Advc N-Series Installation
Advc N-Series Installation
Scope of this   This document describes the installation and           Automatic Circuit Recloser with Advanced
Manual          maintenance procedures for the N-Series                Controller.
Limitations     This document is copyright and is provided solely      party, nor to be used as the basis of a tender or
                for the use of the purchaser. It is not to be copied   specification without the express written
                in any way, nor its contents divulged to any third     permission of the manufacturer.
Disclaimer      The advisory procedures and information                Consequently, this Manual is offered as a guide
                contained within this Manual have been compiled        only. It should be used in conjunction with the
                as a guide to the safe and effective operation of      customers own safety procedures, maintenance
                products supplied by Nu-Lec Industries Pty Ltd.        program, engineering judgement and training
                                                                       qualifications.
                It has been prepared in conjunction with
                references from sub-assembly suppliers and the         No responsibility, either direct or consequential, for
                collective experience of the manufacturer.             injury or equipment failure can be accepted by Nu-
                                                                       Lec Industries Pty Ltd resulting from the use of this
                In-service conditions for use of the products may
                                                                       Manual.
                vary between customers and end-users.
                                                                                                                           iii
N-Series Automatic Circuit Recloser
iv
                                                                                                                                                         Contents
Contents
                                                                                                                                                                                v
N-Series Automatic Circuit Recloser
vi
                                                                                     Scope of this Manual
General          This manual describes the installation and           Inevitably, not all details of equipment are
                 maintenance of the N-Series Automatic Circuit        provided nor are instructions for every variation
                 Recloser and the Advanced Controller.                or contingency during installation, operation or
                 Whilst every care has been taken in the              maintenance.
                 preparation of this manual, no responsibility is
                 taken for loss or damage incurred by the             For additional information on specific problems
                 purchaser or user due to any error or omission       or requirements, please contact the
                 in the document.                                     manufacturer or your distributor.
                 The model number is shown on the equipment           applicable. Please contact the manufacturer or
                 rating plate. If your equipment does not show        your local distributor.
                 one of these model numbers, this manual is not
Software         The software loaded into the ADVC is identified      The software version is shown on the Operator
Identification   by its version number which has the form:            Control Interface Switchgear Wear/General
                                                                      Details page, in the field App.Ver:
                      AXX-XX.XX.
                 This precisely identifies the software loaded into
                 the microprocessor on the controller.                 - - - - - Switchgear Wear/General Details - - - - S
                                                                      U Contact 100.0%           Cubicle S/N 1234
                 In order to obtain effective technical support       V Contact 100.0%           App.Ver A41-01.01
                 from the manufacturer or your distributor it is      W Contact 100.0%
                 vital to record the software version and to quote
                 these when making your inquiry. Without this
                 information it is impossible for our customer
                                                                      See Section 7 (page 7-1) to find out how to use
                 service department to identify the software and
                                                                      the Operator Control Panel.
                 provide correct support.
                                                                                                                         1-1
N-Series Automatic Circuit Recloser
1-2
                                                                                               Introduction
2 Introduction
                 The N-Series remotely controlled and monitored       the ACR is connected to the Advanced
                 automatic circuit recloser consists of an N-          Controller (ADVC) via a control cable
                 Series automatic circuit recloser (ACR)               through the base of the ADVC
                 combined with an Advanced Controller (ADVC).         the ACR can be connected into an insulated
                 The N-Series ACR                                      or bare conductor system.
                    consists of vacuum interrupters in a sealed,    The ADVC reads and displays the information
                     stainless steel tank                            which is stored in the ACR and provides
                                                                     protection and communication properties for the
                    the tank is filled with sulphur hexaflouride
                                                                     ACR. The ADVC
                     (SF6) gas
                                                                      consists of:
                    a pressure transducer is used to monitor gas
                     pressure in the tank                               an operator control panel mounted in the
                                                                          door,
                    surge arresters can be directly fitted to the
                                                                        an electronic switchgear controller that
                     ACR and should be fitted at installation
                                                                          monitors the ACR, and provides
                    voltages are measured on each of the 6               communication and protection functions,
                     bushings
                                                                        a power supply which also supplies power
                    current is measured on each phase                    for customer equipment,
                    the ACR itself retains information such as         an accessories and customer equipment
                     serial number, switchgear type, operations           compartment,
                     and contact wear, independently of the           is powered by an auxiliary voltage supply of
                     ADVC                                              110, 220, or 240 volts AC.
                    the ACR can be tripped from the ground by a      is connected to the ACR via a detachable
                     hookstick and then be locked out by opening       control cable.
                     the isolating switches located on the ADVC.
                                                                     The customer compartment provides ample
                    a clearly visible, external pointer shows       room for equipment. Standard communications
                     whether the ACR is tripped or closed.           cables can be used for connection to the
                 The ACR field-fitting kit includes a polymeric      communications ports on the ADVC and power
                 bushing boot and predetermined length of 120        is readily accessible from the programmable
                 mm,185 mm, or 240 mm aluminium, insulated        power terminal block. (Please refer to
                 water-tight cable tail rated at 250A, 400A, 630A    Communications and Accessories Installation
                 for each of the six bushings.                       on page 4-1.)
                                                                                                                 2-1
N-Series Automatic Circuit Recloser
                .
2-2
                                                                                           Introduction
                                                                     Customer
                                                                     Equipment and
                                                                     Accessories
                                                                     Compartment
                                                                                                   Control and
                                                                                                   Protection
                                                                                                   Enclosure
                                                                                                   (CAPE)
                 Operator
                 Control
                 Panel (OCP)
Batteries
                                                        Power
                                                        Supply
                                                        Unit (PSU)
                                                                                                                   2-3
N-Series Automatic Circuit Recloser
2-4
                                                                                                          Installation
3 Installation
Contents of      Each crate includes:                                     ADVC (which will normally contain two
Crate                                                                      batteries unless arrangements have been
                     ACR.                                                 made to ship batteries separately).
                     Pole mounting bracket with clamps if                Control cable.
                      ordered. If a substation mounting bracket           Six cable tails (where supplied by the
                      was ordered it will be attached to the outside       manufacturer) pre-terminated with either a
                      of the crate.                                        threaded lug to screw into the bushings
                                                                           directly or with a flat lug for bolting to a palm
                     Six bushing boots with clamping rings
                                                                           already fitted onto the bushings.
                      attached.
                                                                         On receipt, the contents should be checked for
                     Six tubes of electrical silicone grease to fill    shipping damage and the manufacturer
                      the bushing boots.                                 informed immediately if any is found.
                     One clamping ring spanner to fit boots to the                   Ensure that the ADVC is stored
                      bushings.                                                       indoors until installation on site. If
                                                                                      storage outdoors is unavoidable,
                     caulking gun.
                                                                                      ensure that the ADVC is kept in an
                     The appropriate mounting kit.                                   upright position.
Unpacking        Tools required:                                              Lift the complete mounting bracket out of the
Procedure         Wrecking bar to remove nails.                              crate.
                  Four D shackles, two slings and crane with a                        Take great care not to drop the
                   safe working load of 300kg to lift the ACR.                         bracket, which weighs nearly 30kg
                                                                                       (66lb), onto the ACR.
                  Screw Driver or Battery Drill with 8mm
                   socket.
                  16mm Spanner or Socket.                                Fit D-shackles to the lifting points on the
                 Procedure:                                                ACR and lift it out of the crate and on to the
                                                                           ground using the crane.
                  Remove top of crate and lift out the control
                                                                          Tip the crate on to its side and remove the
                   cable and bushing boots. Store carefully in a
                                                                           HV cables.
                   clean dry place.
                                                                          Remove the bolts securing the ADVC and
                  Unscrew and remove the four (4) screws
                                                                           slide the unit from the crate.
                   located on the wall of the crate. The
                   mounting bracket, mounting kit and the two                      The control cubicle weighs
                   pieces of wood that the screws have just                        approximately 40 kg (88lb).
                   been removed from are all secured together.
Control Cable    When installing or testing the ACR it is                 To disconnect: (1) Hold the plug by the short
Connection       necessary to connect and disconnect the control             sides and grip hard to release the clips inside
                 cable either from the ACR, the ADVC or both.                the plug (not visible). (2) Wriggle the plug to
                 The control cable is plugged into the base of the           allow the clips to release. (3) Then pull the plug
                 ACR and the other end into the ADVC at the                  out.
                 bottom, right-most socket on the Control and
                 Protection Enclosure (CAPE).
                 To do this successfully requires the correct
                 technique:
                  Power down the control cubicle by switching
                     off all MCBs. This should be done whenever
                     connecting or disconnecting the control cable.
                  To connect: hold the plug by the long sides,
                     check orientation, gently locate it on the socket
                     and push firmly home. Check it has locked by
                     wriggling the plug. If the plug cannot be
                     pushed on with moderate force then it has not
                     been located properly. Heavy force is never               Figure 4: Handling the control cable plug
                     required.
                                                                                                                            3-1
N-Series Automatic Circuit Recloser
                              Never pull the plug out by the
                              cable.
Testing &       The tests can be carried out on site or in the                  The LV auxiliary supply (if applicable) should be
Configuring     workshop as preferred.                                          connected as shown in Figure 6 (page 3-6).
                Unpack the crate as above and put the HV                        Turn on the battery and auxiliary supply circuit
                cables, boots and the control cable in a clean                  breakers at the bottom of the control cubicle and
                safe place where they will not be damaged or                    carry out the following tests:
                soiled. Make a temporary earth connection                       1. Manual trip and close of the ACR.
                between the ADVC and the ACR. 1mm copper
                                                                                2. Insulation test the high voltage connections
                wire is adequate for the purpose.
                                                                                   to earth to check for shipping damage on the
                Raise the ACR using a crane or forklift in order                   high voltage side of the ACR.
                to safely gain access to the bottom of the ACR.                 3. Configure the protection settings.
                Unbolt the cover plate 1 over the switch cable                  4. Perform primary current injection as
                entry module (SCEM) on the bottom of the ACR                       required.
                                                                                5. Perform secondary current injection (if
                                                                                   required by your Authority) using a Test and
                                                                   1               Training Set (TTS).
                                                                                6. Fit and test a radio or modem if required.
                                                                                7. Attend to the battery using the care
                                                                                   instructions given in Battery Care on
                                                                                   page 10-4.
                                                                                          Connecting the batteries with
                                                                                          reverse polarity will cause damage
                and connect the ACR end of the control cable to
                                                                                          to the electronic systems.
                the SCEM.
