English Manual
1. Introduction
                                                                                             The LINDY IPower Switch Classic is an Internet ready device designed and is equipped with an
                                                                                             intelligent current-meter (True RMS) that will indicate the total power consumption of a power
                                                                                             strip. The LINDY IPower Switch Classic offers an easy set up and user-friendly communication
                                                                                             software. This software provides assistance to the network administrator to remotely monitor the
                                                                                             multiple PDU power consumption to realize the total current power consumption.
IPower Switch Classic 8                                                                                                             Features
IPower Switch Classic 16                                                                         Built-in web server, supports real time monitoring for the current
                                                                                                  consumption of the power strip.
                                                                                                 Build-in true RMS current meter.
                                                                                                 Easy setup, the display shows the current IP address of the unit directly.
User Manual                                                             English                  Provides audio alarm when the power consumption exceeds the value setting
                                                                                                  for overload warning.
                                                                                                 Sends email and SMNP traps when the power consumption exceeds the value
                                                                                                  for overload warning.
                                                                                                 Software utility included, which monitors a number of IPower Switches Classic
                                                                                                  simultaneously
                                                                                                 Supports the SNMP protocol and provides an MIB for the unit.
                                                                                                 Provides power protection by a circuit breaker.
                                                                                                 Slim size - suitable for a variety of rack environments.
                                                                                                 Real time control for each outlet.
                                                                                                 LED status indicator for every outlet.
                                                                                                 Power on switching sequence adjustable.
                                                                                             2. Package Content
                                                                                             The standard Amazing PDU package contains a Power Distribution Unit with supporting
                                                                                             hardware and software. The components of the package are:
                                                                                                    Power Distribution Unit.
                                                                                                    Rack mount Brackets.
                                                                                                    CD-ROM, containing:
                                                                                                             User Manual.
                                                                                                             Amazing PDU Software.
                                                                                                             MIB: Management Information Base for Network. (AmazingMIB.mib)
                                                                                                             Adobe Acrobat Reader.
                                 LINDY No. 32657, 32658
       For Home and Office Use
       Tested to Comply with
       FCC Standards
                                 www.LINDY.com                                                                                              2
 LINDY ELECTRONICS LIMITED       &   LINDY-ELEKTRONIK GMBH   -   FIRST EDITION (Jun 2009)
English Manual                                                                                    English Manual
3. Function
                                                                                                     4. Installation
                                                                                                  This section will instruct you to quickly install the Amazing PDU.
    Interface:
Function          Description
Ethernet          Network connection for the built-in web server
Audible Alarm         1. Warning: 1 beep in 1 second
                      2. Overload: 3 beeps in 1 second
                         Note: the overload alarm will not stop until the current falls back to
                         0.5 Amps below the setting value for overload or warning.
Function Button       1. Press and release this button to turn off the warning audible alarm.
                         The overload alarm cant be stopped by this button.
                      2. Pressing the button and releasing it after two beeps will show up
                         the units IP address
                      3. Pressinfg the button and releasing it after 4 beeps changes the IP
                         address mode from fixed to DHCP and vice versa
                      4. Pressing the button and releasing it after 6 beeps restarts the
                         network interface.
Meter             Displays the current or the IP address of the unit
LED Indicator     Current:    Lights to indicate that the power consumtion is shown in the        Hardware Installation
                              display
                  IP Address: Lights to indicate that the IP Address is shown in the display         1. Install mounting brackets.
Output LED        Indicates, wether a power output is switched on                                        The Unit comes with brackets for mounting in a rack. To mount the
                                                                                                         device into a rack, please perform the following procedure:
                                                                                                             I. Attach the mounting brackets to the unit, using the four retaining screws
                                                                                                                 provided for each of the brackets.
                                                                                                             II. Choose a mounting position for the brackets (several options).
                                                                                                             III. Align the mounting holes of brackets with the notched hole on the vertical rail
                                                                                                                 and attach with the retaining screws.
                                                                                                      2. Connect the input and output power cables.
                                                                                                      3. Connect your Ethernet cable to the unit.
                                                                                                      4. Switch on the Ipower Switch Classic.
                                                                                                  Note :
                                                                                                  The default setting for the way to get an IP address is DHCP. If the unit cant get an IP from a
                                                                                                  present DHCP server, the IP address will remain 192.168.0.216
                                                3                                                                                                  4
English Manual                                            English Manual
   5. Web Interface                                                                                 Network
                                                  Index
                                                             1. Provides network information for the
System Information
                                                                IPowerSwitch.
Provide the General Information
                                                             2. The network setting can be changed
for the IPower Switch, including:
                                                                here.
                                                             3. The default ID is snmp, the password
       Model No.
