Manual Del 2kva Liebert PDF
Manual Del 2kva Liebert PDF
2.0      INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1      Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2      What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3      Preparation for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
         2.3.1      Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4      Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
         2.4.1      Tower Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
         2.4.2      Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5      Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
         2.5.1      Connecting Input Plug and Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
         2.5.2      Connecting Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.6      Connecting Communication Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
         2.6.1      Connecting USB Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
         2.6.2      Installing the Optional Liebert IntelliSlot Card and Communication Cables . . . . . . . . . . . . 15
                                                                               i
4.0   OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
4.1   Startup Checklist for the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2   Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3   Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.4   Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.5   Shut Down the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.6   Disconnecting Input Power from the Liebert GXT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.0   COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.1   Liebert IntelliSlot Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
      5.1.1     Liebert MultiLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2   USB Port Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
      5.2.1     Configuration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.3   Terminal Block Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
      5.3.1     Any Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            23
      5.3.2     Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              24
      5.3.3     On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   24
      5.3.4     Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    24
6.0   MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.1   Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
      6.1.1     Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.2   Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.3   Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.4   Checking UPS Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.5   Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.0   TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.1   UPS Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
      7.1.1     Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
      7.1.2     Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.2   Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
                                                                           ii
                                                                   FIGURES
Figure 1    Liebert GXT3-700RT230 - GXT3-3000RT230 UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2    Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA models. . . . . . . . . . . . 5
Figure 3    Rear panel components, Liebert GXT3 230V 2000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4    Rear panel components, Liebert GXT3 230V 3000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5    Operating principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6    Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 7    Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 8    Rotate the operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 9    Tower installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 10   Pulling inner member from each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 11   Installing rear member of each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 12   Installing front member of each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 13   Fastening rear member and front member together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 14   Installing inner members . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 15   Installing ears . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 16   Insert the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 17   Operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 18   Battery level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 19   Load level indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 20   Dry contact pin layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 21   Removing the front plastic bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 22   Disconnecting the battery plug and battery receptacle (front view) . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 23   Pulling out the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 24   Battery level indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 25   Battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
                                                                    TABLES
Table 1     UPS models, power ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2     Specification of input circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 3     Functions of the On/Alarm Silence/Manual Battery Test button . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 4     Functions of the Standby/Manual Bypass button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 5     UPS status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 6     Output voltage option, all models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 7     Indicator descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 8     Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 9      Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 10    Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 11    Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230 . . . . 33
Table 12    Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 13    Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 14    Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
                                                                            iii
iv
IMPORTANT SAFETY PRECAUTIONS
      !      WARNING
             Observe all cautions and warnings in this manual. Failure to do so may result in serious
             injury or death.
             Refer all UPS and battery service to properly trained and qualified service personnel. Do not
             attempt to service this product yourself.
             Opening or removing the cover may expose you to lethal voltages within this unit even when
             it is apparently not operating and the input wiring is disconnected from the electrical source.
             Never work alone.
                                                    1
Battery Safety
  !     CAUTION
        Do not dispose of the battery in a fire. The battery may explode.
        Do not open or damage the battery. Released electrolyte is harmful to skin and eyes. If
        electrolyte comes into contact with the skin, wash the affected area immediately with plenty
        of clean water and get medical attention.
  !     CAUTION
        A battery can present a risk of electrical shock and high short-circuit current. The following
        precautions should be observed when working on batteries:
        • Remove watches, rings and other metal objects.
        • Use tools with insulated handles.
        • Do not short-connect the battery terminals. The battery may catch fire.
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 Series complies with the limits for
a Class A digital device. Operating this device in a residential area is likely to cause harmful interfer-
ence that users must correct at their own expense.
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the pub-
lished technical standards. Continued compliance requires installation in accordance with these
instructions and use of accessories approved by Emerson.
