HGM6000K V1.9 en
HGM6000K V1.9 en
USER MANUAL
   Smartgen Technology
              Chinese trademark
English trademark
Zhengzhou city
Henan Province
P. R. China
Tel: +86-371-67988888/67981888
+86-371-67991553/67992951
+86-371-67981000(overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn
http://www.smartgen.cn
Email: sales@smartgen.cn
All rights reserved. No part of this publication may be reproduced in any material
Smartgen Technology reserves the right to change the contents of this document
                                                CONTENT
1      SUMMARY ................................................................................. 5
2      PERFORMANCE AND CHARACTERISTICS ............................. 6
3      SPECIFICATION ........................................................................ 8
4      OPERATION .............................................................................. 9
     4.1 KEY FUNCTION....................................................................................... 9
     4.2 DISPLAY DESCRIBE ............................................................................. 10
     4.3 AUTOMATIC OPERATION ..................................................................... 11
     4.4 MANUAL OPERATION........................................................................... 13
5      PROTECTION .......................................................................... 15
     5.1 WARN .................................................................................................... 15
     5.2 SHUTDOWN ALARM ............................................................................. 16
6      CONNECTING TERMINAL ...................................................... 19
7      PARAMETER RANGE AND DEFINE........................................ 22
     7.1 PARAMETERS TABLE (TABLE 1) ......................................................... 22
     7.2 OUTPUT 1-4 TABLE (TABLE 2) ............................................................. 29
     7.3 DIGIT INPUT 1-5 TABLE (TABLE 3) ...................................................... 30
     7.4 SENSOR (TABLE 4)............................................................................... 30
     7.5 CONDITION OF CRANK SUCCEED (TABLE 5) .................................... 31
8      SETTING PARAMETER ........................................................... 32
9      SENSOR SETTINGS ............................................................... 33
10     COMMISSIONING.................................................................... 34
11     TYPICAL WIRING DIAGRAM ................................................... 35
12     INSTALLATION ........................................................................ 37
13     FAULT FINDING ....................................................................... 39
HGM6000K Series Automatic Generator Module               ISSUE 2013-08-13        Version 1.9      Page 4 of 40
                     HGM6000K Series Automatic Generator Module
1 SUMMARY
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 5 of 40
                       HGM6000K Series Automatic Generator Module
 Mains                                             Gens
 Line voltage (Uab, Ubc, and Uca)                 Line voltage (Uab, Ubc, and Uca)
 Phase voltage (Ua, Ub, and Uc)                  Phase voltage (Ua, Ub, and Uc)
 Frequency       HZ                              Frequency       HZ
 Load
 Power Current IA, IB, IC
 Active power KW
 Inactive power KVar
 Apparent power KVA
 Power factor Cos
 Accumulate total gens power kWh
■ Mains have over voltage, under voltage, loss phase function; Gens have over
  voltage, under voltage, over frequency, under frequency, over current function;
■ Precision measure and display parameters about Engine,
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 6 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 7 of 40
                       HGM6000K Series Automatic Generator Module
3 SPECIFICATION
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 8 of 40
                     HGM6000K Series Automatic Generator Module
4 OPERATION
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 9 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 10 of 40
                     HGM6000K Series Automatic Generator Module
       Water temperature                                 Gens oil pressure
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 11 of 40
                     HGM6000K Series Automatic Generator Module
7. Whatever times to start genset successfully, it will enter into ―safety on time‖.
    During this period, alarms of low oil pressure, hi-temperature, under speed,
    charge fail and Aux. input (been configured) are inactive. As soon as this delay
    is over, genset will enter into ―start idle delay‖ (if this be configured).
8. During ―start idle delay‖, alarms of under speed, under frequency, under voltage
    are inactive. As soon as this delay is over, genset will enter into ―warming up
    time delay‖ (if this be configured).
9. When ―warming up time delay‖ is over, gens status indicator is light if gens
    normal. If alternator‘s voltage, frequency meets to requirement of load, gens will
    close and relay is outputting, then genset will enter into normal running with load
    and gens indicator is light; if genset voltage and frequency is abnormal,
    controller will alarm and stop engine (gens alarming is displayed LCD).
Sequence of Auto Stop,
1. HGM6020KC, when Mains recovery during genset running, enters into mains
    voltage ―normal delay‖ and its indicator light after Mains normal be confirmed.
    ―Start delay‖ is beginning.