                                                                is 1234.
       Name
       Location
       Contact
       Firmware Version
       MAC Address
Treshold
Shows the warning and overload value
setting
Status:                                                                                                   ID
Indicates the IPower Switchs power
consumption and status.
                                                          Change the ID and password.
                                                          The default ID is snmp,
                                                          The password is 1234.
                                              Control
Status:
   1. Indicates the Ipower Switchs power
      consumption and status.
   2. Select the outlet by check box first and
      click the on or off button to control the
      IPower Switch power output.                                                                        Email
                                                              In case of an SMNP-event or warning ,
Control:                                                       the unit can send out an email
                                                               message to a pre-defined account.
The default ID is snmp and                                  Only support the input of anemail
password is 1234.                                            server with a domain name.
                                                              The message in the email will show as
                                                               below:
                                                              Indicate OutletA~H status order
                                                               0 : means the power off.
                                                               1 : means the power on.
                                                   5                                                      6
English Manual                                                                                 English Manual
                                             Trap
                                                                                               FCC Warning
Defines the IP address, to send event traps to.                                                This device complies with part 15 of the FCC Rules.
The default ID is snmp, the Password is                                                      Operation is subject to the following two conditions:
1234.                                                                                        1. This device may not cause harmful interference, and
                                                                                               2. This device must accept any interference received, including interference that may cause undesired
                                                                                                  operation.
                                                                                               CE Statement, EMC Compatibilty
                                                                                               This device complies with EN Standards EN55022 and EN55024 according to the relevant EC EMC
                                                                                               Directive. It must be used with shielded cables only to maintain EMC compatibility.
                                                                                               Dieses Produkt entspricht den einschlgigen EMV Richtlinien der EU und darf nur zusammen mit
                                                                                               abgeschirmten Kabeln verwendet werden.
   6. Technical Specifications
Interface
       RJ45                             Ethernet
                                                                                               LINDY Herstellergarantie
Nominal Input Frequency                 47~63 Hz Full Range                                    LINDY gewhrt fr dieses Produkt ber die gesetzliche Regelung hinaus eine zweijhrige
                                                                                               Herstellergarantie ab Kaufdatum. Die detaillierten Bedingungen dieser Garantie finden Sie auf der
LED Indicators                                                                                 LINDY Website aufgelistet bei den AGBs.
      Indicator                         (1)yellow LED (1) red LED
Current Meter                           3 digits
                                                                                                     WEEE (Waste of Electrical and Electronic Equipment),
     Range                              0A~20A (True RMS)                                            Recycling of Electronic Products
     Resolution                         0A~20A: 0.1A
     Precision                          0A~20A: +/-2%+/-0.1AMP                                 In 2006 the European Union introduced regulations (WEEE) for the collection and recycling of all waste
                                                                                               electrical and electronic equipment. The wheelie bin symbol shown indicates that this product must not
Alarm                                                                                          be disposed of with household waste. Instead the product must be recycled in a manner that is
        Audible                         1. Warning- 1 beep per second                          environmentally friendly. For more information on how to dispose of this product, please contact your
                                        2. Overload- 3 beeps per second                        local recycling centre or your household waste disposal service. Each individual EU member state has
        Seven Segment                   Warning and Overload - Meter flashes once per second   implemented the WEEE regulations into national law in slightly different ways. Please follow your
                                                                                               national law when you want to dispose of any electrical or electronic products.
Operation & Environment
                                                                                               More details can be obtained from your national WEEE recycling agency.
     Operating Temperature              -5 - 45 degree C
     Relative Humidity                  0 - 95%                                                Germany / Deutschland
     Storage Temperature                -25 - 65 degree C                                      Die Europische Union hat mit der WEEE Direktive umfassende Regelungen fr die Verschrottung und
                                                                                               das Recycling von Elektro- und Elektronikprodukten geschaffen. Diese wurden von der Bundesregierung
                                                                                               im Elektro- und Elektronikgertegesetz  ElektroG in deutsches Recht umgesetzt. Dieses Gesetz
                                                                                               verbietet vom 24.Mrz 2006 an das Entsorgen von Elektro- und Elektronikgerten ber die
                                                                                               Hausmlltonne! Diese Gerte mssen den lokalen Sammelsystemen bzw. rtlichen Sammelstellen
                                                                                               zugefhrt werden! Dort werden sie kostenlos entgegen genommen. Die Kosten fr den weiteren
                                                                                               Recyclingprozess bernimmt die Gesamtheit der Gertehersteller.
                                                                                                                                                                            LINDY No 32657, 32658
                                                                                                                                                                        1st Edition, September 2008
                                                                                                                                                                                  www.lindy.com
                                                  7                                                                                               8