                Lower the ACR on to props so that the control
                                                                                An application note detailing workshop and field
                cable is not damaged by being caught between
                                                                                test procedures is available. Contact your agent
                the base of the ACR and the floor.
                                                                                or distributor.
                Then connect the ADVC end of the cable to the
                                                                                It may be desirable at this time to fit the cable
                socket at the lower right-hand corner of the
                                                                                tails and surge arresters to the ACR. See
                CAPE located inside the ADVC cubicle. (See
                                                                                Figure 5 (page 3-5).
                Site Procedure, Step 15. on page 3-4.)
Transport to    If the unpacking and testing was carried out in                     Disconnect the control cable from both ACR
Site            the workshop then the ACR and ADVC must be                          and ADVC and put back the cover plate on the
                transported safely to site. It is important the                     bottom of the ACR.
                following steps are carried out:
                 Turn off all ADVC circuit breakers and                         Transport the ACR, ADVC and all parts in a
                    disconnect all auxiliary power supplies.                        safe and secure manner to site.
Site                          If you are replacing a pole-top control            If the auxiliary supply is provided by an
Installation                  cubicle (PTCC) with an ADVC, the                    external VT connected through the ACR,
                              following should be considered:                     there are limitations to the supply ratings of
                                                                                  equipment that customers may fit. In ADVC,
                    The ADVC mounting points will be different1.                 General Specifications See Radio/Modem
                                                                                  Power Supply Continuous Power on
                    The connection to the auxiliary supply enters
                                                                                  page 11-5.
                     the cubicle at a different point.
                                                                                 Unlike the PTCC, the ADVC has locking
                    The earth stud is in a different position.
                                                                                  hinges on the door which prevent the door
                    Accessory cables may need extending.                         from swinging or blowing shut. When you
                    Unlike the PTCC which required an auxiliary                  open the door to 180, it locks into that
                     power supply rating of 50VA, the ADVC                        position. To close the door, disengage the
                     requires 100VA.                                              hinge locks by raising the door slightly
                                                                                  before rotating it.
                     1.   An accessory mounting bracket can be purchased to allow the use of the same mounting holes as were used with the
                          manufacturers PTCC. (Part No. 99800125)
3-2
                                                                                                        Installation
Tools Required      Torque wrench and metric socket set,                   Bushing boot clamping spanner, (supplied
                     normal engineers tools.                                 by the manufacturer).
                    24mm Open ended drive to fit the torque
                                                                            Tools to prepare pole as required.
                     wrench (commonly known as a Claw Foot).
                     This is only required with 630A cable tails            Crane or other lift for ACR and ADVC, four D
                     which screw directly into the bushings and              shackles and slings. A 1m spreader bar is
                     are tightened by a 24mm lock-nut.                       also useful, if the surge arresters are to be
                    Standard 300g cartridge applicator,                     fitted onto the ACR tank, to keep the slings
                     (Caulking Gun).                                         away from the surge arresters when lifting.
Parts Required      Two 20mm galvanised or stainless steel                  connection. See Figure 6 (page 3-6),
(Not supplied by     bolts with washers and nuts etc. to bolt the            Figure 8 (page 3-9) and Figure 9 (page 3-
the                  ACR mounting bracket to power pole. See                 10).
manufacturer)        Figure 7 (page 3-8). If the optional pole
                                                                            20mm sealing cable entry glands to suit
                     clamps have been purchased this is not
                                                                             auxiliary supply mains cables, 16mm sealing
                     required.                                               cable entry glands to suit antenna or
                    Mounting parts for the ADVC. Either 20mm                communications cable as required.
                     steel strapping or 10mm galvanised or
                                                                            Antenna, antenna feeder cable, and surge
                     stainless steel bolts, nuts, etc.
                                                                             arrester as required if a radio is fitted (unless
                    Fixing hardware for the control cable. This is
                                                                             supplied by the manufacturer).
                     a 27mm (1 1/16) diameter sheathed conduit
                     and can be fixed to the pole with ties, straps,        Aluminium jointing paste (250A and 400A
                     P-clips or saddles.                                     cable tails only).
                      Earth wire and lugs for the earthing scheme          Heat shrink or insulating tape (800A cable
                       and parts for LV mains auxiliary power                tails only).
Site Procedure     To erect and test the ACR and ADVC, carry out             P1 1 on the SCEM located inside the
                   the following steps. Mounting details are given in        ACR.
                   Figure 7 (page 3-8):
                                                                                                                           3-3
N-Series Automatic Circuit Recloser
                             Note that the                                and then to the switchgear socket 2        on
                            ADVC mounts                                   the CAPE.
                            have key holes as
                            shown here, so                                                                  2
                            that you can lift
                            the ADVC on to
                                                                       16. For LV mains supply run auxiliary wiring as
                            the mounting bolt
                                                                           shown in Figure 8 (page 3-9). Make the
                            and slide it into position.
                                                                           connection inside the ADVC as shown in
                            When mounting the ADVC to a
                                                                           Figure 6 (page 3-6).
                           wooden pole, use a spirit level to
                           ensure correct alignment, and               17. For LV supply from a dedicated transformer
                           minimise torque on the mounting                 supplied by the utility, connect as shown in
                           brackets.                                       Figure 9 (page 3-10).
                13. Attach the control cable to the power pole         18. For Integrated supply from an external
                    maintaining maximum available separation               transformer, connect as shown in Figure 9
                    from the main earth bond (at 200mm for                 (page 3-10). (See also Auxiliary Power from
                    wood and concrete poles and 150mm for                  Integrated Transformer on page 3-6.)
                    steel poles). Ensure that there is enough          19. Power down the ADVC by switching off all
                    cable available at each end to permit                  MCBs. Note that this should be done
                    connection to the equipment.                           whenever connecting or disconnecting the
                14. Run the earth connections as described in              control cable from the ADVC.
                    "Earthing" - page 3-5.                             20. Fit the batteries if they are not already in
                           It is vital that the earthing scheme            place.
                           is carried out as described.                            Fitting the batteries with reverse
                                                                                   polarity will cause damage to the
                                                                                   electronic systems.
                15. Connect the control cable from the ACR
                    through the base of the ADVC 1                     21. If communications equipment is to be
                                                                           installed go to Communications and
                                                                           Accessories Installation on page 4-1.
                                                                       22. Otherwise go to Testing Your Installation on
                                                                           page 5-1.
Cable Tail      HV cables are supplied in one of two forms:             Push the boot down the cable to a distance
Connections      Fitted with a lug to be bolted to a factory fitted     approx. 1 metre from the termination (place a
                  palm on the end of the bushing (250 or 400A).          small amount of grease on the closed end of
                                                                         the boot to assist the boot to slide down the
                 Fitted with a threaded termination that is
                                                                         cable). Fill the bushing boot with the silicone
                  screwed into the bushing (630A).
                                                                         grease provided, starting at the closed end and
                In both cases the procedure is to attach the             finishing approx. 60 mm from the open end of
                cable to the bushing and then cover with the             the boot. Hint - as you fill the boot with grease,
                bushing boot as detailed in the following                keep sliding it down the cable as this pushes
                sections, refer to Figure 5 (page 3-5).                  the grease up into the boot.
                 The bushing is supplied clean, and is
                                                                        For cables terminated with a screw thread,
                  protected with a plastic cap. Ensure the cap is
                                                                         ensure the thread, locknut and bushing
                  undisturbed and the bushing body and tin
                  plated central conductor or palm are clean and         surfaces are clean and dry. Screw the tail into
                  undamaged. If the bushing has become soiled,           the bushing by turning the whole cable tail.
                  clean it with methylated spirits. Sand or brush        Tighten to 60 Nm using a spanner across the
                  the aluminium palm to remove oxide.                    brass locknut fitted. Take care to apply only
                                                                         twisting forces to the terminal (no shear force)
                 Grease the bushing and the conductor with the
                                                                         because of cable stiffness, cross threading is a
                  silicone grease provided (part number
                                                                         possibility.
                  LUB058044).
                 Unpack the cable tail and bushing boots.              For cables terminated with a lug, smear with
                  Check that the cable termination and the boot          aluminium jointing paste and bolt the lug to the
                  are clean and undamaged. If necessary, clean           bushing palm with the bolt provided and
                  with methylated spirits.                               tighten to a maximum of 62-65 Nm.
3-4
                                                                                                                 Installation
                                                                                   Grease the surface of the bushing, slide the
                                                                                    bushing boot down over the bushing while
                                                                                    rotating the boot to and fro. Fix into place using
                                                                                    the clamping ring and spanner provided. The
                                                                                    bottom of the boot should be firmly seated on
                                                                                    the top of the ACR tank. During the clamping
                                                                                    process silicone may bleed from the top of the
                                                                                    boot where the cable tail comes out. This is
                                                                                    normal and can be assisted by sliding a small
                                                                                    screwdriver into the boot alongside the cable
                                                                                    tail. Silicone grease will also come out around
                                                                                    the bottom of the bushing. This is normal.
                                                                                    Wipe off excess silicone grease with a clean
                                                                                    cloth.
Surge Arrester   The ACR is type tested for Impulse Withstand                     brackets using the holes provided. Top holes are
Mounting and     Voltages up to 170kV depending on the model.                     12mm diameter, side holes are 16mm diameter.
Terminating      See "Ratings and Specifications" - page 11-1                     In this way most types of surge arrester can be
                 When there is a possibility that lightning or                    accommodated.
                 network switching conditions may produce peak                    The brackets are tilted to maximise phase/
                 voltages in excess of 70% of the Impulse                         phase clearance. The user should check that
                 Withstand Voltage, the manufacturer                              phase/phase and phase/earth clearance will be
                 recommends the use of suitably rated surge                       sufficient for their particular surge arresters and
                 arresters connected to each terminal of the                      line voltages. For some types of side clamping
                 ACR.                                                             surge arresters, the phase/earth clearance may
                 The arresters should be mounted on the                           be insufficient at the centre phase on the pole
                 mounting brackets supplied by the manufacturer                   side at higher voltages. In this case the surge
                 and earthed as described in Figure 8 (page 3-9).                 arrester can be mounted on the side of the
                                                                                  power pole or an increased clearance ACR
                              If the arresters are not mounted
                                                                                  mounting bracket fitted.