2. HGM6010KC, genset enters into ―stop delay‖ as soon as ―Remote Start‖ putting
    is inactive.
3. As soon as ―stop delay‖ is over, genset enters into ―High Speed cooling delay‖.
    Mains are close and breaker is disconnected. After switch ―rest time delay‖,
    mains are close and relay is output as well as with loading. Gens‘ indicator is
    dark while mains‘ light.
4. Idle relay has power and outputs as soon as entering ―stop idle relay‖ (If this
    been configured).
5. When enters ―ETS relay‖, ETS relay has power and outputs. Oil relay‘s output is
    disconnected.
6. When genset enters ―stop time‖, automatic to decide whether genset is stopped
    or not.
7. When genset will enter into ―over stop time‖ as soon as genset is stopped. If
    genset failed to stop and controller will alarm (―stop failed‖ will be displayed in
    LCD).
Note: This page is nonce genset status, genset status delay countdown display,
for example:
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 12 of 40
                       HGM6000K Series Automatic Generator Module
At the first line, NO 4 is the Start interval state; 3s is the countdown to remain time
intervals of Start interval.
Gens Status List:
 0: Genset Waiting 1: Start preheat 2: Fuel output 3: Start 4: Start Interval
 5: Safety run 6: Start Idling 7: Start warm-up 8: Wait for the Load
 9: Normal Run 10: Stop for cooling 11: Stop idling 12: ETS stop
 13: Wait for stop steady 14: Shutdown failures
1. HGM6020KC, Auto starts mode is active when press and its indicator is
illuminating. Press , then controller under ―Manual Test Mode‖ and its
     indicator is illuminating. Under the both modes, press            to start genset, and it
     can automatic detect start successfully and accelerate to Hi-speed running. If
there is Hi-temperature, low oil level and voltage abnormal during diesel genset
running, controller can protect genset to stop quickly (detail procedures please
     refer to No.4~9 of Auto start operation). Under ―Manual Test Mode               ‖, genset
     with load is decided by Mains is normal or not. If mains are normal, loading
     transferred into gens side. Under ―Manual Test Mode             ‖, after genset runs well
     in high speed, no matter mains is normal or not, loading switch must be
2. HGM6010KC, Auto starts mode is active when press , and its indicator is
Hi-temperature, low oil level and voltage abnormal during diesel genset running,
  HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 13 of 40
                     HGM6000K Series Automatic Generator Module
controller can protect genset to stop quickly (detail procedures please refer to
No.4~9 of Auto start operation). After genset runs well in High speed, controller
3. Manual stop, press can shutdown the running genset (detail procedures
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 14 of 40
                     HGM6000K Series Automatic Generator Module
5 PROTECTION
5.1 WARN
Warns are non-critical alarm conditions and do not affect the operation of the
genset system; they serve to draw the operators attention to an undesirable
condition.
In the event of a warning, the module will display at the last screen of LCD.
Warn is shown as the below:
HIGH ENGINE TEMPERATURE WARN, if the module detects that the engine
coolant temperature has exceeded the high engine temperature setting level after
the Safety On timer has expired and the input of Inhibit WTH stop is activated, a
warn will occur. At the same time LCD screen              icon lighten.
LOW OIL PRESSURE WARN, if the module detects that the engine oil pressure
has fallen below the low oil pressure setting level after the Safety On timer has
expired and the input of Inhibit OPL stop is activated, a warning will occur. At the
same time LCD screen             icon lighten.
LOSS OF SPEED SIGNAL WARN, if the speed sensing signal is lost, a warning
will occur and the lost speed delay set to zero, a warning will occur. At the same
time LCD screen           icon lighten.
GENSET OVER CURRENT WARN, if the module detects a genset output current
in excess of the setting and the over current delay set to zero, a warning is
initiated. At the same time LCD screen           icon lighten.
FAIL TO STOP WARN, if the module detects the engine is still running when the
‗Fail to stop timer‘ expires, a warning is initiated. At the same time LCD screen
icon lighten.
START BATTERY OVER VOLTAGE WARN, if the module detects that the plant
DC supply has risen above the high volts setting level, a warning is initiated. At the
same time LCD screen           icon lighten.
START BATTERY UNDER VOLTAGE WARN, if the module detects that the plant
DC supply has fallen below the low volts setting level, a warning is initiated. At the
same time LCD screen           icon lighten.
