Foreword
Thanks for purchasing our UPS, it is designed for years
of troubles free service, so only minimum maintenance
is required
This manual contains instructions concerning the
installation and putting into operation of the UPS.
It also contains essential information on the usage of
the equipment, it must be kept in a safe place and
Note: As our products are subject to change through
continuous improvements, the products may vary
slightly with the contents included in this manual.
You can contact our local office to get the
information.
Content
1. Summary...................... ... ... ... ... 1
2. Installation...................... ... ... ... 4
3. Operation....................... ... ...... 14
4. Maintenance...................... ...... 18
5. Troubleshooting....................... 19
1. Summary
This chapter mainly introduce the UPS safety marks and
notes, read this chapter carefully before operating the
equipment.
1.1 Safety instruction
There is dangerous voltage and high temperature inside the
UPS. During the installation, operation and maintenance,
please abide the local safety instructions and relative laws,
otherwise you will have the risk of harm to body safety or
damage the equipments. Safety instructions in this manual act
as a supplementary for the local safety instructions.
Our company will not assume the liability that caused by dis-
obey of safety instructions. Please note the following:
1. The output may be energized even when the UPS is not
connected to the main AC.
2. If it is necessary to replace the battery wire or power cord,
please buy them from our service station, otherwise the
capacity may not be enough and will heat up the wires or even
catch them on fire.
3. Do not dispose the batteries with fire, or the battery will be
exploded. Do not open or damage the batteries, the electrolyte
that spilled out from the battery is poisonous and harmful to
body safety.
4. Never short the battery anode and cathode, otherwise you
will receive an electric shock or the batteries will catch on
fire.
5. Do not open the UPS, there is risk of an electric shock.
6. Pay attention to the high voltage that may exist on the
battery.
                               1
1.2 Symbols indication
The following symbols have been placed through out this manual, where
these symbols appear, use extra care and attention.
         Safety Symbol           Indication
                            Attention
                            Static discharge sensitive
                            Dangerous Voltage
There are three levers of safety grade: Dangerous, Warning
and Attention. The remark is on the right side of the safety
symbol, the detailed comments is behind, shown as following:
     Dangerous
Indicate risk of injury or death or seriously damage the
machine .
     Warning
Indicate risk of injury or damage the equipments.
      Attention
Indicates important installation, operation or maintenance
instructions. Always follow these instructions closely.
1.3 System illumination
This series of UPS is an advanced on line sine wave output
power system, with maintenance bypass switch provided. It is
a reliable and excellent AC power supply for your precious
equipments. It is widely applicable, from computers,
communication systems to         industry automatic control
systems. Because of its on line design, it keeps on adjusting
and filtering the AC input, when the main AC fail, UPS would
goes over to battery mode in 0s to support the load
continuously, when there is an overload or inverter failure
situation, UPS would go over to bypass mode, and auto start
when overload is removed.
                                 2
1.4 Model
● 6KVAH/10KVAH is long backup model
● 6KVAS/ 10KVAS is standard model with internal battery
●10KVAH3C is 3 phase in, single phase out long backup model
●15KVAH3C is 3 phase in, single phase out long backup model
● 20KVAH3C is 3 phase in, single phase out long backup model
                               3
2. Installation
2.1 Unpack
1.Unpack unit, kindly check that the following items are includ-
ed: UPS and user manual one each.
2. If your model is 6KVA H/ 1 0 K VAH/10 K VAH 3C, there should
also be a battery cable that should be connected between the UPS
and the battery.
3. Check for any transit damage on the unit. Save the packing
and in case of transit damage contact the insurance company
and the common carriers. Proceed further once it is confirmed
that the UPS is not damaged.
2.2 Safety notice
1. UPS should be placed in a sufficiently ventilated area, keep
it far away from water, flammable gas and corrosive.
2. Do not lay the UPS on side, make sure the ventilation hole
on the front bottom and the cooling fan on the rear panel are not
blocked.