                                                2
GLOSSARY OF SYMBOLS
AC input
AC output
           -       +
                       Indicates the unit contains a valve-regulated lead acid battery
           PbH2SO4
R Recycle
DC voltage
Bonded to ground
AC voltage
OFF/Bypass
WEEE
                                                  3
                                                                                        Product Description
1.1   Features
      The UPS includes the following features:
       • Intelligent battery management to extend the battery life
       • Operation and display panel with LED for monitoring load percentage and battery capacity inde-
         pendently
       • Flexible network management with Liebert MultiLink™ software
       • Fan fault self-inspection and automated diagnostic function
       • Intelligent fan operation, automatically changing rotation speed depending on system require-
         ments, to decrease power consumption and noise
       • Input circuit breaker to ease recovery from overloads
       • CE mark and safety approval from CE
       • Communication options: USB port, Liebert IntelliSlot® port and terminal block communication
       • Dry contacts for remote monitoring
       • Input power factor greater than 0.99
       • Output voltage selection function
                                                    4
                                                                                                 Product Description
                               Ventilation Slots
                                                          Operation and Display Panel
                                                     External Battery
                Terminal Block                                                           C13 Output Receptacles
                                       Cooling Fan   Connector
                Communication
Figure 3       Rear panel components, Liebert GXT3 230V 2000VA models
Liebert IntelliSlot Port                             Input Circuit        C20 Input Receptacle
                            USB Port                 Breaker
                                                           5
                                                                                                    Product Description
                                                                  DC-to-DC
                                                                  Converter
                                      Battery
                                                                    Battery
                                      Charger
      N                                                                                                        N
      G                                                                                                        G
          The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery char-
          ger, DC-to-DC converter, battery, dynamic bypass and UPS output.
                                                         6
                                                                                             Product Description
        Inverter
        In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC circuit to produce
        precise, regulated sine wave AC power. When mains power fails, the inverter receives DC power from
        the battery through the DC-to DC converter. In either operation mode, the UPS inverter is online,
        continuously generating clean, precise, regulated AC output power.
        Battery Charger
        The battery charger utilizes energy from the mains power and precisely regulates it to continuously
        float charge the batteries. The batteries are being charged whenever the Liebert GXT3 is plugged in,
        even when the UPS is not turned on.
        DC-to-DC Converter
        The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for
        the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage,
        increasing reliability.
        Battery
        The Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery
        design life, operate the Liebert GXT3 in an ambient temperature of 0°C to 25°C (32°F to 77°F).
        Optional external battery cabinets are available to extend battery run times.
        Dynamic Bypass
        The Liebert GXT3 provides an alternate path for mains power to the connected loads in the unlikely
        event of a UPS malfunction. Should the Liebert GXT3 have an overload, overtemperature, or UPS
        failure condition, the UPS automatically transfers the connected loads to bypass.
                NOTE
                The bypass power path does not protect the connected loads from disturbances on the mains.
                                                       7
                                                                                           Product Description
          !      CAUTION
                 Turning off the UPS in Bypass Mode will result in loss of output power.
          !      CAUTION
                 Turning Off the Liebert GXT3 when it is in Battery Mode will result in loss of output power.
                 If the UPS is turned Off manually, it must be manually restarted after mains power returns.
                 If the UPS is turned Off by a communication signal or because the batteries are depleted, it
                 will operate as selected in the configuration program for Auto-Restart (Refer to 5.2.1 -
                 Configuration Program).
                 NOTE
                 The default for all models of the Liebert GXT3 is “Auto Sensing - 50Hz or 60 Hz – Bypass
                 Enabled.”
          !      CAUTION
                 Do not touch the AC input receptacle when the UPS is operating. AC input voltages may still
                 be present even when the AC input indicator is Off.
                                                       8
                                                                                                    Installation
2.0 INSTALLATION
               NOTE
               The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two
               spacers for tower configuration and one DC power cable.
               NOTE
               Operating the Liebert GXT3 in temperatures above 25°C (77°F) reduces battery life.
        Installation Clearances
        Maintain a clearance of at least 100mm (4 inches) in the front and rear of the Liebert GXT3. Do not
        obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces
        ventilation and heat dissipation, shortening the service life of the Liebert GXT3.
               NOTE
               When installing the UPS or making input and output connections, comply with all relevant
               safety codes and standards.