                             close to the ACR the protection they
                             provide is significantly reduced.                    Connections from the surge arresters to the
                                                                                  cable tails can be made by stripping off the
                 Lightning induced damage to the ACR or ADVC                      cable tail insulation and using a parallel or T
                 voids the warranty if surge arresters are not                    type clamp to make the connection to the cable
                 fitted.                                                          tail. The connection should be made far enough
                                                                                  up the tail so that phase/phase and phase/earth
                 Mounting brackets are provided for surge                         clearances are maintained. The cable tail is
                 arresters on the tank of the ACR. This is                        watertight1, so additional water blocking where
                 illustrated in Figure 10 (page 3-11) and Figure 7                the insulation has been removed is not required,
                 (page 3-8).                                                      however it is good practice to tape the joint
                 The surge arresters can be mounted on top of                     using a bitumen or mastic tape, to maintain the
                 the brackets or clamped to the side of the                       cabling system insulation.
Earthing         Figure 8 (page 3-9) shows the earthing common                    This arrangement earths the ACR frame and the
                 to all installations.                                            surge arresters directly to earth through a main
                                                                                                                                   3-5
N-Series Automatic Circuit Recloser
                  earth bond consisting of a copper conductor of      the ACR frame and control cubicle frame whilst
                  70 sq. mm. Any surges will flow down this path.     surge currents are flowing down the main earth
                            Do not earth surge arresters by a         bond. No other connections to earth from the
                            different path, doing this may            control cubicle are allowed since surge currents
                            cause damage to the control               will also flow in those paths. Follow this
                            electronics or ACR. Also, any             arrangement on both conducting and insulating
                            antenna should be bonded to the           power poles.
                            ACR or the main earth bond.
                  The control cubicle is connected to this main       Keep the main earth bond physically separated
                  earth bond by a tee-off. The control cubicle        from the control cable, as they run down the
                  electronics are internally protected from           power pole, by the maximum spacing available
                  potential differences which may occur between       and at least 150mm.
LV Auxiliary      Where LV mains are connected to the control         cubicle when surge currents are flowing. Fit
Power from        cubicle to provide auxiliary power the              additional LV surge arresters to all the other LV
Mains             connection must connect the neutral of the LV       phases (if they exist), to balance the supply for
                  system to a tee-off from the main earth bond as     other users connected to the LV system.
                  shown in Figure 8 (page 3-9). A low voltage         If local conditions or wiring rules prohibit
                  surge arrester must also be fitted from the LV      bonding the HV and LV systems in this way,
                  phase connection to this tee-off.                   providing the auxiliary supply to the control
                  This connection scheme bonds the LV and HV          cubicle from the LV mains system is not
                  earths and so protects the primary insulation of    possible. Instead, use one of the alternative
                  the auxiliary supply transformer in the control     arrangements detailed below.
LV Auxiliary      Figure 9 (page 3-10) shows wiring and earthing      Figure 9 (page 3-10) shows that the transformer
Power from        if a dedicated transformer is supplied by the       and any steelwork is earthed to the switchgear
Dedicated         utility. Note that this should not be used to       tank and that one side of the transformer
Utility           supply any other equipment without consulting       secondary is earthed to the earth stud on the
Transformer       the manufacturer to ensure that no hazard is        equipment panel inside the control cubicle.
                  caused to the control cubicle electronics.
Auxiliary Power   The manufacturer can provide a dedicated            An external transformer is mounted on the front
from Integrated   voltage transformer outside the ACR tank which      of the tank as shown in Figure 9 (page 3-10)
Transformer       connects directly into the control electronics.     which also shows suggested HV connections.
                  This is called an Integrated Auxiliary Supply.      The secondary of the external transformer
                                                                      connects into the SCEM on the underside of the
3-6
                                                                               Installation
ACR. To connect the transformer secondary,        No additional earthing for Integrated Auxiliary
remove the SCEM compartment cover plate,          Supply is required in addition to the common
pass the cable which is pre-fitted with a cable   earthing shown in Figure 9 (page 3-10).
gland through the hole, secure the gland,                   If the secondary of the VT is
connect the auxiliary supply to the screw                   earthed, electronics damage will
terminal block on the SCEM and replace the                  occur.
compartment cover.
                                                                                                3-7
N-Series Automatic Circuit Recloser
3-8
                                          Installation
                                                         3-9
N-Series Automatic Circuit Recloser
3-10
                            Installation
                                       3-11
N-Series Automatic Circuit Recloser
3-12
                                                 Communications and Accessories Installation
Radio Antenna   Mount the antenna and run the antenna feed to          antenna, enters the cubicle via the 16mm hole
                the ADVC or run external communications cable          provided on the underside of the cubicle.
                to the ADVC. The communication cable/radio
                           Comms cable/
                           Radio Antenna
                           Entry
                                      Underside of
                                      cubicle
Protection of   It is highly advisable to connect a gas discharge      A feed-through or bulkhead type arrester fitted
Radio           type of surge arrester in the antenna feed to the      to the bottom of the control cubicle is ideal. If
Equipment       radio. Failure to do so will result in loss of radio   fitted internally the surge arrester should be
                and control electronics protection which could         earthed to an equipment panel mounting stud by
                lead to complete electronic failure due to
                                                                       the shortest possible wire. Holes are provided
                lightning activity.
                                                                       for a bulkhead surge arrester.
                           A failure of this nature is not covered
                           by the products general warranty            If a surge arrester is not fitted then the co-axial
                           arrangements.                               earth screen should be earthed to the
                                                                       equipment panel by the shortest possible wire.
                                                                                                                        4-1
N-Series Automatic Circuit Recloser
The Customer      At the top of the customer equipment                   Equipment installed in this compartment can be
Compartment       compartment is an accessory mounting rail for          powered from the terminal block also mounted
                  installing customer equipment and accessories.         on the rail.
           Radio
           Supply
           (+)Terminals
           IOEX
           Supply
           (+)Terminals
                          Heater
                          Supply
                          (+)Terminal
                          (-)Terminal Earth
                                      (-)Terminals
Connecting to     Insert a 4 mm screwdriver or similar tool into the     be inserted. Release and remove the
the Terminal      square hole above the appropriate wiring point         screwdriver then gently tug the inserted cable to
Block             on the terminal block. Angle the head of the           ensure that it is firmly gripped.
                  screwdriver slightly upwards and push it in, then
                  lever it downwards.
Radio/Modem       The battery-backed power supply for a radio/           If the auxiliary power fails, battery power can be
Power             modem is provided on the terminal block as             conserved by automatically shutting down the
                  described above1. See Figure 12 (page 4-2) for         radio/modem power supply. The shutdown takes
                  the correct radio connection point.                    place after the radio holdup time, set in System
                  The radio/modem power supply voltage is set by         Status  RADIO - S: Radio Hold 60 min. page by
                  the user in System Status                              the user, has elapsed. If the Radio Hold time is
                  RADIO - S: Radio Supply 12 Volts page. This is       set to zero then the radio supply will not
                  a password protected parameter.                        shutdown, except under special circumstances
4-2
                                               Communications and Accessories Installation
                or until the unit powers down. The radio/modem      without passwords in System Status
                power supply is restored when the auxiliary          RADIO - S: Radio Supply ON page. If the radio
                supply returns to normal.                           supply has shutdown it will be indicated on 
                The radio/modem power supply can be turned          System Status: RADIO - S.
                on and off by the operator for radio maintenance
IOEX2           The Input Output Expander (IOEX2) module            enclosure which is mounted on, and earthed via,
Installation    provides optically isolated inputs and voltage      the DIN rail in the customer enclosure as shown
                free outputs to allow connection to external        in the following picture: (See Appendix B for
                devices. It is installed in a die cast, sealed      IOEX2 dimensions.)
                 Earth
                 (-)Terminals
                        IOEX2 Power Supply
                The IOEX2 is suspended from the DIN rail by         To fit the IOEX2:
                two fittings on its rear surface:
                                                                    1   Holding the IOEX2 perpendicular, place the
                                                                        upper hooks of the hanging fittings over the
                                                                        top edge of the DIN rail.
                                                                    2   Push the IOEX2 firmly against the back
                                                                        surface of the Customer compartment until
                                                                        the lower end of the hanging fittings engage
                                                                        with the bottom edge of the DIN rail.
                                                                    3   Push the green/yellow earth terminal firmly
                                                                        on to the DIN rail until it is engaged at both
                                                                        the top and bottom.
                                                                    4   Connect the IOEX2 supply using the cable
                                                                        provided to the terminal block connection
                                                                        point      as shown in Figure 12 (page 4-2).
Communication   The ADVC has numerous communications ports          Not all ports are available for use at the same
Ports           available to the user:                              time. The ports can be enabled/disabled via
                                                                    WSOS.
                                                                    Permanently available ports are:
                                                                     RS232 Port D
                                                                     Serial Port E (dedicated to the OCP)
                                                                     10 base T Ethernet
                                                                    Any 3 of the 5 following ports are available:
                                                                                                                    4-3
N-Series Automatic Circuit Recloser
                       RS 232 Port A (enabled by default)             The ports typically have three uses:
                       RS232 Port B (enabled by default)
                                                                           WSOS communications
                       RS 232 Port C (enabled by default)
                       RS485 (disabled by default)                        SCADA communications
                       V23 FSK (disabled by default)                      IOEX communications
RS232           Four RS232 ports (A to D) are provided to              telephone dial up modem, or RS232 radio
                connect to conventional modems that provide            modem. All four ports have standard 9 pin D
                the correct signalling for the communications          male connectors and have the following pin
                network used, e.g. optical fibre modem, or             connections:
                                                                                                Port
                    RS232
                               Direction             Use
                    Pin No
                                                                            A             B              C          D
6 Not connected
9 Resered Yes
                All RS-232 ports are not isolated from one                       Use of serial ports to connect
                another or from the controller electronics. They                 directly to other devices outside
                therefore can only be connected to devices                       the controller can cause damage
                inside the controller that are powered by the                    and void warranty. If connections
                controller radio supply, including modems,             to other devices are required then isolation
                optical isolators, and radios.                         interfaces MUST be used.
3 Not connected
5 Not connected
7 Not connected
9 Shield
4-4
                                             Communications and Accessories Installation
V23 FSK      An in-built FSK modem provides half-duplex           The Push to Talk (PTT) signal is used to key up
             V23 signalling at 1200 bits per second. This         a radio transmitter. PTT is implemented using a
             interface is primarily designed for use with voice   Field Effect Transistor (FET) with an on
             frequency radio systems and provides additional      resistance of 3.3 ohm. When PTT is asserted
             signals for this purpose.                            the transistor is turned on and connects the PTT
             The V23 connector is RJ45:                           signal to 0V.
