The new-age
sustainable solution
AIR INSULATED SWITCHGEAR
Compact l Reliable l Safe
The development of L&T s Air Insulated Switchgear was driven by innovation and
technology. L&T s AIS conforms to the latest international standards and local regulations.
Optimum results are ensured          with enhanced safety, greater reliability, operating cost
efficiencies, effective use of capital, and superior performance.
L&T Electrical and Automation is a part of the multi-billion dollar technology, engineering, construc-
tion, manufacturing and services conglomerate. The Company designs, manufactures and markets a
wide range of low voltage and medium voltage electrical systems, control and automation systems,
electrical products and metering and protection systems.
Our core strength in engineering and MV product development, bolstered by strong R&D with
TAMCO, enables us to deliver the most comprehensive, best-in-class electrical solutions to our diverse
customer base.
                           Safety
              VH - AIS
                          Reliability
                         Convenience
Empowering you with our expertise, support,
millions hours of experience acquired internationally.
                                                                              Safety
                                                                 VH - AIS
                                                                             Reliability
                                                                            Convenience
VH - Air Insulated Switchgear
L&T s VH-AIS is the result of decades of experience in
offering environment-friendly vacuum technology for arc-
quenching in highly reliable and safe air insulation, with
minimal maintenance, compact space solutions and ease of
user management.
VH - AIS comprises metal-clad medium voltage switchgear
assemblies from 3.3 to 36kV. We offer the most compact
switchgear up to a fault level of 50kA, 3s for 12kV &
31.5kA, 3s for 36kV system.
VH - AIS is well designed to function satisfactorily even in
the most adverse environmental conditions, owing to its
robust construction and high performance.
Your indoor switching system is absolutely safe and
protected with VH - AIS, for wide applications ranging from
industries to infrastructure sectors. It adheres to the latest
IEC standards.
IEC62271-100
High Voltage Circuit Breakers (1 kV - 52 kV)
IEC62271-200
High Voltage Metal Enclosed Switchgear (1 kV - 52 kV)
IEC62271-102
High Voltage Disconnectors & Earthing Switches
IEC62271-106
High Voltage Contactors (for Controllers & Motor Starters)
          Safety
Honored protector
VH - AIS is a robust metal-clad switchgear, divided into four
distinct compartments (busbar, circuit breaker, cable and
low voltage equipment) segregated by earthed metal
panels, to assure your protection against electric shock.
                                                                Extreme independence of
                                                                environment
                                                                VH - AIS gives you protection against access to hazardous
                                                                parts and solid foreign bodies and is designed & engineered
                                                                to perform satisfactorily in harsh and corrosive environment
                     Ingress protection                         with dust and pollution.
                            IP4X
Touch protective
The earthed metallic, spring operated shutters ensure
protection against accidental contact even when the
breaker is isolated or withdrawn.
The independent operation and padlocking of the busbar &
cable shutters enhances safety during maintenance.
                                                                                                    Safety
Arc proof          Integral safety
The successful verification of internal arc classification, IAC
A (F,L,R), for our switchgear ensures the highest possible
degree of protection to operating personnel and switchgear
vicinity.
How?
VH-AIS incorporates independent pressure relief flaps for
each compartment and completely separated gas duct.
In the unlikely event of an internal arc fault, the gases are
expelled at the top of the cubicle, as far from the operator as
possible, for improved safety.
                                            Our type-tested VH - AIS also accomplishes the provisions of internal Arc fault
                                            withstand stest as per IEC 62271-200 in all aspects.
                                              Criterion                                                           VH-AIS
                                                Correctly secured doors and covers do not open
                                                No enclosure fragmentation during the test period
                                                No holes in accessible sides up to a height of 2m during an arc
                                                Indicators do not ignite due to hot gases caused by the arc
                                                Earth connections remain intact for the safety of operator
          Safety
A world of Safety interlocks
VH - AIS comprises a set of complete electrical interlocking
in grouping with intelligent & strong mechanical interlocks
to prevent any accidental erroneous operation, resulting in a
safer environment for both plant and personnel.
For maximum safety, all operations are performed from
the front with the door closed, with highly reliable fool-
proof interlocks:
  For rack-in of VCB or VCU, connection of the LV plug
  is mandatory.
  VCB or VCU can be racked-in and withdrawn only in OFF
  condition.
  VCB or VCU can be closed only in Test or Service
  position.
Earth Switch Interlock
  Earth switch can be closed only when VCB or VCU is in
  Test position.
