Commissioning Manual
Commissioning Manual
630 series
Commissioning Manual
             Document ID: 1MRS756801
                   Issued: 2014-11-28
                            Revision: D
                   Product version: 1.3
            Trademarks
            ABB and Relion are registered trademarks of the ABB Group. All other brand or
            product names mentioned in this document may be trademarks or registered
            trademarks of their respective holders.
            Warranty
            Please inquire about the terms of warranty from your nearest ABB representative.
             http://www.abb.com/substationautomation
Disclaimer
             The data, examples and diagrams in this manual are included solely for the concept
             or product description and are not to be deemed as a statement of guaranteed
             properties. All persons responsible for applying the equipment addressed in this
             manual must satisfy themselves that each intended application is suitable and
             acceptable, including that any applicable safety or other operational requirements
             are complied with. In particular, any risks in applications where a system failure and/
             or product failure would create a risk for harm to property or persons (including but
             not limited to personal injuries or death) shall be the sole responsibility of the
             person or entity applying the equipment, and those so responsible are hereby
             requested to ensure that all measures are taken to exclude or mitigate such risks.
             This product has been designed to be connected and communicate data and
             information via a network interface which should be connected to a secure
             network. It is the sole responsibility of the person or entity responsible for network
             administration to ensure a secure connection to the network and to take the
             necessary measures (such as, but not limited to, installation of firewalls, application
             of authentication measures, encryption of data, installation of anti virus programs,
             etc.) to protect the product and the network, its system and interface included,
             against any kind of security breaches, unauthorized access, interference, intrusion,
             leakage and/or theft of data or information. ABB is not liable for any such damages
             and/or losses.
             This document has been carefully checked by ABB but deviations cannot be
             completely ruled out. In case any errors are detected, the reader is kindly requested
             to notify the manufacturer. Other than under explicit contractual commitments, in
             no event shall ABB be responsible or liable for any loss or damage resulting from
             the use of this manual or the application of the equipment.
Conformity
             This product complies with the directive of the Council of the European
             Communities on the approximation of the laws of the Member States relating to
             electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
             electrical equipment for use within specified voltage limits (Low-voltage directive
             2006/95/EC). This conformity is the result of tests conducted by ABB in
             accordance with the product standards EN 50263 and EN 60255-26 for the EMC
             directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
             voltage directive. The product is designed in accordance with the international
             standards of the IEC 60255 series.
Safety information
                     Dangerous voltages can occur on the connectors, even though the
                     auxiliary voltage has been disconnected.
Table of contents
                       Section 1   Introduction.......................................................................3
                                   This manual........................................................................................3
                                   Intended audience..............................................................................3
                                   Product documentation.......................................................................4
                                       Product documentation set............................................................4
                                       Document revision history.............................................................4
                                       Related documentation..................................................................5
                                   Symbols and conventions...................................................................5
                                       Symbols.........................................................................................5
                                       Document conventions..................................................................5
                                       Functions, codes and symbols......................................................6
630 series                                                                                                                            1
Commissioning Manual
Table of contents
Section 6 Glossary.........................................................................43
2                                                                                                                   630 series
                                                                                                         Commissioning Manual
1MRS756801 D                                                                                  Section 1
                                                                                           Introduction
Section 1 Introduction
630 series                                                                                                 3
Commissioning Manual
Section 1                                                                                                                                                1MRS756801 D
Introduction
                                                                                                                                           Maintenance
                                                                              Engineering
                                                                 Planning &
Installation
                                                                                                                             Operation
                                                                 purchase
                 Quick start guide
                 Quick installation guide
                 Brochure
                 Product guide
                 Operation manual
                 Installation manual
                 Engineering manual
                 Technical manual
                 Application manual
                 Communication protocol manual
                 Point list manual
                 Commissioning manual
               GUID-C8721A2B-EEB9-4880-A812-849E1A42B02C V1 EN
Figure 1: The intended use of documents during the product life cycle
4                                                                                                                                                   630 series
                                                                                                                                         Commissioning Manual
1MRS756801 D                                                                                Section 1
                                                                                         Introduction
1.4.1 Symbols
                                     The tip icon indicates advice on, for example, how to design your
                                     project or how to use a certain function.