                                                      9
                                                                                                    Installation
Support Bases
        2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the
           spacers delivered with the battery cabinet.
        3. Connect the spacers and the support bases as shown in Figure 6. Each Liebert GXT3 needs two
           assembled support bases, one in the front and one in the rear.
        4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3.
           a. Remove the front plastic bezel cover (see Figure 7).
           Front Plastic
           Bezel Cover
           b. Pull the operation and display panel, rotate it 90 degrees clockwise and snap it back into
              position (see Figure 8).
           c.  Pull the logo on the front plastic bezel cover, rotate it 90 degrees clockwise and snap it back
               into position. The rotated front plastic bezel cover is shown in Figure 9.
           d. Replace the front plastic bezel cover on the Liebert GXT3. At this point, the UPS operation
               and display panel and logo have been rotated 90 degrees clockwise, which provides upright
               viewing for users.
        5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs
           four support bases, as shown in Figure 9.
                                                      10
                                                                                                           Installation
                                                 Operation and
                                                 Display Panel
                                                  Rotated for
                                                Tower Operation
                 NOTE
                 • When the Liebert GXT3 is installed in a rack, the UPS must be supported by a shelf,
                   brackets, or slide rails on each side. The factory-supplied ears cannot support the weight of
                   the UPS. They are used to move the UPS into and out of the rack and attach the UPS to the
                   rack.
                 • Mounting hardware and slide rails are sold separately. Contact your local dealer or
                   Emerson representative for these options and any assistance.
                                           ut
                                    ll o
                                  Pu
Bracket assembly
                                                                  Retaining latch
                                                          Inner member
                                                           11
                                                                                                       Installation
       3. Determine the desired height and mounting position of the Liebert GXT3 inside the rack’s vertical
          rails.
            !      CAUTION
                   Reduce risk of tipping the rack by installing the Liebert GXT3 in the lowest possible rack
                   position.
       4. Attach the rear member of each bracket assembly to the rack’s vertical rails with two factory-
          supplied M5 screws (see Figure 11).
Figure 11       Installing rear member of each bracket assembly
Vertical pole
M5 screw (4 pcs)
                                                                              Rear member
                                                                              Front member
       5. Extend bracket assembly by sliding the front member forward until it touches the rack’s front
          vertical rails (adjustable length: 18 inches to 32 inches).
       6. Use two M5 screws to attach each front member onto the front vertical rails through the
          installation holes. Make sure that the bracket assemblies are at the same mounting height on all
          four of the rack’s vertical rails (see Figure 12.)
Figure 12 Installing front member of each bracket assembly
                                                    de
                          Front vertical pole   Sli
Front member
                                                                                    Rear member
                       M5 screw (4 pcs)
       7. Fasten the rear and front members together using four M4 screws and four M4 nuts (M4 nuts
          have been installed on the rear member before delivery) per bracket assembly, as shown in
          Figure 13.
Figure 13 Fastening rear member and front member together
                                                                            Rear member
                                                                            M4 screw (8 pcs)
                                                                            M4 nut (8 pcs)
Front member
       8. Fasten inner members pulled from the bracket assemblies in Step 2 to the UPS on both sides with
          eight M4 screws provided in this kit. Make sure that the retaining latch is near the rear of the
          UPS, as shown in Figure 14.
                                                         12
                                                                                                          Installation
Inner Member
Retaining Latch
M4 screw, 8 pieces
       9. Use M4 screws to install ears of accessories on both sides of the UPS, as shown in Figure 15.
Figure 15 Installing ears
Ear, 2 pieces
M4 Screw, 8 pieces
       10. Insert the UPS, with inner members attached, into bracket assemblies by inserting top and
           bottom edges of inner members into the top and bottom curved tracks of front members and
           sliding the UPS into the rack, as shown in Figure 16.
Figure 16 Insert the UPS
Insert
Front Member
Inner Member
              NOTE
              Ends of inner members are tapered to allow the rear of the UPS to be angled upward before
              insertion, if space allows.
              The UPS should move smoothly into the bracket assemblies. If not, recheck alignment of front
              and rear members from Steps 4 through 7.
