NG125 MCB

The document discusses circuit breakers and switchboards in electrical distribution. It provides an overview of the Merlin Gerin NG125 range, which offers protection specially designed for modular enclosure incomers. Key features include a wide choice of indication functions, rapid and safe intervention, and selective options for outgoers to optimize continuity of supply. Schneider Electric is the only manufacturer that offers a complete solution specifically designed for modular enclosure incomers when used with their Distribloc splitter.

Uploaded by

Saswita Sakti
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
357 views9 pages

NG125 MCB

The document discusses circuit breakers and switchboards in electrical distribution. It provides an overview of the Merlin Gerin NG125 range, which offers protection specially designed for modular enclosure incomers. Key features include a wide choice of indication functions, rapid and safe intervention, and selective options for outgoers to optimize continuity of supply. Schneider Electric is the only manufacturer that offers a complete solution specifically designed for modular enclosure incomers when used with their Distribloc splitter.

Uploaded by

Saswita Sakti
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

protect general presentation of NG125

load protection circuit-breakers

circuit-breaker functions in electrical distribution

direct outgoers
local load protection

high
power
incomer
switchboards 2501600 A > 32 kA

main direct
line
incomer outgoers
outgoers
1080 A
50400 A

loads

medium
power incomer incomer
50160 A 1535 kA 50400 A 2570 kA
switchboards

direct
line direct line outgoers
main 1050 A
outgoers outgoers outgoers
incomer
50125 A 5080 A 50125 A

loads loads

final switchboard incomer

final
switchboards
incomer incomer
50125 A 50125 A
325 kA 325 kA

final final
outgoers outgoers
1032 A 1032 A

loads loads

90230E.fm/2 Updated: 09/11/99 Schneider Electric


protect general presentation of NG125
load protection circuit-breakers

modular switchboard incomer: overview of the Merlin Gerin solutions


The NG125 range is the first to offer # extensive choice of indication functions for Schneider is thus the only manufacturer to
protection specially designed for the modular local or remote enclosure monitoring, propose a complete offer specifically
enclosure incomer. Combined with the # rapid, safe intervention, designed for the modular enclosure incomer.
Distribloc splitter, it enables rapid production # a selective option for outgoers, providing
of an "incomer" assembly providing users optimum continuity of supply.
with all the functions they require:

rated with protection


current circuit-breaker residual current circuit-breaker residual current device

160 A + T R + T R

Compact NSA160 Vigicompact NSA160NA Vigicompact NSA160

125 A
M ERLIN
NG125
GERIN

I . ON
M ERLIN
NG125
GERIN

I . ON
+
+ test mensuel

test monthly

set
10
40
60

80
I
n
0,3

A
0,5

3
1
s


01

t (ms)
60

150
vigi

I/S/S+
L

0,3A
125
3A

-25
C
dconnecter

avant
test

dilectrique

disconnect

for

dielectric

test

27508
M ERLIN
NG125
GERIN

I . ON
++ test mensuel

test monthly

10
40
60

80
I
n
0,3
0,5

3
1
s


01
60

t (ms)
150
vigi

I/S/S+
L

0,3A
125
3A

-25
C
dconnecter

avant
test

dilectrique

disconnect

for

dielectric

test

27508

set A

n (%)
I n (%)
I

NG125 Vigi NG125NA Vigi NG125

+
O-OFF
O-OFF
T
OFF
O-OFF
O-OFF
+ T

C120 ID100/125 Vigi C120

functions

manual operating # # #
mechanism

isolation # # #

remote # # #
opening

overcurrent # #
protection

earth leakage # #
protection

Schneider Electric Updated: 09/11/99 90230E.fm/3


protect general presentation of NG125
load protection circuit-breakers

without protection installation


switch-disconnector trip-free switch-disconnector

.1
.2
.4

Interpact INS160 Compact NSA160NA + auxiliaries on rail

.1
.2
.4

Interpact INS125

M ERLIN
NG125
GERIN multi 9
Mg modular
+
MX

I . ON

installation
system

NG125NA + auxiliaries

I125

# #

# #

90230E.fm/4 Updated: 09/11/99 Schneider Electric


protect general presentation of NG125
load protection circuit-breakers

terminal screw
shield shield

special
70 mm2
lug

comb insulated tunnel terminal accessories for lugs and busbars


busbars sub- for 70 mm2
distribution aluminium
terminal cable
MXV
auxiliary
SDV
auxiliary