                       •   Abbreviations and acronyms are spelled out in the glossary. The glossary also
                           contains definitions of important terms.
                       •   Push button navigation in the LHMI menu structure is presented by using the
                           push button icons.
630 series                                                                                                 5
Commissioning Manual
Section 1                                                                                 1MRS756801 D
Introduction
6                                                                                              630 series
                                                                                    Commissioning Manual
1MRS756801 D                                                                                 Section 1
                                                                                          Introduction
630 series                                                                                                 7
Commissioning Manual
Section 1                                                                                 1MRS756801 D
Introduction
8                                                                                           630 series
                                                                                 Commissioning Manual
1MRS756801 D                                                                            Section 1
                                                                                     Introduction
630 series                                                                                      9
Commissioning Manual
Section 1                                                                                1MRS756801 D
Introduction
10                                                                                         630 series
                                                                                Commissioning Manual
1MRS756801 D                                                                                 Section 2
                                                                                            Starting up
Section 2 Starting up
                       •   Acceptance testing
                       •   Commissioning testing
                       •   Maintenance testing
                       This manual describes the workflow and the steps to carry out the commissioning
                       testing.
                       Factory acceptance testing (FAT) is typically done to verify that the IED and its
                       corresponding configuration meet the requirements of the utility or industry. This
                       test is the most complex and in depth, as it is done to familiarize the user with a
                       new product or to verify a new configuration. The complexity of this testing
                       depends on several factors.
                       •   New IED type
                       •   New configuration
                       •   Modified configuration
                       Maintenance testing is a periodic verification that the IED is healthy and has
                       correct settings, depending on changes in the power system. There are also other
                       types of maintenance testing.
              Check that the auxiliary supply voltage remains within the permissible input
              voltage range under all operating conditions. Check that the polarity is correct
              before powering the IED.
              •   Energize the power supply of the IED to start it up. This can be done in a
                  number of ways, from energizing a whole cubicle to energizing a single IED.
              •   Set the IED time if no time synchronization source is configured.
              •   Check the self-supervision function via the LHMI path Main menu/
                  Monitoring/IED status or Main menu/Monitoring/Internal events to verify
                  that the IED operates properly.
              •   The green Ready LED starts flashing instantly and the ABB logo is shown on
                  the LCD.
              •   After approximately 30 seconds, "Starting" is shown on the LCD.
              •   Within 90 seconds, the main menu is shown on the LCD and the green Ready
                  LED shows a steady light, which indicates a successful startup.
12                                                                                          630 series
                                                                                 Commissioning Manual
1MRS756801 D                                                                                 Section 2
                                                                                            Starting up
                       If the green Ready LED continues to flash after the startup, the IED has detected an
                       internal error. Navigate via Main menu/Monitoring/IED status to investigate the
                       error description.
                       The communication between the IED and PCM600 is independent of the used
                       communication protocol within the substation or to the NCC.
The communication media is always Ethernet and the used protocol is TCP/IP.
                       Each IED has an Ethernet interface connector on the front and on the rear side.
                       Both Ethernet connectors can be used for communication with PCM600.
                       For the connection of PCM600 to the IED, two basic variants have to be considered.
                       •    Direct point-to-point link between PCM600 and the IED front port.
                       •    Indirect link via a station LAN or from remote via a network.
                       The physical connection and the IP address must be configured in both cases to
                       enable communication.
                       Setting up IP addresses
                       The IP address and the corresponding mask can be set via the LHMI for each
                       available Ethernet interface in the IED. Each Ethernet interface has a default
                       factory IP address when the complete IED is delivered.
                       •    The default IP address for the IED front port is 192.168.0.254 and the
                            corresponding subnetwork mask is 255.255.255.0, which can be set via the
                            local HMI path Main menu/Configuration/Communication/TCP-IP
                            configuration/Front port.
