Outdoor Instrument Transformers
Buyer’s Guide
Contents	
            Table of Contents
                                                                            Chapter - Page
            Products        Introduction                                            A-2
                            Explanations                                            B-1
                            Silicone Rubber (SIR) Insulators                       C-1
                            Design Features and Advantages
                             Current Transformers IMB                               D-1
                             Inductive Voltage Transformer EMF                      E-1
                             Capacitor Voltage Transformer CPA/CPB                  F-1
            Technical       Technical Catalogues
            Information
                             CT IMB                                                G-1
                             VT EMF                                                H-1
                             CVT CPA/CPB (IEC)                                      I-1
                             CVT CPA/CPB (ANSI)                                     J-1
                            Optional
                             Cable Entry Kits - Roxtec CF 16                        K-1
                            Quality Control and Testing                             L-1
                            Inquiry and Ordering Data                              M-1
A-1                       Edition 5, 2008-03       ABB Instrument Transformers — Buyer’s Guide
                                                                                                                       Introduction
Day after day, all year around—
with ABB Instrument Transformers
ABB has been producing instrument trans-                       All instrument transformers supplied by ABB
formers for more than 60 years. Thousands                      are tailor-made to meet the needs of our
of our products perform vital functions in                     customers.
electric power networks around the world –                     An instrument transformer must be capable of
day after day, all year round.                                 withstanding very high stresses in all climatic
Their main applications include revenue                        conditions. We design and manufacture our
metering, control, indication and relay pro-                   products for a service life of at least 30 years.
tection.                                                       Actually, most last even longer.
 Product range                                                 Type                                       Highest
                                                                                                         Voltage for
                                                                                                         Equipment
                                                                                                             (kV)
                  Current Transformer IMB
 Hairpin/Tank type                                             IMB 36 - 800                               36 - 765
 Paper, mineral oil insulation, quartz filling
 Inductive Voltage Transformer EMF
 Paper, mineral oil insulation, quartz filling                 EMF 52 - 170                               52 - 170
 Capacitor Voltage Transformer CP
 CVD: Mixed dielectric polypropylene-film and synthetic oil.
                                                               CP 72 - 800                               72.5 - 765
 EMU: Paper, mineral oil
 Coupling Capacitors CCA or CCB
 Intended for power line carrier applications                  CCA (high capacitance) 72 - 800           72.5 - 765
 (identical to CVD above but without intermediate voltage
 terminal.)                                                    CCB (extra high capacitance) 145 - 800     145 - 765
 We are flexible and tailor each instrument transformer the needs of our customers. Sizes other than those mentioned
 above can be supplied upon request.
ABB Instrument Transformers — Buyer’s Guide                 Edition 5, 2008-03                                                  A-2
Explanations	
Technical Specifications – General
Standard/Customer        There are international and national standards, as well as customer specifications.
specification            ABB High Voltage Products can meet most requirements, as long as we are aware of them. When in
                         doubt, please enclose a copy of your specifications with the inquiry.
Rated voltage            The rated voltage is the maximum voltage (phase-phase), expressed in kV rms, of the system for
                         which the equipment is intended. It is also known as maximum system voltage.
Rated insulation level   The combination of voltage values which characterizes the insulation of an instrument transformer with
                         regard to its capability to withstand dielectric stresses.
                         The rated value given is valid for altitudes ≤1000 m above sea level. A correction factor is introduced
                         for higher altitudes.
Lightning impulse test   The lightning impulse test is performed with a standardized wave shape – 1.2/50 µs – for simulation of
                         lightning overvoltage.
Rated                    This test is to show that the apparatus can withstand the power frequency over-voltages that can
Power Frequency          occur.
Withstand Voltage        The Rated Power Frequency Withstand voltage indicates the required withstand voltage. The value is
                         expressed in kV rms.
Rated SIWL               For voltages ≥300 kV the power-frequency voltage test is partly replaced by the switching impulse
                         test. The wave shape 250/2500 µs simulates switching over-voltage.
                         The rated Switching Impulse Withstand Level (SIWL) indicates the required withstand level phase-to-
                         earth (phase-to-ground), between phases and across open contacts. The value is expressed in kV as
                         a peak value.
Rated Chopped Wave The rated chopped wave impulse withstand level at 2 μs and 3 μs respectively, indicates the required
Impulse Withstand      withstand level phase-to-earth (phase-to-ground).
voltage Phase-to-earth
Rated frequency          The rated (power) frequency is the nominal frequency of the system expressed in Hz, which the instru-
                         ment transformer is designed to operate in.
                         Standard frequencies are 50 Hz and 60 Hz.
                         Other frequencies, such as 16 2/3 Hz and 25 Hz might be applicable for some railway applications.
Ambient temperature      Average 24 hours ambient temperature above the standardized +35 °C influences the thermal design
                         of the transformers and must therefore be specified.
Installation altitude    If installed >1000 m above sea level, the external dielectric strength is reduced due to the lower density
                         of the air. Always specify the installation altitude and normal rated insulation levels. ABB will make the
                         needed correction when an altitude higher than 1000 meters ASL is specified. Internal insulation is not
                         affected by installation altitude and dielectric routine tests will be performed at the rated insulation levels.
Creepage distance        The creepage distance is defined as the shortest distance along the surface of an insulator between
                         high voltage and ground.
                         The required creepage distance is specified by the user in:
                         - mm (total creepage distance)
                         - mm/kV (creepage distance in relation to the highest system voltage).
Pollution level          Environmental conditions, with respect to pollution, are sometimes categorized in pollution levels. Four
                         pollution levels are described in IEC 60815.
                         There is a relation between each pollution level and a corresponding minimum nominal specific creep-
                         age distance.
                         Pollution level 	   Creepage distance
                         I - Light 	         16 mm/kV
                         II - Medium 	       20 mm/kV
                         III - Heavy 	       25 mm/kV
                         IV - Very Heavy 	   31 mm/kV
Wind load                The specified wind loads for instrument transformers intended for outdoor normal conditions are
                         based on a wind speed of 34 m/s.
B-1                                                      Edition 5, 2008-03                  ABB Instrument Transformers — Buyer’s Guide
	                                                                                                                      Explanations
Technical Specifications – Current Transformers
    Currents                     The rated currents are the values of primary and secondary currents on which performance is based
    Rated primary current        The rated current (sometimes referred to as rated current, nominal current or rated continuous cur-
                                 rent) is the maximum continuous current the equipment is allowed to carry.
                                 The current is expressed in A rms.
                                 The maximum continuous thermal current is based on average 24 h ambient temperature of +35 °C.
                                 It should be selected about 10 - 40% higher than the estimated operating current.
                                 Closest standardized value should be chosen.
    Extended current ratings     A factor that multiplied by the rated current gives the maximum continuous load current and the limit
                                 for accuracy. Standard values of extended primary current are 120, 150 and 200% of rated current.
                                 Unless otherwise specified, the rated continuous thermal current shall be the rated primary current.
    Rated secondary current      The standard values are 1, 2 and 5 A. 1 A gives an overall lower burden requirement through lower
                                 cable burden.
    Rated short-time thermal     The rated short-time withstand current is the maximum current (expressed in kA rms) which the
    current (Ith)                equipment shall be able to carry for a specified time duration.
                                 Standard values for duration are 1 or 3 s. Ith depends on the short-circuit power of the grid and can
                                 be calculated from the formula: Ith = Pk (MW) / Um (kV) x √3 kA.
    Rated dynamic current        The dynamic short-time current is according to IEC, Idyn = 2.5 x Ith
    (Idyn)                       and according to IEEE, Idyn = 2.7 x Ith
    Reconnection                 The current transformer can be designed with either primary or secondary reconnection or a com-
                                 bination of both to obtain more current ratios.
    Primary reconnection         The ampere-turns always remain the same and thereby the load capacity (burden) remains the
                                 same. The short-circuit capacity however is reduced for the lower ratios. Primary reconnection is
                                 available for currents in relation 2:1 or 4:2:1. See pages I-5 and I-9.
    Secondary reconnection       Extra secondary terminals (taps) are taken out from the secondary winding. The load capacity
                                 drops as the ampere-turns decrease on the taps, but the short-circuit capacity remains constant.
                                 Each core can be individually reconnected.
    Burden and
    Accuracy Class (IEC)
    Burden                       The external impedance in the secondary circuit in ohms at the specified power factor. It is usu-
                                 ally expressed as the apparent power – in VA -, which is taken up at rated secondary current. It
                                 is important to determine the power consumption of connected meters and relays including the
                                 cables. Unnecessary high burdens are often specified for modern equipment. Note that the accu-
                                 racy for the measuring core, according to IEC, can be outside the class limit if the actual burden is
                                 below 25% of the rated burden.
    Accuracy                     The accuracy class for measuring cores is according to the IEC standard given as 0.2, 0.2S, 0.5,
                                 0.5S or 1.0 depending on the application. For protection cores the class is normally 5P or 10P.
                                 Other classes are quoted on request, e.g. class PR, PX, TPS, TPX or TPY.
    Rct                          The secondary winding resistance at 75 °C
    Instrument Security          To protect meters and instruments from being damaged by high currents, an FS factor of 5 or 10 often
    Factor (FS)                  is specified for measuring cores. This means that the secondary current will increase a maximum of 5 or
                                 10 times when the rated burden is connected. FS10 is normally sufficient for modern meters.
    Accuracy Limit Factor        The protection cores must be able to reproduce the fault current without being saturated.
    (ALF)                        The overcurrent factor for protection cores is called ALF. ALF = 10 or 20 is commonly used.
                                 Both FS and ALF are valid at rated burden only. If lower burden the FS anf ALF will increase
    Burden and Accuracy          More detailed information about standards other than IEC can be found in our Application
    Class for other standards,   Guide, Outdoor Instrument Transformers, Catalog Publication 1HSM 9543 40-00en or in the
    such as ANSI, IEEE, etc.     actual standard.
ABB Instrument Transformers — Buyer’s Guide                  Edition 5, 2008-03                                                      B-2
Explanations	
Technical Specifications – Voltage Transformers
Voltages               The rated voltages are the values of primary and secondary voltages on which the performance is
                       based.
Voltage factor (Vf)    It is important that the voltage transformer, for thermal and protection reasons, can withstand and
                       reproduce the continuous fault overvoltages that can occur in the net. The over-voltage factor is
                       abbreviated as Vf.
                       The IEC standard specifies a voltage factor of 1.2 continuously and simultaneously 1.5/30 sec. for
                       systems with effective grounding with automatic fault tripping, and 1.9/8 hrs for systems with insu-
                       lated neutral point without automatic ground fault systems.
                       Accuracy, according to IEC, for measuring windings is fulfilled between 0.8 and 1.2 x rated voltage
                       and for protection windings up to the voltage factor (1.5 or 1.9 x rated voltage).
Reconnection           The voltage transformer can be designed with secondary reconnection.
                       Secondary reconnection means that extra secondary terminals (taps) are taken out from the
                       secondary winding(s).
Burden and accuracy
class
Burden                 The external impedance in the secondary circuit in ohms at the specified power factor. It is usually
                       expressed as the apparent power – in VA -, which is taken up at the rated secondary voltage.
                       (See Current Transformers above).
                       The accuracy class for measuring windings, according to IEC, is given as 0.2, 0.5 or 1.0 depending
                       on the application. A rated burden of around 1.3-1.5 times the connected burden will give maximum
                       accuracy at the connected burden.
                       For protection purposes the class is normally 3P or 6P
Simultaneous burden    Metering windings and protection windings not connected in open delta are considered as simultane-
(IEC)                  ously loaded. A protection winding connected in open delta is not considered as a simultaneous load.
                       Thermal limit burden is the total power the transformer can supply without excessively high tempera-
Thermal limit burden   ture rise. The transformer is engineered so that it can be loaded with the impedance corresponding to
                       the load at rated voltage, multiplied by the square of the voltage factor. This means that at a voltage
                       factor of 1.9/8h, for example, the limit burden = total rated burden x 1.92.
                       The transformer cannot be subjected to a higher limit burden without being loaded higher than the
                       rated burden. Consequently, because of loading considerations, it is unnecessary to specify a higher
                       thermal limit burden.
                       The voltage drop in an external secondary circuit (cables and fuses) can have a significantly larger
Voltage drop           influence on the ratio error than incorrect burden.
                       Ferroresonance is a potential source of transient overvoltage. Three-phase, single-phase switching,
Ferro-resonance        blown fuses, and broken conductors can result in overvoltage when ferroresonance occurs between
                       the magnetizing impedance of a transformer and the system capacitance of the isolated phase or
                       phases. For example, the capacitance could be as simple as a length of cable connected to the
                       ungrounded winding of a transformer. Another example of ferroresonance occurring is when an induc-
                       tive voltage transformer is connected in parallel with a large grading capacitor across the gap of a
                       circuit breaker.