                                                    13
                                                                                                       Installation
        11. Through the ears, use M5 screws provided in this kit to secure the front of the UPS to the rack’s
            vertical rails to prevent the UPS from sliding out of position.
        12. If optional Liebert external battery cabinets will be connected to the UPS, they can be placed all
            on one side of the UPS or stacked beneath the UPS. The installation procedures are the same as
            those for the UPS.
                  NOTE
                  Up to four external battery cabinets can be connected to the Liebert GXT3. Each cabinet will
                  increase the battery recharge time.
                  NOTE
                  Ensure that all the loads are turned off.
                  Prepare an input power supply that is properly protected by a circuit breaker in accordance
                  with national and local electrical codes. The wall receptacle must be grounded.
                  Emerson recommends installing an upstream circuit breaker of the same series as the Liebert
                  GXT3’s input circuit breaker. The upstream breaker should have a higher capacity than the
                  UPS input circuit breaker.
        The specification of input circuit breaker on the rear panel of the UPS is given in Table 2.
        Table 2       Specification of input circuit breaker
                              Rated Circuit
              Model             Breaker
         GXT3-700RT230             10A
         GXT3-1000RT230            10A
         GXT3-1500RT230            10A
         GXT3-2000RT230            16A
         GXT3-3000RT230            16A
1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.
                  NOTE
                  Do not overload any one output receptacle.
2. Plug the input receptacle of the Liebert GXT3 into the input power connection.
                                                         14
                                                                                                   Installation
2.6.2   Installing the Optional Liebert IntelliSlot Card and Communication Cables
        1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT3 and set it aside.
        2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws.
        3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided
           with the card.
        To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual.
        Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site:
        www.liebert.com
                                                     15
                                                                                                           Operation and Display Panel
                                                                    16
                                                                                      Operation and Display Panel
3.2     Indicators
        The operation and display panel has seven indicators (see Figure 16). The indicators can be divided
        into two groups according to their applications: level indicators and UPS status indicators.
          21 - 40%
                              ON   Flash   OFF   OFF    OFF               ON     ON   OFF   OFF   OFF
          41 - 60%
                              ON   ON      Flash OFF    OFF               ON     ON   ON    OFF   OFF
          61 - 80%
                              ON     ON     ON   Flash OFF                ON     ON   ON     ON   OFF
          81 - 100%
                              ON   ON      ON    ON     Flash             ON     ON   ON     ON   ON
            Fully
           Charged
                              ON   ON      ON    ON     ON                ON     ON   ON     ON   ON
                               0 - 25%
                                                   ON      OFF    OFF   OFF    OFF
                              26 - 50%
                                                   ON        ON   OFF   OFF    OFF
                              51 - 75%
                                                   ON        ON   ON    OFF    OFF
                              76 - 100%
                                                   ON        ON   ON    ON     OFF
                              Overload
                                                   ON        ON   ON    ON     ON
                                                        17
                                                                                            Operation and Display Panel
Fault Indicator Red On if the UPS has detected a fault; Off if there is no fault
                                                      18
                                                                                                    Operation
4.0   OPERATION
      This section describes checks to be made before starting the UPS, how to start the UPS, manual bat-
      tery test, manual bypass, shutting down the UPS and disconnecting the mains power from the UPS.
             NOTE
             The Liebert GXT3’s battery has been fully charged before delivery, but some charge will be lost
             during storage and shipping. To ensure that the battery has adequate reserve power to protect
             the connected load, charge the battery for three hours before putting the UPS into service.
                                                    19
                                                                                                 Operation
                                                   20
                                                                                               Communication
5.0     COMMUNICATION
        This section describes UPS communication over the three types of communication connections on the
        rear of the Liebert GXT3:
         • Liebert IntelliSlot port
         • USB port (standard B-type)
         • Terminal Block Communication
          !      CAUTION
                 To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
                 should be segregated and run separate from all other power cables.
                                                       21
                                                                                                  Communication
          !       WARNING
                  The output voltage settings cannot be changed while the UPS is on and powering connected
                  loads.