                       •    The default IP address for the IED rear port is 192.168.2.10 and the
                            corresponding subnetwork mask is 255.255.255.0, which can be set via the
                            local HMI path Main menu/Configuration/Communication/TCP-IP
                            configuration/LAN1.
630 series                                                                                               13
Commissioning Manual
Section 2                                                                            1MRS756801 D
Starting up
                            The front and rear port IP addresses cannot belong to the same
                            subnet or communication will fail. It is recommended to change the
                            IP address of the front port if the front and rear port are set to the
                            same subnet.
                            See the operating system manual for details on how to obtain the IP
                            address automatically.
                            1.   Connect the PC network adapter to the IED front port.
                            2.   Wait until the operating system automatically acquires the
                                 network address.
                            3.   Check that the front port connector green status LED is lit.
                            4.   Ping the IED to verify that the connection is correctly
                                 established. The default IP address of the front port is
                                 192.168.0.254.
              •   Create the application configuration using PCM600 and then write it to the
                  IED.
              •   Establish a connection between PCM600 and the IED when an application
                  configuration must be written to the IED.
14                                                                                        630 series
                                                                               Commissioning Manual
1MRS756801 D                                                                                  Section 2
                                                                                             Starting up
                                     Be sure to set the correct technical key in both the IED and
                                     PCM600 to prevent writing an application configuration to a wrong
                                     IED.
                       The CTs must be connected in accordance with the terminal diagram provided with
                       the IED, both with regards to phases and polarity. The following tests are
                       recommended for every primary CT or CT core connected to the IED.
                       •   Primary injection test to verify the current ratio of the CT, the correct wiring
                           up to the protection IED and correct phase sequence connection (that is L1,
                           L2, L3.)
                       •   Polarity check to prove that the predicted direction of the secondary current
                           flow is correct for a given direction of the primary current flow. This is an
                           essential test for the proper operation of the directional function, protection or
                           measurement in the IED.
                       •   CT secondary loop resistance measurement to confirm that the current
                           transformer secondary loop DC resistance is within specification and that there
                           are no high resistance joints in the CT winding or wiring.
                       •   CT excitation test to ensure that the correct core in the CT is connected to the
                           IED. Normally only a few points along the excitation curve are checked to
                           ensure that there are no wiring errors in the system, for example, due to a
                           mistake in connecting the CT's measurement core to the IED.
                       •   Earthing check of the individual CT secondary circuits to verify that each three-
                           phase set of main CTs is properly connected to the station earth and only at
                           one electrical point.
                       •   Insulation resistance check.
630 series                                                                                                15
Commissioning Manual
Section 2                                                                               1MRS756801 D
Starting up
Check that the wiring is in strict accordance with the supplied connection diagram.
              •   Polarity check
              •   VT circuit voltage measurement (primary injection test)
              •   Earthing check
              •   Phase relationship
              •   Insulation resistance check
              The polarity check verifies the integrity of circuits and the phase relationships. The
              polarity must be measured as close to the IED as possible to ensure that most of the
              wiring is also checked.
              The primary injection test verifies the VT ratio and the wiring all the way from the
              primary system to the IED. Injection must be performed for each phase-to-neutral
              circuit and each phase-to-phase pair. In each case, voltages in all phases and
              neutral are measured.
              The RTXP test switch is designed to provide the means of safe testing of the IED.
              This is achieved by the electromechanical design of the test switch and test plug
              handle. When the test plug handle is inserted, it first blocks the trip and alarm
              circuits then it short circuits the CT secondary circuit and opens the VT secondary
              circuits making the IED available for secondary injection.
              When pulled out, the test handle is mechanically stopped in half withdrawn
              position. In this position, the current and voltage enter the protection, but the alarm
              and trip circuits are still isolated. Before removing the test handle, check that no
              trip or alarms are present in the IED.
              The trip and alarm circuits are not restored for operation until the test handle is
              completely removed.
16                                                                                           630 series
                                                                                  Commissioning Manual
1MRS756801 D                                                                                  Section 2
                                                                                             Starting up
                                      By pulling in all cables, verify that the contact sockets have been
                                      crimped correctly and that they are fully inserted. Never do this
                                      with current circuits in service.