LOW FUEL LEVEL WARN, if the module detects that the engine oil level has
fallen below the low level setting level has expired, a warning will occur. At the
same time LCD screen           icon lighten.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13    Version 1.9   Page 15 of 40
                       HGM6000K Series Automatic Generator Module
FAILED TO CHARGE WARN, if the module detects that the charge of volts has
fallen below the setting level has expired, a warning will occur. At the same time
LCD screen         icon lighten.
GENSET OVER VOLTAGE WARN, if the module detects a genset output voltage
in excess of the setting a warning is initiated. At the same time LCD screen
icon lighten.
GENSET UNDER VOLTAGE WARN, if the module detects a genset output voltage
below the setting a warning is initiated. At the same time LCD screen                         icon
lighten.
OVER SPEED WARN, if the engine speed exceeds the setting value a warning is
initiated. At the same time LCD screen            icon lighten.
UNDER SPEED WARN, if the engine speed falls below the setting value after the
Safety On timer has expired, a warning is initiated. At the same time LCD screen
     icon lighten.
GENSET OVER FREQUENCY WARN, if the module detects a genset output
frequency in excess of the setting value a warn in is initiated. At the same time
LCD screen           icon lighten.
GENSET UNDER FREQUENCY WARN, if the module detects a genset output
frequency below the setting value after the Safety On timer has expired, a warning
is initiated. At the same time LCD screen           icon lighten.
Safety On timer has expired, a shutdown will occur. At the same time LCD screen
     flicker.
LOW OIL PRESSURE, if the module detects that the engine oil pressure has
fallen below the low oil pressure setting level after the Safety On timer has
expired, a shutdown will occur. At the same time LCD screen                    flicker.
OVERSPEED, if the engine speed exceeds the setting value a shutdown is
initiated. At the same time LCD screen            flicker.
UNDERSPEED, if the engine speed falls below the setting value after the Safety
On timer has expired, a shutdown is initiated. At the same time LCD screen
flicker.
LOSS OF SPEED SIGNAL, if the speed sensing signal is lost, a shutdown is
initiated. At the same time LCD screen             flicker.
GENSET OVER FREQUENCY, if the module detects a genset output frequency
in excess of the setting value a shutdown is initiated. At the same time LCD
screen          flicker.
GENSET UNDER FREQUENCY, if the module detects a genset output frequency
below the setting value after the Safety On timer has expired, a shutdown is
initiated. At the same time LCD screen             flicker.
GENSET OVER VOLTAGE, if the module detects a genset output voltage in
excess of the setting value a shutdown is initiated. At the same time LCD screen
    flicker.
GENSET UNDER VOLTAGE, if the module detects a genset output voltage
below the setting value after the Safety On timer has expired, a shutdown is
initiated. At the same time LCD screen            flicker.
GENSET OVER CURRENT, if the module detects a genset output current in
excess of the setting value is initiated, a shutdown is initiated. At the same time
LCD screen          flicker.
FAIL TO START, if the engine does not fire after the pre-set number of attempts
has been made a shutdown will be initiated. At the same time LCD screen
flicker.
AUXILIARY INPUTS, if an auxiliary input has been configured as a shutdown the
appropriate information will be displayed. At the same time LCD screen
flicker.
 HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9     Page 17 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module     ISSUE 2013-08-13   Version 1.9   Page 18 of 40
                     HGM6000K Series Automatic Generator Module
6 CONNECTING TERMINAL
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 20 of 40
                      HGM6000K Series Automatic Generator Module
 Pin          Function           Dim                            Description
          Mains neutral
 34                            1.0mm2        Connect to mains neutral terminal.
          input
          RS485 port
 35                            0.5mm2
          common GND
                                             Use only 120Ω RS485 approved cable.
 36       RS485 port A(-)      0.5mm2
 37       RS485 port B(+)      0.5mm2
 38       Auxiliary input 4    1.0mm2        Switch to -ve
 39       Auxiliary input 5    1.0mm2        Switch to -ve
 40       Common port          1.0mm2        Auxiliary input common port
Note:
  1. These terminals of 31, 32, 33, and 34 are not used for HGM6010KC
        module.
  2. Back LINK interface as a parameter programming interface, used by SG72
        adapter PC controller programming.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13     Version 1.9   Page 21 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 22 of 40
                     HGM6000K Series Automatic Generator Module
Num        Parameter            Range         Default                   Remark
                                                           When the engine start not
 P 11 Crank interval                                       successful, in the second
                     (3-60)s                      10
(P06) time                                                 plus electric before the start
                                                           of the waiting time.