                                                                  A busy signal can be provided by the radio to
                                                                  indicate receive channel busy. High level is
                                                                  +2.0V to +3.3V, and low level is 0V to +0.5V.
                                                                  The busy signal should be driven by an open
                                                                  collector output or current limited to 10 mA.
                                                                             Levels in excess of 13V should
                                                                             not be applied. The FET is rated for
                                                                             a maximum of +32V and negative
                                                                             voltages are not permitted.
             Pin   Direction    Use                               Transmit and receive are unbalanced signals
                                                                  relative to 0 volts and are not isolated. If a
             1     To ADVC      Receive, 10 kOhm impedance
                                                                  DC level is imposed by the radio on the
                                Sensitivity 0.1  2V pk-pk
                                                                  transmit line then this should be less than
             2                  0 Volts (ground/earth)            2.5 VDC.
7 Not connected
9 Shield
7 Not connected
8 Not connected
Windows      Windows Switchgear Operating System                  the port are 57600 baud, 8 bit, no parity, and 1
Switchgear   (WSOS) is a software package available on a          stop bit. WSOS communication set up
Operating    PC that enables configuration, control and           parameters are user configurable.
System       monitoring of the controller.
(WSOS)       The controller has its hatch port physically
             connected to Port A via an interconnecting
             cable. The default WSOS communications via
                                                                                                                4-5
N-Series Automatic Circuit Recloser
4-6
                                                                              Testing Your Installation
Powering Up    1   Turn on the battery circuit breaker,            3   Turn on the VT supply to cubicle circuit
the ADVC                                                               breaker if the auxiliary supply is being
                                                                       provided by an integrated transformer.
                                                                   4   Powering up the ADVC with the ACR
                                                                       connected will cause the ADVC to read data
                                                                       from the ACR. This will take up to 60
                                                                       seconds during which the message:
                                                                       READING - Do NOT disconnect
                                                                       Switchgear will flash at the top of the
                                                                       display. The System OK LED on the OCP
                                                                       should flash to indicate that the ADVC is
                                                                       powered and functioning.
                                                                   5   If the configuration file containing the
                                                                       settings to be used in operation has not
                          The batteries are capable of                 previously been loaded, it should be loaded
                          supplying very high currents.                now using WSOS, or the settings should be
                          Always turn off the battery circuit          entered via the OCP.
                          breaker before connecting or             The ACR and ADVC are now ready for
               disconnecting the batteries in the cubicle.         operation. Prior to energising the ACR, you
               Never leave flying leads connected to the           should perform the following checks to confirm
               battery.                                            that the equipment is fully operational and
               2 Turn on the auxiliary supply circuit breaker if   properly configured.
                  the auxiliary supply is being provided by
                                                                             If you are familiar with navigating
                  either an LV mains or dedicated auxiliary
                                                                             Operator Control Interface display
                  transformer.
                                                                             groups, proceed with the checks
                                                                             described below. Otherwise, please
                                                                   read the chapter, Operator Control Panel on
                                                                   page 7-1 before continuing.
                                                                                                                          5-1
N-Series Automatic Circuit Recloser
                    Ensure the Aux Supply status is Normal. If                         recent event) contains the Battery OFF
                    not, you cannot perform the remaining                              event.
                    battery checks at this stage.                                             When the battery status is Low Volts,
                3   Switch the battery circuit breaker off and                                but the voltage is close to the normal
                    check that the battery status changes to                                  range lower limit, the battery will
                    OFF. (Allow 3 - 5 seconds.)                                               charge up when the auxiliary supply is
                                                                                   turned on. If the voltage is very low, replace the
                4   Go to page EVENT LOG and check that                          battery.
                    the bottom line of the display (the most                       5 Switch the battery back on.
Connection      1   In the System Status group, go to page                              Invalid) then re-plugged (Switch status
between the          SWITCHGEAR STATUS - S                                             Connected), the Switch Data status will
ADVC and the    2   Check the Switch status.
                                                                                        remain Invalid during the time taken to read
ACR                                                                                     switch data from the SCEM, and a message
                                                                                        to that effect is displayed.
                 - - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S              If Switch Data remains Invalid, check the
                 Work Tag OFF                SF6 Normal 37kPag                          following:
                 Aux Supply Normal           Battery Normal 27.5V
                                                                                       Examine each end of the control cable,
                 Switch Connected            Switch Data Valid
                                                                                        checking for bent or broken pins and rectify if
                                                                                        found. Also check the socket at both the
                    It may be in either of two states: Connected                        SCEM and P1 in the ADVC for damage.
                    or Disconnected. Connected is the normal                         If the pins are OK, the cable itself may be
                    state. If Switch is Disconnected, check the                       faulty1, therefore test the control cable for
                    control cable at both ends. If the status                           continuity.
                    remains Disconnected, the cable may be
                                                                                       If Switch Data remains Invalid, check the
                    faulty.
                                                                                        power supply to the SCEM by checking the
                3   Check that the Switch Data status is Valid.                         voltage on Pins 2 and 5 of the control cable.
                    In normal operation, if Switch status is                            The voltage should be approximately 36VDC
                    Connected, Switch Data will be Valid.                           if the auxiliary supply is present or
                    If the control cable has been unplugged                             approximately 26VDC if running on
                    (Switch Disconnected, Switch Data                                 batteries.
Auxiliary       1   In the System Status group, go to page                            switch off the VT supply to cubicle circuit
Supply               SWITCHGEAR STATUS - S                                           breaker. Check that the Aux Supply status
                                                                                      changes to Fail. (Allow 3 - 5 seconds.)
                2   Check the Aux Supply status.
                                                                                   4 Check that the battery voltage has dropped
                                                                                      by approximately 2V, and that the battery
                 - - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S            remains in Normal state.
                 Work Tag OFF                SF6 Normal 37kPag                                     If the battery voltage continues
                 Aux Supply Normal           Battery Normal 27.5V                                  dropping, and the battery state is
                 Switch Connected            Switch Data Valid                                     LOW, the batteries may be flat. If
                                                                                                   the batteries are flat, replace
                                                                             T
                                                                                   them.
                    he auxiliary supply may be in either of two
                    states: Normal or Fail.                                        5    Go to page EVENT LOG and check that
                    Ensure the battery status is Normal.                                the bottom line of the display (the most
                3   If using LV auxiliary supply, switch the                            recent event) contains the Aux Supply Off
                    auxiliary supply off, OR if using integrated                        event.
                    auxiliary supply and the VT is energised,                      6    Switch the auxiliary supply back on.
                    1.   It is possible for the Switch status to be showing Connected though thecontrol cablet core is faulty, causing the Switch
                         Data to show Invalid.
5-2
                                                                              Testing Your Installation
                   The tag has two possible settings: Applied or    6   Go to page EVENT LOG and check that
                   OFF. OFF is the default.                             the bottom line of the display (the most
               4   Press the SELECT key to select the work tag          recent event) contains the Work Tag Applied
                   field.                                               event.
               5   Press  to change the setting to Applied
                                                                    7   Return to page
                   and then press ENTER to activate the setting.
                   The message: WORK TAG APPLIED will                  SWITCHGEAR STATUS - S and change the
                   flash at the top of the display.                     setting back to OFF.
Power Flow     The ACR is a symmetrical device meaning that         Power flow direction setting is used to
Direction      either side can be connected to the power            determine:
Setting        source.
                                                                       Whether the source or load corresponds to
               Consequently, after installation, the controller         (1) or (2) on the voltage measurement
               must be configured to designate the source               displays.
               side.                                                   Which direction is positive power flow for use
               The power flow direction is configured on page           on the kWh totals in the Maximum Weekly
                SYSTEM STATUS - PHASE VOLTAGE and POWER                Demand display and APGS.
               FLOW:                                                   Which is the source or load for Live Load
               and may be either                                        Blocking.
               Source 1, Load 2 or Source 2, Load 1.                   Which is the source or load for Directional
               When changed, this reverses the power flow               Blocking/Protection.
               direction but not the phasing.                       
Tripping and   If system conditions allow, tripping or closing      2   Tripping and closing should cause the LED
Closing        can be carried out at this point.                        on the appropriate TRIP/CLOSE button to
               1   Trip and close the ACR from the ADVC. See            illuminate which should agree with the
                   Operator Control Panel on page 7-1. for            position of the pointer on the ACR.
                   information on the Trip and Close controls.
Enable/        For each of the CLOSE and TRIP keys in turn, test               When the CLOSE or TRIP mechanism is
Disable        ENABLE and DISABLE by:                                          disabled, the message
Switches       1   Disable either mechanism e.g. CLOSE.                        The TRIP or CLOSE circuit is isolated
                                                                                                                      5-3
N-Series Automatic Circuit Recloser
                will flash in every display page title, alternately               mechanism the Event Log should display
                with the actual title of the page.                                Trip Coil Isolate.)
                                                                            3     With both mechanisms disabled, check that
                2     Go to page EVENT LOG and check that                       pressing each of the CLOSE and TRIP keys
                      the bottom line of the display (the most                    is ineffective.
                      recent event) contains the Close Coil Isolate         4     Enable both CLOSE and TRIP mechanisms.
                      event. (For the same test of the TRIP
Mechanical      1     Use a hook stick to manually trip the ACR             2     Go to page EVENT LOG and check that
Trip                  via the manual trip lever.                                  the bottom line of the display (the most
                                                                                  recent event) contains the Mechanical Trip
                                                                                  event.
Secondary       If secondary injection testing is required to test          If tripping and closing of the ACR is possible and
Injection       protection settings but operation of the ACR is             preferred, perform secondary injection testing
Testing         not possible, secondary injection can be                    with the TTS in parallel mode.
                performed with a suitable current injection set                           Any secondary injection must use a
                with the Test and Training Set (TTS) in                                   frequency which corresponds to the
                standalone mode connected to the ADVC, and                                frequency set in the controller.
                the ACR disconnected.
Power Flow      This test is to ensure that the source and load             2     With the recloser energized but still open, in
Direction       designations are correct.                                         System Measurement, go to  SOURCE
Testing                       This test is valid only if the ACR is               SIDE VOLTAGES - M
                              being supplied from a single source           3      Check the source side voltages - either
                              and can be energised before closing.                phase to ground or phase to phase e.g.
5-4
                                                                                     Testing Your Installation
On Load   Once the ACR is closed and taking load, the                      Use this page to confirm that system
Checks    following on-load checks can be carried out. To                  measurements and power flow signs are as
          confirm correct operation, check the current                     expected.
          against a known reading.