GERIN
MERLIN
NG125

6T3

auxiliaries circuit-breaker or switch


Vigi module
fixed
adjustable

Vigi module
terminal shields

distribloc rotary handle


splitter

additional
information

Schneider Electric Updated: 09/11/99 90230E.fm/5


protect NG125N circuit-breakers
circuit protection B, C and D curves
IEC 60947-2: 25 kA

function This circuit-breaker is specially designed for


functions requiring a high breaking capacity
(up to 25 kA):
- modular enclosure incomer,
- main incomer in sub-distribution
switchboards,
- outgoer, protection of loads directly
supplied by a power switchboard.

description common technical data # weight (g):


# rating: 10125 A type 1P 2P 3P 4P
# reference temperature: 40 C
# Uimp: 8 kV 240 480 720 960
# Ui: 690 V
# maximum voltage rating: 500 V AC # compatible with the Pragma F24 and
# breaking capacity: Prisma G/GX enclosures and the Prisma P
as in IEC 60947.2 cabinets,
type voltage breaking capacity #degree of protection: IP20B (IP40D for the
(V AC) (A) part outside the enclosure)
# connection:
1P 220240 25000
5 6 63 A ratings: tunnel terminals for 1.5 to
1P 380415 6000 (1) 50 mm2 copper cables
2, 3, 4P 380415 25000
(1) 1-pole breaking capacity in the IT isolated
5 80 to 125 A ratings: tunnel terminals for 16
to 70 mm2 copper cables
neutral system (double fault).
5 aluminium cables, copper cables with lug
or busbar (see connection accessories)
# isolation with positive break indication
# 3-position toggle: open-tripped-closed 5 on 3P and 4P: upstream voltage taps on
# built-in padlocking facility on 3P and 4P each pole, by 6.35 mm Fast-on lugs, for
auxiliary circuit supply
# fault display on front face by:
5 fault indicator
5 position of toggle: tripped B curve
# the magnetic trip units operate at
# test button to check proper operation of 4 In 20 %
the tripping mechanism
# fast closing C curve
# electrical durability: 10 000 cycles at In # the magnetic trip units operate at
# tropicalisation as in IEC 68.1: treatment 2 8 In 20 %
(relative humidity: 95 % at 55 C)
D curve
# the magnetic trip units operate at
12 In 20 %

catalogue numbers type rating catalogue width


(A) number in mod.
of 9 mm
NG125N B curve

3P 80 18663 9
1 3 5 100 18664 9
125 18665 9

2 4 6

4P 80 18666 12
1 3 5 7 100 18667 12
125 18668 12

2 4 6 8

90233E.fm/2 Updated: 5/07/01 Schneider Electric


protect NG125N circuit-breakers
circuit protection B, C and D curves
IEC 60947-2: 25 kA

catalogue numbers type rating


(A)
catalogue
number
width
in mod.
of 9 mm
NG125N C curve

1P 10 18610 3
16 18611 3
20 18612 3
1 25 18613 3
32 18614 3
40 18615 3
50 18616 3
63 18617 3
80 18618 3

18617 2

2P 10 18621 6
1 3 16 18622 6
20 18623 6
25 18624 6
32 18625 6
40 18626 6
50 18627 6
63 18628 6
80 18629 6
2 4

18628

3P 10 18632 9
1 3 5 16 18633 9
20 18634 9
25 18635 9
32 18636 9
40 18637 9
50 18638 9
63 18639 9
2 4 6 80 18640 9
100 18642 9
125 18644 9
18644

3P + N 80 18646 12
100 18647 12
N 1 3 5 125 18648 12

N 2 4 6
18648

4P 10 18649 12
16 18650 12
1 3 5 7 20 18651 12
25 18652 12
32 18653 12
40 18654 12
50 18655 12
63 18656 12
80 18658 12
100 18660 12
2 4 6 8
125 18662 12
18662