                                                           At this time, low oil
                                                           pressure,        high      water
                                                           temperature, under speed,
 P 12                                                      under frequency, under
      Safe run time        (1-60)s                10
(P07)                                                      voltage and charging failure
                                                           and        auxiliary        input
                                                           (configured) alarm is void
                                                           volume.
 P 13                                                      Start genset idle running
      Start idle time      (0-3600)s               0
(P08)                                                      time.
                                                           Genset entered high speed
 P 14 Warming         up
                           (3-3600)s              10       operation, in the warm-up
(P09) time
                                                           before closed for time.
                                                           After unloading in genset,
 P 15
      Cooling time         (3-3600)s              10       the time needed to cool
(P10)
                                                           before shutdown.
 P 16                                                      When stop idling genset
      Stop idle time (0-3600)s                     0
(P11)                                                      running time.
 P 17 ETS solenoid                                         It‘s the delay for energizing
                     (0-120)s                     20
(P12) hold                                                 to stop.
                                                           When        "ETS       solenoid
                                                           shutdown output time" for
                                                           zero, idle time delay stop
                                                           steady to time, and when
 P 18 Fail to stop
                   (0-120)s                        0       "ETS solenoid hold output
(P13) delay
                                                           time" is not equal to zero,
                                                           from        ETS        solenoid
                                                           shutdown delay end to stop
                                                           steady need of time.
                                                           Mains or Genset switch
 P 19 ATS          close                                   closing pulse width, when it
                           (0-10)s                5.0
(P14) time                                                 is     zero,       output       is
                                                           continuous.
                                                           The flywheel teeth on
                                                           engine starter teeth, used
                                                           for     starters     separation
 P 20 Flywheel
                           (10-300)              118       condition judgment and
(P15) teeth
                                                           engine speed detection, see
                                                           behind       the     installation
                                                           instructions.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 23 of 40
                     HGM6000K Series Automatic Generator Module
Num        Parameter            Range         Default                   Remark
      Gens
 P 21                                                      Too high or too low voltage
      abnormal             (0-20.0)s             10.0
(P16)                                                      genset alarm delay.
      delay
                                                           When genset voltage is
                                                           over than the point, genset
      Gens     over
 P 22                                                      over shutdown voltage is
      volt          (30-360)V                    264
(P17)                                                      active. When the point is
      shutdown
                                                           360V, genset over voltage is
                                                           disabled.
                                                           When genset voltage is
                                                           under than the point, genset
      Gens under
 P 23                                                      under shutdown voltage is
      volt       (30-360)V                       196
(P18)                                                      active. When the point is
      shutdown
                                                           30V, genset under voltage is
                                                           disabled.
                                                           When the engine speed is
                                                           under than the point and
 P 24 Under speed
                           (0-6000)RPM           1200      hold great than 10 seconds,
(P19) shutdown
                                                           genset under shutdown
                                                           speed is active.
                                                           When the engine speed is
                                                           over than the point and hold
 P 25 Over speed
                           (0-6000)RPM           1710      great than 2 seconds,
(P20) shutdown
                                                           genset     over    shutdown
                                                           speed is active.
                                                           When genset frequency is
      Gens under                                           low than the point, genset
 P 26
      freq       (0-75.0)Hz                      45.0      low frequency shutdown
(P21)
      shutdown                                             and hold great than 10
                                                           seconds is active.
                                                           When genset frequency is
      Gens     over                                        over than the point and hold
 P 27
      freq          (0-75.0)Hz                   57.0      great than 2 seconds,
(P22)
      shutdown                                             genset     over    shutdown
                                                           frequency is active.
                                                           When engine temperature
                                                           sensor value is large than
                                                           this point and remain for 2
      High                                                 seconds,       send      out
 P 28
      temperature          (80-140)°C             98       shutdown alarm. When the
(P23)
      shutdown                                             value is 140, send out
                                                           warning alarm. (It‘s suited
                                                           for engine temperature
                                                           sensor only).