  VCB or VCU can be racked in only when Earth switch is
  in open condition.
Earthing Truck Interlock
  The Bus / Cable circuit can be earthed with the earthing
  truck only when there is no voltage on Bus / Cable.
Customized Rear Door Interlock
   Rear compartment door opens only when the VCB or
   VCU is in test position with earth switch closed.
                                                                The VH - AIS comes with a host of safety
                                                                interlocks. Additional interlocking can be
                                                                engineered to your requirements.
                                                                                                  Safety
Trusted busbar zone
Generous and optimum clearances for main busbars
and connectors warrant unmatched safety for you.
Supports and insulation materials are flame resistant, track
resistant and non-hygroscopic exhibiting outstanding
electrical properties.
                                                               Earthing Switch
                                                               Safeguarding of operating personnel is achieved by
                                                               providing make-proof earthing switch for cable, as well as
                                                               busbar compartments.
                                                               You have an option to select an integral earthing switch or a
                                                               separate earthing truck.
                                                               The switch is tested to make and carry the rated short-circuit
                                                               current for 3s.
                Safety First
         Reliability
Unmatched structural integrity
Our cubicles are made of high-grade pickled & oiled mild
steel sheets, cut and folded on numerically controlled
machines, making the enclosure sturdy and reliable.
                                                           Surface protector
                                                           The 9-tank pre-treatment paint process along with powder
                                                           coating with robotic paint applicator ensures that your
                                                           cubicle has a long lasting, high-gloss finish and is optimally
                                                           protected against corrosion and weathering.
Infinite cycles
Our Vacuum Circuit Breakers require minimal maintenance
and have a design life of 20 years or 10,000 mechanical
operations.
For motor switching applications, you can rely on our
vacuum contactors with a capacity of up to 3 million
mechanical operations.
                                                                                   Reliability
Dynamic driver
Our AIS systems are seismically qualified. They are enhanced
for rigidity and tested for stable operation in earthquake
prone areas up to Zone V as per latest codes & standards.
                                                                  A Global validation
                                                                  VH - AIS is completely type-test-verified at
                                                                  reputed international third-party laboratories
                                                                  to assure you best-in-class products.
     CPRI            ERDA     KEMA             CESI        ASTA
Factory specialist
The performance of your assemblies is guaranteed by
carrying out the following checks as our routine factory
test plan:
  Electrical tests
  Visual Checks
  Measurement Checks
  Mechanical tests
  Physical tests
          Convenience
Smart addition
Panel coupling at site is made simple and safe through easily
accessible bus bar connections and links.
                                                                More space. More capability.
                                                                The cable termination height is well above floor level, and
                                                                generous space is provided for terminating power cables.
                                                                This ensures a higher bending radius and reduces tension on
                                                                the terminals.
Stay connected
Our Vacuum Circuit Breakers and Contactor Units are truck-
mounted, the movement of which is interlocked with the
door to make it very convenient for your operators.
                                                                Ergonomic
                                                                VH-AIS comes with a single-handle for opening and closing
                                                                the breaker door, eliminating fasteners. This makes the
                                                                operation quick and easy.
                                                                                    Convenience
Minimum Footprint.
Optimum Utilisation.
VH - AIS can accommodate 2 VCBs / VCUs in a single vertical
section, thereby saving space.
Also, Bus PT and Line PT can be offered in a two-tier
arrangement.
                                                                  Maximize your space
                                                                  VH - AIS is characterized by a reduced width which offers
                                                                  savings on space and civil costs. Even with panels as slim as
                                                                  600mm, it offers spacious compartments allowing easy
                                                                  access for installation and maintenance.
         0.1   0.2   0.3   0.4   0.5 0.6 0.7   0.8   0.9   1.0
                                                           mtrs
Visual appeal
The detailed instructions about operations & interlocks
are screen printed on the VCB compartment door for
convenience.
Moreover, the front viewing window shows a clear visual
display of circuit breaker position, ON/OFF condition, spring
charged / discharged and earthing switch status.
                                                                  Customize your experience
                                                                  Round-the-clock project management executives and after-
                                                                  sales teams support your installation, commissioning and
                                                                  maintenance needs.