                       Ferroresonance is usually known as a series resonance.
B-3                                                  Edition 5, 2008-03               ABB Instrument Transformers — Buyer’s Guide
	                                                                                                            Explanations
Technical Specifications – Voltage Transformers
    Additional for
    Capacitor Voltage
    Transformers (CVT)
    and Capacitor Voltage
    Divider (CVD)
    Capacitance             Requirements for capacitance values can be applicable when using the CVT for communication over
    phase - ground          lines (for relay functions or remote control).
                            PLC = Power Line Carrier.
                            Higher capacitance => Smaller impedance for signal.
                            Frequency ranges 50-500 kHz. The line matching unit can be adjusted to any capacitance.
                            The lower applied frequency decide the minimum capacitance of coupling capacitor.
    More information        More detailed information about instrument transformers can be found in our
    regarding instrument    Application Guide, Outdoor Instrument Transformers. Catalog Publication 1HSM 9543 40-00en
    transformers
ABB Instrument Transformers — Buyer’s Guide             Edition 5, 2008-03                                               B-4
Silicone Rubber Insulators	
Silicone Rubber as an Insulator
                 Wide range of instrument                                 ABB Manufacturing Technique
                 transformers with silicone rubber                        The patented helical extrusion moulded silicone
                 (SIR) insulators                                         rubber insulators without joints (chemical bounds
                 ABB AB, High Voltage Products can supply                 between spirals) minimizes electrical field con-
                 most of our instrument transformers with                 centrations and reduces build-up of contamina-
                 patented helical extrusion-moulded silicone              tion. The cross-laminated fiberglass tube inside
                 rubber insulation.                                       the insulator provides high mechanical strength.
                   CT IMB 36-800 kV                                       Completed Tests
                   VT EMF 52-170 kV                                       The silicone material used for ABB AB, High
                   CVT CPA/CPB 72-800 kV                                  Voltage Products, Instrument Transformers is
                                                                          approved according to IEC and ANSI/IEEE stan-
                 Why Silicone Rubber Insulators?                          dards.
                 Ceramic (porcelain) insulators have performed
                 well for several decades, but one of the dis-            Tests performed:
                 advantages with porcelain is its fragility.              •	Accelerated ageing test (1,000 h)
                  Listed below are some of the advantages                 •	Lightning impulse test, wet power frequency
                 of silicone rubber insulators compared to                  test and wet switching impulse test
                 porcelain:                                               •	Short circuit test
                 •	Non-brittle                                            •	Temperature rise test
                 •	Minimum risk for handling and transport
                   damages                                                Color
                 •	Minimum risk for vandalism                             The (SIR) insulators for the instrument trans-
                 •	Light-weight                                           formers are supplied in a light gray color.
                 •	Explosion safety
                 •	Excellent pollution performance                        Deliveries
                 •	Minimum maintenance in polluted areas                  ABB in Ludvika has supplied instrument trans-
                 •	Hydrophobic                                            formers with (SIR) insulators for the most severe
                                                                          conditions, from marine climate to desert and/or
                 There are several polymeric insulator                    polluted industrial areas.
                 materials available, of which silicone                     A reference list can be provided on request.
                 has proven to be superior
                 Comparison of Polymeric Insulators
                                   Epoxy       EP-rubber    Silicone
                  Brittle            Low        Excellent   Excellent
                  Insulation         Fair        Good       Excellent
                  Weight            Good        Excellent   Excellent
                  Mech. strength   Excellent     Good       Excellent
                  Safety            Good         Good       Excellent
                  Earthquake        Good        Excellent   Excellent
                  Handling          Good        Excellent   Excellent
                  Maintenance        Fair         Fair      Excellent
                  Ageing             Fair        Good       Excellent
                  UV-resistance     Good         Good       Excellent
                 Experience of Material
                 ABB has used silicone rubber (SIR) insulators            More Information
                 since 1985, starting with surge arresters, and           For additional information please refer to
                 has gained considerable experience.                      publication 1HSM 9543 01-06en.
C-1                                                  Edition 5, 2008-03              ABB Instrument Transformers — Buyer’s Guide
                                                s
                          es r´
                       ot e
                      N omt
                       us
               C
ABB Instrument Transformers — Buyer’s Guide   Edition 5, 2008-03   C-2
Design	                                                                            Current Transformer
IMB Design Features and Advantages
          ABB’s oil minimum current transform-              around the whole periphery of the core. The
          ers type IMB is based on a hairpin                leakage reactance in the winding and also
          design (shape of the primary conduc-              between extra tapping is therefore negligible.
          tor) also known as tank type. The                 Impregnation
          basic design has been used by ABB                 Heating in a vacuum dries the windings. After
          for 60 years, with more than 160,000              assembly all free space in the transformer
          units delivered.                                  (app. 60%) is filled with clean and dry quartz
                                                            grain. The assembled transformer is vacuum-
          The design corresponds with the demands           treated and impregnated with degassed min-
          of both the IEC and IEEE standards. Special       eral oil. The transformer is always delivered
          design solutions to meet other standards          oil-filled and hermetically sealed.
          and/or specifications are also available.
           The unique filling with quartz grains satu-      Tank and Insulator
          rated in oil gives a resistant insulation in a    The lower section of the transformer consists
          compact design where the quantity of oil is       of an aluminum tank in which the secondary
          kept to a minimum                                 windings and cores are mounted. The insu-
           The IMB transformer has a very flexible          lator, mounted above the transformer tank,
          design that, for example, allows large and/or     consists as standard of high-grade brown-
          many cores.                                       glazed porcelain. Designs using light gray
                                                            porcelain or silicon rubber can be quoted on
          Primary Winding                                   request.
          The primary winding consists of one or more
          parallel conductor of aluminum or copper          The sealing system consists of O-ring gas-
          designed as a U-shaped bushing with volt-         kets.
          age grading capacitor layers.
          The insulation technique is automated to give     Expansion System
          a simple and controlled wrapping, which im-       The IMB has an expansion vessel placed on
          proves quality and minimizes variations.          top of the insulator. A hermetically sealed
            The conductor is insulated with a special       expansion system, with a nitrogen cushion
          paper with high mechanical and dielectric         compressed by thermal expansion of the oil,
          strength, low dielectric losses and good          is used in the IMB as the standard design.
          resistance to ageing.                             An expansion system with stainless steel ex-
            This design is also very suitable for primary   pansion bellows can be quoted on request.
          windings with many primary turns. This is
          used when the primary current is low, for         On Request – Capacitive Voltage Tap
          instance unbalance protection in capacitor        The capacitive layers in the high voltage insu-
          banks. (Ex. ratio 5/5A)                           lation can be utilized as a capacitive voltage
                                                            divider. A tap is brought out from the second
          Cores and Secondary Windings                      to last capacitor layer through a bushing on
          The IMB type current transformers are flex-       the transformer tank (in the terminal box or in
          ible and can normally accommodate any             a separate box, depending on the IMB tank
          core configuration required.                      design). An advantage of the capacitive ter-
            Cores for metering purposes are usually         minal is that it can be used for checking the
          made of nickel alloy, which features low          condition of the insulation through dielectric
          losses (= high accuracy) and low saturation       loss angle (tan delta) measurement without
          levels.                                           disconnecting the primary terminals. The tap
            The protection cores are made of high-          can also be used for voltage indication, syn-
          grade oriented steel strip. Protection cores      chronizing or similar purpose, but the output
          with air gaps can be supplied for special         is limited by the low capacitance of the lay-
          applications.                                     ers.
                                                              The load connected must be less than
          The secondary winding consists of double          10 kohms and the tap must be grounded
          enameled copper wire, evenly distributed          when not in use.
D-1                                   Edition 5, 2008-03            ABB Instrument Transformers — Buyer’s Guide
Current Transformer	                                                                                            Design
IMB Design Features and Advantages
Climate                                           Seismic Strength
The transformers are designed for, and are        The IMB has a mechanically robust construc-
installed in, widely shifting conditions, from    tion, designed to withstand high demands
polar to desert climates all over the world.      of seismic acceleration without the need of
                                                  dampers.
Service Life
The IMB transformer is hermetically sealed
and the low and even voltage stress in the                       1                               8
primary insulation gives a reliable product
with expected service life of more than 30                   2                                   9
years. The IMB and its predecessors have
since the 1930s been supplied in more than                                                       10
160,000 units.
                                                             3
Expansion System
The expansion system, with a nitrogen gas
cushion, increases operating reliability and
minimizes the need of maintenance and
inspections. This type of expansion system
can be used in the IMB since the quartz filling
reduces the oil volume and a relatively large
gas volume minimizes pressure variations.                    4
  For higher rated currents an expansion
vessel with external cooling fins is used to
increase the cooling area and heat dissipa-
tion to the surrounding air.
  An expansion system with stainless steel
expansion bellows surrounded by the oil can
be quoted on request.
Quartz Filling
Minimizes the quantity of oil and provides a
mechanical support for the cores and prima-
ry winding during transport and in the event
of a short-circuit.
                                                         5
Flexibility
The IMB covers a wide range of primary cur-
rents up to 4,000 A. It can easily be adapted            6
for large and/or many cores by increasing the            7
volume of the tank.
                                                                                                 11
Resistance to Corrosion
The selected aluminum alloys give a high
degree of resistance to corrosion, without the               Current Transformer Type IMB
need of extra protection. Anodized parts for
IMB 36-170 kV can be offered on request.            1. Gas cushion                  6. Secondary terminal box
                                                    2. Oil filling unit (hidden)    7. Capacitive voltage tap
For use in extreme environments
                                                    3. Quartz filling                  (on request)
IMB >170 kV can be delivered with a protec-
                                                    4. Paper-insulated primary      8. Expansion vessel
tive painting.                                         conductor                    9. Oil sight glass
                                                    5. Cores/secondary             10. Primary terminal
                                                       windings                    11. Ground terminal
ABB Instrument Transformers — Buyer’s Guide          Edition 5, 2008-03                                            D-2
Design	                                                               Inductive Voltage Transformer
EMF Design Features and Advantages
          ABB’s inductive voltage transformers              former consists of an aluminum tank in which
          are intended for connection between               the winding and core are placed. The tank
          phase and ground in networks with                 consists of selected aluminum alloys that
                                                            give a high degree of resistance to corrosion,
          insulated or direct-grounded neutral              without the need of extra protection. Anod-
          points.                                           ized details can be offered on request. The
                                                            sealing system consists of O-ring gaskets.
          The design corresponds with the require-            The insulator, in its standard design, con-
          ments in the IEC and IEEE standards. Spe-         sists of high quality, brown glazed porcelain.
          cial design solutions to meet other standards     The voltage transformers can also be sup-
          and customer requirements are also pos-           plied with silicone rubber insulators.
          sible.
            The transformers are designed with a low        Expansion System
          flux density in the core and can often be         The EMF has an expansion vessel placed
          dimensioned for 190% of the rated voltage         on the top section of the porcelain. The EMF
          for more than 8 hours.                            has a closed expansion system, without
                                                            moving parts and with a nitrogen cushion,
          Primary Windings                                  that is compressed by the expansion of the
          The primary winding is designed as a multi-       oil. A prerequisite for this is that the quartz
          layer coil of double enameled wire with layer     sand filling reduces the oil volume, and the
          insulation of special paper. Both ends of the     use of a relatively large gas volume, which
          windings are connected to metal shields.          gives small pressure variations in the system.
          Secondary and Tertiary Windings                   Ferro-Resonance
          In its standard design the transformer has a      The design of the EMF notably counteracts
          secondary measurement winding and a ter-          the occurrence of ferro-resonance phenom-
          tiary winding for ground fault protection, but    ena:
          other configurations are available as required.     - The low flux in the core at the operating
          (2 secondary windings in a design according       voltage gives a large safety margin against
          to IEEE standard)                                 saturation if ferro-resonance oscillations
            The windings are designed with double           should occur.
          enameled wire and are insulated from the            - The flat magnetization curve gives a
          core and the primary winding with press-          smooth increase of core losses, which
          board (presspahn) and paper.                      results in an effective attenuation of the ferro-
            The windings can be equipped with addi-         resonance.
          tional terminals for other ratios (taps).           If the EMF transformer will be installed in a
                                                            network with a high risk for ferro-resonance,
          Core                                              it can, as a further safety precaution, be
          The transformer has a core of carefully se-       equipped with an extra damping burden, on
          lected material, to give a flat magnetization     a delta connected tertiary winding. See the
          curve. The core is over-dimensioned with a        figure below.
          very low flux at operating voltage.