                                                                           3   Go to the System Measurement page
          1   Go to the System Measurement page                              SOURCE VOLTAGE LOAD e.g.
              CURRENT e.g.
                                                                           SOURCE - - - - - - - - VOLTAGE - - - - - - - - - LOAD M
           - - - - - - - - - - - - - CURRENT - - - - - - - - - - - - - M   11000 Volt                 A-P              11000 volt
          A Phase         123 Amp       Earth                     6 Amp    11000 Volt                 B-P              11000 volt
          B Phase         128 Amp        Ipps                              11000 Volt                 C-P              11000 volt
          C Phase         121 Amp       Inps
                                                                                                                                5-5
N-Series Automatic Circuit Recloser
5-6
                                                                          Control Electronics Operation
Sealing &      All cubicle vents are screened against vermin          Condensation can be expected to form under
Condensation   entry and the cubicle door is sealed with              some atmospheric conditions such as tropical
               replaceable foam tape.                                 storms. However, condensation will be on metal
               Complete sealing against water entry under all         surfaces where it is of no consequence. The
               conditions is not expected e.g. during operation       water runs out in the same way as any other
               in the rain. Instead, the design is such that if any   water entering the cubicle. Condensation will
               water does enter, it will run out of the bottom        run out of the bottom or be dried by ventilation
               without affecting the electrical or electronic         and self heating.
               parts. The extensive use of stainless steel and
               other corrosion proof materials ensures that the       All electronic modules are fully sealed and have
               presence of moisture has no detrimental effects.       self heating.
Auxiliary      The auxiliary supply is used to maintain charge        A low power mode is activated when the
Power Source   on the sealed lead-acid batteries that provide         batteries are nearly exhausted due to loss of the
               standby power when auxiliary power is lost. The        auxiliary supply. This mode minimises power
               controller monitors the status of both the             consumption while still maintaining basic
               auxiliary and battery supplies.                        functionality.
Controller     The controller consists of 3 modules (See                  Basic Display Unit (BDU).
               Figure 17 (page 6-3):                                  The ADVC block diagram is given in Figure 18
                Power supply unit (PSU)                              (page 6-4).
                Control and protection enclosure (CAPE)
PSU Module     The PSU module supplies power to the CAPE,             (country customizable). The incoming power is
               and to the customer compartment. The PSU               protected and isolated by a circuit breaker. The
               module:                                                supply from the batteries is protected and
                connects to the batteries                            isolated by a circuit breaker.
                controls the supply from external auxiliary
                                                                      The electronic components are contained inside
                 sources
                                                                      a housing that provides environmental
                filters these supplies and manages the               protection, sealing and EMI shielding. The
                 battery power level.                                 power outlet, circuit breakers and switches are
               It also performs battery testing and has a non-        easily accessible when the ADVC door is
               volatile, real time clock. A general purpose           opened. The batteries are located and retained
               power outlet is available as an optional extra         on the exterior top of the PSU module.
CAPE Module    The CAPE Module comprises two printed circuit          provides EMC shielding for the CAPE
               board assemblies and the trip and close                electronics.
               capacitors housed in a die-cast aluminium
               enclosure. The two printed circuit board               The PCOM is the heart of the ADVC and
               assemblies are:                                        includes the data acquisition hardware
                                                                      (including a powerful Digital Signal Processor)
                PCOM: Protection and Communication
                                                                      and communications hardware (Ethernet,
                 Module
                                                                      RS232, RS485 and V23). All user-interface,
                SWGM: Switchgear Module
                                                                      measurement, protection, communication and
               The CAPE enclosure is manufactured from                control functionality is provided by software
               pressure die-cast aluminium. The front surface         running on the PCOM. The PCOM includes a
               with the user and switchgear connectors, and           PowerPC microprocessor, a DSP, an FPGA, 16
               the rear surface, are gasketed to provide an           Mbytes of flash memory and 24 Mbytes of RAM
               IP65 Degree of Protection. The enclosure also          memory.
                                                                                                                    6-1
N-Series Automatic Circuit Recloser
                  The SWGM contains the switchgear interface          protection and filtering devices and high voltage
                  hardware, SCEM interface hardware, EMC              inverters for the trip and close capacitors.
Operator          The operator interface is provided by a separate    can be latched open, is the usual access point
Interface/ Door   module - the basic display unit (BDU) with its      to the OCP.
Assembly          own processor. The BDU comprises the
                  electronics compartment cover, an operator          When you are commissioning the ADVC, you
                  control panel (OCP) with LCD display, a             can lock the door open and swivel the OCP
                  membrane keyboard and its controlling               open 90 degrees to the door. See Figure 17
                  microprocessor and the WSOS communications          (page 6-3). This allows you to gain access to the
                  port.                                               OCP at the same time as commissioning the
                  The BDU is attached to the door of the cubicle      equipment in the customer compartment.
                  and the operator control panel (OCP) can be
                  accessed through a hatch in the front door.         The BDU plugs into Port E of the CAPE and
                  Under normal circumstances the hatch, which         uses this port for its power and communications
WSOS Interface    Connect your PC serial port to the maintenance      DB9 male to DB9 female, straight-through
                  port provided below the OCP. Use an RS232,          cable.
Customer          The compartment is fitted with a panel tray that    a terminal block for the radio supply and power
Compartment       facilitates the mounting of your equipment e.g. a   for accessories such as an IOEX. An accessory
                  radio or modem including any special interfaces.    heater can also be fitted which is controlled by
                  See Figure 17 (page 6-3). The compartment has       the PSU.
6-2
                                                               Control Electronics Operation
                                                                                               6-3
N-Series Automatic Circuit Recloser
6-4
                                                                                           Operator Control Panel
Description   The operator control panel (OCP) is the user                   OCP turns ON automatically when the hatch is
              interface to the basic display unit (BDU) which is             opened, or if the door is opened and the panel is
              mounted on the door of the ADVC.The OCP                        repositioned as shown in Figure 17 (page 6-3)
              consists of a four-line liquid crystal display                 and OFF when it is closed. The OCP also turns
              (LCD) and keypad with switches and light                       OFF automatically if no keys are pressed for 10
              emitting diodes (LEDs), which are used to select               minutes. Pressing any key for 1 second will
              and monitor the functionality of the ACR. The                  reactivate it.
2 17 16 14
                                                                                      15                             13
                         3
6 12 11
5 4
7 9 8 10
                       Close key          Generates a Close request to the CAPE when the OCP is active. A red LED is
              2
                                          embedded in the key.
                       Enable/       Disables the Close key. When the switch is in the isolate (Disable)position the close coil
               3
                       Disable Close in the ACR is electrically disconnected from the control electronics. Thus the switch
                       switch        provides a physical isolation point for the control circuitry. The ACR cannot be closed
                                     and an audible alarm in the OCP will sound. The Close key operates normally when the
                                     switch is in the Enable position.
                       Trip key           Generates a Trip request to the CAPE when the OCP is active. A green LED is
              4
                                          embedded in the key.
                       Enable/            Disables the Trip key. When the switch is in the isolate (Disable) position the trip coil in
               5
                       Disable Trip       the ACR is electrically disconnected from the control electronics. Thus the switch
                       switch             provides a physical isolation point for the control circuitry. The ACR cannot be opened
                                          and an audible alarm in the panel will sound. The Trip key operates normally when the
                                          switch is in the Enable position.
                       Custom Menu Gives access to the custom menu which was configured using WSOS5. The custom
               6       key         menu is configured to provide a regular, updated data display by allowing a cycle of up
                                   to 12 screens. See Custom Menu on page 14-7.
                       System OK          The red System OK LED flashes while the BDU is ON.
              7
                       Enter key          Press this key in order to commit a setting change that has been made. (Unlike the
               8
                                          adjacent Quick Keys, the ENTER key is not configurable.)
                       Configurable       Default linkage is to AUTO ON/OFF. See Quick Keys on page 7-4.
               9
                       Quick Key
                                                                                                                                  7-1
N-Series Automatic Circuit Recloser
                        Configurable   Default linkage is to PROT GROUP. See Quick Keys on page 7-4.
                 10
                        Quick Key
                        Configurable   Default linkage is to EARTH PROT. See Quick Keys on page 7-4.
                 11
                        Quick Key
                        Configurable   Default linkage is to LOCAL/REMOTE. See Quick Keys on page 7-4.
      11         12     Quick Key
                 13
                        RIGHT scroll    Select the next screen in a display group or, if a setting is selected, increase its
                        key            value.
                        SELECT key     Press to SELECT a setting.
                 14
                 15
                        LEFT scroll     Select the previous screen in a display group or, if a setting is selected, decrease
                        key
                                       its value.
                        MENU scroll    Displays the first page of the next group. Pressing the MENU key after changing a
                 16
                        key            setting causes the setting change to take effect.
                        ALT            The alternative function key gives access to an alternative Event Log display.
                 17
                           As well as each isolate/enable               while the ACR is tripped will prevent the
                          switch affecting its associated               operation of the CLOSE button thus preventing
                          button, isolating the TRIP button             a manual close on to a fault.
Display         The OCP displays are organized into logical             Each page consists of fields. A field may contain
Groups          groups called Display Groups. Within each               either:
                group is a menu of pages and some pages have             a setting, which can be changed - ON/OFF
                sub-pages.                                                is the most common; or
                                                                         a status.
                (There are labels similar to that shown below
                affixed to the door of the ADVC.)                       .
7-2
                                                                                         Operator Control Panel
Custom Menu      It is possible to configure a custom menu                   more information. Where a custom menu has
                 comprising those display group pages which are              been configured, you access it by pressing the
                 particularly required, or those used most                   Custom Menu button on the OCP.
                 frequently. Please see the Operation Manual for
Operator         Find the display page containing the setting to             4   Press SELECT to highlight the setting. A
Settings         be changed:                                                     highlighted setting blinks.
                 1   Press the MENU key to display the group                 Alternatively, if a QUICK KEY is linked to the
                     you require.                                            setting, you can use it to go directly to relevant
                                                                             display page where you will find the highlighted
                 2   Communications Group (only) is divided into             setting. (See Quick Keys on page 7-4.)
                     subgroups for different protocols. Press                5   Once you have selected the setting to be
                     SELECT to display the subgroup you
                                                                                 changed, use  or  to change its
                     require.
                                                                                 setting.
                 3   Press  to display the page you require.                6   Press ENTER to activate the new setting.
Password         Some settings are password protected. You will              4. Press Enter.