                       •    Verify from the manufacturer that the total circuit resistance is under specified
                            values from the instrument (transducer) manufacturer.
Do not use AC voltage. Binary inputs are rated for DC voltage only.
630 series                                                                                                  17
Commissioning Manual
Section 2                                                                                 1MRS756801 D
Starting up
18                                                                                           630 series
                                                                                  Commissioning Manual
1MRS756801 D                                                                                       Section 2
                                                                                                  Starting up
                       Table 3:         mA outputs
                        Terminal                                  Value
                        Output range                               ±20 mA
                        Accuracy                                   ±0.2 mA (ambient temperature -25ºC...+55ºC)
                                                                   ±1 mA (ambient temperature -40ºC...-25ºC /
                                                                   55ºC...70ºC)
                        Max load                                   700 Ω (including lead wire resistance)
                        Isolation                                  4 kV (output to output, output to inputs and
                                                                   output to protective earth)
630 series                                                                                                        19
Commissioning Manual
20
1MRS756801 D                                                                 Section 3
                       Establishing connection and verifying the station communication
                           IEC 61850 communication is always included in 630 series IEDs and it is enabled
                           by default. IEC 61850 communication configuration is done using IET600 and
                           PCM600.
                           Based on ordering and licensing either DNP3 or IEC 60870-5-103 can be included
                           in addition to IEC 61850. Mapping data points to DNP3 protocol is done using
                           Communication Management in PCM600, and mapping data points to IEC
                           60870-5-103 protocol is done using Application Configuration in PCM600.
                           If the station control system is not available for verifying the communication, then
                           separate testing or diagnostics tools made for the specific protocol must be used.
                           For example, for IEC 61850 communication, ABB provides Integrated Testing
                           Tool ITT600 SA Explorer. It is designed for easy on-line diagnosis and
                           troubleshooting of IEC 61850 based substation automation systems.
630 series                                                                                                    21
Commissioning Manual
22
1MRS756801 D                                                                            Section 4
                                                                            Testing IED operation
                       •   During testing, observe that the right testing method, that corresponds to the
                           actual parameters set in the activated parameter setting group, is used.
                       •   Set and configure the functions before testing.
                           Most functions are highly flexible and permit a choice of functional and
                           tripping modes. The various modes are checked at the factory as part of the
                           design verification. In certain cases, only modes with a high probability of
                           coming into operation need to be checked when commissioned to verify the
                           configuration and settings.
                           Requirements for testing the function.
630 series                                                                                                  23
Commissioning Manual
Section 4                                                                                   1MRS756801 D
Testing IED operation
                        •       Calculated settings
                        •       Valid configuration diagram for the IED
                        •       Valid terminal diagram for the IED
                        •       Technical manual
                        •       Three-phase test equipment
                   •    The test equipment should be able to provide a three-phase supply of currents
                        and three-phase voltage. The magnitude and angle of currents (and voltages)
                        should be possible to vary. Check that the IED is prepared for test before
                        starting the test session. Consider the logic diagram of the function when
                        performing the test.
                                     Do not switch off the auxiliary power supply to the IED before the
                                     changes, for example, setting parameter or local/remote control
                                     state changes, are saved.
                   A mechanism for limiting the number of writings per time period is included in the
                   IED to prevent the flash memory from wearing out due to too many writings
                   caused by the application configuration. As a consequence, saving application
                   function states may take up to an hour. If the auxiliary power is interrupted before
                   the states are saved, that change is lost. Settings and configuration parameters are
                   saved without delay.
                   Put the IED into the test mode before testing. The test mode blocks all protection
                   functions and some of the control functions in the IED, and the individual functions
                   to be tested can be unblocked to prevent unwanted operation caused by other
                   functions. In this way, it is possible to test slower back-up measuring functions
                   without the interference from faster measuring functions. Test mode is indicated
                   when the yellow StartLED flashes.
24                                                                                               630 series
                                                                                      Commissioning Manual
1MRS756801 D                                                                            Section 4
                                                                            Testing IED operation
                       The IED can be equipped with a test switch of type RTXP8, RTXP18 or RTXP24.