            Construction
Typical VH - AIS Arrangement
A - VCB / VCU Compartment
B - Busbar Compartment
C - Cable Compartment
D - Low Voltage Compartment
                                                                                                                           19
                                                            D
                                                                                                                           13
                                                                         A             B                  C
                                             9
                                             12
                                   1
                                                                                                                           16
                                   2
   3
                                   4                                                                                        20
   5
                                   6                                                                                       17
                                                                                                                           18
                                   7
                                                          10                    15     11                   14
             FRONT VIEW                                                        SECTIONAL VIEW
01 - Test / Service position Indicator            08 - Routing communication wires              15 - Earth switch
02 - VCB door handle & padlocking                 09 - Routing Interpanel wires                 16 - Rear Door Interlock
                                                                                                                           Customised
03 - Manual trip                                  10 - Control cable entry                      17 - Surge Arrester
04 - Manual close                                 11 - Earth bar                                18 - CBCT
05 - Viewing window for VCB ON/OFF                12 - VCB safety shutters                      19 - Gas Duct
       & Spring charging status indication
                                                  13 - Pressure relief flaps                    20 - Voltage Detecting
06 - VCB Racking slot                                                                                Insulator
                                                  14 - Power cable entry
07 - Earth switch operating slot
                                                    Construction
Typical configurations
  - Busbar      - Line PT
  - Gas Duct    - VCB / VCU
  - Metering    - Cable
  - Bus PT
    Incomer / outgoing        Incomer / outgoing     Buscoupler with Bus PT
  with bottom cable entry     with top duct entry       and Riser panel
      Two tier PT Panel       Two tier VCU Panel            Incomer
                                                          with Line PT
IEC 62271
                  Technical Specifications
                                                              7.2 kV AIS with VCU
                                      Standards                                                           IEC 62271-200
            Panel Details
                                      Type Designation                                                        VH1H
                                      Voltage                                                              up to 7.2 kV*
                                      Power Frequency Withstand Voltage                                      20 kVrms
            Voltage ratings
                                      Impulse Withstand Voltage                                              60 kVp
                                      Frequency                                                             50 / 60 Hz
                                      Rated Current                                                         200 - 400 A
            Current ratings           Short Time Withstand Current                                          up to 8 kA
                                      Short Time Withstand Current (with Fuse)                            25 / 40 / 50 kA
                                      Width#                                                                 600 mm
            Dimension                 Depth#                                                              1570 / 1970 mm
                                      Height#                                                                2495 mm
                                      Partition Class                                                          PM
                                      Loss of Service continuity                                              LSC-2B
            Construction              Degree of protection                                       IP4X (Higher IP on request)
                                                                                                              Type C
                                                                                                  A (F, L,R), 40kA, up to 1s
                                      IEC Standard                                                        IEC 62271-106
                                      VCU Type                                           Non Latched                           Latched
                                      Type Designation                              VCU7N200     VCU7N400           VCU7L200          VCU7L400
                                      Opening time                                                           < 35 ms
            VCU                       Mechanical Endurance                              up to 3 Million                    up to 0.3 Million
                                      Electrical Endurance                                         up to 0.3 Million (AC-3)
                                      Rated Duties (40% on Load Factor)                                     Class 300
                                                                                                          110 / 220 V DC
                                      Auxiliary Contacts                                                    3NO+3NC
            * 12 kV VCU offered on request
                                                                                                                                                  IEC 62271
                                                                 Technical Specifications
                                                   12 kV AIS with VCB
                          Standards                                                                            IEC 62271-200
Panel Details
                          Type Designation                                                                          VH1H
                          Voltage                                                                                up to12 kV
                          Power Frequency Withstand Voltage                                                    28 /38* kVrms
Voltage ratings
                          Impulse Withstand Voltage                                                              75 / 95* kVp
                          Frequency                                                                              50 / 60 Hz
                          Rated Current                                               630 / 800 A       1250 A         2000 A        3150 / 4000^ A
                                                                                                 25 / 26.3 kA
                          Short Time Withstand Current (3s)
Current ratings                                                                                                   40 / 50 kA
