SITE REPORT
Panel Ref. : Description: TAP changer Relay
Equip./ Dev. Ref.: TAPCON BU Drawing ref.: Sheet : 1
Customer : MR Location : Riyadh
1. GENERAL DATA AND INFORMATION.
Panel No: Designation TAPCON BU
Make MR Rated AC 110V,1 A
Serial No: Aux: Voltage 125 V DC
Model No: TAPCON BU Application VOLTAGE REGULATION
2. MECHANICAL CHECKS AND VISUAL INSPECTION.
ITEM DESCRIPTION REMARKS
1. Inspect for any physical damage or defects.
2. Verify connections as per approved drawing.
3. Check tightness of all connections.
4. Check Apparatus list.
3. ELECTRICAL TESTS:
3.1 FUNCTION TEST:
ITEM DESCRIPTION REMARKS
1. Check of LED Indications
2. Check of LCD Display
3. Watch dog contact checked
4. Binary inputs checked.
5. TAP Position indication checked
3.2 Check of Voltage Measurement : Limits: +/- 0.3%
Applied Voltage (V) Measured Voltage (V) % Error
25V
50V
75V
110V
Description Tested by Witnessed by
Name
Signature
Company
SITE REPORT
Panel Ref. : Description: TAP changer Relay
Equip./ Dev. Ref.: TAPCON BU Drawing ref.: Sheet : 2
Customer : MR Location : Riyadh
3.3 Check of Current Measurement: Limits: +/- 0.5%
Injected Current (A) Measured Current (A) % Error
0.20
0.60
0.80
1.00
3.4 Check of Bandwidth:
Band Calculated Value Measured Values
Width % set
Raise Lower Raise Lower
2.0 -2.0 +2.0
Limits: +/- 0.3%
3.5 Check of Time Linear: Bandwidth = +/- 2%
Desired Injected Voltage( V) Actual Time T1
Volt(V) Selected Time
Raise Lower T1(linear) (Sec) Raise Lower
110 105 115 40
Limits: +/- 10% Calculated Time Value
3.6 Check of Delay Time 2:
Desired Selected Actual Time T1+T2
Injected Voltage( V) Selected Time
Volt(V) Time (Sec)
T1(linear)(Sec)
Raise Lower T2(Sec) Raise Lower
110 105 115 40 10
Limits: +/- 10% Calculated Time value
3.7 Under Voltage Blocking Check: OK
3.8 Over Voltage Blocking Check: OK
3.9 Over Current Blocking Check: OK
Testing Equipment Used: FREJA 300 -
Description Tested by Witnessed by
Name
Signature
Company