                       The test switch and its associated test plug handle (RTXH8, RTXH18 or RTXH24)
                       are a part of the COMBITEST system, which provides secure and convenient
                       testing of the IED.
                       •   Connect the test equipment according to the IED specific connection diagram
                           and the needed input and output signals for the function under test.
                       •   Connect the current and voltage terminals. Pay attention to the current polarity.
                           Make sure that the connection of input and output current terminals and the
                           connection of the residual current conductor is correct. Check that the input
                           and output logical signals in the logic diagram for the function under test are
                           connected to the corresponding binary inputs and outputs of the IED under test.
630 series                                                                                               25
Commissioning Manual
Section 4                                                                                  1MRS756801 D
Testing IED operation
                                  To ensure correct results, check that the IED as well as the test
                                  equipment are properly earthed before testing.
                   Release or unblock the function to be tested to ensure that only the function or the
                   chain of functions to be tested are in operation and that other functions are
                   prevented from operating. Release the tested function(s) by setting the
                   corresponding Blocked parameter under Function test modes to “No” in the LHMI.
                   When testing a function in this blocking feature, not only the actual function but
                   the whole sequence of interconnected functions (from measuring inputs to binary
                   output contacts) including logic must be activated. Before starting a new test mode
                   session, scroll through every function to ensure that only the function to be tested
                   (and the interconnected ones) have the parameters Blocked and eventually
                   EvDisable set to “No” and “Yes” respectively. A function is also blocked if the
                   BLOCK input signal on the corresponding function block is active, which depends
                   on the configuration. Ensure that the logical status of the BLOCK input signal is
                   equal to 0 for the function to be tested. Event function blocks can also be
                   individually blocked to ensure that no events are reported to a remote station
                   during the test. This is done by setting the parameter EvDisable to “Yes”.
                   Verify that the connections are correct and that measuring and scaling is done
                   correctly. This is done by injecting current and voltage to the IED.
26                                                                                              630 series
                                                                                     Commissioning Manual
1MRS756801 D                                                                                      Section 4
                                                                                      Testing IED operation
                       Also the Signal Monitoring tool in PCM600 can be used to read the measured
                       values. In many cases it is more convenient to use PCM600 since, for example,
                       reports on measured values can be exported from the Signal Monitoring tool to
                       other tools (for example, MS Excel) for further analysis.
630 series                                                                                                           27
Commissioning Manual
Section 4                                                                                1MRS756801 D
Testing IED operation
28                                                                                            630 series
                                                                                   Commissioning Manual
1MRS756801 D                                                                               Section 5
                                                                                     Troubleshooting
Section 5 Troubleshooting
                       1.   Check the error origin from IED's internal event list Main menu/Monitoring/
                            Internal events.
                       2.   Reboot the IED and recheck the supervision events to see if the fault has
                            cleared.
                       3.   In case of persistent faults, contact ABB for corrective actions.
                       •    Check the communication status in the internal event list in Main menu/
                            Monitoring/IED status.
                       •    In case of persistent faults originating from IED's internal faults such as
                            component breakdown, contact ABB for repair or replacement actions.
630 series                                                                                                29
Commissioning Manual
Section 5                                                                                  1MRS756801 D
Troubleshooting
                  There are several different communication links on the product. First check that all
                  communication ports that are used for communication are turned on.
                  •    Select Main menu/Monitoring/IED status and check the status of the time
                       synchronization on Time Synch.
                       The Time synch value is Ready when the synchronization is in order.
30                                                                                              630 series
                                                                                     Commissioning Manual
1MRS756801 D                                                                                 Section 5
                                                                                       Troubleshooting
                       The ABB logo together with the IED FAILURE message appear on the screen
                       after a five minutes' communication break between the LHMI and the IED. The
                       LHMI panel displays the message due to a communication failure or a severe
                       functional error in the IED. The protection functionality of the device can be
                       ensured by testing the IRF contact status.
