INSULATION TEST
HOW TO APPLY THE CORRECTION TEMPERATURE FACTOR
FORMULA :
DIMANA :
Rmeasured is the measured insulation resistance. Typically in mega ohm or giga ohm
Rstandard is insulation resistance at the standard temperature ( 20 celcius )
F is insulation resistance temperature correction factor from the table appendix.
Table temperature correction factor
Contoh :
Tmeasured = 50 celcius , CLASS A, RMEASURED = 10 GIGA OHM
SEHINGGA CORRECTION FACTOR: 10 GIGA OHM x 10.45 = 104.5 GIGA OHM