3. The ambient temperature should be between 0~40°C.
4. There is a phenomena of condensing when the UPS is installed
under low temperature. Make sure the UPS is completely dry
before installing, otherwise you would receive an electrical
shock.
      NOTE:
« Do not connect inductance load such as fluorescent lamp,
copy cat and generator to the UPS outlet.
« Plug-in the UPS input cord to a 3-pin wall socket with
current limit protection and a reliable low impedance earth
connection.
« The output may be energized even when the UPS is not
connected to the main AC. To make the UPS output no energy,
Please first switch off the switch, then cancel the main AC.
                               4
« To connect the UPS with laser printer, please select the
UPS rating according to the UPS start power.
2.3 Front panel display and indicators and buttons instruction
                                                           LED Green light
                                                           LED Yellow light
                                                           LED Red light
                Front panel and LCD UPS display
LCD PART
    l The first line is the digital s ection, and is consisted of two small
      digital sections and the related unit sections on the right side.
      It is used to display the numerical value of the certain item on
      the second line.
    l The second line is the item section which include input, battery,
      output, load and temperature, etc.
    l The third line is the graphic section which has the load capactiy
      ( left) and battery capacity (right) displayed in graphics. The
      fault icon will be displayed when there is a fault.
    l The fourth line is the status section, and is the area of machine
      status in English. The utility mode is displayed as“on line”.
      The battery mode is displayed as “on batt”. The bypass mode is
      displayed as “on bps”.
LED PART
    l Red LED is on: UPS is fault and has no output. For example:
      Overload beyond the allowed time, inverter fault, BUS fault,
      over temperature fault etc.
                                   5
  l Yellow LED is on: UPS is alarming. For example: With utility in
    but not turn on the UPS, Bypass mode, batteries are over
    charged, charger fault, fan stop working, batteries are
    discharged to battery low voltage when UPS works on battery
    mode.
   l Green LED is on: UPS is normally powered by utility or battery
     inverter mode.
                      Description of the Buttons
BUTTONS PART
   l ON/OFF button
     Press and hold for some time to turn on/off the UPS.
   l FUNCTION button
     Press and hold for some time on utility mode: UPS runs a self-
     test function.
     Press and hold for some time on battery mode: Mute function.
   l INQUIRING button
       Press for short time: Indicate the items of the second line item
     section orderly. Press and hold for some time: Circularly and
     orderly display the items from “INPUT, BATTERY, OUTPUT,
     LOAD, TEMPERATURE” every 2 seconds. When you press and
     hold the button for some time again, it will turn to static output
     status.
2.4 Installation
The installation must only be performed by qualified
personnel and abide to the electrical law. To ensure the safety,
please cut off the AC input before performing the installation.
If your model is long backup type, you should also cut off the
battery breaker.
1. Open the cover of the terminal block on UPS rear panel.
2. Refer to the following to select the UPS input/output wire:
                                 6
   6KVAH(S)                    UL1015 10AWG (6mm2 )
   10KVAH(S) / 10KVAH3C UL1015 8AWG (10mm2 )
   15KVAH3C/20KVAH3C           UL1015 6AWG (25mm2 )
      Note:
*The rating of the wall socket should be bigger than the
UPS rating, otherwise it will get burned.
3. Refer to the below figure, connect the input/output cords to
the terminal block.
     Note:
*Make sure the terminals are properly tightened.
4. Refer to the following table to select the earthing wires.
   6KVAH(S)                   UL1015 10AWG (6mm2)
   10KVAH(S) / 10KVAH3C UL1015 8AWG (10mm2)
   15KVAH3C/20KVAH3C          UL1015 6AWG (25mm2)
5. After the installation is completed, please double check if the
connection is right and properly tightened.
6. If you want to install the leak current protection switch,
please connect it to the UPS output end.
7. To connect the loads with UPS, please turn off the loads first,
then connect the wires, turn on the loads one by one at last.
8. The output may be energized even when the input is not
connected to the main AC. Just by shut down the UPS can not
ensure that the UPS internal is safe. If you want the UPS have
no output, please turn off the UPS and then cut off the AC input.