                       Different actions are taken depending on the severity of the fault. If the fault is
                       found to be permanent, the IED stays in internal fault mode. The IED continues to
                       perform internal tests during the fault situation.
                       When a fault appears, the fault indication message is to be recorded and stated
                       when requesting support or service.
630 series                                                                                                    31
Commissioning Manual
Section 5                                                                                                  1MRS756801 D
Troubleshooting
5.2.2             Warnings
                  The warning message associated with the fault is found in the internal event list in
                  the LHMI menu Main menu/Monitoring/Internal events. The message includes
                  the date, time, description and signal state for the fault. The current status of the
                  internal fault signals can also be checked via the LHMI in Main menu/Monitoring/
                  IED status.
                  When a fault appears, record the fault indication message and state it when
                  ordering service.
32                                                                                                            630 series
                                                                                                   Commissioning Manual
1MRS756801 D                                                                                            Section 5
                                                                                                  Troubleshooting
                       The messages are listed in the LHMI menu under the event list. The signal status
                       data is found under the IED status and in the internal event list.
630 series                                                                                                               33
Commissioning Manual
Section 5                                                                                1MRS756801 D
Troubleshooting
                  The physical inspection of wiring connections often reveals the wrong connection
                  for phase currents or voltages. Even when the phase current or voltage connections
                  to IED terminals are correct, wrong polarity of one or more measurement
                  transformers can cause problems.
                  •   Check the current or voltage measurements and their phase information from
                      Main menu/Measurements.
                  •   Check that the phase information and phase shift between phases is correct.
                  •   Correct the wiring if needed.
                      •     Change the parameter ReversePolarity in Configuration/I/O modules/
                            AIM2 for the channel n (n= the number of the channel that has wrong
                            polarity).
                      •     In PCM600, change the parameter CTStarPointn (n= the number on the
                            current input) under the parameter settings for each current input.
                  •   Check the actual state of the connected binary inputs.
                      •     In LHMI, select Main menu/Monitoring/I/O status/Binary input
                            modules. Then navigate to the board with the actual binary input to be
                            checked.
                      •     With PCM600, right-click the product and select Signal Monitoring.
                            Then navigate to the actual I/O board and to the binary input in question.
                            The activated input signal is indicated with a yellow-lit diode.
                  •   Measure output contacts using the voltage drop method of applying at least the
                      minimum contact load given for the output relays in the technical data, for
                      example, 100 mA at 24 V AC/DC.
34                                                                                            630 series
                                                                                   Commissioning Manual
1MRS756801 D                                                                                      Section 5
                                                                                            Troubleshooting
V 2
A 1 3
                                                                   4
                       GUID-BBAEAF55-8D01-4711-A71D-BBC76B60BA3D V1 EN
                         1 Contact current
                         2 Contact voltage drop
                         3 Load
                         4 Supply voltage
630 series                                                                                                   35
Commissioning Manual
Section 5                                                                                   1MRS756801 D
Troubleshooting
1 V
GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN
                  •   To check the status of the output circuits driving the output relay via the
                      LHMI, select Main menu/Monitoring/I/O status/Binary output modules
                      and then navigate to the board with the actual binary output to be checked.
                  •   Test and change the relay state manually.
                      1.         To set the IED to test mode, select Main menu/Test/IED test mode/
                                 TestMode and set the parameter to ”On”.
                      2.         To operate or force the output relay to operate, select Main menu/Test/
                                 Forcing/Binary output values and then navigate to the board with the
                                 actual binary output relay to be operated/forced.
                      3.         Select the BOn_PO to be operated or forced and press       and    or
                                 to operate the actual output relay.
                                 In PCM600, only the result of these operations can be checked by right-
                                 clicking the product and selecting Signal Monitoring and then navigating
36                                                                                               630 series
                                                                                      Commissioning Manual
1MRS756801 D                                                                                         Section 5
                                                                                               Troubleshooting
                                     to the actual I/O-board and the binary input in question. The activated
                                     output signal is indicated with a yellow-lit diode. Each BOn_PO is
                                     represented by two signals. The first signal in LHMI is the actual value
                                     “1” or “0” of the output, and in PCM600 a lit or dimmed diode. The
                                     second signal is the status Normal or Forced. Forced status is only
                                     achieved when the BO is set to “Forced” or operated on the LHMI.
