THE JERSEY CITY MUNICIPAL UTILITIES AUTHORITY
REQUIREMENTS FOR FIRE AND DOMESTIC WATER LINE AND METER
                           INSTALLATIONS
1) All fire service applications and all domestic service applications two (2) inches and
   larger must be submitted to the JCMUA’s Bureau of Water Engineering for
   approval. Five (5) sets of plans shall be submitted for approval. All plans shall be
   signed and sealed by a Professional Engineer or Registered Architect licensed to
   practice in New Jersey.
2) Submitted plans shall be standard engineering drawings, size 24 inches x 36
   inches. Included shall be a site plan showing adjacent streets with water main,
   service, and details indicated. Also included shall be a key map showing general
   location within the City.
3) Indicated on the submitted plans shall be the size of tap, location of tapping and
   curb gate valves, detailed meter set-up, and size of facility’s meter. Also indicated
   on the plans shall be the type of occupancy of the facility receiving the water
   service. (i.e. hospital, warehouse, apartment building, etc.)
4) All existing water service lines to be abandoned shall be cut and capped at the
   main, in accordance with JCMUA standards, and inspected within 24 hours after
   installation of new tap. The maximum of one (1) tap shall be made for both
   domestic and fire service per facility. The tap shall be the maximum of one (1) size
   smaller than the City’s water main. No tapping shall be done by anyone except by
   United Water Jersey City (UWJC) unless specifically approved by JCMUA.
5) Only one domestic/ fire service is allowed for each facility. Applicant may install
   check meters on individual branch connections downstream of domestic meter
   setup where there is more than one owner/ tenant for a facility. However, only one
   water bill will be issued for the facility.
6) A solid ductile iron tapping sleeve such as Mueller H-615 tapping sleeve or
   approved equal shall be utilized for all taps 2-inches and larger. The tapping sleeve
   shall pass pressure testing based on AWWA standards before tap is made.
7) For all services included herein, two (2) gate valves are required that are to be
   installed by the applicant; a tapping valve, located at the tap and curb valve, located
   in the sidewalk before the meter. Tapping gates shall be furnished opened right.
   All tapping and curb valves shall be double disc gate valves and meet AWWA
   standards. The wet tap up to 12 inches shall be performed by UWJC.
8) For taps off mains sixteen (16) inches and larger, the applicant shall furnish and
   install an additional gate valve adjacent to the tapping valve. No taps shall be
    permitted on mains larger than twenty (20) inches unless there is no alternative
    water source, and special written approval is issued by the JCMUA.
9) Valve box parts for all valves shall be provided by the applicant. All tapping gate
   valves larger than 2-inches and all curb valves / stops regardless of size require a
   valve box with the word “Water” cast in the cover. Buried corporation valves/ stops
   shall be used at the tap for Class K copper services 2-inches and smaller.
10) All service pipes, sizes 2-inches through 12-inches, shall be Pressure Class 350
    psi, cement-lined ductile iron pipe with mechanical joints.
11) The applicant shall install the meter inside the building. If the building line is in
    excess of 75 ft. from the main, the applicant shall place the meter in a pit near the
    sidewalk or street in close proximity to the tap.
12) For a regular fire suppression system (combined service line larger than 2”), a
    combined reduced pressure detector assembly (Ames 5000 SS, Ames 5000 RPDA
    or Watts 909 RPDA*) shall be installed on the main fire service line and a reduced
    pressure backflow preventer on the bypass (Ames 4000 SS or Watts 909*) (refer to
    Figure 1). On the limited fire suppression system (combined service line 1.5” or 2”),
    a fire line detector check with a single check valve (Ames 1000 DCV*) shall be
    installed on the main fire line and a reduced pressure backflow preventer (Ames
    4000 SS or Watts 909*) shall be installed downstream of the bypass (refer to Figure
    2). All regular fire suppression systems must have OS&Y valves, however, limited
    fire suppression systems may use ball valves (Victaulic Series 728 Firelock*)
    instead of OS&Y valves. The fire unit shall be furnished with a 5/8 inch x 3/4 inch
    metered bypass. Bypass meters shall be Jersey City standard single displacement
    Sensus meters with touchpad and radio read capabilities. The same radio MXU
    unit shall be used for a combined domestic and fire service.