          Impregnation
          Heating in a vacuum dries the windings. After
          assembly, all free space in the transformer
          (approximately 60%) is filled with clean and
          dry quartz grains. The assembled trans-
          former is vacuum-treated and impregnated
          with degassed mineral oil. The transformer
          is always delivered oil-filled and hermetically
          sealed.
          Tank and Insulator
          EMF 52-170: The lower section of the trans-             Damping of ferro-resonance
E-1                                   Edition 5, 2008-03            ABB Instrument Transformers — Buyer’s Guide
Inductive Voltage Transformer	                                                                           Design
EMF Design Features and Advantages
Climate
                                                1
These transformers are designed for, and are
installed in a wide range of shifting condi-
                                                                                           9
tions, from polar to desert climates all over
the world.                                      2
                                                                                           3
Service Life
The low and even voltage stresses in the
primary winding give a reliable product with
a long service life. EMF and its predecessors
have been supplied in more than 55,000                                                     4
units since the 1940s.
Expansion System                                5
The expansion system based on the nitrogen
cushion gives superior operating reliability
and minimizes the need of maintenance and
inspection of the transformer.
Quartz Filling
Minimizes the quantity of oil and provides a
                                                                                          10
mechanical support to the cores and primary
winding.                                                                                  11
                                                6
Resistance to Corrosion                                                                   12
EMF 52-170: The selected aluminum alloys
give a high degree of resistance to corrosion   7                                         13
without the need of extra protection. Anod-                                               14
ized details can be offered on request.         8
                                                                                          15
Seismic Strength
EMF is designed to withstand the high de-                Voltage transformer EMF 145
mands of seismic acceleration.
                                                1.   Primary terminal          9.   Expansion system
                                                2.   Oil level sight glass    10.   Paper insulation
                                                3.   Oil                      11.   Tank
                                                4.   Quartz filling           12.   Primary winding
                                                5.   Insulator                13.   Secondary windings
                                                6.   Lifting lug              14.   Core	
                                                7.   Secondary terminal box   15.   Ground connection
                                                8.   Neutral end terminal
ABB Instrument Transformers — Buyer’s Guide     Edition 5, 2008-03                                          E-2
Design	                                                             Capacitor Voltage Transformer
CPA and CPB Design Features
          ABB’s capacitor voltage transformers               The capacitor elements are designed with
          (CVTs) and coupling capacitors are               respect to the demands made by revenue
          intended for connection between                  metering, and their active component con-
                                                           sists of aluminum foil, insulated with paper/
          phase and ground in networks with                polypropylene film, impregnated by a PCB-
          isolated or grounded neutral.                    free synthetic oil, which has better insulat-
                                                           ing properties than normal mineral oil and is
          ABB offers a world-class CVT with superior       required for the mixed dielectric. Due to its
          ferro-resonance suppression and transient        unique proportions between paper and poly-
          response.                                        propylene film, this dielectric has proven itself
            The design corresponds to the require-         virtually insensitive to temperature changes.
          ments of IEC and ANSI and all national
          standards based on them. Special designs to      Electromagnetic Unit
          meet other standards and customer specifi-       The voltage divider and the electromagnetic
          cations are also available.                      unit are connected by internal bushings,
            Due to the design of the capacitor ele-        which is necessary for applications with high
          ments, described below, CPA and CPB              accuracy.
          are, with regard to temperature stability and      The EMU has double-enameled copper
          accuracy, equivalent to inductive voltage        windings and an iron core made of high qual-
          transformers.                                    ity steel sheet and is oil insulated in a hermet-
                                                           ically sealed aluminum tank with mineral oil.
          Difference and Composition of                      The primary coil is divided into a main
          CPA and CPB                                      winding, and a set of externally connected
          A capacitor voltage transformer with an elec-    trimming windings. The nominal intermediate
          tromagnetic unit (EMU), type EOA is called       voltage is approx. 22/√3 kV.
          CPA and with EMU, type EOB is called CPB.          The EOA and EOB have a reactor, which is
          The design of the EOA and EOB is basically       connected in series between the voltage di-
          identical, however the EOB has a larger tank     vider and the high voltage end of the primary
          and core, with space for larger windings,        winding. This reactor compensates for the
          making it capable of withstanding higher bur-    shift in phase angle caused by the capacitive
          dens.                                            voltage divider. The inductive reactances are
            Our standard voltage divider, type designa-    tuned individually on each transformer before
          tion CSA (high capacitance) or CSB (extra        accuracy testing.
          high capacitance) is mounted on an electro-
          magnetic unit (EMU), making a complete           For special applications, HVDC stations,
          capacitor voltage transformer.                   metering of harmonics, etc. there is another
            A coupling capacitor (without an EMU) is       type of EMU available, the EOAL. The EOAL
          called CCA (high capacitance) or CCB (extra      is basically an EOA but without a separate
          high capacitance).                               compensating reactor. In the EOAL, the
                                                           compensating reactor and transformer is
          Capacitor Voltage Divider                        combined into one piece, which gives several
          The capacitor voltage divider (CVD) consists     advantages.
          of one or two capacitor units, assembled on        The useful frequency range is wider since
          top of each other. Each unit contains a large    the internal resonance frequency of the
          number of series-connected, oil-insulated        EMU is higher than for an EOA or EOB. The
          capacitor elements. The units are completely     already excellent transient response of the
          filled with synthetic oil, which is kept under   EOA and EOB is improved even further.
          a slight overpressure by the design of the       However the EOAL is limited to burdens
          expansion system. O-ring seals are used          lower than the EOA.
          throughout the design.
F-1                                   Edition 5, 2008-03           ABB Instrument Transformers — Buyer’s Guide
Capacitor Voltage Transformer	                                                                                         Design
CPA and CPB Design Features
Climate
These transformers are designed for, and are                                                                8
installed in widely varying conditions, from
arctic to desert climates, on every continent.
                                                         1
Ferro-resonance
The low induction, combined with an effi-
cient damping circuit, gives a safe and stable
damping of ferro-resonance at all frequencies
and voltages up to the rated voltage factor;
see page I-2 or J-2.                                     2
Life Time
The low voltage stress within the capacitor
elements ensures a safe product with an
expected service life of more than 30 years.
Transient Properties
The high intermediate voltage and high ca-
pacitance result in good transient properties.
Adjustment
The adjustment windings for ratio adjust-
ment are accessible in the terminal box.
Power Line Carrier                                       3
                                                                                                            9
The CPA and CPB are designed with the
compensating reactor connected on the high
voltage side of the primary winding, providing           4                                                  10
the option of using higher frequencies (> 400                                                               11
                                                         5
kHz) for power line carrier transmission.
                                                         6
Stray Capacitance
The design with the compensating reactor                 7
on the high voltage side of the main winding
ensures less than 200 pF stray capacitance,                                                                 12
which is the most stringent requirement in
the IEC standard for carrier properties.
Stability                                                Capacitor Voltage Divider CSA or CSB
The CPA and CPB have a high Quality Fac-                      1.	   Expansion system
tor, as a result of their comparatively high                  2.	   Capacitor elements
capacitance, combined with a high interme-                    3.	   Intermediate voltage bushing
                                                              8.	   Primary terminal, flat 4-hole Al-pad
diate voltage.
                                                             10.	   Low voltage terminal (for carrier frequency use)
  The Quality Factor = Cequivalent x U²intermediate is
a measure of the accuracy stability and the              Electromagnetic unit EOA or EOB
transient response. The higher this factor, the               4.    Oil level glass
better the accuracy, and the better the                       5.    Compensating reactor
transient response.                                           6.    Ferroresonance damping circuit
                                                              7.    Primary and secondary windings
                                                              9.    Gas cushion
                                                             11.    Terminal box
                                                             12.    Core
ABB Instrument Transformers — Buyer’s Guide              Edition 5, 2008-03                                               F-2
                               s
          es r´
       ot e
      N omt
       us
      C
F-3       Edition 5, 2008-03   ABB Instrument Transformers — Buyer’s Guide
Outdoor Current Transformers	                                                                  IMB 36-800 kV
Tank Type Current Transformer IMB
For revenue metering and protection           The unique quartz filling minimizes the
in high voltage networks, the oil-paper       quantity of oil and provides a mechanical
insulated current transformer IMB is the      support to the cores and primary winding.
most sold transformer in the world.           Due to the low center of gravity the IMB
                                              is very suitable for areas with high seismic
•	Designed for widely shifting conditions,    activity.
  from polar to desert climate                From international studies we can see
•	Flexible tank type design allows large      that the IMB design is a reliable product
  and/or many cores                           (failure rate more than 4 times lower than
                                              average) with no need for regular main-
                                              tenance.
                                              Brief Performance Data
                                              Installation             Outdoor
                                              Design                   Tank (Hairpin) type
                                              Insulation               Oil-paper-quartz
                                              Highest voltage for      36-765 kV
                                              equipment
                                              Max primary current      Up to 4000 A
                                              Short-circuit current    Up to 63kA/1 sec
                                              Insulators               Porcelain
                                                                       On request silicon rubber
                                                                       (SIR) up to 550 kV
                                              Creepage distance        ≥ 25 mm/kV
                                                                       (Longer on request)
                                              Service conditions
                                               Ambient temperature     -40 °C to +40 °C
                                                                       (Others on request)
                                                Design altitude        Maximum 1000 m
                                                                       (Others on request)
ABB Instrument Transformers — Buyer’s Guide      Edition 5, 2008-03                                      G-1
IMB 36-800 kV	                                                               Outdoor Current Transformers
Tank Type Current Transformer IMB
                 Material                                           Maintenance
                 All external metal surfaces are made of an         The maintenance requirements are small, as
                 aluminum alloy, resistant to most known en-        IMB is hermetically sealed and designed for a
                 vironment factors. Bolts, nuts, etc. are made      service life of more than 30 years. Normally it
                 of acid-proof steel. The aluminum surfaces         is sufficient to check the oil level and that no
                 do not normally need painting. We can, how-        oil leakage has occurred. Tightening of the
                 ever, offer anodized or a protective paint.        primary connections should be checked oc-
                                                                    casionally to avoid overheating.
                 Creepage Distance                                    A more detailed check is recommended
                 As standard, IMB is offered with creepage          after 20-25 years of service. A manual for
                 distance ≥ 25 mm/kV. Longer creepage dis-          conditional monitoring can be supplied on
                 tance can be provided on request.                  request. This gives further guarantees for
                                                                    continued problem-free operation.
                 Mechanical Stability                                 The methods and the scope of the checks
                 The mechanical stability gives sufficient          depend greatly on the local conditions.
                 safety margins for normal wind loads and           Measurements of the dielectric losses of the
                 terminal forces. Static force on primary ter-      insulation (tan delta-measurement) and/or
                 minal may be up to 6,000 N in any direction.       oil sampling for dissolved gas analysis are
                 The IMB will also withstand most cases of          recommended check methods.
                 seismic stress.                                      Maintenance instructions are supplied with
                                                                    each delivery.
                 Rating Plates
                 Rating plates of stainless steel with engraved     Oil Sampling
                 text and the wiring diagram are mounted on         This is normally done through the oil-filling
                 the cover of the terminal box.                     terminal. If required, we (ABB, HV Compo-
                                                                    nents) can offer other solutions and equip-
                 Transport - Storage                                ment for oil sampling.
                 The IMB 36 - 145 is normally transported
                 (3-pack) and stored vertically. If horizontal      Impregnation Agent
                 transport is required this must be stated on       Oil of type Nynäs Nytro 10 XN (according to
                 the order.                                         IEC 60296 grade 2) is free of PCB and other
                   The IMB 170 - 800 is packed for horizontal       heavily toxic substances and has a low im-
                 transport (1-pack).                                pact on the environment.
                   Long-term storage of more than six months
                 should preferably be made vertically. If this is   Disposal
                 not practical please contact ABB.                  After separating the oil and quartz the oil can
                                                                    be burned in an appropriate installation. Oil
                 Arrival Inspection - Assembly                      residue in the quartz can be burnt, where
                 Please check the packaging and contents            after the quartz can be deposited.
                 with regard to transport damage on arrival. In       The disposal should be carried out in accor-
                 the event of damage to the goods, contact          dance with local legal provisions.
                 ABB for advice before further handling of the        The porcelain can, after it has been crush-
                 goods. Any damage should be documented             ed, be used as landfill.