Protected        be prompted for a password before you can
                 change the setting. To enter the password:                  While the operator panel is ON you will not be
Settings
                                                                             required to enter the password again.
                 1. Press either of the  keys until the
                 first character of the password is displayed.               The default factory password is AAAA but you
                                                                             can change it using the Windows Switchgear
                 2. Press the SELECT key.                                    Operator System (WSOS) program. The factory
                 3. Repeat Steps 1 and 2 until the password is               password does not have to be remembered -
                 complete.                                                   the controller prompts you for it automatically.
Protection       Protection settings are password protected. To              When you have completed making all the
Settings         change a protection setting, follow the steps               setting changes you require, press ENTER. The
                 detailed in the Operator Settings section above             following text will be displayed:
                 but, in addition, enter the password when
                 prompted. When you have completed the                       CHANGED ACTIVE PROTECTION SETTING
                 setting change by pressing ENTER, the                                      [A]
                 following message will flash at the top of the
                                                                             The changed active PROTECTION SETTINGS
                 screen:
                                                                               are now in service. Select the MENU or
                     Active Protection Setting has changed.                           ENTER key to continue.
                 At this point, the changed setting will be                  The changed settings are now in service. Press
                 displayed but not in service. If further setting            MENU or ENTER to return to the normal menu
                 changes are required, they can be made now.                 display.
Page Layout      The display area consists of four lines, each               indicating the display group to which the page
                 forty characters long.The top line of the display           belongs:
                 is the page title. To the right of the title is a letter,
                                                                                                                            7-3
N-Series Automatic Circuit Recloser
                S           System Status Display Group                           The next three lines are the data on display.
                                                                                  Most pages have six data fields.
                E           Event Log
C Communications Setup
Quick Keys      The operator settings that you will frequently                    Otherwise, any one of the following settings can
                change can each be linked to a Quick Key. You                     be linked to one of the four Quick Keys:        .
Earth Prot
Live Block
Using a Quick   1     Press a Quick Key at any time to display the                    selected:
Key                   relevant page, with the linked setting
7-4
                                                                            Operator Control Panel
2    Press the same Quick Key again to display                     return to the page that was displayed when
     the next setting option for that setting.                     you first pressed the Quick Key.1
     Repeat until you have displayed the setting
     you require.                                             Whenever a Quick Key is in use the            
                                                              and SELECT keys are disabled.
3    Press the ENTER key to activate the
     displayed setting AND, after a short delay, to
1. A particular option may not be available to the operator if it has been disabled on the SYSTEM STATUS-OPTIONS page
                                                                                                                      7-5
N-Series Automatic Circuit Recloser
7-6
                                                                                                             Event Log
8 Event Log
                When the status of the control electronics or                  Events are dated, time stamped to a 10ms
                switchgear changes, events are generated                       resolution and displayed in the order in which
                which are recorded in an Event Log for display                 they occurred.
                to the operator. Examples of such events are                   The  key scrolls the display downward to
                Load Supply On or Lockout.                                 show older events, the key scrolls the
                Events are viewed on the Event Log pages and                   display upward to show more recent events.
                can also be up-loaded and viewed with the                      Pressing the  key removes the title of the
                Windows Switchgear Operating System.                           display to make more room for events. The title
                The event log display looks like this:                         will only be restored when the event log is
                                                                               selected again from the top level menu.
                 - - - - - - - - - - - - -EVENT LOG - - - - - - - - - - - -E
                10/01/01 12:09:02.06 Battery Normal
                10/01/01 12:09:03.95 Panel close req
                10/01/01 12:09:37.95 Load Supply ON
Display         The event log display will update automatically                events occur they are entered at the bottom of
Updating        with new events, provided the most recent event                the screen and the older events are scrolled up.
                is on the bottom line of the screen. When new
Event Log       Each event occupies one line of the event log.                    the event description.
Format          The standard display contains (reading from the                Additional information e.g. event source is
                left):                                                         recorded and can be made visible if you press
                   the date of the event,                                     the ALT key while the event is displayed.
                   the time of the event, and
Using the ALT   If the Alt key is pressed whilst the event log is on           Additional event details are available where the
Key             display, the date and time details may be                      combination of the source plus event description
                replaced with extra information that includes, at              alone will not precisely identify the event e.g.
                far left, the event source and followed by, if                 protection events or events sourced to WSOS.
                applicable, additional event details. Examples of              Examples of additional details are:
                source codes are:
                                                                                the protection group
                                                                                curve
                Identifier          Event (settings change) source
                                                                                trip number
                WSOS                Windows SOS change                          port identification
                                                                                protocol.
                OCP                 Operator control panel change
Typical Event   A typical sequence of events for a phase/phase                 Reset Time has expired, as shown in Figure 21
Log Displays    fault, which had instantaneous protection on the               (page 8-2).
                first trip and inverse time protection on the
                second trip, with two trips to lockout might be as
                shown in Figure 20 (page 8-2).
                However, if the fault was cleared after the first
                trip has occurred, the controller will generate a
                Sequence Reset event once the Sequence
                                                                                                                            8-1
N-Series Automatic Circuit Recloser
- - - - - - - - - - - - - - - - - - - - - - - EVENT LOG- - - - - - - - - - - - - - - - - - - - - E
- - - - - - - - - - - - - - - - - - - - - - - - EVENT LOG- - - - - - - - - - - - - - - - - - - - - E
8-2
                                                                                  Power System Measurements
Power System   The controller must be set for the correct power               This is set on page
Frequency      system frequency  either 50 or 60 Hz.                         SYSTEM STATUS - PHASE VOLTAGE and POWER
                                                                              FLOW
Real Time      The first five screens of the System                               The Positive Phase Sequence Current
Displays       Measurements group contain real time displays.                     (IPPS) and Negative Phase Sequence
               They are:                                                          Current (Inps).
               1    System Measurements
               2    Current (includes phase angles)                             - - - - - - - - - - - - - CURRENT - - - - - - - - - - - - - M
               3    Voltage                                                    A Phase         123 Amp       Earth                    6 Amp
               4    Sequence Voltage                                           B Phase         128 Amp        Ipps                       120
                                                                               C Phase         121 Amp       Inps                         10
               5    Power
               The ninth screen, Maximum demand Indicator,                       Voltage
               also contains some real time data.                                 The voltages displayed can be either phase
               Data displayed is as follows:                                      to phase or phase to earth.
                                                                                  This is a selectable item from
                   System Measurements
                                                                                  page
                    This is a summary page. The current and
                    voltage values displayed are an average of
                                                                                   SYSTEM STATUS - PHASE VOLTAGE and
                                                                                  POWER FLOW: Display Ph-Ph Vol
                    the three phases.
                    Frequency is measured on the first available
                    bushing. Frequency is Unavailable if all                   SOURCE- - - - - - - - - VOLTAGE - - - - - - - - - LOAD M
                    bushings are dead.                                         11000 Volt                 A-P               11,000 Volt
                                                                               11000 Volt                 B-P               11,000 Volt
                 - - - - - - - - - SYSTEM MEASUREMENTS - - - - - - - - M       11000 Volt                 C-P               11,000 Volt
                Current         100 Amp      Power (P)         1638 kW
                Voltage 6350 Volt            Power (Q)       476 kVAR
                Frequency 50.0Hz             Power Factor          0.86          Sequence Voltage
                                                                                  This screen displays the Zero, Positive and
                                                                                  Negative phase sequence voltages.
                   Current
                    This screen displays, for each phase, the                   - - - - - - - - - - SEQUENCE VOLTAGE- - - - - - - - - - M
                    current and phase angle.                                   Uzps           100 Volt
                    The earth current.                                         Upps 11,000 Volt
                                                                               Unps           200 Volt
1. The ADVC measures the temperature of the SCEM in the ACR and from that, calculates the switchgear temperature.
                                                                                                                                           9-1
N-Series Automatic Circuit Recloser
                    Power                                                            Real Power (kW), this is a signed quantity
                     This screen displays real and reactive                           unless Power Flow Unsigned has been
                     power, as well as the power factor on a per                      selected on page
                     phase basis.                                                      SYSTEM STATUS - PHASE VOLTAGE and
                                                                                      POWER FLOW: Power Flow Signed/Unsigned
                                                                                      Power Factor (PF), this is an unsigned
                  - - - - - - - - - - - - - - POWER- - - - - - - - - - - - - - M      quantity.
                 A P              540 kW        Q         158 kVAR PF 0.86
                 B P              551 kW        Q         167 kVAR PF 0.86
                 C P              547 kW        Q         151 kVAR PF 0.86
9-2
                                                                                               Maintenance
10 Maintenance
              Maintenance can be carried out using standard                   Be careful to ensure that if working
              electricians and mechanics tools.                             on the ADVC with the door open in
                                                                              heavy rain, water does not enter
                                                                              the circuit breakers or general
                                                                              power outlet.
ACR           No user maintenance of the ACR mechanism is           Every five years the bushing boots should be
Maintenance   required.                                             checked, cleaned if necessary and the pointer
              The ACR should be returned to the                     checked to ensure it is free from mechanical
              manufacturer for refurbishment if the                 obstructions. In areas of high atmospheric
              mechanical duty or breaking duty is exceeded.         pollution more frequent cleaning may be
              This is checked by examining the remaining            appropriate.
              contact life on the Operator Control Panel.           At suitable intervals check the gas low alarm is
              When the remaining contact life in any phase          not showing on the operator control panel. If gas
              approaches zero, the ACR has reached the end          low is showing, this may indicate a leak which
              of its life and must be replaced.                     must be found. Recharging the ACR SF6 using
                       A warning is displayed in the event log      a gas fill adaptor is described below.
                       when the remaining contact life reaches
                       20%.
ACR SF6       The ACR is refilled to a pressure of 35kPa on         altitudes above 1000m the gauge pressure
Recharging    the gauge corrected by +0.46kPa for every             should be corrected for altitude.
              degree Celsius above 20 Celsius and -0.46kPa                   Do not attempt to recharge the gas
              for every degree below 20 Celsius. For                         without first removing the ACR
                                                                              from service.
Safety        REMOVAL FROM SERVICE                                     Replacement O-Ring to suit the gas fill valve
              The gas fill valve is located between the ACR             nut, Part No: ORG 025024.
              body and the mounting bracket.                           32mm Ring Spanner.
              To fit the Gas Fill Adaptor whilst in service it is      250mm Adjustable Wrench.
              necessary to approach the ACR.
                                                                       Silicone O-Ring Grease (DOW 111 or
              Ensure that the ACR is removed from service               equivalent), Nu-Lec Part No: LUB058044.
              before fitting the gauge and taking a reading.