Schneider Electric Updated: 5/07/01 90233E.fm/3


protect NG125N circuit-breakers
circuit protection B, C and D curves
IEC 60947-2: 25 kA

catalogue numbers type rating


(A)
catalogue
number
width
in mod.
of 9 mm
NG125N D curve

3P 80 18669 9
1 3 5 100 18670 9
125 18671 9

2 4 6

4P 80 18672 12
1 3 5 7 100 18673 12
125 18674 12

2 4 6 8

additional auxiliaries: page 90250/2


dimensions: page 90148/2
derating: page 92515/2
information accessories: page 90251/2
tripping curves: page 90180/2
Vigi module: page 90243/2
discrimination table: page 92511/2

90233E.fm/4 Updated: 5/07/01 Schneider Electric


circuit protection NG125H circuit-breakers
circuit-breakers up to 80 A C curve
IEC 947.2: 36 kA

function This circuit-breaker is specially designed for


functions requiring a high breaking capacity
(up to 36 kA):
- main incomer in the sub-distribution
switchboards;
- outgoer, protection of loads directly
supplied by a power switchboard.

description common technical data # electrical durability: 10 000 cycles at In


# rating: 1080 A # tropicalisation as in IEC 68.1:
# reference temperature: 40 C treatment 2 (relative humidity: 95 %
# Uimp: 8 kV at 55 C)
# Ui: 690 V # weight (g):
# maximum voltage rating: 500 V AC type 1P 2P 3P 4P
# breaking capacity:
as in IEC 947.2 240 480 720 960
type voltage breaking capacity
(V) AC (A) # compatible with Pragma F24 and Prisma
G/GX enclosures and Prisma P cabinets
1P 220240 36000 # degree of protection: IP20B (IP40D for the
1P 380415 9000 (1) part outside the enclosure)
2, 3, 4P 380415 36000 # connection:
(1) 1-pole breaking capacity in the IT isolated 5 6 63 A ratings: tunnel terminals for 1.5 to
neutral system (double fault). 50 mm2 copper cables
5 80 A rating: tunnel terminals for 16 to
# isolation with positive break indication 70 mm2 copper cables
# 3-position toggle: open-tripped-closed 5 connection of aluminium cables, copper
# built-in padlocking facility on 3P and 4P cables with lug or busbar for 3P and 4P (see
# fault display on front face by: connection accessories)
5 fault indicator 5 upstream voltage taps on each pole, by
5 position of toggle: tripped 6.35 mm Fast-on lugs, for auxiliary circuit
# test button to check proper operation of supply
the tripping mechanism
# fast closing C curve
# the magnetic trip units operate at
8 In 20 %

catalogue numbers type rating catalogue width


(A) number in mod.
of 9 mm
NG125H C curve

1P 10 18705 3
1 16 18706 3
20 18707 3
25 18708 3
32 18709 3
40 18710 3
50 18711 3
63 18712 3
80 18713 3
18712 2

2P 10 18714 6
1 3 16 18715 6
20 18716 6
25 18717 6
32 18718 6
40 18719 6
50 18720 6
63 18721 6
2 4 80 18722 6

18721

90236E.fm/2 Updated: 09/11/99 Schneider Electric


circuit protection NG125H circuit-breakers
circuit-breakers up to 80 A C curve
IEC 947.2: 36 kA

catalogue numbers type rating catalogue width


(A) number in mod.
of 9 mm
NG125H C curve (continued)

3P 10 18723 9
1 3 5 16 18724 9
20 18725 9
25 18726 9
32 18727 9
40 18728 9
50 18729 9
63 18730 9
2 4 6 80 18731 9
18730

4P 10 18732 12
1 3 5 7 16 18733 12
20 18734 12
25 18735 12
32 18736 12
40 18737 12
50 18738 12
63 18739 12
2 4 6 8 80 18740 12

18739

auxiliaries: page 90250/2 dimensions: page 90148/2


additional accessories: page 90251/2 derating: page 92515/2
Vigi module: page 90243/2 tripping curves: page 90180/2
information discrimination table: page 92511/2

Schneider Electric Updated: 09/11/99 90236E.fm/3