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 24 of 40
                     HGM6000K Series Automatic Generator Module
Num        Parameter            Range         Default                   Remark
                                                           When engine oil pressure
                                                           sensor value is less than
                                                           this point and remain for 2
      Low      oil                                         seconds,       send      out
 P 29
      pressure     (0-400)kPa                    103       shutdown alarm. When the
(P24)
      shutdown                                             value is zero, send out
                                                           warning alarm. (It‘s suited
                                                           for oil pressure sensor
                                                           only).
                                                           When low Fuel level sensor
 P 30 Low           Fuel                                   value is less than this point
                           (0-100)%               10
(P25) level                                                and remain for 10 seconds,
                                                           send out warning alarm.
                                                           When speed is zero and
                                                           remain for the delay, send
 P 31 Lose        speed
                           (0-20.0)s              5.0      out shutdown alarm. When
(P26) delay
                                                           the delay is zero, send out
                                                           warning alarm.
                                                           When genset voltage is
                                                           over than the point, genset
 P 32 Gens      over                                       over warning voltage is
                     (30-360)V                   256
(P27) volt warn                                            active. When the point is
                                                           360V, genset over voltage is
                                                           disabled.
                                                           When genset voltage is
                                                           under than the point, genset
 P 33 Gens under                                           under warning voltage is
                 (30-360)V                       205
(P28) volt warn                                            active. When the point is
                                                           30V, genset under voltage is
                                                           disabled.
                                                           When the engine speed is
 P 34 Under speed                                          under than the point, genset
                           (0-6000)RPM           1350
(P29) warn                                                 under warning speed is
                                                           active.
                                                           When the engine speed is
 P 35 Over        speed                                    over than the point, genset
                           (0-6000)RPM           1650
(P30) warn                                                 over warning speed is
                                                           active.
                                                           When genset frequency is
 P 36 Gens under                                           low than the point, genset
                 (0-75.0)Hz                      47.0
(P31) freq warn                                            under warning frequency is
                                                           active.
                                                           When genset frequency is
 P 37 Gens      over                                       over than the point, genset
                     (0-75.0)Hz                  55.0
(P32) freq warn                                            over warning frequency is
                                                           active.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 25 of 40
                     HGM6000K Series Automatic Generator Module
Num        Parameter            Range         Default                   Remark
                                                           During genset is running,
                                                           when charge alternator
 P 38 Charge          fail                                 WL/D+ voltage is low than
                             (0-30)V              6.0
(P33) volt                                                 this point and remain for 5
                                                           seconds,       genset       will
                                                           warning alarm.
                                                           When        genset      battery
                                                           voltage is over than the
 P 39 Battery       over                                   point and hold for 20
                             (12-40)V            33.0
(P34) volt                                                 seconds,      battery     over
                                                           voltage signal is active. It‘s
                                                           a warning alarm.
                                                           When        genset      battery
                                                           voltage is less than the point
 P 40 Battery under                                        and hold for 20 seconds,
                    (4-30)V                       8.0
(P35) volt                                                 battery under voltage signal
                                                           is active. It‘s a warning
                                                           alarm.
                                                           When engine temperature
                                                           sensor value is large than
      High                                                 this point, send out warning
 P 41
      temperature            (80-140)ºC           95       alarm. When the value is
(P36)
      warn                                                 140, send out warning
                                                           alarm. (It‘s suited for engine
                                                           temperature sensor only).
                                                           When engine oil pressure
                                                           sensor value is less than
      Low             oil                                  this point send out warning
 P 42
      pressure               (0-400)kPa          124       alarm. When the value is
(P37)
      warn                                                 zero, send out warning
                                                           alarm. (It‘s suited for oil
                                                           pressure sensor only)
 P 43
      CT rate       (5-6000)/5                   500       Current transformer rate
(P38)
 P 44 Full     load                                        Mains    or     genset      set
                    (5-5000)A                    500
(P39) current                                              maximum rated current.
      Over current                                         When the load current is
 P 45
      shutdown      (50-130)%                    120       over than the point, the over
(P40)
      percentage                                           current delay is initiated.
                                                           When load current is over
                                                           than the point and hold
      Over current
 P 46                                                      great than the timer, send
      shutdown               (0-3600)s           1296
(P41)                                                      out over current signal.
      delay
                                                           When the delay is zero,
                                                           over current is disabled.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 26 of 40
                     HGM6000K Series Automatic Generator Module
Num        Parameter            Range         Default                   Remark
      Over current                                         When the load current is
 P 47
      warn                 (50-130)%             110       over than the point, over
(P42)
      percentage                                           current warn icon illume.