9. It is advisable to charge the batteries for 8 hours before using.
After all the connections are done, as long as the UPS input
breaker is placed to ON, the battery would get charged.
10. To connect inductance load like the generator, monitor and
laser printer to UPS outlet, the UPS rating should be of two to
four times of the loads power, as the starting power of these
loads would be much bigger then usual.
                                7
                             N       L       JP1 JP2   L     N
   Input earth                                                       Output earth
   Input neutral                                                     Output neutral
   Input line                                                        Output line
        JP1JP1                                                        JP2
                                                                     JP2
                           HP9106H    £ S̈£ ©
                                            /HP9110H£ S̈£ ©
                                6KVAH(S)/10KVAH(S)
                       Input, output terminal block connection
Note: If the UPS is used in single machine, then JP1 and JP2
should be shorted with wire, for 6KVAH(S) the wire should be
at least 12AWG, for 10KVAH(S)/10KVAH3C, the wire should
be at least 10AWG.
If the UPS is used in parallel, please remove the wirethat be
tween the JP1 and JP2.
                         N       A       B    C    JP1 JP2   L   N
    Input earth                                                      Output earth
    Input neutral                                                    Output neutral
    Input phase A                                                    Output line
    Input Phase B                                                    JP2
                                                                     JP2
    Input phase C                                                    JP1
                                                                     JP1
              HP9310H input¡ ¢
              10KVAH3C       output terminal block connection
Note: If the UPS is used in single machine, then Jp1 and Jp2
should be shorted with wire, the wire should be at least 10A
WG.
If the UPS is used in parallel, please remove the wire that
                                               8
                         N   A   B   C JP1 JP2   L   N                           +   -
  Input earth                                                Output earth
  Input neutral                                              Output neutral   Battery battery
  Input phase A                                              Output line      anode cathode
  Input Phase B                                              JP2
                                                            JP2
  Input phase C                                             JP1
                                                             JP1
                          HP9315H/HP9320H
                              15KVAH3C/20KVAH3C
                  Input, output terminal block connection diagram
Note: If the UPS is used in single machine, then JP1 and JP2
should be shorted with sheet copper that provided with the UPS,
  If the UPS is used in parallel, please remove the sheet copper
that connected between the JP1 and JP2.
2.5 External battery connection
1. The DC voltage of this UPS is 240VDC, when you are
connecting the external batteries, please connect 20pcs of
12VDC batteries in series(in one string), and you can connect
any strings in parallel. The batteries in every string should be
20pcs, should not be more connected or less connected.
2. For 6KVAH(S)/10KVAH(S)/10KVAH3C, connect one end of
the battery cable to the UPS, the other end is open two
c a b l e s u s e d t o c o n n e c t t h e b a t t e r i e s . T h e 1 5 K VA H 3 C
/20KVAH3C use the terminal block. The procedure is very
important, pleasefollow the steps, otherwise you will receive
an electrical shock.
l There should be a DC breaker between the battery and UPS,
                  Model                DC voltage          Battery current
                  6KVAS/H                240VDC               24Amax
                  10KVAS/H               240VDC               40Amax
                  10KVAH3C               240VDC                 40Amax
                  15KVAH3C               240VDC                 60Amax
                  20KVAH3C               240VDC                 80Amax
                                                 6
²Place the battery breaker to OFF, connect the 20pcs of batter-
ies in series.
²First connect the battery cable to battery, (do not connect the
cable to UPS first, there is a risk of electric shock), connect red
cable to battery anode, connect the black cable to battery
cathode.
²The battery cable for 15KVAH3C/20KVAH3C should be
Ul1015 6AWG(25mm), the yellow wire should connect toUPS
                       2
earth and battery cabinet.
²Connect the battery cable to UPS battery socket, then the
connection is completed. Now do not connect any load to the
UPS. First connect the input power cord, then place the input
switch to ON position, and the battery breaker to ON, the UPS
would start charging the batteries.
