0C over an ambient temp.
               Maximum temperature 50 0C
               rise   of       windings
               immersed in oil
      xii)     Rated Overload            150% of     full   load    for   15
                                         minutes
      xiii)    Rated Burden & Class Core-1           Core-     Core-2&4
               of Accuracy of different              3
               cores
                                        Protection   R met     Protection
               Burden in VA              40          40        -
               Accuracy Class            5P20        0.2       PS
               Instrument       Security -           <5        -
               factor
               Knee point voltage        -           -         >750V
               Iex (max) at Vk/2         -           -         <100 mA
               Rct (max)                 -           -         <1.0 Ohm
                                                               at   max.
                                                               tap.
2.1
      a) multi ratio specified         shall be obtained by taps on
         secondary side.
      b) The values specified above for metering & protection
         core shall be met for the lowest tap. (except) Rct and
         knee point voltage for PS core which is at the highest
         tap).
      c)      P1 and P2 markings to be permanently riveted.
      d) CT shall be of dead tank design.
      e) Power factor terminal (test tap) shall be provided inside the
          secondary terminal box.
       f)     The disposition of various CT cores and detailed drawings
              along with SOGP shall be furnished for RDSOs approval
              before manufacture is taken up.
3.0           Construction:
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)          Page 27 of 27
          The current transformers shall be hermitically sealed. They
          shall be suitable for upright mounting on steel structures.
          They shall be provided with Nitrogen cushions/stainless
          steel bellows. CTs shall be suitable for hot line washing.
          The Current Transformer winding shall be housed in a
          galvanized tank suitable for outdoor duty. Earthing
          arrangement shall be provided for CT tank.
3.1       Tank Fabrication
          The tank shall be fabricated from tested quality low carbon
          steel suitable for welding and of adequate thickness. The
          tank shall be designed to withstand mechanical shocks
          during transportation, vacuum filling of oil and continuous
          internal pressure over normal hydrostatic pressure of oil
          and short circuit forces.
          The construction of the tank shall be designed to prevent
          ingress of water into or leakage of oil from the tank. All
          bolted connections shall be fitted with weather proof, hot
          oil resistant gasket in between (Butile Nitrile/Neoprene
          Rubber), for complete oil tightness. If gasket is
          compressible, metallic stops shall be provided to prevent
          over compression.
          Tank fabrication drawings shall be submitted for approval
          before the manufacturing is taken up.
3.2       SPECIAL CONSTRUCTION NOTE:
          After the internal elements such as primary & secondary
          windings are sealed in the tank with porcelain shell, the
          assembled CTs shall be subjected to vacuum & heat
          treatment and finally filled with degasified oil in vacuum.
4.0       General
4.1       Current Transformers shall be provided with unthreaded
          stud terminals at top for connections to 110 kV, 50 mm
          OD aluminium busbar. The primary current terminals shall
          be of tinned copper.
4.2       The current transfer area of the terminals shall be
          adequate to meet the temperature rise requirements as
          per IEC: 44-1/IS: 2705 for CTs. The cross-section area of
          the terminal shall be indicated in the drawings.
4.3       Mechanical load test on primary terminals: Test reports
          are to be submitted as per IEC 44-1.
4.4       The Burdens specified for different cores refer exclusively
          to connected burden and should exclude the bleeder
          resistance if any. Current transformers guaranteed
          burdens and accuracy class are to be intended as
          simultaneous for all cores.
4.5       CTs shall be provided with a capacitance test tap in the HV
          lead to enable future monitoring of conditions of HV
          insulation.
4.6       Earthing terminals shall be provided in the secondary
          junction box for earthing of secondary winding of CT.
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)             Page 28 of 27
4.7        The alignment and centre line of CT primary terminals
           shall be correct so as to avoid bending of connections.
4.8        The CT secondary terminal box shall be of GI (IP 55) and
           shall be provided with collar to prevent entry of moisture &
           good neoprene gaskets designed to prevent entry of
           foreign particles. Junction box shall be sufficiently large to
           connect 1100 V upgrade, 4C x 6 sq. mm cables through
           cable glands for all the secondary cores.
4.9        CT secondary terminals shall be terminated to stud type
           non disconnecting terminal blocks inside the terminal box.
           CT secondary terminals shall be provided with lock nuts.
4.10       All ferrous parts exposed to atmosphere including main
           tank, secondary terminal box & top metallic should be hot
           dip galvanized.
4.11       The current transformer shall be supplied complete with
           insulating oil conforming to IS: 12463 and Railway
           requirements. The insulating oil shall be procured from the
           manufacturers approved by RDSO. The successful
           tenderer/manufacturer shall submit test certificates as per
           IS: 12463 for oil.
4.12       The tenderer shall furnish their compliance or otherwise
           against    each     clause/sub-clause     of    the technical
           specification. If the tenderer wishes to deviate from the
           provision of any clause/sub-clause, he shall furnish the full
           details with justification for such deviations.
4.13       Detailed drawings of CT along with SOGP shall be
           furnished for RDSOs approval before manufacture is taken
           up.
4.14       The CT shall be used for following additional protective
           devices/relays.
           i) Fibre optic line differential protection
           ii) Directional over current relay.
           iii) LBBU relay (LBB- breaker failure relay)
           iv) Bus bar differential low impedance type protection
               relay
           v) Energy metering
  5.0 The following Type and Routine Tests as per IEC:44-1, IS:270-
      5 and RDSO specification No. ETI/PSI/117(07/88) with A&C
      slip No. 1 to 6 shall be conducted on the Current Transformer
      required for Mumbai area under DC-AC conversion.
  5.1 Type Tests
       1. Visual inspection
       2. Temperature rise test
       3. Impulse voltage test
       4. Short time current test
SPECIFICATION NO. TI/SPC/PSI/CT/0515(05/2015)              Page 29 of 27
        5. Excitation test and plotting of magnetizing
           characteristic curves.
        6. Radio interference test
        7. Seismic withstand test.
        8. Thermal stability test.
        9. Thermal co-efficient test i.e. Measurement of tan delta
            as a function of temperature.
        10.   The CTs shall be subjected to special i.e. Multiple
        chopped impulse test on primary winding as per clause 6.3 (C)
        and Annexure - (B) of IEC 60044-1 in order to evaluate the
        ageing characteristics of the CT insulation. This test is to be
        done to assess the CT performance in service to withstand the
        high frequency over voltage generated due to closing and
        opening operations of isolators.
  5.2   Routine Tests
        1. Dimensional check
        2. Verification of terminal marking and polarity
        3. Power frequency voltage withstand test on primary winding.
        4. Power frequency voltage withstand test on secondary
        winding.
        5. Accuracy tests.
        a)    Current error and phase displacement at the rated
               primary current.
        b)    Composite error at rated accuracy limit primary current.
        6.    Measurement of knee point voltage, exciting current
              and ISF test (only for metering core).
        7.    Measurement of winding resistance test.
        8.    Insulation resistance measurement test.
        9.    Inter turn over-voltage test.
        10.   Partial discharge test (PI) value shall be less than
              5pC).
        11.   Capacitance and tan delta value measurement than
              delta value should be less than .5%
        12.   Oil leakage test.