STATCOM
Static Synchronous
Compensators
Designed by Endoks, Turkey
STATCOM
Systems
STATIC SYNCHRONOUS COMPENSATOR
Statcom (Static Synchronous Compensator) is a converter based
digital controlled FACTS device providing complete solution for
reactive power, harmonics, voltage unbalance, voltage fluctuations
and neutral current problems. Statcom provides simultaneous
solution to power quality problems according to operating priorities
selected by user.
SYSTEM APPLICATION
Capacitive / Inductive Loads
Nonlinear Loads
Unbalanced loads
Loads and drivers connected to weak grids
SYSTEM ADVANTAGES
• Step-less and exact compensation
• Reduction in system losses, maintenance costs and increased productivity
• Fastest response time to voltage sags / swells
• Preventing penalties against power quality parameters such as reactive power,
harmonics and flicker
• Insensitive to network disturbances and no performance reduction against network
parameters variation
• Elimination of resonance risks
• Extended equipment lifetime and protection of sensitive electronic equipment
• Fully programmable interface including industrial communication protocols and
monitoring options
• Modular and expandable structure, easy integration to existing systems
www.endoks.com.tr
E
nergy
ngineering
fficiency
SYSTEM FUNCTIONALITY
• Reactive Power Compensation
• Harmonic Filtering
• Load Balancing
• Voltage Regulation
APPLICATION AREAS
• Wind Power Plants
• Railway Industry
• Iron and Steel Industry
STATCOM systems generate its rated reactive
• Cement Production Industry
power both in inductive and capacitive regions
• Automotive – Welding Industry
• Water Treatment and Pump Units irrespective of supply voltage contrary to
• Hydroelectric Application conventional compensation systems. STATCOM
• Aviation – Marine Application systems can provide active harmonic filtering and
load balancing features in addition to reactive
power compensation.
STATCOM, realizes these functions by its DSP
based digital control system and voltage Custom designed STATCOM systems can be
source converter topology. manufactured according to customer needs in
addition to standard product configurations.
www.endoks.com.tr
STATCOM PRODUCT FAMILY
MODELS ES400 / ES400N ES690 ES1000
Nominal Reactive Power * ±100 to ±250 kVAr ±250 to ±500 kVAr ±500 to ±1000 kVAr
Nominal Voltage ** 400 Vrms (±10 %) 690 Vrms (±10 %) 1000 Vrms (±10 %)
160 to 400 Arms
Nominal Current 232 to 465 Arms 320 to 640 Arms
(x3 Neutral Current for ES400N)
Overload Capability Optional
Network Frequency 50-60Hz (±5 %)
Line Connection 3 phase/3 wire - 3 phase/4 wire 3 phase/3 wire 3 phase/3 wire
Operation Modes Reactive / Harmonic / Unbalance / Voltage Regulation
Compensation Modes Closed Loop / Open Loop / Fixed / Hybrid / Remote
Harmonics Elimination Selective / 3 (ES400N) , 5, 7, 11, 13
Load Balancing *** Phase to Phase / Phase to Neutral (for ES400 and ES400N)
Efficiency <2,7% <3% <3%
Response Time <1ms
Parallel Operation Up to 8 Modules in Master / Slave Configuration
User Interface **** 4.3' Touch Screen 4.3' Touch Screen 10' Touch Screen
Communication MODBUS RTU / TCP
50'C without derating 50'C without derating 45'C without derating
Operation Temperature (IEC60721-3-3, Class 3k3) (IEC60721-3-3, Class 3k3) (IEC60721-3-3, Class 3k3)
Cooling Method Air Air Liquid
Noise Level <68dBA <70dBA <76dBA
Humidity 5% to 85% (IEC60721-3-3, Class 3k3)
Installation Altitude 1000m without derating (IEC60721-3-3, Class 3k3)
* Other power ratings available on customer request *** Max 50 % of nominal current
** Other voltage ratings available on customer request **** Other screen sizes up to 10' available on customer request
www.endoks.com.tr
www.endoks.com.tr
V
I
OPERATION PRINCIPLES
• Statcom is a controlled current source device
with IGBT based converter technology.
• Reactive power is transferred through a coupling
reactor in capacitive and inductive regions by
the generation of magnitude controlled voltage
Before Harmonic Reactive Power at the converter ouput. STATCOM provides its nominal
Before STATCOM
Statcom Harmonic
Filtering Reactive Power
Compensation
Filtering Compensation current irrespective of the network voltage by con-
I. Bölge trolling converter output voltage.
• Statcom is able to inject anti-phase low order har-
I monic currents to minimize current distortion at supply
side. Harmonic filtering is limited to most common LV
network harmonics which are 3 rd, 5 th, 7 th,11 th and 13 rd
harmonics.
• Unsymmetrical load currents are balanced by inject-
ing negative sequence currents to the network.
• STATCOM provides the best voltage regulation perfor-
mance during voltage sags/swells by using its overload
capability in addition to fastest reactive power
generation.
Before Statcom Load Balancing
Before STATCOM Load Balancing
I. Bölge
www.endoks.com.tr
Your Local Contact;
İnönü Mah. 1748 sok. No:1 06370 Batıkent
Yenimahalle Ankara / TURKEY
Phone : +90 312 256 00 86
Fax : +90 312 257 27 50
Email : info@endoks.com.tr
Web : www.endoks.com.tr
1kV / 1MVAr STATCOM, 2009
www.endoks.com.tr