                                                                       Temperature Gauge.
              SULPHUR HEXAFLUORIDE SAFETY DATA SHEET
                                                                       ACR Manufacturers Gas Fill Adaptor:
              See Appendix C for reproduction of original
              Material Safety Data Sheet.                                Part No: GFA-003 (for CIG cylinders).
                                                                         Part No: GFA-004 (for Linde Gas
              EQUIPMENT REQUIRED
                                                                          cylinders).
              Use of the correct tools and equipment will
              reduce the risk of sub-component or fastenings        (Standard gas supply hose GFA-002 is 2m
              damage during this procedure.                         long).
                                                                                                                  10-1
N-Series Automatic Circuit Recloser
                Cylinder pressure gauge and regulator valve.             tank starts to fill with gas, the pressure
                Tank pressure                                            gauge will display the increasing pressure:
                 gauge and                                              Care must be taken not to over-pressurise
                 shut-off valve                                          the tank. A relief valve is fitted to the gas fill
                                                                         adaptor. If the tank pressure exceeds 60
                                                                         kPa, the valve will open and vent to
                                                                         atmosphere.
                                                                        Pressure in excess of that required and 60
                                                                         kPa must be removed using a reclamation
                 Cylinder pressure
                 gauge and                                               unit or similar means.
                 regulator                                             The tank's pressure may be checked at any time
                 valve                                                 by closing the shut-off valve:
                                                                        Allow the gas pressure gauge to stabilise
                                                                         before taking a reading.
                2   Fit the Gas Fill Adaptor to the cylinder and        Open the shut-off valve to recommence the
                    tighten using the correct spanner:                   gas flow in to the tank.
                3   Open both the shut-off and gas cylinder            CONFIRMING THE GAS PRESSURE
                    valves.                                            13 If the ADVC is connected to the ACR, the
                4   Adjust the regulator valve until gas flows            OCP display may be used to confirm the gas
                    through and purges the line.                          pressure within the tank against the reading
                                                                          at the Tank Pressure gauge:
                5   Immediately close the shut-off valve.
                                                                        Close the shut-off valve and allow the gauge
                6   Ensure the adaptor is free of dirt or                 to stabilise.
                    contaminants before inserting into the valve.
                                                                        Note the gas pressure gauge reading.
                 Locking pin                                           14 To confirm that the readings shown on the
                                                                          gas cylinder pressure gauge and the
                                                                          Switchgear Status page are the same go to
                                                                          the
                                                                           SYSTEM STATUS - SWITCHGEAR STATUS
                 Handle                                                    page
                                                                         - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S
                                                                        Work Tag OFF               SF6 Normal 37kPag
                                                                        Aux Supply Normal          Battery Normal 27.5V
                7   Insert the gas line adaptor into the gas fill       SWGR Connected             SWGR Data Valid
                    valve:
                8   Retract the locking pin on the gas fill tool and                                                  -
                                                                       DISCONNECTING THE GAS FILL ADAPTOR
                    slide it over the gas fill boss on the tank.
                    Allow the locking pin to spring into the           15 Close the shut-off valve.
                    groove. Gently check that the tool cannot be       16 Fully close the gas cylinder valve.
                    pulled off.                                        17 Turn the regulator anti-clockwise to reduce
                9   Push the handle into the plug and rotate              the internal pressure on the regulator:
                    anticlockwise until the bayonets drop into the               Never disconnect the gas line
                    slots. Continue to rotate until it becomes                   without first reducing the pressure
                    difficult to turn. Do not force the handle                   on the regulator.
                    further.
                FILLING WITH GAS                                       18 Disconnect the gas fill adaptor from the gas
                10 Calculate the gas pressure required for the            fill valve.
                   local conditions:                                   19 Firmly tighten the gas fill plug by rotating the
                                                                          handle of the gas fill tool clockwise.
                The default gas pressure is 35 kPa.
                                                                       20 Retract the locking pin and slide the tool
                The final pressure is dependent upon the                  from the switch.
                ambient temperature at the site.
                                                                       21 Open the shut-off valve to purge the gas
                   For temperatures above 20 C, add 0.46 kPa             line.
                    for each degree in temperature.                    22 Remove the gas fill adaptor from the gas
                   For temperatures below 20 C, deduct 0.46              cylinder.
                    kPa for each degree in temperature.                23 Refit the protective plastic cap on the
                11 Open the shut-off valve to commence the                adaptor to protect the thread form during
                   flow of gas into the recloser tank.                    further transportation.
                12 Slowly turn the regulator clockwise to              24 Store the adaptor and cylinder.
                   increase the flow of gas into the tank. As the
10-2
                                                                                                 Maintenance
ADVC             Maintenance of the ADVC is required every five               Take care to ensure, when accessing
Maintenance      years. The manufacturer recommends the work                  the cubicle compartment in heavy rain,
                 described below.                                             that water does not penetrate the circuit
                                                                              breakers.
Cleaning         Check for excessive dirt on the cubicle,             Ensure that the mesh covering the air vents and
                 particularly the roof, and clean off.                the water drainage holes in the base are clean.
Battery Heater   Where the battery heater accessory has been          4   Remove batteries and replace with new
Accessory        fitted the following procedure should be                 batteries.
                 followed:                                                        Ensure that battery polarity is
                 1   Turn off the battery circuit breaker.                        correct.
                 2   Disconnect batteries and heater.
                 3   Open straps and remove heater box.               5   Replace the heater box, close straps.
                            The battery heater box is heavy           6   Reconnect batteries and heater.
                            and should be removed with                7   Turn on the battery circuit breaker and
                            caution. Do not tilt the heater box.          ensure that Battery Normal status, is
                            The cover may slide off and the               restored on the page
                            batteries may fall out.
                                                                           SYSTEM STATUS-SWITCHGEAR STATUS
Heater Connection
                                                                                                                    10-3
N-Series Automatic Circuit Recloser
Battery Care    The battery is predicted to provide good                they should be taken out, cycled and have
                performance for the recommended five year               their capacity checked before being returned
                service period. This is based on the battery            to service.
                manufacturer's data. No battery warranty is          To cycle a battery, discharge with a 10 Ohm 15
                given by the manufacturer of the ADVC.               Watt resistor to a terminal voltage of 10V. Next,
                Once in service, batteries need little care.         recharge it with a voltage regulated DC supply
                Procedures for storage and other contingencies       set to 13.8V. A 3A current limited supply is
                are as follows:                                      appropriate.
                 Batteries should be stored at a temperature        Battery type, either standard or extended
                  of between 0C to 30C (32F to 86F) and          temperature, is given in Appendix A. More
                  cycled every six months. Batteries should be       information on the battery care is available from
                  stored for a maximum of one year.                  the battery manufacturer.
                 Batteries should be cycled prior to putting                  These batteries are capable of
                  into service if they have not been cycled                    supplying very high currents.
                  within three months. When shipped by the                     Always turn off the battery circuit
                  manufacturer the batteries will have been                    breaker before connecting or
                  cycled within the previous 30 days.                disconnecting the batteries in the cubicle.
                 If the batteries become exhausted in service       Never leave flying leads connected to the
                  and are left for more than two weeks without       battery.
                  auxiliary supply being restored to the ADVC
Abnormal        The operation of the capacitor charging inverter     following features are used to protect the ADVC
Operating       can be affected under abnormal conditions such       in this situation while still allowing the ACR to
Conditions      as when the battery capacity is very low. The        keep operating.
Low Power       When the batteries are nearly exhausted, the         cannot be recharged quickly enough. Operator
Mode            ADVC will change its capacitor charging mode         close and trip operations can be performed, but
                from normal to low power. In low power mode          at a longer time interval than normal. If an
                the controller takes longer to charge the            operator trip or close request is denied, a Cap
                capacitors and the radio supply is shut down. A      Chrg event will be logged.
                Low Power Mode event is logged whenever            To return to normal power mode, the auxiliary
                this happens.                                        supply must have been switched back on for a
                When a trip occurs in low power mode, the            minimum of 15 minutes, and the batteries may
                recloser will go to lockout if the capacitors        have to be replaced.
Excess Close    During testing it is possible to carry out so many   service (it only happens during excessive
Operations      trip/close operations that the capacitor charging    testing).
                inverter shuts itself down before it overheats. It   When this happens the inverter shuts down for 5
                takes more than 20 operations within a minute        minutes and a Cap Excess Closes event is
                to do this and is not going to happen while in       logged. During this time all trip/close requests
                                                                     will be denied.
Fault Finding
ADVC Check      Fault finding within the ADVC involves                 with the display itself and the BDU should be
                determining whether the fault lies in the              replaced.
                electronic modules, the wiring or elsewhere. The      If the display is operating, check the
                electronic modules are user replaceable items.          SYSTEM STATUS - SWITCHGEAR STATUS
                Other faults require the ADVC to be returned to
                the factory.                                           page for an indication of any power supply
                                                                       problems (Aux Supply Fail and/or Battery
                A suggested fault finding approach is as follows:      OFF) which can be traced and rectified.
                   If the System OK LED on the OCP is                If the System OK LED is not flashing, check
                    flashing then the CAPE microprocessor and          for loss of power. Check that the BDU is
                    the BDU microprocessor are running. If the         plugged in to the CAPE. Check that the
                    OCP does not operate there is a problem            battery circuit breaker is on and that full
10-4
                                                                                           Maintenance
                   battery voltage is present at the terminals.    If power supply is present then attempt to go
                   Check the presence of aux supply on the          on-line with WSOS to determine whether the
                   aux supply circuit breaker. Check that the       CAPE is functioning correctly. Replace the
                   supply between the PSU and CAPE has not          CAPE or BDU as required.
                   been disconnected. Rectify if a problem is      If this does not rectify the problem then the
                   discovered.                                      ADVC should be returned for factory repair.
Replacement     Electronic modules are user replaceable. Care     PSU and CAPE firmware can be upgraded
of Electronic   should be taken to avoid damage to the            through WSOS. Refer to the Operator Manual
Modules and     modules while they are outside the cubicle and    for further details.
Upgrades        replacement should only be carried out by                   Removal of parts from modules will
                competent personnel.                                        void the warranty.
                                                                                                             10-5
N-Series Automatic Circuit Recloser
10-6
                                                                            Ratings and Specifications
Equipment
and Crating
Dimensions     Equipment Weights
               HV cables (185mm2 Al cables, qty 6, length as ordered) complete with bushing   26 (57)
               boots.