                 (photographed).                                      The metals used in the transformer can
                   The transformer must be assembled on a           be recycled. To recycle the aluminum and
                 flat surface. An uneven surface can cause          copper in the windings, the oil-soaked paper
                 misalignment of the transformer, with the risk     insulation should be burnt.
                 of oil leakage.
                   Assembly instructions are provided with
                 each delivery.
G-2                                           Edition 5, 2008-03            ABB Instrument Transformers — Buyer’s Guide
Outdoor Current Transformers	                                                                                                                           IMB 36-800 kV
Tank Type Current Transformer IMB
Primary Terminals
IMB 36 – 800 is as standard equipped with
aluminum bar terminals, suitable for IEC and
NEMA specifications. Other customer speci-
fic solutions can be quoted on request.
  Maximum static and dynamic force on the
terminal is 6,000 and 8,400 N respectively.
Maximum torsional moment is 1,000 Nm.
Secondary Terminal Box and
Secondary Terminals                                                                    Dangerous Voltage
The transformer is equipped with a secon-
                                                                                       Must not be opened
                                                                                        while in service
dary terminal box, protection class IP 55,
according to IEC 60529. This box is
equipped with a detachable, undrilled gland
                                                                                                              1S1   1S2   1S3   1S4   2S1   2S2   2S3   2S4   3S1   3S2   3S3   3S4
plate, which on installation can be drilled for
                                                                                                              1S1   1S2   1S3   1S4   2S1   2S2   2S3   2S4   3S1   3S2   3S3   3S4
cable bushings.
 The terminal box is provided with a drain.
The standard terminal box can accommo-
date up to 30 terminals of the type PHOENIX                            Standard for IMB 36 - 170
10N for cross section <10 mm2. Other types
of terminals can be quoted on request.
 A larger terminal box with space for more
secondary terminals or other equipment,
such as heater or protective spark gaps, is
supplied when needed.
                                                                       Standard for IMB 245 - 800
Ground (Earth) Terminal
The transformer is normally equipped with
a ground clamp with a cap of nickel-plated
brass, for conductors 8-16 mm
(area: 50-200 mm2), which can be moved to
either mounting foot.
  A stainless steel bar, 80 x 145 x 8 mm, can       IMB 36-170                                              IMB 245-420
be quoted on request. The bar can be supp-
lied undrilled or drilled according to IEC or
NEMA standards.
  The ground terminal for the secondary
windings is located inside the terminal box.
                                                    IMB 420-550                                             IMB 420-800
ABB Instrument Transformers — Buyer’s Guide       Edition 5, 2008-03                                                                                                                  G-3
IMB 36-800 kV	                                                                                                 Outdoor Current Transformers
Design Data
 Maximum Rated Current and Short-time Current
  Type                     Normal              Cooling              Cooler             Maximum                Maximum                       Maximum
                           current             flanges                                 short-time             short-time                    dynamic
                                                                                        current                current                       current
                                                                                         1 sec                  3 sec
                              A                   A                   A                    kA                    kA                        kA peak value
  IMB 36-170                2400                   -                 3150                  63                    40                            170
                            1200                   -                 1500                  40                    40                            108
                             400                   -                   -                  31,5                   18                             85
                             150                   -                   -                   16                     9                             43
  IMB 245                   2000                 2400                3150                  63                    63                            170
                            1000                 1200                1500                  40                    40                            108
                             300                   -                   -                  31,5                   18                             85
                             150                   -                   -                   16                     9                             45
  IMB 300-420               2500                   -                 3150                  63                    63                            170
                            1200                   -                 1500                  40                    40                            108
  IMB 420-550               2500                   -                 4000                  63                    40                            170
                            1200                   -                 2000                  40                    40                            108
  IMB 800                     -                    -                 4000                  63                    40                            170
 Other types of primary conductors can be supplied on request
 Maximum continuous primary current = load factor x primary rated current related to a daily mean temperature that does not exceed 35 oC
 Primary winding can be designed with reconnection alternative between two or three primary rated currents with a ratio of 2:1 or 4:2:1
 Test Voltages IEC 60044-1
  Type              Highest voltage           AC voltage test,             Lightning             Switching              RIV test               Max RIV
                     for equipment               1 minute                   impulse               impulse               voltage                 level
                          (Um)                    wet/dry                  1.2/50 μs            250/2500 μs
                            kV                       kV                         kV                    kV                 kV Max.                  µV
  IMB 36                    36                     70/70                       170                     -                     -                     -
  IMB 72                  72,5                   140/140                      325                      -                     -                     -
  IMB 123                  123                   230/230                      550                      -                    78                   2500
  IMB 145                  145                   275/275                      650                      -                    92                   2500
  IMB 170                  170                   325/325                      750                      -                   108                   2500
  IMB 245                  245                   460/460                      1050                     -                   156                   2500
  IMB 300                  300                     -/460                      1050                   850                   191                   2500
  IMB 362                  362                     -/510                      1175                   950                   230                   2500
  IMB 420                  420                     -/630                      1425                  1050                   267                   2500
  IMB 550                  550                     -/680                      1550                  1175                   334                   2500
  IMB 800                  765                     -/975                      2100                  1550                   486                   2500
 Test voltages above applies at <1000 meters above sea level.
 Test Voltages IEEE C 57.13
  Type               Highest      Power frequency     AC-test Wet,   Lightning                                  Chopped           RIV test        Max RIV
                  system voltage applied voltage test   10 sec     impulse (BIL)                                impulse           voltage          level 1)
                                                                     1.2/50 µs
                           kV                         kV                      kV               kV Max.               kV               kV             µV
  IMB 36                  36.5                        70                      70                 200                230               21             125
  IMB 72                  72.5                       140                     140                 350                400               42             125
  IMB 123                 123                        230                     230                 550                630               78             250
  IMB 145                 145                        275                     275                 650                750               92             250
  IMB 170                 170                        325                     315                 750                865              108             250
  IMB 245                 245                        460                     445                1050               1210              156             250
  IMB 362                 362                        575                       -                1300               1500              230             250
  IMB 550                 550                        800                       -                1800               2070              334             500
 1) Test procedure according to IEC, 2) Test voltages above applies at <1000 meters above sea level
G-4                                                                   Edition 5, 2008-03                     ABB Instrument Transformers — Buyer’s Guide
Outdoor Current Transformers	                                                                                                 IMB 36-800 kV
Design Data
Nominal Flashover and Creepage Distance (Porcelain)
                      Normal creepage distance 25 mm/kV                              Long creepage distance 31 mm/kV
                                 (Min. values)                                                 (Min. values)
 Type               Flashover             Total              Protected           Flashover          Total         Protected
                    distance            creepage             creepage            distance         creepage        creepage
                                        distance             distance                             distance        distance
                        mm                   mm                  mm                  mm              mm              mm
 IMB 36                  -                    -                   -                  630            2248            1020
 IMB 72                  -                    -                   -                  630            2248            1020
 IMB 123               1120                 3625                1400                1120            4495            1860
 IMB 145               1120                 3625                1400                1120            4495            1860
 IMB 170                 -                    -                   -                 1330            5270            2200
 IMB 1701                -                    -                   -                 1600            6525            2740
 IMB 245               1915                 6740                2850                2265            8490            3685
 IMB 300               2265                 8250                3495                2715           10430            4645
 IMB 362               2715                10430                4645                3115           12480            5630
 IMB 420               3115                12480                5630                3635           14325            6465
 IMB 420               3220                11550                4800                3820           15280            6870
 IMB 550               3820                15280                6870                4715           18944            8340
 IMB 800               5220                18624                7950                  -               -               -
Note: Long creepage distance effects dimensions A, B, D (see dimensions)
1) 38 mm/kV for 170 kV system voltage and 45 mm/kV for 145 kV system voltage is available.
Standard accuracy Classes.
Current transformers of the type IMB are designed to comply with the following accuracy
classes. Other classes can be quoted on request.
                  IEC 60044 – 1                                        IEEE C57.13 / IEEE C57.13.6
      Class                    Application                            Class                  Application
        0.2                                                            0.15          Precision revenue metering
                      Precision revenue metering
        0.2S                                                           0.3           Standard revenue metering
        0.5           Standard revenue metering                        0.6                    Metering
        0.5S          Precision revenue metering                       1.2                    Metering
        1.0              Industrial grade meters                      C100                   Protection
        3.0                     Instruments                           C200                   Protection
        5.0                     Instruments                           C400                   Protection
        5P                       Protection                           C800                   Protection
        5PR                      Protection
        10P                      Protection
      10PR                       Protection
        PX                       Protection
        TPS                      Protection
        TPX                      Protection
        TPY                      Protection
ABB Instrument Transformers — Buyer’s Guide                            Edition 5, 2008-03                                               G-5
IMB 36-800 kV	                                                               Outdoor Current Transformers
Design Data
                 Burdens
                 Our current transformer IMB has a very flexible design allowing large burdens. However, it is
                 important to determine the real power consumption of connected meters and relays including
                 the cables. Unnecessary high burdens are often specified for modern equipment. Note that
                 the accuracy for the measuring core, according to IEC, can be outside the class limit if the
                 actual burden is below 25% of the rated burden.
                 Over-Voltage Protection Across Primary Winding
                 The voltage drop across the primary winding of a current transformer is normally very low.
                 At rated primary current it is only a couple of volts and at short-circuit current a few hundred
                 volts.
                   If a high frequency current or voltage wave passes through the primary winding can, due to
                 the winding inductance, high voltage drops occur. This is not dangerous for a current trans-
                 former with a single-turn primary winding, but for multi-turn primaries may it lead to dielectric
                 puncture between the primary turns.
                   It is therefore ABB’s practice to protect the primary winding in multi-turn designs with a
                 surge arrester connected in parallel with the primary.
                 Standard design of IMB current transformer is without surge arrester. Surge arrester of type
                 POLIM – C 1.8 will however be supplied automatically when needed.