      Switching
 P 48
      value output1        (0-11)                  2       ETS solenoid to stop
(P43)
      set
      Switching
 P 49
      value output 2       (0-11)                  3       Idle control
(P44)
      set
      Switching
 P 50
      value output 3       (0-11)                  5       Close Gens
(P45)
      set
      Switching
 P 51                                                      Close mains (6010KC has
      value output 4       (0-11)                  6
(P46)                                                      no function).
      set
 P 52 Aux.    input1                                       High Temperature           alarm
                           (0-10)                  1
(P47) set                                                  switch input
 P 53 Aux. input 1
                           (0-20.0)s              2.0
(P48) delay
 P 54 Aux. input 2
                           (0-10)                  2       Low oil pressure input
(P49) set
 P 55 Aux. input 2
                           (0-20.0)s              2.0
(P50) delay
 P 56 Aux. input 3
                           (0-10)                  3       Auxiliary warning input
(P51) set
 P 57 Aux. input 3
                           (0-20.0)s              2.0
(P52) delay
 P 58 Aux. input 4
                           (0-10)                  6       Oil engine closed state input
(P53) set
 P 59 Aux. input 4
                           (0-20.0)s              2.0
(P54) delay
 P 60 Aux. input 5
                           (0-10)                 10       Remote start input
(P55) set
 P 61 Aux. input 5
                           (0-20.0)s              2.0
(P56) delay
                                                           0: Stop mode
 P 62 Module
                           (0-2)                   0       1: Manual mode
(P57) power on
                                                           2: Auto mode
 P 63 Module
                           (1-254)                 1
(P58) address
 P 64 Passwords
                           (0-9999)              1234
(P59) set
      Crank
 P 65 success                                              Setting item is given in
                           (0-5)                   2
(P60) condition                                            Table 5.
      select
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 27 of 40
                     HGM6000K Series Automatic Generator Module
Num        Parameter            Range         Default                   Remark
                                                           When engine speed is large
 P 66 Speed
                           (0-3000)RPM           360       than this point, starter will
(P61) disconnect
                                                           disconnect.
                                                           When genset frequency is
 P 67 Freq
                           (10-30)Hz              14       large than this point, starter
(P62) disconnect
                                                           will disconnect.
                                                           When engine oil pressure is
 P 68 OP
                           (0-400)kPa            200       large than this point, starter
(P63) disconnect
                                                           will disconnect.
                           0 3P 4L
 P 69 Select AC
                           1 2P 3L                 0       3P4L(3 phase 4 wire)
(P64) system
                           2 1P 2L
 P70     Select temp.
                           (0-8)                  08       SGX
(P65)    sensor
 P71     Select press      (0-8)
                                                  08       SGX
(P66)    sensor
 P72     Select liquid
                           (0-5)                  03       SGD
(P67)    level sensor
                                                           Need to set up eight first
                                                           acts of the current data set
                                                           the number of items, the
      Temperature
                                                           second act to set the
 P73 sensor
                                                           resistance value of the third
(P68) custom curve
                                                           act to set the resistance
      setting
                                                           value of the temperature
                                                           corresponding to the value
                                                           of.
                                                           Need to set up eight first
                                                           acts of the current data set
                                                           the number of items, the
      Oil pressure
                                                           second act to set the
 P74 sensor
                                                           resistance value, the third
(P69) custom curve
                                                           act to set the resistance
      setting
                                                           value of the pressure
                                                           corresponding to the value
                                                           of.
                                                           Need to set up eight first
                                                           acts of the current data set
      Liquid level                                         the number of items, the
 P75 sensor                                                second act to set the
(P70) custom curve                                         resistance value, the third
      setting                                              act to set the resistance
                                                           value of the value of the
                                                           corresponding level.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 28 of 40
                     HGM6000K Series Automatic Generator Module
 Num       Parameter            Range         Default                   Remark
                                                           Number of magnetic poles,
 P76 Number of                                             used for calculating rotating
                           (2-32)                 04
(P71) poles                                                speed of generator without
                                                           speed sensor.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 29 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13    Version 1.9   Page 30 of 40
                     HGM6000K Series Automatic Generator Module
 Num           Items                    Content                           Remark
                               4        SGD(DongKang
                               sensor)
                               5 CURTIS
                               6 DATCON 10Bar
                               7 VOLVO-EC
                               8 SGX
                               0 Not used
                               1 Defined RT
                                                                Defined input resistance
         Fuel          level   2 SGH
   3                                                            range is 0-999.9 ohm,
         Sensor                3 SGD
                                                                factory default is SGD
                               4 Reserved 1
                               5 Reserved 2
1. The crank disconnect condition has three kinds, the magnetic pickup sensor
   and the genset voltage can be used alone, the oil pressure must be used with
   the magnetic pickup sensor and the genset voltage, the purpose is to make
   the starter and the engine to disconnect as soon as possible.