                       An initially high contact resistance does not cause problems as it is reduced quickly
                       by the electrical cleaning effect of fritting and thermal destruction of layers,
                       bringing the contact resistance back to the mOhm range. As a result, practically the
                       full voltage is available at the load.
                       •   Verify the sensor measuring mode by using a suitable resistor instead of a real
                           sensor.
                           •         PT100 80...170 Ω
                           •         PT250 220...430 Ω
                           •         NI100 80...240 Ω
                           •         NI120 100...280 Ω
                           •         CU10 8...16 Ω
                           Resistance measuring mode can be verified with a resistance from 0...10 KΩ.
630 series                                                                                                        37
Commissioning Manual
Section 5                                                                                              1MRS756801 D
Troubleshooting
GUID-327C519C-BA13-4161-A62C-B94074ECEC01 V1 EN
38                                                                                                          630 series
                                                                                                 Commissioning Manual
1MRS756801 D                                                                                            Section 5
                                                                                                  Troubleshooting
GUID-A1C53A59-D607-4E0D-B3BF-7E12BEA35E9A V1 EN
GUID-DC08299A-C531-4C02-9273-AA9BD6ED7F6E V1 EN
630 series                                                                                                             39
Commissioning Manual
Section 5                                                                                             1MRS756801 D
Troubleshooting
GUID-E486DBB7-EB19-436C-9294-90B8B5FF398D V1 EN
                  •   Check the status of the output circuits driving the mA outputs via the LHMI.
                      Select Main menu/Monitoring/I/O status/mA output modules/RTD3 and
                      check the output status and value for the channel under inspection.
                  •   Test and change the output manually.
                      1.         Select Main menu/Test/IED test mode/TestMode and set the
                                 parameter to “On”.
                      2.         Select Main menu/Tests/Forcing/Analog output values/RTD3.
                      3.         Select the AOn to be forced.
                      4.         Force the actual output using and   or    .
                      Each AOn is represented by two signals. The first signal in LHMI is the actual
                      primary value of the output. The second signal is the status Normal or Forced.
                      Forced status is only achieved when the AO is set to “Forced” on the LHMI.
40                                                                                                         630 series
                                                                                                Commissioning Manual
1MRS756801 D                                                          Section 5
                                                                Troubleshooting
630 series                                                                           41
Commissioning Manual
42
1MRS756801 D                                                                            Section 6
                                                                                        Glossary
Section 6 Glossary
                       AC          Alternating current
                       CAT 5       A twisted pair cable type designed for high signal integrity
                       CT          Current transformer
                       DC          1. Direct current
                                   2. Disconnector
                                   3. Double command
                       DHCP        Dynamic Host Configuration Protocol
                       EMC         Electromagnetic compatibility
                       Ethernet    A standard for connecting a family of frame-based computer
                                   networking technologies into a LAN
                       FAT         Factory acceptance testing
                       HMI         Human-machine interface
                       HW          Hardware
                       I/O         Input/output
                       IEC         International Electrotechnical Commission
                       IED         Intelligent electronic device
                       IET600      Integrated Engineering Toolbox
                       IP          Internet protocol
                       IP address A set of four numbers between 0 and 255, separated by
                                  periods. Each server connected to the Internet is assigned a
                                  unique IP address that specifies the location for the TCP/IP
                                  protocol.
                       IRF         1. Internal fault
                                   2. Internal relay fault
                       LAN         Local area network
                       LC          Connector type for glass fibre cable
                       LCD         Liquid crystal display
                       LED         Light-emitting diode
                       LHMI        Local human-machine interface
                       NCC         Network control center
                       PC          1. Personal computer
                                   2. Polycarbonate
630 series                                                                                        43
Commissioning Manual
Section 6                                                               1MRS756801 D
Glossary
44                                                                           630 series
                                                                  Commissioning Manual
45
Contact us
www.abb.com/substationautomation