NOTE: Do not invert the battery connection, otherwise the
UPS would be damaged.
2.6 Parallel
1.Parallel Redundant
N+X is now the most stable structure of power supply, N
standfor the basic UPS quantity demanded for the loads, X
stand for the redundant UPS quantity. The reliability increase
as the X goes up. Only with the parallel wire, you will have
max. 3pcs of UPS connected in parallel.
2. Installation
²User provide the standard 25pin parallel cable (25pin,
shielded), the length should be no more than 3m.
²The requirments, please refer to the single unit installation.
²Connect the output of each UPS to a socket board, then
connect loads to the switch board.
²The jumper or copper sheet between the JP1 and JP2 should
be removed.
²Every single UPS should connect with its own battery pack.
²Refer to the figure to connect the units. Pay attention to the
                               10
                     Model           The rating of the breaker
      6KVAH(S)                           ≥40A/250VAC
      10KVAH(S)/ 10KVAH3C                ≥60A/250VAC
      15KVAH3C/ 20KVAH3C                ≥100A/250VAC
The length of the wires should be:
If the distance between the loads and UPS is less than 20m the
difference of every wire length should be less than 20%, If the
distance exceeds 20m the difference of every wire length
2.7 Operation and Maintenance
                       AC input
             UPS11
             UPS             UPS12
                             UPS           UPS13
                                           UPS
             Output
             socket
             board
                        Load Load Load Load
                        Parallel diagram
1. Please refer to the single units operation to operate the units.
2.Turn on: After all the UPS are turned on one by one, the units
would go to inverter mode together.
Turn off: After all the UPS are turned off one by one, the unit
would go to bypass mode together.
3.The maintenance, please refer to the maintenance procedure.
                               11
                          N            L           JP1 JP2       L   N                             N    L    JP1 JP2            L          N
                                                  UPS1 input                                                UPS2 input
                                                  distribution                                              distribution
                                                  switch                                                    switch
-12
 10-
                                                                                                    UPS2 output
                                                                                                    distribution switch
                                                        UPS1 output
                                                        distribution
                                                        switch
                                     Input Line
                                                                                                                          Input Line
                                                                             6KVAH(S)/10KVAH(S)
                                                                         HP9106H  £ S̈£ ©
                                                                                        / HP9110H£ S̈£ ©
                                                                                                                                                       Input earth
       Input earth
                     Input neutral
                                                                                                                                       Input neutral
                                                                         Parallel connection diagram
                              N             A               B               C              JP1 JP2   L    N              N   A    B   C    JP1 JP2         L             N
                                                                                           UPS1 input                                      UPS2 input
                                                                                           distribution                                    distribution
                                                                                           switch                                          switch
     - 11-
13
                                                                                                                                 UPS2 output
                                                                                                                                 distribution switch
                                                                                               UPS1 output
                                                                                               distribution
                                                                                               switch
                                                                                                     HP9310H/ HP9315H/ HP9320H
                                                                                                 10KVAH3C/15KVAH3C/20KVAH3C
                                                                                                     Parallel connection diagram
             Input earth
                                           Input Phase A
                                                           Input Phase B
                                                                           Input Phase C
                           Input neutral
                                                                                                                                                       Output Line
                                                                                                                                                                                      Output earth
                                                                                                                                                                     Output neutral
3. Operation and Running
The operation is very simple, before operate the UPS , please
read the manual first.
3.1 Operation
3.1.1 Turn on the UPS on AC mode
1. Make sure the utility connection is correct, switch on the input
switch, then the fan works, and the UPS powers the load by bypass and
it is working on bypass mode, Yellow LED will light ON and the LCD
status will show“on bps”,the output indication is utility parameter.
2 . Continuously press the ON/OFF button for above 1s to turn on the
UPS, then the inverter will start up.
3 . When UPS starts up, It will firstly do self-checking, when the green
LED“ ON” and the LCD status section displays“ on line” , it
shows UPS is working on utility mode. If the utility is abnormal, UPS
will work on battery mode, and the LCD item section characters
“INPUT”will flash .