13) For domestic service, an approved reduced pressure backflow preventer (Ames
    4000 SS or Watts 909*) is required when the JCMUA determines that there is a
    cross-connection hazard and the facility presents a threat to the City’s distribution
    system water quality in accordance with the Plumbing Subcode of the New Jersey
    State Uniform Construction Code, NJAC 5:23-3.15 and the New Jersey Safe
    Drinking Water Act NJAC 7:10-10 Physical Connections and Cross Connections
    Control by Containment. Some services which require such devices include: a
    hospital, school, chemical plant, factory, and a facility with sewage ejectors.
14) If a reduced pressure backflow preventer is not required on the domestic service, a
    check valve should be installed downstream of the test tee.
15) All meters sizes 2 inches through 6 inches shall be single compound meters and all
    meters 8 inches and larger shall be duplex compound manifold meters.
16) All meters shall be adequately restrained with metal brackets fastened to the floor or
    wall or other approved means such as uniflanges where internal pipe pressure and
    flow warrant such restraints. Meters, detector checks, and valves may be seated on
    concrete block and tapered shims to provide adequate support. Meters shall be
    installed approximately 36” above floor grade.
17) All meter installations in meter pit or vault shall be pre-approved by JCMUA and
    have proper access openings for meter reading and replacement.
18) Each compound meter shall have strainer installed on the inlet side immediately
    before the meter. All strainers must be purchased from JCMUA or its authorized
    agent.
19) All meters 2” and larger shall be furnished with Sensus ECR/WP Remote Touch
    Pad Modules and Radio MXU units for both types of reading capabilities.
20) Remote Touch Pad Module wire shall be connected to the meter register utilizing a
    gel cap for watertight sealing of all terminal connections. Touch pads may be wall
    mounted or lid mounted where a meter pit is utilized. Touch pads are to be installed
    on exterior building wall facing the street and located as close as possible to street.
    The radio MXU unit must be installed with mounting bracket and likewise is to be
    installed in proximity to street.
21) All installations of equipment and components shall be performed in accordance
    with manufacturer’s recommendations.
22) All meters including touch pad modules, and radio MXU units shall be purchased
    through the permit clerk at JCMUA office. Approved plans must be submitted to the
    permit clerk for issuance of required permits.
23) After obtaining the required permits (street opening, tap, and meter) the applicant
    shall call UWJC at (201) 239-1108 to schedule the tap. The excavation shall be
    completed twenty-four (24) hours prior to the scheduled tap, and verified by JCMUA
    or its authorized agent before the tap will be installed. Excavation shall be
    constructed in accordance with OSHA requirements for sheeting and safety.
24) Upon completion of the installation, the applicant shall submit three (3) sets of “as
    built” plans, to the JCMUA’s Bureau of Water Engineering. The JCMUA will
    authorize supply water upon acceptance of the “as built” drawings.
* Specified model or approved equal.