                  NOTE
                  Programming the output voltage of a 230V model of the Liebert GXT3 to 220V automatically
                  derates the UPS to 96% of both the VA and Watt ratings (refer to 9.0 - Specifications for VA
                  and Watt ratings).
                  NOTE
                  • This program is compatible with UPS models beginning with ‘GXT3,’ as in
                    ‘GXT3-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.
                  • A computer running Windows 2000®, XP® or Vista® is required to set up and run the
                    configuration program.
                                                       22
                                                                                              Communication
                                         1           Any Mode
                                         2           Shut Down
                                         3           Battery Mode
                                         4           Shut Down
                                         5
                                                     Battery Mode
                                         6
                                         7
                                                     Low Battery
                                         8
               NOTE
               Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
               depending on the settings in the configuration program.
               A current-limited source (+12VDC, 50mA) will be available from the UPS.
               The connection to the UPS for remote connection will be via terminal block connector.
               Any Mode Shutdown wiring must conform to all national, regional and local wiring
               regulations.
          !    WARNING
               When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1
               and Pin 2, the Liebert GXT3’s output can turn On automatically and without warning if the
               Pin 1 and Pin 2 connection is changed.
                                                     23
                                                                                              Communication
               NOTE
               Remote Power Off will be performed by NO contact.
               The current-limited source (+12VDC, 50mA) will be available from UPS.
               The connection to the Liebert GXT3 for remote connection will be via terminal block connector.
               Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes
               and laws.
               This signal must last for 1.5 seconds or longer.
               A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute
               shutdown timer. This timer cannot be stopped once triggered. If the mains power returns
               during this countdown, the Liebert GXT3 will still shut down and must remain shut down for
               10 seconds. Whether the UPS turns back on when the power is restored depends on the
               auto-restart setting.
5.3.3   On Battery
        On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
        from the battery this dry contact will be closed.
               NOTE
               The rated values for the dry contacts are:
               • Rated Voltage: 5V
               • Working Voltage Range: 4.5-10V
               • Rated Current: 30ma
                                                      24
                                                                                                   Maintenance
6.0       MAINTENANCE
          This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s
          status and checking UPS functions.
Screws, 6
Front Bezel
          4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown
             in Figure 22.
Figure 22 Disconnecting the battery plug and battery receptacle (front view)
          5. Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in
             Figure 23.
Figure 23 Pulling out the battery
           Battery
           Handle
                               Pull Out with Battery Handle
                                                         25
                                                                                                   Maintenance
      6. Unpack the new internal battery pack. Take care not to destroy the packing.
          Compare the new and old internal battery packs to make sure they are the same type and model.
          If they are the same, proceed with Step 7; if they are different, stop and contact your local Emer-
          son representative or Emerson Channel Support.
      7. Line up and slide in the new internal battery pack.
      8. Reconnect the battery plug and battery receptacle
      9. Gently push the battery wire and internal battery pack back into the UPS.
      10. Reattach the front battery door with the six screws.
      11. Reattach the front plastic bezel cover to the UPS.
               NOTE
               The internal battery pack is hot-swappable. However, caution should be exercised because
               during this procedure the load is unprotected from disturbances and power outages.
        !      WARNING
               The battery can present a risk of electrical shock and high short circuit current. The following
               precautions should be observed before replacing the battery pack:
               • Remove rings, watches and other metal objects.
               • Use tools with insulated handles.
               • Do not lay tools or other metal objects on the batteries.
               • If the battery kit is damaged in any way or shows signs of leakage, contact your local Emer-
                 son representative immediately.
               • Do not dispose of batteries in a fire. The batteries may explode.
               • Handle, transport and recycle batteries in accordance with local regulations.
6.3   Precautions
      Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper
      use can result in electrical shock or fire. To ensure safety, observe the following precautions:
       •    Turn Off and unplug the Liebert GXT3 before cleaning it.
       •    Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
       •    Never block or insert any objects into the ventilation holes or other openings of the UPS.
       •    Do not place the Liebert GXT3 power cord where it might be damaged.