Dimensions mm (ins)
Crate Dimensions
ACR
Rated Voltage
N15 15.5 kV
N27 27 kV
N38a 38 kV
                                                                                                                     11-1
N-Series Automatic Circuit Recloser
N15 110kV
N27 150kV
N38 170kV
N15 50kV
N27 60kV
N38 70kV
Applicable Standards
11-2
                                                                                         Ratings and Specifications
Breaking Duty   The duty limits of the ACR are shown in the                      for each interrupter by the ADVC on the basis of
                table below. It is rated for ANSI C37.60 duty                    fault current and mechanical operations.
                cycle.Contact wear is automatically calculated                   The remaining contact life is shown on the
                                                                                 operator control panel.
Bushing Boots   The ACR is normally supplied with outdoor                        characteristics of the boot alone (disregarding
                elastomeric bushing boots. The boots suit                        the cable insulation) are detailed in the following
                insulated cable sized 16-32 mm diameter and                      table.
                comprise an unscreened insulated system.The
HV Cables       Cable is usually provided by the manufacturer                    equipment only if suitably insulated and
                pre-cut and terminated to fit the ACR bushings                   watertight cable and terminations are used.
                and rated to suit the requirements of the utility.               Contact the manufacturer or your local
                Alternatively cable can be supplied by the utility               distributor to check cable type for suitability.
                if appropriate (e.g. to terminate HV Aerial                      Standard cable supplied by the manufacturer is
                Bundled Cable). The manufacturer warrants the                    detailed in the following table.
                                                                                                                                        11-3
N-Series Automatic Circuit Recloser
Ratio 2000:1
Environmental
a. For altitudes above 1000 meters some ratings must be de-rated per ANSI C37.60.
ADVC
General
Specifications
                      Cubicle material                                                                   316 stainless steel
Humidity 0 to 100%
Maximum vertical separation from ACR with standard control cable. 5m (16.4)
Battery (With battery heater option, 12AH batteries are standard.) 2 x 12V 7.2Ah
                      Battery hold up time from fully charged at 25C                                    38 hours with 7Ah
                                                                                                         52 hours with 12Ah
                      Capacity available for communications, hold up time (no heater, OCP or IOEX)       20 hours
                      13.8V TX:2.1A, 15min, RX 320mA
11-4
                                                                          Ratings and Specifications
 Radio/Modem
 A radio or modem may be fitted by the manufacturer or by the utility, for remote communications. Space,
 power and data interfaces are provided within the control cubicle.
Control Electronics
                                                                                                                           11-5
N-Series Automatic Circuit Recloser
Voltage Resolution 1V
SF6 Gas
Pressure             Nominal Pressure at 20C                                                         35 kPa Gauge
Measurement
                     Gas Pressure Display Resolution                                                  1 kPa
11-6
Appendix A Replaceable Parts & Tools
             All replacement parts listed in the following table
             are available from the manufacturer.
Silicone O-Ring grease: Dow 111 Valve and o-ring grease. LUB058040
IOEX2 998000080
                                                                                                            A-1
N-Series Automatic Circuit Recloser
A-2
Appendix B Dimensions
ACR
Dimensions
                                                    B-1
N-Series Automatic Circuit Recloser
ADVC
Dimensions
B-2
Pole Mounting
Brackets
                                                       B-3
N-Series Automatic Circuit Recloser
IOEX2
Dimensions
B-4
Appendix C Safety Data Sheet - Sulphur Hexafluoride
              The following is reproduced from the original
              data sheet supplied by LINDE Gas Pty Ltd.
               Product:
               MSDS No: 110                        Sulphur Hexafluoride
               Version 1.18 dated 29/06/99
Company Identification LINDE Gas Pty Ltd., 66 Loftus Rd, YENNORA, 2161 NSW Australia
CAS Nr 02551-62-4
3 HAZARDS IDENTIFICATION
                     Skin / eye contact            Immediately flush eyes thoroughly with water for at least 15 minutes.
                                                   Apply a sterile dressing. Obtain medical assistance.
                     Hazardous combustion          If involved in a fire the following toxic and/or corrosive fumes may be
                     products                      produced by thermal decomposition:
                                                   a) Hydrogen fluoride
                                                   b) Sulphur dioxide
                     Specific methods              If possible, stop flow of product. Move container away or cool with water
                                                   from a protected position.
                                                                                                                             C-1
N-Series Automatic Circuit Recloser
                 Product:
                 MSDS No: 110                     Sulphur Hexafluoride
                 Version 1.18 dated 29/06/99
                      Handling and storage        Suck back of water into the container must be prevented.
                                                  Do not allow backfeed into the container.
                                                  Use only properly specified equipment which is suitable for this product,
                                                  its supply pressure and temperature. Contact your gas supplier if in any
                                                  doubt.
                                                  Refer to suppliers container handling instructions.
                                                  Keep container below 50 C in a well ventilated place.
                      Exposure limit value for    Great Britain: STEL: 1250 ppm LTEL: 100 ppm (EH 40/97).
                      country                     Germany: MAK = 1000 ppm.
                      Other data                  Gas/vapour heavier than air, may accumulate in confined spaces
                                                  particularly at or below ground level.
11 TOXICOLOGICAL INFORMATION
12 ECOLOGICAL INFORMATION
13 DISPOSAL CONSIDERATIONS
                      General                     Do not discharge into any place where its accumulation could be
                                                  dangerous. Contact supplier if guidance is required.
C-2
 Product:
 MSDS No: 110                        Sulphur Hexafluoride
 Version 1.18 dated 29/06/99
14 TRANSPORT INFORMATION
UN Nr 1080.
Class/Div 2.2
ADR/RID Hazard Nr 20
      Other transport information    Avoid transport on vehicles where the load space is not separated from
                                     the drivers compartment.
                                     Ensure vehicle driver is aware of the potential hazards of the load and
                                     knows what to do in the event of an accident or an emergency.
                                     Before transporting product containers ensure that they are firmly
                                     secured and:
                                     a) cylinder valve is closed and not leaking.
                                     b) valve outlet cap nut or plug (where provided) is correctly fitted.
                                     c) valve protection device (where provided) is correctly fitted.
                                     d) there is adequate ventilation.
                                     e) compliance with applicable regulations.
15 REGULATORY INFORMATION
16 OTHER INFORMATION
                                                                                                             C-3
N-Series Automatic Circuit Recloser
C-4
                                                                                                                                                Index
Index
                                                                                                                                                     Index-I
N-Series Automatic Circuit Recloser
M                                                                                 Replacement of electronic modules ................... 10-5
Main earth bond ................................................... 3-6           replacement parts ................................................. 1-1
Maintenance .............................................. 10-1, 10-3             reverse polarity ..................................................... 3-4
maintenance port ................................................. 6-2            RIGHT scroll key .................................................. 7-2
mechanical duty ................................................. 10-1            S
MENU scroll key ................................................... 7-2           SCADA ................................................................. 4-6
modem ................................................................. 4-2       SCEM ................................................................... 1-1
Mounting brackets ................................................ 3-5            Sealing and condensation .................................... 6-1
N                                                                                 SELECT key ......................................................... 7-2
navigation symbol ................................................ 1-1            Select key ............................................................. 7-3
navigation within groups ....................................... 7-3              setting the phasing ............................................... 5-3
note symbol .......................................................... 1-1        settings ................................................................. 7-2
O                                                                                 SF6 ....................................................................... 2-1
OCI ....................................................................... 1-1   SF6 ..................................................................... 10-1
OCP .............................................................. 6-1, 7-1       Silicone grease ..................................................... 3-4
Operator Control Panel ........................................ 6-1               Site installation ..................................................... 3-2
operator control panel .......................................... 7-1             Site procedure ............................................... 3-3, 5-3
operator interface ................................................. 6-2          Software
P                                                                                      Capability ....................................................... 1-1
pages ................................................................... 7-2     software version ................................................... 1-1
Parts and tools ..................................................... 1-1         status .................................................................... 7-2
Parts required ....................................................... 3-3        sub-pages ............................................................. 7-2
password .............................................................. 7-3       sulphur hexaflouride ............................................. 2-1
PCOM .................................................................. 1-1       Supervisory Control and Data Acquisition ............ 4-6
pointer ................................................................ 10-1     Surge arresters ..................................................... 3-5
Power Factor (PF) ................................................ 9-2                 LV .................................................................. 3-6
Power Flow direction ............................................ 5-3                  Mounting and terminating .............................. 3-5
Power supply unit ................................................. 6-1           SWGM .................................................................. 1-1
Power System measurements ............................. 9-1                       T
Press to Talk (PTT) .............................................. 4-5            Test and Training Set ........................................... 1-2
Protection                                                                        Testing & configuring ............................................ 3-2
    Of radio equipment ........................................ 4-1               Tools required ...................................................... 3-3
Protection settings ................................................ 7-3          Transport to site ................................................... 3-2
PSU ............................................................... 1-1, 6-1      Trip key ................................................................. 7-1
PSU module ......................................................... 6-1          TRIP or CLOSE LED .......................................... 10-4
PTCC ................................................................... 1-1      U
Q                                                                                 Updating the Event Log ........................................ 8-1
Quick Key ............................................................. 7-4       user interface ........................................................ 7-1
quick keys ............................................................ 7-4       V
R                                                                                 vermin ................................................................... 6-1
radio ..................................................................... 4-2   Voltage free output contacts ................................. 4-3
Radio Aerial .......................................................... 4-1       W
Radio holdup time ................................................ 4-2            warning symbol .................................................... 1-1
radio/modem power supply voltage ..................... 4-2                        Windows Swirchgear Operating System .............. 4-5
Real Power (kW) .................................................. 9-2            Windows Switchgear Operating System (WSOS) 8-1
Real Time Displays .............................................. 9-1             Windows Switchgear Operator System ................ 7-3
recloser bushings ................................................. 2-3           WSOS .................................................................. 7-4
Recloser earthing ................................................. 3-5           WSOS Interface ................................................... 6-2
re-configuring the Quick Keys .............................. 7-4
Index-II
III
N-Series Automatic Circuit Recloser
IV
Nu-Lec Industries   Corporate office &           USA office                 As standards, specifications and designs change from time to
                    factory                                                 time, please ask for confirmation of the information given in this
                                                                            publication.
                    35-37 South Street           1252 Old Alpharetta Road
                    Lytton, 4178                 Alpharetta, Georgia
                    Queensland                   30005-3986
                    Australia                    United States of America
                                                                                                                                                 ADC-1007-NI