3.1.2 Turn on the UPS on DC mode (without utility)
1. Without utility input, long press the ON/OFF button for above 1s to
turn on the UPS.
2. When UPS starts up, it will firstly do self-checking, when LCD
status section displays“ on batt” , it shows UPS is working on
battery mode .
3.1.3 Turn off the UPS on AC mode
1. Long press the ON/OFF button for above 1s to shut down the UPS
and internal inverter.
2. When UPS shuts down, It will firstly do self-checking, when the
yellow LED is “ ON” and the LCD status section displays “ on
bps” , it shows UPS is working on bypass mode and UPS has bypass
output. If want to make the UPS has no output, you have to turn off the
input switch, In this condition, the UPS will keep self-checking till the
display panel has no display and indication and the UPS has no output .
3.1.4 Turn off the UPS on DC mode (without utility)
1. Long press the ON/OFF button for above 1s to shut down the UPS.
2. When turning off the UPS, the UPS will keep self-checking till the
                                  14
display panel has no display and indication and the UPS has no output.
3.2 Running mode
3.2.1 Bypass mode
1. The display panel indication on bypass running mode is as below
figure, the yellow LED lights on, and the load/battery capacity will be
indicated according to the real capacity value. UPS will beep once
every 2 minutes.
2. If the LCD status section displays “ INPUT”characters , it shows
the AC input voltage or frequency is beyond the normal range.
3. When UPS works on bypass mode, it doesn't have backup function,
and the load is powered directly by utility system after filtering.
                       UPS bypass running mode
3.2.2 AC mode
1 . The display panel indication on AC running mode is as below
figure, and the LCD status section indicates “on line”, and the
load/battery capacity will be indicated according to the real capacity
value.
2 . If LCD status section indicates“on batt”, it shows the AC input
voltage or frequency is beyond the normal range and UPS is working
on battery mode.
3 . If the load capacity is >100%, the buzzer will beeps once every half
second, and LCD graphic section load capacity blocks will flash which
means UPS is overload, in this condition, you should remove some
unnecessary load till the UPS load is below 95%, and then the overload
warning will automatically disappear.
4 . Press the INQUIRING button to check the input parameters, you can
also check the R, S, T three phase input information for three phase
input UPS.
                                  15
                         UPS AC running mode
3.2.3 Battery mode
1. The display panel indication on battery running mode is as below
figure, and the LCD status section indicates “on batt”, and the
load/battery capacity will be indicated according to the real capacity
value.
2. Muting function: When UPS works on battery mode, the buzzer will
beep once every 4s,then long press the FUNCTION button for above
1s, the buzzer will stop beeping, if long press the FUNCTION button
for above 1s again, the buzzer will come back to beep warning.
3. When the battery capacity is decreased, the number of battery
capacity indication blocks will be minus, when the battery voltage
drops to battery low voltage, the buzzer will beep once every second,
and the yellow LED will light on which reminds the users the battery
capacity is not enough and need to save the useful data and shut down
the load at once.
                    UPS battery running mode
                                 16
       Pay attention:
« If connect the UPS to generator, please operate as steps below:
1. Start up the generator, when the generator runs normally, connect
the generator output to UPS input, then turn on the UPS, after the UPS
runs, please connect the load to the UPS step by step.
2. It's recommended to choose the generator whose capacity is twice of
UPS capacity.
3.2.4 Abnormal mode
Display panel indication:
                     UPS abnormal running mode
Red LED lights on, the triangle fault mark on the LCD is indicated,
and the right of digital section indicates fault code, and there is some
simple fault information in status section, please refer to table (5-2) for
the solution.
                                    17
4. Maintenance and Service
Only minimum maintenance is required for this series of UPS.
The battery is sealed lead acid maintenance free, only by
frequent charging would obtain the expected battery life.
UPS would charge batteries once it is connected to main AC,
also, protection would be provided for battery against over-
charging and deep discharging.
4.1 Battery maintenance
1. If UPS is not used for a long time, battery should be charged
and discharged once every four to six months.