06/28/06
                          FIGURE 1. J.C.M.U.A. REQUIREMENTS FOR FIRE AND DOMESTIC WATER LINE AND METER INSTALLATIONS
                                                                                                            RPZ DOUBLE
                                                                                                            DECTECTOR
                                                                                                            CHECK (1)
                            TAPPING                                                          OS &Y GATE                   DRESSER
                                                                                                                          COUPLING            OS &Y GATE
                            VALVE                                                            VALVE
                                                                                                                                              VALVE
                                                                                                                                                              FIRE
                                                                                                                                                              SERVICE
                                                          CURB
                             GATE VALVE                   GATE
                             (ONLY IF WATER
                                                          VALVE                                                                      CHECK
 JERSEY CITY WATER MAIN
                             MAIN IS 16” OR                                                                                          VALVE
                             LARGER)                                                                OS &Y
                                                                                  DOMESTIC          GATE
                                                                                  SERVICE           VALVE
                                                                                                                    5/8” X ¾” WATER METER
                                                                                                                    (PURCHASED FROM JC)
                                                                  BUILDING LINE
                                              SIDE WALK
                                                                                                                                                   2” BRASS GATE VALVE
                                                                                   OS &Y GATE VALVE (3)                                            WITH PLUG
                                                                                                            RPZ BACKFLOW      DRESSER
                                                                                   GATE                                                                             GATE
                                                                                                            PREVENTOR (2)     COUPLING
                                                                                   VALVE                                                                            VALVE
                                                                                             SENSUS
                                                                                             STRAINER                    RPZ BACKFLOW
                                                                                                                                                                CHECK
                                                                                                                         PREVENTOR (2)           TEST TEE
                                                                                                                         (ONLY IF REQUIRED)                     VALVE
                                                                                              SENSUS WATER METER
                                                                                              (PURCHASED FROM JC)
(1) Ames 5000 SS, Ames 5000 RPDA or Watts 909 RPDA, (2) Ames 4000 SS or Watts 909, (3) Gate valve sealed by JCMUA or agent (UWJC)
Must use model # specified or approved equal                                                                                  Revised 06/28/06
                            FIGURE 2. J.C.M.U.A. REQUIREMENTS FOR FIRE AND DOMESTIC WATER LINE AND METER INSTALLATIONS
                                           (LIMITED FIRE SUPPRESSION SYSTEM - CONNECTION SIZE OF 1 ½” OR 2”)
                                                                                                        FIRE LINE DETECTOR
                                                                                                        CHECK (WITH SINGLE
                                                                                                        CHECK) (1)
                                                                                                OS &Y GATE                                 OS &Y GATE
                              TAPPING                                                                                      DRESSER                         RPZ BACKFLOW
                                                                                                OR BALL                    COUPLING        OR BALL         PREVENTOR (2)
                              VALVE                                                             VALVE (3)                                  VALVE (3)
                                                             CURB                                                                                              FIRE
                                GATE VALVE                   GATE                                                                                              SERVICE
                                (ONLY IF WATER
                                                             VALVE                                                                   CHECK
   JERSEY CITY WATER MAIN
                                MAIN IS 16” OR                                                                                       VALVE
                                LARGER)                                                              OS &Y
                                                                                     DOMESTIC        GATE OR
                                                                                     SERVICE         BALL
                                                                                                     VALVE (3)       5/8” X ¾” WATER METER
                                                                                                                     (PURCHASED FROM JC)
                                                                     BUILDING LINE
                                                 SIDE WALK
                                                                                     OS &Y GATE VALVE (4)                                       2” BRASS GATE VALVE
                                                                                                                                                WITH PLUG
                                                                                                   SENSUS WATER METER           DRESSER
                                                                                      GATE         (PURCHASED FROM JC)
                                                                                                                                COUPLING                          GATE
                                                                                      VALVE
                                                                                                                                                                  VALVE
                                                                                                 SENSUS                    RPZ BACKFLOW
                                                                                                                                                              CHECK
                                                                                                 STRAINER                  PREVENTOR (2)       TEST TEE
                                                                                                                           (AS NEEDED)
                                                                                                                                                              VALVE
(1) Ames 1000 DCV, (2) Ames 4000 SS or Watts 909, (3) Victaulic Series 728 Firelock Ball Valve, (4) Gate valve sealed by JCMUA or agent (UWJC)
Must use model # specified or approved equal                                                                                         Revised 06/28/06
                              FIGURE 3. J.C.M.U.A. REQUIREMENTS FOR DOMESTIC WATER LINE AND METER INSTALLATIONS
                                                                                                                                     2” BRASS GATE VALVE
                                                                                                                                     WITH PLUG
                                                                                         SENSUS WATER METER
                            CORPORATATION                                       GATE     (PURCHASED FROM JC)
                                STOP                                                                                                                     GATE
                                                                                VALVE                                                                    VALVE
   JERSEY CITY WATER MAIN
                                                                                        SENSUS                 RPZ BACKFLOW
                                                        CURB                                                                                      CHECK
                                                                                        STRAINER               PREVENTOR            TEST TEE
                                                        GATE                                                   (ONLY IF REQUIRED)                 VALVE
                                                                                                                                                  (ONLY IF NO
                                                        VALVE                                                                                     RPZ)
                                                                BUILDING LINE
                                            SIDE WALK
** Gate valve sealed by JCMUA or agent (UWJC)                                                                                                  Revised 07/16/04