G-6                                          Edition 5, 2008-03             ABB Instrument Transformers — Buyer’s Guide
Outdoor Current Transformers	                                                                                                  IMB 36-800 kV
Design and Shipping Data
Dimensions
                      A             B              C               D               E              F         G     H            J           K
 Type               Total        Height to     Ground Flashover Length                                  Dimen-              Height to Spac-
                   height         primary       level distance across                                   sion of             terminal  ing for
                                 terminal      height           primary                                 bottom                box    mounting
                                                                terminal                                 tank                          holes
                                                                bushing
                     mm            mm             mm               mm             mm          mm            mm    mm          mm           mm
 IMB 361            2000           1635           840              630            475             270       410   460          60          410
 IMB 721            2000           1635           840              630            475             270       410   460          60          410
 IMB 123   1
                    2490           2125           840              1120           475             270       410   460          60          410
 IMB 1451           2490           2125           840              1120           475             270       410   460          60          410
 IMB 1701           2700           2335           840              1330           475             270       410   460          60          410
 IMB 2452           3630           3045           965              1915           476             270       395   885         485          450
 IMB 3002           4150           3405           965              2265           491             270       395   885         485          450
 IMB 362   2
                    4600           3855           965              2715           491             270       395   885         485          450
 IMB 4202           5000           4255           965              3115           491             270       395   885         485          450
 IMB 4203           5505           4760           1365             3220           491             320       380   1040        783          500
 IMB 4204           5580           4790           1390             3220           526             360       410   1105        805          600
 IMB 5503           6105           5360           1365             3820           491             320       380   1040        783          500
 IMB 550   4
                    6180           5390           1390             3820           526             360       410   1105        805          600
 IMB 8004           8540           6790           1390             5220           526             360       410   1105        805          600
1) Standard tank, 2) Hexagonal tank, 3) Octagon tank, 4) HV tank                                                        E
                                                                                                                                           A
                                                                                                                                   D
          D
                                                                                                                                       B
                                          A
                                              B
                                                                                                                                   C
         C
                                                                                                                                25
                                                                       25
                             K                           K
               J
                                                   G         F
                                                                                                                       H
                                                                                                                       K
                                                                         K    H
                                                                                                                               F
               IMB 36 - 170                                                                       IMB 245
                                                                                                                               G
ABB Instrument Transformers — Buyer’s Guide                                  Edition 5, 2008-03                                                  G-7
IMB 36-800 kV	                                                       Outdoor Current Transformers
Design and Shipping Data
                      E
                                                    E
                          D
                                  A
                              B
                          C
                  J
          25
      K               K
                                                            D
                      H
                      K
                                                                B
                                                                    A
                          F
                          G
  IMB 300 - 420
                                                            C
                                  J
                                                                                                           30
                                                     K                                             K
                                                                                      K
                                            IMB 420 - 550
                                                                                               F       G
G-8                                   Edition 5, 2008-03            ABB Instrument Transformers — Buyer’s Guide
Outdoor Current Transformers	                                                           IMB 36-800 kV
Design and Shipping Data
                                  E
                                                      A
                                                  B
                                              C
                                                                                   30
                                 K                                         K
                                                          K
                          IMB 420 - 550                               F        G
ABB Instrument Transformers — Buyer’s Guide           Edition 5, 2008-03                          G-9
IMB 36-800 kV	                                                          Outdoor Current Transformers
Design and Shipping Data
                                            A
                                   D
                                       B
                                   C
                 J
                                                                                30
                         K                                              K
                                                                K
                         IMB 800                                    F       G
G-10                                       Edition 5, 2008-03       ABB Instrument Transformers — Buyer’s Guide
Outdoor Current Transformers	                                                                                              IMB 36-800 kV
Design and Shipping Data
Changes, special design of dimensions
                                   A, B, C                A                     A                   A
 Tank-type                        Increased        Cooling flange            Cooler            Three primary
                                 tank height                                                       ratios
                                    mm                   mm                    mm                   mm
 Standard tank                      210                   -                    255                   0
 Hexagon tank                    210 or 420              210                35 / 240 *)              -
 Octagon tank                       150                   -                    440                   -
 HV tank                         200 or 400               -                   400 **)                -
*) 35 mm for IMB 245, 240 mm for IMB 300 - 420
**) 400 mm for IMB 420 - 550, IMB 800 is always equipped with cooler
Shipping Data for Standard IMB
 Type               Net weight               Oil      Shipping                    Shipping                   Shipping
                     Incl. oil                         weight                   dimensions                    volume
                                                   1-pack/3-pack               1-pack/3-pack              1-pack/3-pack
                           kg                kg           kg                         LxWxH m                      m3
 IMB 36    1
                          420                45      550 / 1630          2.26x0.6x0.94 / 1.67x0.8x2.21          1.3 / 3
 IMB 721                  420                45      550 / 1630          2.26x0.6x0.94 / 1.67x0.8x2.21          1.3 / 3
 IMB 123       1
                          490                50      650 / 1850          2.75x0.6x0.94 / 1.67x0.8x2.7          1.5 / 3.6
 IMB 145       1
                          490                50      650 / 1850          2.75x0.6x0.94 / 1.67x0.8x2.7          1.5 / 3.6
 IMB 1701                 550                55         700 / -                2.96x0.6x0.94 / -                1.7 / -
 IMB 245       2
                          1100            110          1390 / -                3.82x1.06x1.02 / -               4.2 / -
 IMB 3002                 1400            170          1815 / -                4.76x1.08x1.10 / -               5.7 / -
 IMB 362       2
                          1500            180          1915 / -                4.76x1.08x1.10 / -               5.7 / -
 IMB 4202                 1600            190          2050 / -                5.21x1.08x1.10 / -               6.2 / -
 IMB 420       3
                          2500            300          3120 / -                5.82x1.23x1.22 / -               8.8 / -
 IMB 4204                 2600            290          3220 / -                5.74x1.06x1.47 / -               9.0 / -
 IMB 550       3
                          2800            330          3480 / -                6.42x1.23x1.22 / -               9.7 / -
 IMB 5504                 3500            510          4180 / -                6.34x1.06x1.47 / -               9.9 / -
 IMB 800       4
                          4200            670          6400 / -                8.71x1.06x1.47 / -              13.5 / -
1)	     Standard tank	
2)	     Hexagonal tank	
3)	     Octagon tank
4)	     HV tank
      IMB 36 - 145 is normally packed for vertical transport in a 3-pack.
      Vertical transport in a 1-pack can be quoted on request.
      IMB 170 - 800 is always packed for horizontal transport in 1-pack.
Additional weights
Weight indicated in table above is for standard IMB.
Additional weights may occur depending on requirements and configuration.
ABB Instrument Transformers — Buyer’s Guide                            Edition 5, 2008-03                                           G-11
IMB 36-800 kV	                                                                Outdoor Current Transformers
Reconnection
                 General
                 The current transformer can be reconnected to adapt for varying currents. The IMB type can
                 be delivered in a configuration that permits reconnecttion either on primary or
                 secondary side, or a combination of the two.
                   The advantage of primary reconnection is that the ampere-turns remains the same and
                 thereby the output (VA). The disadvantage is that the short-circuit capability will be reduced
                 for the lower ratio(s).
                 Primary Reconnection
                 Two primary ratios for two turns                 Two primary ratios, connected for one turn
                                            C1
                 C2                                                                                               C1
                                                                                 C2
                 Connection above is for the lower current            Connection above is for the higher current
                 Secondary Reconnection
                                P1                                                             P2
                                           S1       S2           S3     S4       S5
                 The unused taps on the reconnectable secondary winding must be left open.
                 If windings/cores are not used in a current transformer they must be short-circuited
                 between the highest ratio taps (e.g. S1 - S5) and shall be grounded.
                    Caution!
                    Never leave an unused secondary winding open.
                    Very high-induced voltages are generated across the terminals
                    and both the user and the transformer are subjected to danger.
G-12                                        Edition 5, 2008-03               ABB Instrument Transformers — Buyer’s Guide
Outdoor Voltage Transformers	                                                                 EMF 52-170 kV
Inductive Voltage Transformer EMF
For revenue metering and protection           The unique quartz filling minimizes the
in high voltage networks, the oil-paper       quantity of oil and allows a simple and reli-
insulated voltage transformer EMF is the      able expansion system.
most sold inductive voltage transformer       •	Low flux in the core at operating voltage
in the world.                                   gives a wide safety margin against
•	Designed for widely shifting conditions,      saturation and ferro-resonance.
  from polar to desert climates.
                                              Brief Performance Data
                                              Installation             Outdoor
                                              Design                   Inductive type
                                              Insulation               Oil-paper-quartz
                                              Highest voltage for      52-170 kV
                                              equipment
                                              Voltage factor (Vf)      Up to 1.9/8 hrs
                                              Insulators               Porcelain
                                                                       On request silicon
                                                                       rubber (SIR)
                                              Creepage distance        ≥ 25 mm/kV
                                                                       (Longer on request)
                                              Service conditions
                                               Ambient temperature     -40 °C to +40 °C
                                                                       (others on request)
                                                Design altitude        Maximum 1000 m
                                                                       (others on request)
ABB Instrument Transformers — Buyer’s Guide      Edition 5, 2008-03                                     H-1
EMF 52-170 kV	                                                              Outdoor Voltage Transformers
Inductive Voltage Transformer EMF
                 Material                                           Normally it is only necessary to check that
                 EMF 52-170: All external metal surfaces are      the oil level is correct, and that no oil leakage
                 made of an aluminum alloy, resistant to most     has occurred. The transformers are hermeti-
                 known environment factors. Bolts, nuts, etc.     cally sealed and therefore require no other
                 are made of acid-proof steel. The aluminum       inspection.
                 surfaces do not normally need painting. We         A comprehensive inspection is recommen-
                 can, however, offer a protective paint or        ded after 30 years. This provides increased
                 anodized.                                        safety and continued problem-free operation.
                                                                  The inspection methods and scope very sig-
                 Creepage Distance                                nificantly depending on the local conditions.
                 EMF is available as standard with normal or      As the primary winding is not capacitive
                 long creepage distances according to the         graded, the measurement of tan-delta gives
                 table on page J-4. Longer creepage distanc-      no significant result. Therefore oil sampling
                 es can be quoted on request.                     for dissolved gas analysis is recommended
                                                                  for checking the insulation.
                 Mechanical Stability
                 The mechanical stability gives a sufficient      Maintenance instructions are supplied with
                 safety margin for normal wind loads and          each delivery.
                 stress from conductors. EMF can also with-
                 stand high seismic forces.                       ABB, High Voltage Products is at your dis-
                                                                  posal for discussions and advice.
                 Rating Plates
                 Rating plates of stainless steel, with engra-    Impregnation Agent
                 ved text and wiring diagrams are mounted         Oil of type Nynäs Nytro 10 XN
                 on the transformer enclosure.                    (according to IEC 296 grade 2) is free of PCB
                                                                  and other heavily toxic substances and has a
                 Arrival Inspection - Assembly                    low impact on the environment.
                 Please check the packaging and contents
                 with regard to transport damage on arrival. In   Disposal
                 the event of damage to the goods, contact        After separating the oil and quartz the oil can
                 ABB for advice, before further handling of the   be burned in an appropriate installation. Oil
                 goods. Any damage should be documented           residue in the quartz can be burnt, where
                 (photographed).                                  after the quartz can be deposited.
                   The transformer must be assembled on a           The disposal should be carried out in accor-
                 flat surface. An uneven surface can cause        dance with local legal provisions.
                 misalignment of the transformer, with the risk     The porcelain can, after it has been
                 of oil leakage.                                  crushed, be used as landfill.
                                                                    The metals used in the transformer can be
                 Assembly instructions are provided with each     recycled. To recycle the copper in the wind-
                 delivery.                                        ings, the oil-soaked paper insulation should
                                                                  be burnt.
                 Maintenance
                 Maintenance requirements are insignificant
                 as EMF is designed for a service life of more
                 than 30 years.
H-2                                          Edition 5, 2008-03           ABB Instrument Transformers — Buyer’s Guide
Outdoor Voltage Transformers	                                                               EMF 52-170 kV
Inductive Voltage Transformer EMF
Primary Terminals
EMF 52-170 is as standard equipped with an
aluminum bar terminal, suitable for IEC and
NEMA specifications.
The primary terminal is a voltage terminal and
should therefore, according to standards, with-
stand static force of 1,000 N for Um
(system voltage) 123 – 170 kV and 500 N for
lower voltages. Withstand dynamic force is
1,400 and 700 N respectively.
                                                                          EMF 52-170
Secondary Terminal Box and
Secondary Terminals
The terminal box for the secondary winding ter-
minal is mounted on the transformer enclosure.
As standard the terminal box is manufactured of
corrosion resistant, cast aluminum.
 This box is equipped with a detachable,
undrilled gland plate, which on installation can
be drilled for cable bushings. It can, on request,
be quoted with cable glands according to the                                  EMF 52-84
customer’s specification.
 The terminal box is provided with a drain.
 EMF 52-170: Secondary terminals accept
wires with cross-sections up to 10 mm2.
Protection class for the terminal box is IP 55.
                                                                          EMF 123-170
Ground (Earth) Connections
The transformer is normally equipped with a
ground terminal with a clamp of nickel-plated
brass. For conductors Ø=5-16 mm
(area 20-200 mm2), see the figure.
It can also be quoted on request with a connec-
tion for a ground bar.
Grounding of the secondary circuits is made
inside the terminal box.
                                                                  EMF 52-84               EMF 123-170
ABB Instrument Transformers — Buyer’s Guide          Edition 5, 2008-03                                 H-3
EMF 52-170 kV	                                                                                        Outdoor Voltage Transformers
Design Data
             Nominal Flash-Over and Creepage Distance
                                                    Normal porcelain                              Porcelain with long creepage distance
                                                   (min. nom. values)                                       (min. nom. values)
              Type                  Flash-over            Creepage           Protected           Flash-over         Creepage               Protected
                                     distance             distance           creepage             distance          distance               creepage
                                                                             distance                                                      distance
                                         mm                  mm                  mm                  mm                  mm                  mm
              EMF 52                     630                 2248                1020                 -                   -                      -
              EMF 72                     630                 2248                1020                 -                   -                      -
              EMF 84                     630                 2248                1020                 -                   -                      -
              EMF 123                   1200                 3625                1400                 -                   -                      -
              EMF 145                   1200                 3625                1400               1330                 5270                2200
              EMF 170                   1330                 5270                2200                 -                   -                      -
             Test Voltages IEC 60044-2, (SS-EN 60044-2)
              Type                  Highest voltage                1min                    LIWL                 RIV test               RIV level
                                     for equipment                wet/dry                1.2/50 µs              voltage
                                          (Um)
                                             kV                       kV                    kV                    kV Max.                    µV
              EMF 52                         52                       95                    250                     30                      125
              EMF 72                        72.5                     140                    325                     46                      125
              EMF 84                         84                      150                    380                     54                      125
              EMF 123                       123                      230                    550                     78                      2500
              EMF 145                       145                      275                    650                     92                      2500
              EMF 170                       170                      325                    750                    108                      2500
             Test voltages above are valid for altitudes <1000 meters above sea level.