                                                      26
                                                                                               Maintenance
      Emerson recommends checking the UPS functions once every six months.
      Back up the load data before conducting the UPS functions check. Procedures are as follows:
      1. Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal.
      2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators
         are on and the UPS is operating normally.
      3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.
         The UPS should initiate a battery self-test. Check to determine whether the battery is operating
         normally. If not, stop and contact your local Emerson representative or Emerson Channel Support
                                                   27
                                                                                                               Troubleshooting
7.0     TROUBLESHOOTING
        This section indicates various UPS symptoms a user may encounter and provides a troubleshooting
        guide in the event the UPS develops a problem. Use the following information to determine whether
        external factors caused the problem and how to remedy the situation.
7.1.1   Indicators
        In addition to the fault indicator being illuminated, one or more of LED segments of battery level indi-
        cator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 24. The
        descriptions are listed in Table 7.
                                                   A       B         C        D        E
        Table 7       Indicator descriptions
             Indicator          Diagnosis/Audible alarm
         A-E                    On bypass from output overload (half-second beep every half second)
         A                      On bypass due to overtemperature condition (1-second beep every 4 seconds)
         B                      On bypass due to DC bus overvoltage (1-second beep every 4 seconds)
         C                      On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)
         D                      PFC failure (1-second beep every 4 seconds).
         E                      On bypass due to inverter failure (1-second beep every 4 seconds)
         A&C                    UPS failed battery test (2-second beep every 60 seconds)
         C&E                    UPS shutdown by command from communication (USB port or Liebert IntelliSlot port) (no
                                audible)
         A&B                    UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery
                                charger failure) and continuous alarm
         Battery Indicator      Internal Battery source not available (continuous horn); check battery connection, power down
         Flashing               and reboot UPS.
         Bypass Indicator
                                Mains power voltage or frequency is out of tolerance; bypass is unavailable
         Flashing
         A - E indicators are shown in Figure 24
                                                               28
                                                                                                              Troubleshooting
7.2       Troubleshooting
          In the event of an issue with the UPS, refer to Table 9 to determine the cause and solution. If the
          fault persists, contact Emerson Channel Support.
Table 9         Troubleshooting table
            Problem                             Cause                                        Solution
 UPS fails to start when the                                          Ensure UPS is Off. Disconnect all loads and ensure
                                    UPS is short-circuited or
 On/Alarm Silence/Manual                                              nothing is lodged in output receptacles. Ensure loads
                                    overloaded
 Battery Test button is pressed                                       are not defective or shorted internally.
                                                                      UPS is operating from battery mode. Ensure UPS is
                                    UPS is not plugged in
                                                                      securely plugged into the wall receptacle.
                                                                      UPS is operating from battery mode. Save data and
                                    UPS input protection fuse has
                                                                      close applications. Replace UPS input fuse, then restart
 Battery indicator is illuminated   blown/opened
                                                                      UPS.
                                                                      UPS is operating from battery mode. Save data and
                                    Mains power is out of tolerance   close applications. Ensure mains supply voltage is
                                                                      within acceptable limits for UPS.
                                                                      Keep UPS plugged in continuously at least 24 hours to
                                    Batteries are not fully charged
                                                                      recharge batteries.
                                                                      Check load level indicator and reduce the load on the
 UPS has reduced battery            UPS is overloaded
                                                                      UPS.
 backup time
                                                                      Replace batteries. Contact your local dealer, Emerson
                                    Batteries may not be able to
                                                                      representative or Emerson Channel Support for
                                    hold a full charge due to age
                                                                      replacement battery kit.
 Fault and Bypass indicators
                                                                      Check load level indicator and remove non-essential
 and all LED segments of            UPS is overloaded or load is
                                                                      loads. Recalculate the load and reduce number of loads
 battery level indicator are        faulty
                                                                      connected to UPS. Check load for faults.
 illuminated
                                                                      Ensure UPS is not overloaded, ventilation holes are not
                                                                      blocked and room ambient temperature is not
 Fault and Bypass indicators        UPS has been shut down due
                                                                      excessive. Wait 30 minutes to allow UPS to cool, then
 and diagnostic A indicator are     to temperature condition; load
                                                                      restart UPS. If UPS cannot restart, contact your local
 illuminated                        is on bypass power
                                                                      dealer, Emerson representative or Emerson Channel
                                                                      Support.