2. Magnetic pickup sensor is installed in the engine block number of magnetic
   device testing flywheel.
3. When choosing magnetic pickup sensor, ensure engine flywheel teeth setting,
   otherwise may appear over speeding shutdown or loss speed shutdown.
4. If the genset is not magnetic pickup sensors, please don't choose
   corresponding, otherwise this will occur fail to start or loss of speed alarm and
   shutdown.
5. If the genset has no oil pressure sensor, please don't choose corresponding.
6. If the genset starting conditions has not be selected, the controller will not
   measure and display the relative parameters (This can be applied to the pump
   set), if not choose magnetic pickup sensor, the speed signal will come from
   the generating AC signal.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13    Version 1.9   Page 31 of 40
                      HGM6000K Series Automatic Generator Module
8 SETTING PARAMETER
After controller powered on, press           to enter into the parameters setting menu:
 ◙   Set parameters
  When entering password, entering "1234" can set the item 1 to 47in the table
  (parameters table [Table 1]), entering "0318" can set all items.
NOTE:
a. When the controller type is HGM6010KC, you will not have a table with a 1-5;
     the programmable output 1-4 will have no power of some mains switch output.
b. Please modify the parameters (such as crank disconnect, input and output
     configuration, various time, etc.) in standby mode, otherwise it might alarm
     shutdown or other abnormal behavior.
c. The over-voltage threshold must be greater than the under-voltage threshold;
     otherwise both will occur at the same time over-voltage and under-voltage
     situation.
d. The over-speed threshold must be greater than under-speed threshold,
     otherwise you will receive both the over speed and under speed.
e. As far as possible set the frequency (crank disconnect) to lower numerical, in
     order to quickly crank disconnect when crank success.
f. Configurable input port 1-5 cannot set for the same items, otherwise cannot
     appear correct function, configurable output 1-4 can be set for the same item.
g. If need to shutdown after cooling, please set any one configurable input as "
     stop after cooling ", then connect this input with GND.
 ◙   Information
  LCD will display the controller software version, issue date.
  Note: Press the key           will display the states of configurable input port and
  output port state.
 ◙   Set language
  User may set display interface language as Chinese, English and Spanish.
* Remark: Press the key will exit setting interface at any time.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 32 of 40
                     HGM6000K Series Automatic Generator Module
9 SENSOR SETTINGS
1. When the choice sensor, the sensor to standard curve will call. If factory set
    temperature sensor for SGX (resistance-type), sensor curve for SGX
    (resistance-type), 120 degrees Celsius (elected SGD type), resistively curve
    for temperature sensor SGD curve.
2. If use standard sensor with the curve, can differ option "item sensor curve
    input", after adjusting adjustment can be determined according to save.
3. When the input sensor curve, X (resistance) must be in accordance with the
    order of big from small, otherwise will enter errors.
4. When the sensor is choosing "nothing", the sensor curves no affection, LCD
    display temperature or pressure for---.
5. If there is no pressure sensor, only low pressure alarm switch, it must be
    alarm settings for pressure sensor "nothing", otherwise may appear oil
    pressure low alarm shutdown.
6. Can set up several point of forehand or several point of backmost ordinate the
    same. The following picture:
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13    Version 1.9   Page 33 of 40
                     HGM6000K Series Automatic Generator Module
10 COMMISSIONING
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 34 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 35 of 40
                     HGM6000K Series Automatic Generator Module
Note: Recommend that the output of crank and Fuel expand high capacity relay.
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 36 of 40
                     HGM6000K Series Automatic Generator Module
12 INSTALLATION
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 37 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 38 of 40
                     HGM6000K Series Automatic Generator Module
13 FAULT FINDING
HGM6000K Series Automatic Generator Module   ISSUE 2013-08-13   Version 1.9   Page 39 of 40
                     HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2013-08-13 Version 1.9 Page 40 of 40