             Test Voltages IEEE C 57.13 (CAN 3 – C 131 – M83)
              Type                          Highest voltage                   AC test                   AC test                         BIL
                                             for equipment                   dry, 1 min                wet, 10 sec                   1.2/50 µs
                                                  (Um)
                                                     kV                           kV                         kV                       kV Max.
              EMF 52                                 52                           95                         95                            250
              EMF 72                                72.5                         140                        175                            350
              EMF 123                             121 (123)                      230                        230                            550
              EMF 145                                145                         275                        275                            650
              EMF 170                             169 (170)                      325                      315 (325)                        750
             Values within brackets refer to CAN 3-C13.1-M79. Test voltages above are valid for altitudes < 1000 meters above sea level.
H-4                                                         Edition 5, 2008-03                      ABB Instrument Transformers — Buyer’s Guide
Outdoor Voltage Transformers	                                                                                                             EMF 52-170 kV
Design Data According to IEC
Secondary Voltages and Burdens
 Standards                                   International IEC 60044-2, (IEC 186)
                                             Swedish Standard SS-EN 60044-2
 Rated data at 50 or 60 Hz,                  The transformer normally has one or two windings for
 Voltage factor 1.5 or 1.9                   continuous load and one residual voltage winding. Other
                                             configurations can be quoted according to requirements.
Standard Accuracy Classes and Burdens
 According to IEC
   50 VA class 0.2                                                    100 VA class 3P
 100 VA class 0.5                                                     100 VA class 3P
 150 VA class 1.0                                                     100 VA class 3P
 For lower or higher burdens please contact us.
The standards state as standard values for rated voltage factor 1.5/30 sec. for effectively earthed systems, 1.9/30 sec. for systems
without effective earthing with automatic earth fault tripping and 1.9/8 hrs for systems with insulated neutral point without automatic
earth fault tripping.
 Since the residual voltage winding is not loaded except during a fault, the effect of its load
 on the accuracy of the other windings is disregarded in accordance with IEC.
 Please note that modern meters and protection require much lower burdens
 than those above, and to achive best accuracy you should avoid specifying
 burdens higher than necessary; see page B-3.
ABB Instrument Transformers — Buyer’s Guide                                 Edition 5, 2008-03                                                      H-5
EMF 52-170	                                                               Outdoor Voltage Transformers
Design Data According to IEEE and CAN3
              Secondary Voltages and Burdens              		
               Standards                          American IEEE C57.13-1993
                                                  Canadian CAN3-C13-M83
               Rated data at 60 Hz,               The transformer normally has one or two secondary
               Voltage factor 1.4                 windings for continuous load (Y-connected).
              Standard Accuracy Classes and Burdens
               According to IEEE and CAN3
               0.3 WXY                          0.6 WXYZ                        1.2/3P WXYZ
               For lower or higher burdens please contact us.
               Rated burdens
               W = 12.5 VA power factor 0.1
               X = 25 VA power factor 0.7
               Y = 75 VA power factor 0.85
               YY = 150 VA power factor 0.85
               Z = 200 VA power factor 0.85
               ZZ = 400 VA power factor 0.85
              Example of turn ratio:
              350-600:1 means one secondary winding with the ratio 350:1 and one tertiary winding ratio 600:1
              350/600:1:1 means one secondary winding and one tertiary winding both with taps for ratios 350:1
              and 600:1
              Protective classes according to CAN (1P, 2P, 3P) can be quoted on request.
              Voltage factor 1.9 according to CAN can be quoted on request.
H-6                                      Edition 5, 2008-03             ABB Instrument Transformers — Buyer’s Guide
Outdoor Voltage Transformers	                                                                                  EMF 52-170 kV
Design Data - Dimensions
Voltage Transformers EMF
                  A              B            C                D                  E              F
 Type           Total     Flash-over      Height to       Fixing hole    Ground level   Expansion
               height      distance     terminal box      dimensions        height    vessel diameter
                mm            mm              mm             mm                  mm             mm
EMF 52          1464          630             114         335 x 335              540            324
EMF 72          1464          630             114         335 x 335              540            324
EMF 84          1464          630             114         335 x 335              540            324
EMF 123         2360         1200             65          410 x 410              760            416
EMF 145         2360         1200             65          410 x 410              760            416
EMF 170         2490         1330             65          410 x 410              760            416
                                               135
                             B
                                                      A
                             E
    C
                                              20 mm
                   D                     D
                    EMF 52-84                                                          EMF 123-170
             Note: Primary terminal will                                         Note: Primary terminal will
                be mounted at site                                                  be mounted at site
ABB Instrument Transformers — Buyer’s Guide                 Edition 5, 2008-03                                           H-7
EMF 52-170	                                                                    Outdoor Voltage Transformers
Design Data - Shipping Data
              Voltage Transformers EMF
              Type          Net weight          Oil      Shipping weight   Shipping dimensions     Shipping volume
                              incl. oil                      3-pack               3-pack               3-pack
                         Porcelain insulator                                    LxWxH
                                  kg             kg                 kg               m                     m3
              EMF 52             300             40            1040            1.6 x 0.9 x 1.7             2.5
              EMF 72             300             40            1040            1.6 x 0.9 x 1.7             2.5
              EMF 84             300             40            1040            1.6 x 0.9 x 1.7             2.5
              EMF 123            570             80            1975              2 x 1 x 2.6               5.2
              EMF 145            570             80            1975              2 x 1 x 2.6               5.2
              EMF 170            610             83            2130              2 x 1 x 2.7               5.4
               EMF 52 - 84 must not be tilted more than 60° during transport and storage.
               Signs are placed on the transformer’s rating plate.
               EMF 123 - 170 is normally packed for vertical transport (3-pack).
               However, it can be transported in a horizontal position and is available on request for horizontal
               transport (1-pack).
H-8                                            Edition 5, 2008-03            ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                CPA and CPB 72-800 kV
and Coupling Capacitors	                                                               CCA and CCB 72-550 kV
Capacitor Voltage Transformer CPA and CPB (IEC)
For revenue metering and protection in        The CPA and CPB have a high Quality
high voltage networks. The overall design     Factor, as a result of their comparatively
of the CVT and the mixed dielectric in the    high capacitance, combined with a high
capacitor elements have proven to be          intermediate voltage.
insensitive to temperature changes, and       The Quality Factor = Cequivalent x U²intermediate
the accuracy is equivalent to inductive       is a measure of the accuracy stability. The
voltage transformers. These CVTs are          higher this factor, the better the accuracy,
designed for widely shifting conditions,      and the better the transient response.
from polar to desert climates.
                                              Brief Performance Data
                                              Installation                Outdoor
                                              Design                      Capacitor type
                                                                          Meets IEC standards
                                              Insulation
                                                CVD                       Aluminum-foil/paper/ poly-
                                                                          propylene film, synthetic oil
                                                EMU                       Paper - mineral oil
                                              Highest voltage for         72-765 kV
                                              equipment
                                              Voltage factor (Vf)         Up to 1.9/8 hrs
                                              Insulators                  Porcelain - on request silicon
                                                                          rubber (SIR)
                                              Creepage distance           ≥ 25 mm/kV
                                                                          (longer on request)
                                              Service conditions
                                               Ambient temperature        -40 °C to +40 °C
                                                                          (others on request)
                                                Design altitude           Maximum 1000 m
                                                                          (others on request)
ABB Instrument Transformers — Buyer’s Guide       Edition 5, 2008-03                                       I-1
Outdoor Capacitor Voltage Transformers	                                              CPA and CPB 72-800 kV
and Coupling Capacitors	                                                             CCA and CCB 72-550 kV
Capacitor Voltage Transformer CPA and CPB (IEC)
                   Material                                             The CPA and CPB use a damping circuit,
                   All external metal surfaces are made of an         connected in parallel with one of the second-
                   aluminum alloy, resistant to most known en-        ary windings (see diagram on page I-11). The
                   vironment factors. Bolts, nuts, etc. are made      damping circuit consists of a reactor with an
                   of acid-proof steel. The aluminum surfaces         iron core, and an oil-cooled resistor in series.
                   do not normally need painting. We can, how-        Under normal use, the iron core of the damp-
                   ever, offer a protective paint, normally light     ing reactor is not saturated, yielding high
                   gray.                                              impedance, so that practically no current is
                                                                      flowing through this circuit.
                   Creepage Distance                                    The damping circuit has two bridged termi-
                   As standard, CPA and CPB are offered with          nals; d1- d2, behind a sealed covering hood
                   creepage distance 25 mm/kV. Longer creep-          in the terminal box. In particular cases and
                   age distances can be offered on request.           after agreement this bridge can be opened,
                                                                      to check that the circuit is intact, by resis-
                   Silicone Rubber Insulators                         tance measurement.
                   The complete CVT and CC range is available
                   with silicone rubber (SIR) insulators. Our SIR     Ratio Adjustment
                   insulators are produced with a patented heli-      The transformer of the electromagnetic unit
                   cal extrusion molding technique, which gives       has five adjustment windings on the earth
                   completely joint-free insulators with outstand-    side of the primary winding. The numbers of
                   ing performance. All CVTs and CCs with this        turns of these windings have been chosen
                   type of insulators have the same high creep-       so that the ratio can be adjusted ±6.05% in
                   age distance, 25 mm/kV, as porcelain.              steps of 0.05%. These windings are external-
                                                                      ly accessible behind a sealed covering hood
                   Mechanical Stability                               in the secondary terminal box. The CVT is
                   The mechanical stability gives sufficient a        delivered adjusted for a specified burden and
                   safety margin for normal wind loads and con-       class, and normally no further adjustment is
                   ductor forces. In most cases, with help of the     necessary.
                   optional top plate, it is also possible to mount     If needed, the adjustment windings enable
                   line traps for power line carrier equipment        exchange of the voltage divider on site, and
                   directly on top of the capacitor divider. The      readjust the transformer for the new combi-
                   CPA and CPB will also withstand most cases         nation of voltage divider/electromagnetic unit.
                   of seismic stress.
                                                                      Rating Plates
                   Ferroresonance Damping Circuit                     Corrosion resistant rating plates with text and
                   All CVTs need to incorporate some kind of          wiring diagrams are used. General data can
                   ferro-resonance damping, since the capaci-         be found on the door of the terminal box,
                   tance in the voltage divider, in series with the   connection diagrams and secondary winding
                   inductance of the transformer and the series       data on the inside.
                   reactor, constitutes a tuned resonance cir-         The capacitors are marked with measured
                   cuit.                                              capacitance on the insulator(s) base flange.
                     This circuit can be brought into reso-
                   nance, that may saturate the iron core of the      Power Line Carrier (PLC)
                   transformer by various disturbances in the         As an option all CVTs can be equipped with
                   network. This phenomenon can also over-            Carrier Accessories. Modern PLC equip-
                   heat the electro-magnetic unit, or lead to         ments are adapted for a wide range of cou-
                   insulation breakdown.                              pling capacitors. None specific capacitance
                                                                      is required. Only minimum capacitance must
                                                                      be specified due to choice of frequency.
I-2                                             Edition 5, 2008-03            ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                 CPA and CPB 72-800 kV
and Coupling Capacitors	                                                                CCA and CCB 72-550 kV
Capacitor Voltage Transformer CPA and CPB (IEC)
Primary Terminal
CPA and CPB are normally delivered with a flat 4-hole
aluminum pad, suitable for bolts C-C from 40 to
50 mm and for connecting normal aluminum cable
clamps. Other primary terminals can be offered on
request, such as a round aluminum studs, Ø=30 mm.
  Maximum static force on the primary terminal is
1,500 N in all directions. Maximum dynamic force is
2,100 N
(Static/dynamic 1,300/1,800 N for CPB 800)
Secondary Terminal Box and
Secondary Terminals
The transformer is equipped with a
secondary terminal box, protection                                                                L
class IP 55. This box is equipped with
a detachable, undrilled gland plate,
which on installation can be drilled for
cable bushings. The box is provided
with a drain.
The transformer can also be equipped
with a larger terminal box, with space
for fuses or micro circuit breakers and                                                               A
/ or protection for power line carrier
equipment.
The secondary terminals normally consist of Phoenix
standard terminal blocks for wire cross-section 10
                                                                          Standard Terminal Box
                                                                 Without Carrier Accessories and Fuses
mm². In the terminal box are also terminals (d1-d2) for
damping circuit, terminals for the adjustment windings
(B1 to B10) and the capacitor low voltage terminal ”L”
(for power line carrier equipment). Terminals d1 - d2
and B1 - B10 are intended for factory settings and
thus located behind a sealed covering hood to pre-
vent inadvertent reconnection.
  The ”L” terminal must always be grounded
  if no carrier equipment is connected.