                                                                                               62.5 / 65.75 kAp
                          Short Circuit Making current
                                                                                                               100 / 125 kAp
                          Width#                                                               600 mm                 800 mm            1000 mm
Dimension                 Depth #                                                                     1570 / 1970 / 2170 / 2270 mm
                          Height                                                                                  2495 mm
                          Partition Class                                                                            PM
                          Loss of Service continuity                                                               LSC-2B
Construction
                          Degree of protection                                                          IP4X (Higher IP on request)
                          Internal Arc Classification                                               A (F, L,R), up to 40 / 50kA , up to 1s
                          IEC Standard                                                                         IEC 62271-100
                          Type Designation                                                                        VK series
                          Operating Sequence                                                               O-0.3sec-CO-3min-CO
                          Opening time                                                                             < 35 ms
VCB                       Break time                                                                              < 3 cycles
                          Mechanical Operations                                                                    10,000
                          Closing /Tripping Coil                                                         24 / 48 / 110 / 220 V DC
                          Spring charging motor                                                24 / 48 / 110 / 220 V DC l 110 / 240 V AC
                          Auxiliary Contacts                                                            6NO+6NC / 12NO+12NC*
* offered on request   ^ with forced ventilation    # 50kA Panel width & depth starts from 800mm & 1970mm respectively
IEC 62271
                  Technical Specifications
                                                             36 kV AIS with VCB
                                      Standards                                                                            IEC 62271-200
            Panel Details
                                      Type Designation                                                                          VH3
                                      Voltage                                                                                  36 kV
                                      Power Frequency Withstand Voltage                                                      70 kVrms
            Voltage ratings
                                      Impulse Withstand Voltage                                                               170 kVp
                                      Frequency                                                                              50 / 60 Hz
                                      Rated Current                                                      800 A                1250 A             2000 / 2500* A
            Current ratings           Short Time Withstand Current (3s)                                                     25 / 31.5 kA
                                      Short Circuit Making current                                                          63 / 79 kAp
                                      Width                                                                                  1000 mm
            Dimension                 Depth**                                                                             2650 / 2950 mm
                                      Height***                                                                              2500 mm
                                      Partition Class                                                                           PM
                                      Loss of Service continuity                                                              LSC-2B
            Construction              Degree of protection                                                           IP4X (Higher IP on request)
                                      Internal Arc Classification                                                      A (F, L,R), 31.5kA , 1s
                                      IEC Standard                                                                         IEC 62271-100
                                      Type Designation                                                                       VY series
                                      Operating Sequence                                                               O-0.3sec-CO-3min-CO
                                      Opening time                                                                            < 35 ms
            VCB                       Break time                                                                             < 3 cycles
                                      Mechanical Operations                                                                    10,000
                                      Closing /Tripping Coil                                                          24 / 48 / 110 / 220 V DC
                                      Spring charging motor                                                 24 / 48 / 110 / 220 V DC l 110 / 240 V AC
                                      Auxiliary Contacts                                                                     6NO+6NC
            * Offered on request.
            ** Depth may vary with cable size & number of Current Transformer.
            *** Height is without gas duct and may change (increase/decrease) depending on LV Components / Relays.
The Perfect Match for your VH - AIS
L&T's VH - AIS offers the widest range of electrical solutions up to 36kV. Our In-house design and testing facilities
enable us to create customized solutions with type tested switchboard combining VCBs and VCUs in perfectly matched
configuration as per your requirements. We ensure that you achieve the highest level of cost & design optimisation with
our VH - AIS.
Vacuum Circuit Breaker
  VCB Class - E2 | C2 | M2
  Customized 2 trip coils configuration
  Common design & safety interlocks up to 36kV
  Rated current capacity up to 4000A
  Short circuit breaking capacity up to 50kA
  Built - in anti-pumping feature
  User-friendly truck mounted design
  Single operating handle for VCB door
                                                             Vacuum Contactor Unit
                                                               Fused Short circuit protection up to 50kA
                                                               Available in latched & non latched configurations
                                                               Encapsulated current carrying parts for higher safety
                                                               Truck mounted design similar to VCBs
                                                               Suitable for motor starters with numerous switching
                                                               operations
                                                               Two VCUs can be accommodated in single panel for