                                                                29
                                                                                                                  Troubleshooting
 Fault indicator and diagnostic    UPS PFC (Power Factor               UPS requires service. Contact your local dealer,
 D indicator are illuminated       Correction Circuit) fault           Emerson representative or Emerson Channel Support.
                                                                 30
                                                                                                Battery Cabinet
Input Breaker
Battery Ports
         !     WARNING
               Do not contact the battery ports and ground without wearing protective gloves and clothing
               and taking other precautions against electrical shock. The battery loop and AC input are not
               insulated, which may cause a dangerous voltage between the battery ports and ground.
               NOTE
               The length of the standard battery cable delivered with the battery cabinet is 0.65m (2.13ft).
                                                      31
                                                                                                                 Specifications
9.0      SPECIFICATIONS
         The specifications of the Liebert GXT3 are listed in Table 10 and Table 11.
Table 10      Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS
                                                                    Product model
           Parameters                        GXT3-700RT230                               GXT3-1000RT230
           Model Rating                        700VA/630W                                 1000VA/900W
 Dimensions, D x W x H, mm (in)
                                                                     497 x 430 x 85
                             Unit
                                                                   (19.6 x 16.9 x 3.3)
                                                                    617 x 570 x 262
                        Shipping
                                                                  (24.3 x 22.4 x 10.3)
 Weight, kg (lb)
                             Unit                                      16.8 (37)
                        Shipping                                        20 (44)
 Input AC
         Voltage Range (typical)                   230VAC nominal; variable based on output load
            90% ~ 100% loading                                     177VAC/280VAC
             70% ~ 90% loading                                     168VAC/280VAC
             30% ~ 70% loading                                     150VAC/280VAC
                0 ~ 30% loading                                    115VAC/280VAC
                      Frequency                              40Hz ~ 70Hz; Auto Sensing
        Input Power Receptacle                                            C14
 Output AC
             Output Receptacles                                         C13 × 6
                          Voltage                     220/230/240VAC (user configurable); ±3%
                      Frequency                                      50Hz or 60Hz
                       Waveform                                        Sine wave
      Mains (AC) Mode Overload              200% for 2 seconds; 150% for 1 minute with transfer to bypass
 Battery
                            Type                        Valve-regulated, nonspillable, lead acid
                Qty × V× Rating                                    4 × 12V × 5.0Ah
               Battery Mfr/Part#                         YUASA/NPH5-12; CSB/ HR 1221W
                    Backup Time                            See Table 14 - Battery run times
                                          3 hours to 90% capacity after full discharge with 100% load till UPS
                 Recharge Time
                                                       auto-shutdown (Internal Batteries Only)
 Environmental Requirements
                Operating Temp      0ºC to +40ºC (+32ºF to +104ºF); Table 13 - Operating temperature parameters
                   Storage Temp                             -15ºC to +50ºC (5ºF to 122ºF)
               Relative Humidity                          0%RH to 95%RH, non-condensing
             Operating Elevation               Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating
              Storage Elevation                              15,240 (50,000 ft.) maximum
                                                      < 46 dBA, at 1 meter (3.2ft) from the rear
                   Audible Noise
                                                  < 43 dBA, at 1 meter (3.2ft) from the front or sides
 Agency
                           Safety                             EC/EN/AS 62040-1-1:2008
                         RFI/EMI                   IEC/EN/AS 62040-2 2nd Ed =CISPR22 Class A
                Surge Immunity                                    IEC 62040-2 2nd Ed
                   Transportation                                 ISTA Procedure 1A
                                                             32
                                                                                                                     Specifications
                                                                 33
                                                                                                 Specifications
                                                                  34
                                                                                                                      Specifications
                                                                    35
     Specifications
36
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2009 Emerson Electric Co.