Ground Terminals
The transformer is normally equipped with an ground
clamp with a cap of nickel-plated brass, for conduc-
tors 8-16 mm (area 50-200 mm2), which can be
moved to either mounting foot.
A stainless steel bar, 80 x 145 x 8 mm, can be quoted
on request. The bar can be supplied undrilled or
drilled according to IEC or NEMA standards. Ground-
ing terminals for the secondary circuits are placed
inside the terminal box.
ABB Instrument Transformers — Buyer’s Guide          Edition 5, 2008-03                                    I-3
Outdoor Capacitor Voltage Transformers	                                               CPA and CPB 72-800 kV
and Coupling Capacitors	                                                              CCA and CCB 72-550 kV
Installation and Maintenance (IEC)
                   Unpacking                                           • Control measurements of the EMU
                   Please check the crates and their contents          A simple test is to measure the insulation
                   for damage during transportation upon re-           resistance in mega-ohms (max. test voltage
                   ceipt. Should there be any damage, please           1,000 VDC) of the secondary windings.
                   contact ABB for advice before the goods               Since the high voltage winding of the trans-
                   are handled further. Any damage should be           former is not capacitively graded, a measure-
                   documented (photographed).                          ment of the loss angle (tan delta) will give no
                                                                       significant result.
                   Assembly                                              What is possible, however, is to take an oil
                   The electromagnetic unit and the capacitor          sample, for gas chromatography analysis
                   voltage divider are delivered as one unit for       from the electromagnetic unit to assess its
                   CVTs with system voltages up to 245 kV.             condition.
                     CVTs with higher system voltages, having            The tank of the electromagnetic unit can,
                   more than one CVD part, are delivered with          on request, be equipped with a sampling
                   the bottom unit of the CVD assembled onto           valve, and we can deliver suitable sampling
                   the EMU.                                            equipment. A simpler method is to take the
                     The EMU, with the bottom CVD unit should          oil sample from the oil-filling hole. Sampling
                   be installed first, before the top part(s) of the   intervals will vary, depending on service con-
                   CVD is (are) mounted in place. Lifting instruc-     ditions; generally, no oil analysis should be
                   tions are included in each package.                 necessary during the first 20 years of service.
                     Check that the top and the bottom insulator
                   have the same serial number (for CVDs with          Environmental Aspects
                   more than one capacitor unit).                      Impregnant
                                                                       Both Faradol 810 (the synthetic oil in the
                   Maintenance                                         voltage dividers), and Nynäs NYTRO 10 XN
                   The CPA and CPB are designed for a service          (the standard transformer oil in the electro-
                   life of more than 30 years, and are practically     magnetic unit) are free from PCB and other
                   maintenance-free. We recommend however              strongly harmful substances, and pose a low
                   the following controls and measures.                impact to the environment.
                   • Visual check                                      Destruction
                   We recommend a periodic inspection, to              After draining the oils, they can be burnt in
                   check for oil leakages and also to inspect the      an appropriate plant. In this respect, Faradol
                   insulator for collection of dirt.                   has similar combustion properties as normal
                                                                       mineral oil.
                   • Control measurements of the CVD                     The disposal should be carried out in accor-
                   Since the voltage dividers are permanently          dance with local legal provisions, laws and
                   sealed under slight over pressure it is not         regulations.
                   possible to take oil samples from them.               The porcelain can be deposited after it has
                     Under normal service conditions, no notice-       been crushed.
                   able ageing will occur within the capacitors          The metals in the electromagnetic unit and
                   (verified by ageing tests). However discrepan-      the housings of the voltage divider can be
                   cies between the secondary voltages in par-         recycled. Aluminum parts are labeled with
                   allel phases can be an indication of a fault in     material specifications. In order to recycle
                   a capacitor part of one of the voltage trans-       the copper in the windings, the oil-saturated
                   formers, which is why such a comparison             paper insulation should be burnt.
                   is recommended. In such a case a further              The aluminum in the capacitor elements,
                   measurement of the capacitance value is rec-        with their combination of foil, paper and
                   ommended. Readings can be taken between             polypropylene film, can be recycled after the
                   the top and the ”L” terminal in the secondary       insulation has been burnt; the plastic film will
                   terminal box.                                       not emit any harmful substances during this
                                                                       process.
I-4                                             Edition 5, 2008-03             ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                                          CPA and CPB 72-800 kV
and Coupling Capacitors	                                                                                         CCA and CCB 72-550 kV
Design Data According to IEC
Number of capacitor units, capacitance, flash-over and creepage distance
(CSA, standard capacitance) (also valid for CCA)
                                                                       Normal porcelain (min. nom. values)
                                                                                                                          Porcelain with extra
 Type                  Number of            Standard            Flashover            Creepage      Protected creepage        long creepage
                     capacitor units       capacitance          distance             distance           distance                distance
                                                                                                                           (min. nom. values)
                                           pF (+10; -5%)             mm                mm                   mm
CPA/CPB 72                   1                 23500                 700               2200                 890
CPA/CPB 123                  1                 14500                 980               3160                1282
CPA/CPB 145                  1                 12600                1190               3880                1545
CPA/CPB 170                  1                 10500                1400               4600                1835           Offered on request.
                                                                                                                          Normally porcelain
CPA/CPB 245                  1                  7500                1960               6510                2610
                                                                                                                           as for the nearest
CPA/CPB 300                  2                  6300                2380               7760                3090              higher voltage
CPA/CPB 362                  2                  5200                2800               9200                3670
CPA/CPB 420                  2                  4700                3220              10630                4250
CPA/CPB 550                  2                  3500                4200              13980                5610
Number of capacitor units, capacitance, flash-over and creepage distance
(CSB, extra high capacitance) (also valid for CCB)
                                                                           Normal porcelain (min. nom. values)
                                                                                                                          Porcelain with extra
 Type                  Number of             Extra high         Flashover            Creepage        Protected creepage      long creepage
                     capacitor units        capacitance         distance             distance             distance              distance
                                                                                                                           (min. nom. values)
                                           pF (+10; -5%)             mm                mm                   mm
 CPA/CPB 145                  1                 18900               1400               4600                 1835
 CPA/CPB 170                  1                 15700               1400               4600                 1835
 CPA/CPB 245                  1                 11300               2100               6990                 2805
                                                                                                                          Offered on request.
 CPA/CPB 300                  2                 9400                2800               9200                 3670          Normally porcelain
 CPA/CPB 362                  2                 7900                2800               9200                 3670           as for the nearest
                                                                                                                             higher voltage
 CPA/CPB 420                  2                 7100                3220              10630                 4250
 CPA/CPB 550                  2                 5200                4200              13980                 5610
 -----/CPB 800                3                 3500                6300              20970                 8415
Test Voltages: IEC 60044-5
        Type         Highest voltage         1min            LIWL           Switching         PD Test      Max. PD     RIV test    RIV level
                      for equipment         wet/dry        1.2/50 µs         impulse          voltage       level      voltage
                           (Um)                                            250/2500 µs
                             kV                 kV             kV               kV              kV           pC *)     kV Max.         µV
  CPA/CPB 72                72.5            140/140           325                -            1.2 x Um           10        -            -
 CPA/CPB 123                123             230/230           550                -            1.2 x Um           10       78          2500
 CPA/CPB 145                145             275/275           650                -            1.2 x Um           10       92          2500
 CPA/CPB 170                170             325/325           750                -            1.2 x Um           10       108         2500
 CPA/CPB 245                245             460/460           1050               -            1.2 x Um           10       156         2500
 CPA/CPB 300                300               -/460           1050             850            1.2 x Um           10       191         2500
 CPA/CPB 362                362               -/510           1175             950            1.2 x Um           10       230         2500
 CPA/CPB 420                420               -/630           1425            1050              Um               10       267         2500
 CPA/CPB 550                525               -/680           1550            1175              Um               10       349         2500
 -----/CPB 800              765               -/975           2100            1425              Um               10       508         2500
Test voltages above are valid for altitudes < 1000 meters above sea level. *) 5 pC at test voltage 1.2 x Um/√3
ABB Instrument Transformers — Buyer’s Guide                       Edition 5, 2008-03                                                         I-5
Outdoor Capacitor Voltage Transformers	                                                                       CPA and CPB 72-800 kV
and Coupling Capacitors	                                                                                      CCA and CCB 72-550 kV
Design Data According to IEC
                   Secondary Voltage and Burdens
                   Standards IEC 60044-5
                   Rated data at 50 or 60 Hz, Voltage factor 1.5 or 1.9
                   The transformer normally has one or two windings for continuous load, and one earth-fault
                   winding. Other configurations can be offered according to requirements.
                   Approximate Maximum Total Burdens in VA
                                                                          Measuring winding
                       Highest class                        Voltage factor 1.5*)                                   Voltage factor 1.9*)
                                                         CPA                        CPB                        CPA                         CPB
                              0.2                         70                        120                          40                        100
                              0.5                        200                         400                        125                        300
                         1.0/3P T1                       400                         400                        200                        400
                                                  Earth-fault winding, irrespective of the voltage factor
                        3P T1/6P T1                      100                         100                        100                        100
                   *) The IEC standards state as standard values for effectively earthed systems 1.5/30 sec. For systems without effective earthing with
                   automatic earth fault tripping rated voltage factor 1.9/30 sec., and 1.9/8 hrs for systems with insulated neutral point without automatic
                   earth fault tripping.
                   The above values may, depending on configuration, be extended by the use of an extra-high capacitance voltage
                   divider (CSB). Please consult us for details.
                   The above values are total maximum values for                           Since the residual voltage winding is not
                   the secondary winding(s), voltage 100/√3 or                           loaded except during a fault, the effect of its
                   110/√3 V and one or no residual voltage wind-                         load on the accuracy of the other windings is
                   ing, class 3P, intended for connection in open                        disregarded in accordance with IEC.
                   delta, voltage 100 or 110 (100/3 or 110/3) V.                           Stated values should only be considered as
                     For other configurations please consult us.                         maximum values. Please note that modern
                   If the transformer has more than one contin-                          meters and protection require much lower
                   uously loaded winding, possibly with different                        burdens than those above, and to achieve
                   classes, the table above must be applied to                           best accuracy you should avoid specifying
                   the sum of these burdens and the most                                 burdens higher than necessary: see page
                   accurate class.                                                       B-3.
I-6                                                       Edition 5, 2008-03                         ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                                              CPA and CPB 72-800 kV
and Coupling Capacitors	                                                                                             CCA and CCB 72-550 kV
Dimensions
Capacitor Voltage Transformer CPA
                                                      A                        B                C             D               E
 Type                     Number of                 Total              Flashover            Height to    Mounting hole   Ground level
                        capacitor units            height              distance              flange*)      distance         height
                                                     mm                       mm               mm            mm              mm
 CPA 72                          1                  1660                  700                  340           335             740
 CPA 123                         1                  1940                  980                  340           335             740
 CPA 145                         1                  2150**)              1190**)               340           335             740
 CPA 170                         1                  2360                  1400                 340           335             740
 CPA 245                         1                  2920**)               1960**)              340           335             740
 CPA 300                         2                  3690**)               2380**)              340           335             740
 CPA 362                         2                  4110                  2800                 340           335             740
 CPA 420                         2                  4530                  3220                 340           335             740
 CPA 550                         2                  5510                  4200                 340           335             740
* Valid for standard terminal box only. ** Valid for high capacitance only.
Capacitor Voltage Transformer CPB
                                                        A                       B                C             D               E
 Type                     Number of                   Total              Flashover           Height to   Mounting hole   Ground level
                        capacitor units              height              distance             flange*)     distance         height
                                                      mm                       mm               mm            mm              mm
 CPB 72                          1                   1715                      700              390           410            790
 CPB 123                         1                   1995                      980              390           410            790
 CPB 145                         1                   2205**)                  1190**)           390           410            790
 CPB 170                         1                   2415                     1400              390           410            790
 CPB 245                         1                   2975**)                  1960**)           390           410            790
 CPB 300                         2                   3745**)                  2380**)           390           410            790
 CPB 362                         2                   4165                     2800              390           410            790
 CPB 420                         2                   4585                     3220              390           410            790
 CPB 550                         2                   5565                     4200              390           410            790
 CPB 800                         3                   8015                     6300              390           410            790
*) Valid for standard terminal box only.
**) Valid for high capacitance only.
                                                   CPA/CPB
ABB Instrument Transformers — Buyer’s Guide                                     Edition 5, 2008-03                                      I-7
Outdoor Capacitor Voltage Transformers	                                                 CPA and CPB 72-800 kV
and Coupling Capacitors	                                                                CCA and CCB 72-550 kV
Design Data and Dimensions
              Coupling Capacitors
              Coupling capacitors types CCA (standard capacitance) and CCB (extra high capacitance) are in-
              tended for power line carrier applications. The insulator and capacitor design are identical to
              capacitor voltage dividers type CSA and CSB, but without an intermediate voltage terminal.