2. In high temperature area, battery should be charged and
discharged once every two months.
3. Under normal condition, UPS should be charged and
discharged once every four to six months, the recharge time
should be more than 2 hours.
4. Normally, the battery working life is three to five years.
If you find that the battery do not act well, like short backup
time, too much differences on battery voltage and so on,
the battery should be replaced as soon as possible, which
shouldbe performed by qualified personnel.
5. To replace batteries, It is not recommended to change
battery separately, batteries should be changed all together
at one time.
     Note:
*Before replacing batteries, make sure that the UPS is
turned off, metallic things like rings and watches are
removed.
*The screw driver you used should be with insulation
handle,Do not lay tools or other metallic goods onto the
battery.
* Never revert or short the battery connection.
                              18
5. Trouble shooting
When there is some failure in the UPS, please pay attention to
the UPS indication and alarm, it will help you to find and solve
the problem.
1. Fault indicator ON, indicate that the UPS has detected some
failure inside UPS.
2. Buzzer beeps, indicates that the UPS should be payed
attention to.
3. To contact our service department, the following messages
should be provided for analysis.
    ◆ UPS model and Serial number
    ◆The date when the problem happened
    u Detailed description of the problem, including panel
    indications.
                              19
5.1 Information inquiry
5.1.1 LCD/LED indication and warning(5-1.1)
 No.   Workings tatus       LCD display                           LED indication         Warning and beeps
  1    AC mode              “on line”                             Green “ON”             None
  2    Battery mode         “on batt”                             Green “ON”             Once every 4s
       Battery low on       “on batt”, battery section
  3                                                               Yellow “ON”            Once every 1s
       Battery mode         flashes
  4    Bypass mode          “on bps”                              Yellow “ON”            Once every 2min
       Overload on
                            Alternate indication between
       AC mode, not
  5                         “on line” and “load hi”, load         Yellow “ON”            Twice per second
       turn to bypass
                            section flashes.
       mode
       Overload on
       AC mode and
  6                         “on bps”, load section flashes.       Yellow “ON”            Twice per second
       turn to bypass
       mode
                            Alternate indication between
       Overload on
  7                         “on batt” and “load hi”, load         Yellow “ON”            Twice per second
       battery mode
                            section flashes.
       Overload on
       battery mode
  8                                   load section flashes. Red “ON”
                            “load hi”£¬                                                  Long beeps
       and shut down
       the output
5.1.2 Fault information inquiry table(5-1.2)
                                                                    LCD display fault code
             6-20KVA                      Bypass          AC           Battery        Battery self-checking
                                           mode          mode           mode                 mode
       BUS voltage abnormal               30,31,32       05,25,15       06,26,16             40,41,10
         Inverter abnormal                                 04              08                  42
        Output short circuit                               09              09                  09
         Over-temperature                    33            06              02                  43
             Overload                        35            03              09                  45
           Fan abnormal                      36            09              29                  46
           Charger fault                     07            07              07                  07
  Internal communication fault               88            88              88                  88
  Parallel communication fault               82            82              82                  82
 Parallel number exceeds max. number         85            85              85                  85
           Parallel fault                                 84,81          84,81                84,81
                                                         20
5.2 Abnormal status handling (Table 5.2)
     Abnormal Status             Possible Reason                    Dealing way
 No indication and no    Switch on back pane is       Place the switch to ON, check the
 alarm                   not turned on, no input      input power.
                         Too Short holding            Press and hold the ON button for
 Press and hold the ON time                           above 1s
 button, but UPS can not Battery low,or without       Check the battery voltage, reconnect the
 start                   battery connected            batteries
                             UPS failure              Contact the franchiser for repairing
 Red LED lights “ON” and
                         UPS fault                    Please contact with your supplier.
 continuous warning
                             AC voltage or            UPS is working on battery mode,
 LCD items section
                             frequency exceeds        make sure it’s in UPS allowed range of
 “INPUT” characters flash
                             normal input range       input voltage or frequency.