                                                               optimum space utilisation
                                                               VCU panels can be coupled with VCB panels owing to
                                                               similar dimensions
Sales Ofces - India                                                 Sales Ofces - International
Bengaluru                                                            Australia                                                                 Oman
                                                                     TAMCO Electrical Industries Australia Pty                                 P.O.Box 598, Ruwi, Postal Code-112
Bengaluru 560001                                                     Ltd                                                                       Sultanate of Oman
Tel: 080-25020319                                                    31 Kitchen Road, Dandenong 3175                                           Tel:+968 98034317
Fax: 080-25596397                                                    Melbourne, Victoria, Australia                                            Mob:+968 98034317
Email: ese-chn@Lntebg.com                                            Tel:+613 9706 7288                                                        EMail: ese-oman@Lntebg.com
                                                                     Fax:+613 9706 9112
Chennai                                                              Email: sales@tamcoaustralia.com.au                                        Qatar
L&T Construction Campus                                              www.tamcoaustralia.com.au
TC-1 Building, II Floor
Mount-Poonamallee Road                                               India                                                                     Najma Intersection, Opp: Doha Cinema
Manapakkam, Chennai 600 089                                          L&T Gate NO. 5, L&T Business Park TC -II,                                 C-Ring Road,P.O Box No- 24399
Tel:+91-44-2270 6801                                                 Tower B - 7 th oor, Saki vihar road,                                      Doha, Qatar
Fax:+91-44-2270 6930                                                 Mumbai 400 072                                                            Tel: +974-44-239 000
Email: ese-chn@Lntebg.com                                            Tel:+91-22-6705 2813                                                      Fax: +974-44-551 286
                                                                     Fax:+91-22-6705 1024                                                      Email: ese-qatar@Lntebg.com
Hyderabad                                                            Email: ese-intl@Lntebg.com
Post Bag 12, Vasantha Chambers                                                                                                                 Saudi Arabia
                                                                     Indonesia                                                                 L&T Electricals Saudi Arabia Company
Hyderabad 500 004                                                    PT. TAMCO Indonesia                                                       Limited - L. L. C
Tel: +91-40-6672 0210                                                F-36, Jalan Jababeka Raya                                                 MH-4, Plot: 17+19
Fax: +91-40-2324 2356                                                Jababeka Industrial Estate
Email: ese-hyd@Lntebg.com                                            Cikarang Utara, Bekasi, 17530,Indonesia                                   Kingdom of Saudi Arabia
                                                                     Tel.: +62 21 893 5070                                                     Tel: +966-3-8127708
Kolkata
                                                                     Fax: +62 21 893 5071                                                      Fax: +966-3-8127780
Post Bag 619
                                                                     Email: sales@tamco.co.id                                                  Email: Ltesa@Lntebg.com
                                                                     www.tamco.co.id
Kolkata 700 071
Tel. : +91-33-4400 2550 / 2558                                       Kuwait                                                                    2203, 22nd Floor
Fax. : +91-33-22827587 / 1025                                        Kana Controls General Trading &
Email: ese-kol@Lntebg.com                                            Contracting Co. W.L.L
                                                                     P.O Box: 25593 Safat, 13116                                               Abu Dhabi, UAE
Mumbai
                                                                     Kuwait                                                                    Tel. : +971-2-676 5988
L&T Gate NO. 5, L&T Business Park TC -II,
                                                                     Tel: +965-2474 1373                                                       Fax. : +971-2-676 6399
Tower B - 7 th oor, Saki vihar road,
                                                                     Faxs: +965-2474 1537                                                      Email: ese-uae@Lntebg.com
Mumbai 400 072
                                                                     Email: ese-kwt@Lntebg.com
Tel:+91-22-6705 3083
Fax:+91-22-6705 1556                                                 Malaysia
Email: ese-intl@Lntebg.com                                           TAMCO SWITCHGEAR (MALAYSIA) SDN
                                                                     BHD
New Delhi
                                                                     Sub Lot 24, Lot 16505, Jalan Keluli 1
Post Bag 6223
32, Shivaji Marg
                                                                     Section 7
New Delhi 110 015
Tel: +91-11-4141 9620/9942
                                                                     Tel: +603 3361 8200
Fax: +91-11-4141 9625
                                                                     Fax: +603 3341 6200
Email: ese-del@Lntebg.com
                                                                     Email: tamco@tamco.com.my
                                                                     www.tamco.com.my
Radhadaya Complex, J. P. Road
Vadodara 390 015
Tel: +91-265-66136 37/38
Fax: +91-265-2336 184
Email: ese-vad@Lntebg.com
                                                                                                                                                                                          ACA19.11.2015
Larsen & Toubro Limited, Electrical Systems & Equipment - Head Of ce                                                                                              Registered Of ce:
7C, TC II, Tower B, Level 7, L&T Gate No. 5, Saki Vihar Road, Powai, Mumbai 400 072.                                                                              L&T House, N. M. Marg
Tel: +91-22-6705 1748 Fax: +91-22-6705 1556                                                                                                                       Ballard Estate
                                                                                                                                                                  Mumbai 400 001, INDIA
Email: ese-cmt@Lntebg.com Website: www.lntebg.com
The information contained herein is correct at time of printing, but as the products and its manufacturing processes are being developed continuously,
this information is subject to change without notice and the company cannot be held liable for any alleged misinterpretation howsoever arising.