 Red LED lights ON and
                             UPS overload or load Remove the unnecessary load and check
 load capacity blocks flash,
                             system fault           if the load system is fault.
 buzzer is long beeping.
                                                    Check the UPS battery part, well
 LCD graphic section         Battery voltage is too
                                                    connect the batteries, if the batteries are
 battery capacity blocks     low, or battery is not
                                                    damaged, please replace them and make
 flash.                      (well) connected.
                                                    sure the battery switch is to “ON” state.
                             Battery is not fully Continuously charge the batteries above
                             charged                10hrs.
 Battery discharge time is
                             Batteries damaged      Replace batteries
 short
                             Charger fault            Please contact with the supplier
                                             21
5.3 Performance
                                 Input                Output         Fre-   Dimension Weight
  Model           Rating                                             quency W*L*H(mm) (KG)
                               Voltage     Current Voltage Current
 6KVAS        6KVA/4.2KW (176-276)VAC 30Amax 220VAC 27A              50Hz 270*570*720   91
 6KVAH        6KVA/4.2KW (176-276)VAC 30Amax 220VAC 27A              50Hz 270*570*720   36
 10KVAS       10KVA/7KW (176-276)VAC 51Amax 220VAC 45A               50Hz 270*570*720   94
 10KVAH       10KVA/7KW (176-276)VAC 51Amax 220VAC 45A               50Hz 270*570*720   39
 10KVAH3C     10KVA/7KW (304-480)VAC 51Amax 220VAC 45A               50Hz 270*570*720   40
 15KVAH3C     15KVA/10.5KW (304-480)VAC 73Amax 220VAC 68A            50Hz 270*570*720   60
 20KVAH3C     20KVA/14KW (304-480)VAC 100Amax 220VAC 91A             50Hz 270*570*720   60
u Electrical performance
                                            Input
         Model                           Voltage       Frequency  Power factor
                                         Single phase
   6KVAH(S)/10KVAH(S)                       220Vac     46Hz-54Hz >0.95(full load)
   10KVAH3C/15KVAH3C                     Three phase
   /20KVAH3C                             380Vac/220Vac 46Hz-54Hz >0.95(full load)
                                     Battery Input
                                                       6KVAH/10KVAH/
  Model                       6KVAS       10KVAS 10KVAH3C/15KVAH3C/20KVAH3C
  Battery Voltage                                240VDC
  Backup Time
  Full load /Half load(min)     7 / 20      5 / 13
                                          Output
 Output Power                 Frequency                               Overload      Crest
 Stability factor             Stability              THD              capacity      factor
                    Under normal condition, (in                      105%~130%
                    AC mode, and frequency is                        load, 10min go
                    in t he limits) , Output      Under full         to bypass,     3:1
                    f requency would synchro- linear load,           >130% load     max
            0.7                                   THD<3%
                         nize with input, other wise,                1min shut
                    frequency stability wo uld                       down output
                    be 0.5%
                                            22
◆Environment
  Temperature                           0℃~40℃
  Humidity                        0~95% Non-condensing
  Altitude                        Less than 1000m.
  Storage temperature                   0 ℃~ 40 ℃
● In case you are using the UPS on above 1000m altitude,the
UPS rating would be decreased.
 Altitude       1000 1500   2000    2500   3000   3500 4000 4500 5000
 Load percentage
 that permitted  100% 93%   90%     80%    78%    75%   72% 68%   65%
5.4 Net Communication
This series of UPS provides a card slot for the intelligent LAN
card(Optional), which helps to realize the remote monitoring,
contact the franchiser for the details.
5.4.1 RS232 communication interface
RS232 is a serial port interface provided to monitor the main
AC and UPS, UPS control is also available via this port.
1. Setting of the RS232 port
Baud rate: 2400bps
Stop bit: 1bit
Data bit: 8bit
Parity bit: None                     Gnd        Rxd Txd
  Pin       Function    I/O
   2          TXD      Output
   3          RXD      Input
   5          GND      Gound
                                   23