              Previous descriptions of the voltage divider are therefore applicable for the coupling capacitors.
              Other capacitance values than those listed below are available on request.
                A line trap can in most cases be mounted directly on top of the coupling capacitor. Primary
              terminal according to ABB standard (see page I-3), as well as insulators for the pedestrial mounting
              are part of the delivery. Test values are shown in page I-5 for the different designs.
              Modern PLC equipment is adapted for a wide range of coupling capacitors. No specific capaci-
              tance is required. Only minimum capacitance must be specified due to choice of frequency.
               Type              Number of           Standard          Extra high             A           Flashover and
                               capacitor units     capacitance        capacitance                         creepage dis-
                                                   pF (+10; -5%)      pF (+10; -5%)      Total height         tances
                                                        CCA               CCB                mm
               CCA 72                 1                 23500               -                1140
               CCA 123                1                 14500               -                1420
                                                                                                             Please see
               CCA/CCB 145            1                 12600            18900            1630/1840
                                                                                                          previous page,
               CCA/CCB 170            1                 10500            15700            1840/1840       table “Nominal
               CCA/CCB 245            1                 7500             11300            2400/2540        capacitance,
               CCA/CCB 300            2                 6300              9400            3170/3590       flashover- and
                                                                                                             creepage
               CCA/CCB 362            2                 5200              7900            3590/3590           distance”
               CCA/CCB 420            2                 4700              7100            4010/4010
               CCA/CCB 550            2                 3500              5200            4990/4990
                                                      CCA/CCB
I-8                                              Edition 5, 2008-03              ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                                   CPA and CPB 72-800 kV
and Coupling Capacitors	                                                                                  CCA and CCB 72-550 kV
Shipping Data CPA and CPB
Capacitor Voltage Transformers CPA
 Type         Net weight         Oil     Shipping weight                     Shipping dimensions                 Shipping volume,
               incl. oil                     3-pack                                 3-pack                         3-pack/Total
                  kg*            kg*              kg*                              LxWxH m                                m3
CPA 72            320            73             1085                            1.73x0.74x1.93                           2.51)
CPA 123           350            74             1185                            1.73x0.74x2.21                           2.81)
CPA 145           370            76             1255                            1.73x0.74x2.42                           3.11)
CPA 170           390            78             1320                            1.73x0.74x2.54                           3.31)
CPA 245           450            82            3 x 635                        3 x (3.11x0.69x0.91)                     3 x 2.02)
CPA 300           520            97          1235 + 655               1.73x0.74x2.42 + 1.82x1.55x0.80                 3.1 + 2.33)
CPA 362           565           100          1305 + 750               1.73x0.74x2.54 + 2.03x1.55x0.80                 3.3 + 2.53)
CPA 420           610           105          1385 + 835               1.73x0.74x2.81 + 2.24x1.55x0.80                 3.6 + 2.83)
CPA 550           710           111        3x650 + 1035            3 x (3.25x0.69x0.91) + 2.79x1.55x0.80            3 x 2.0 + 3.54)
Capacitor Voltage Transformers CPB
 Type        Net weight         Oil       Shipping weight                   Shipping dimensions                  Shipping volume,
              incl. oil                       3-pack                               3-pack                          3-pack/Total
                  kg*           kg*               kg*                              LxWxH m                                m3
CPB 72            425            95              1440                           2.06x0.90x2.00                           3.71)
CPB 123           455            96              1550                           2.06x0.90x2.49                           4.61)
CPB 145           475            98              1610                           2.06x0.90x2.49                           4,61)
CPB 170           495           100              1675                           2.06x0.90x2.70                           5.01)
CPB 245           555           104            3 x 755                       3 x (3.21x0.80x1.01)                      3 x 2.62)
CPB 300           625           119          1590 + 670               2.06x0.90x2.49 + 1.82x1.55x0.80                 4.6 + 2.33)
CPB 362           670           122          1660 + 750               2.06x0.90x2.70 + 2.03x1.55x0.80                 5.0 + 2.53)
CPB 420           715           127          1735 + 835               2.06x0.90x2.91 + 2.24x1.55x0.80                 5.4 + 2.83)
CPB 550           815           133        3 x 770 + 1035          3 x (3.35x0.80x1.01) + 2.79x1.55x0.80            3 x 2.7 + 3.54)
CPB 800          1065           161       3x770 + 2x1025        3 x (3.35x0.80x1.01) + 2 x (2.79x1.55x0.80)       3 x 2.7 + 2 x 3.54)
   1) 	Vertical 3-pack
   2) 	Horizontal 1-pack (normally, due to transport height)
   3) 	Bottom part vertical 3-pack; top part horizontal 3-pack
   4) 	Bottom part horizontal 1-pack; top part horizontal 3-pack (normally, due to transport height)
   *) The weights for extra high capacitance CVTs are 5 to 10% higher, but the shipping volumes are the same as for standard capaci-
   tance CVTs.
ABB Instrument Transformers — Buyer’s Guide                      Edition 5, 2008-03                                                     I-9
Outdoor Capacitor Voltage Transformers	                                                            CPA and CPB 72-800 kV
and Coupling Capacitors	                                                                           CCA and CCB 72-550 kV
Shipping Data CCA and CCB
           Coupling Capacitors CCA
           Type              Net             Oil           Shipping                 Shipping dimensions          Shipping volume
                           weight                           weight                         3-pack                  3-pack/Total
                           incl. oil                        3-pack
                             kg*            kg*               kg*                        LxWxH m                         m3
           CCA 72            135             18               565                     1.33x1.55x0.80                     1.65)
           CCA 123           165             19               675                     1.61x1.55x0.80                     2.05)
           CCA 145           180             21               735                     1.82x1.55x0.80                     2.35)
           CCA 170           205             23               825                     2.03x1.55x0.80                     2.55)
           CCA 245           265             27              1060                     2.59x1.55x0.80                     3.25)
           CCA 300           335             42           730 + 670                  2x(1.82x1.55x0.80)              2.3 + 2.36)
           CCA 362           380             45           810 + 750                  2x(2.03x1.55x0.80)              2.5 + 2.56)
           CCA 420           425             50           895 + 835                  2x(2.24x1.55x0.80)              2.8 + 2.86)
           CCA 550           525             56          1095 + 1035                 2x(2.79x1.55x0.80)              3.5 + 3.56)
           Coupling Capacitors CCB
           Type               Net            Oil           Shipping                 Shipping dimensions           Shipping volume
                            weight                          weight                         3-pack                   3-pack/Total
                            incl. oil                       3-pack
                              kg*            kg*              kg*                        LxWxH m                          m3
           CCB 145            240            32               930                     2.03x1.55x0.80                     2.55)
           CCB 170            240            29               930                     2.03x1.55x0,80                     2.55)
           CCB 245            315            36              1220                     2.79x1.55x0.80                     3.55)
           CCB 300            455            65           925 + 865                  2x(2.03x1.55x0.80)               2.5 + 2.56)
           CCB 362            455            58           925 + 865                  2x(2.03x1.55x0.80)               2.5 + 2.56)
           CCB 420            505            64           1015 + 955                 2x(2.24x1.55x0.80)               2.8 + 2.86)
           CCB 550            635            74          1260 + 1200                 2x(2.79x1.55x0.80)               3.5 + 3.56)
            5) 	Normally, coupling capacitors are packed in horizontal 3-pack
            6) 	Top and bottom part(s) are packed in two cases, horizontal 3-pack
I-10                                                    Edition 5, 2008-03                  ABB Instrument Transformers — Buyer’s Guide
CPA and CPB 72-800 kV	                                                 Outdoor Capacitor Voltage Transformers
Capacitor Voltage Transformer Type CPA and CPB (IEC)
Schematic Diagram of Capacitor Voltage Transformer
              BN
           Ground
1	Electromagnetic unit (EMU): Intermediate voltage transformer with compensating reactor
2	Primary winding of the intermediate voltage transformer
3	Compensating reactor
4	Adjustment windings
5	Secondary windings
6	Ferro-resonance damping circuit
Option – Carrier Accessories
                                                                       Drain coil available for
                                                                       12, 24 or 48 mH.
ABB Instrument Transformers — Buyer’s Guide       Edition 5, 2008-03                                      I-11
                                s
           es r´
        ot e
       N omt
        us
       C
I-12       Edition 5, 2008-03   ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers 	                                                  CPA and CPB 72-550 kV
Capacitor Voltage Transformer CPA and CPB (ANSI)
For revenue metering and protection in        The CPA and CPB have a high Quality
high voltage networks. The overall design     Factor, as a result of their comparatively
of the CVT and the mixed dielectric in the    high capacitance, combined with a high
capacitor elements have proven to be          intermediate voltage.
insensitive to temperature changes, and       The Quality Factor = Cequivalent x U²intermediate is
the accuracy is equivalent to inductive       a measure of the accuracy stability. The
voltage transformers. These CVTs are          higher this factor, the better the accuracy,
designed for widely shifting conditions,      and the better the transient response.
from polar to desert climates.
                                               Brief Performance Data
                                               Installation                 Outdoor
                                               Design                       Capacitor type
                                                                            Meets ANSI standards
                                               Insulation
                                                 CVD                        Aluminum-foil/paper/ poly-
                                                                            propylene film, synthetic oil
                                                EMU                         Paper - mineral oil
                                               System voltage               69-500 (765) kV
                                               Nominal
                                               Insulators                   Porcelain - on request silicon
                                                                            rubber (SIR)
                                               Creepage distance            ≥ 25 mm/kV
                                                                            (longer on request)
                                               Service conditions
                                                Ambient temperature         -40 °C to +40 °C
                                                                            (others on request)
                                                Design altitude             Maximum 1000 m
                                                                            (others on request)
ABB Instrument Transformers — Buyer’s Guide       Edition 5, 2008-03                                         J-1
CPA and CPB 72-550 kV	                                              Outdoor Capacitor Voltage Transformers
Capacitor Voltage Transformer CPA and CPB (ANSI)
                 Material                                             The damping circuit consists of a reactor
                 All external metal surfaces are made of an           with an iron core, and an oil-cooled resistor
                 aluminum alloy, resistant to most known en-          in series. Under normal use, the iron core of
                 vironment factors. Bolts, nuts, etc. are made        the damping reactor is not saturated, yielding
                 of acid-proof steel. The aluminum surfaces           high impedance, so that practically no cur-
                 do not normally need painting. We can, how-          rent is flows through this circuit.
                 ever, offer a protective paint, normally light         The damping circuit has two bridged termi-
                 gray.                                                nals; d1- d2, behind a sealed covering hood
                                                                      in the terminal box. In particular cases and
                 Creepage Distance                                    after agreement this bridge can be opened,
                 As standard, the CPA and CPB are offered             to check that the circuit is intact, by resis-
                 with creepage distance 25 mm/kV. Longer              tance measurement.
                 creepage distances can be offered on re-
                 quest.                                               Ratio Adjustment
                                                                      The transformer of the electromagnetic unit
                 Silicone Rubber Insulators                           has five adjustment windings on the ground
                 The complete ranges of the CVT and CC are            side of the primary winding. The numbers of
                 available with silicone rubber (SIR) insula-         turns of these windings have been chosen
                 tors. Our SIR insulators are produced with a         so that the ratio can be adjusted ±6.05% in
                 patented helical extrusion molding technique,        steps of 0.05%. These windings are exter-
                 which gives completely joint-free insulators         nally accessible behind a sealed covering
                 with outstanding performance. All CVTs and           hood in the secondary terminal box. The CVT
                 CCs with this type of insulators have the            is delivered adjusted for a specified burden
                 same high creepage distance, 25 mm/kV, as            and class, and normally no further adjust-
                 porcelain.                                           ment is necessary. If needed, the adjustment
                                                                      windings enable exchange of the voltage
                 Mechanical Stability                                 divider on site, and readjust the transformer
                 The mechanical stability gives a sufficient          for the new combination of voltage divider/
                 safety margin for normal wind loads and con-         electromagnetic unit.
                 ductor forces. In most cases, with help of the
                 optional top plate, it is also possible to mount     Rating Plates
                 line traps for power line carrier equipment          Corrosion resistant rating plates with text and
                 directly on top of the capacitor divider. The        wiring diagrams are used. General data can
                 CPA and CPB will also withstand most cases           be found on the door of the terminal box,
                 of seismic stress.                                   connection diagrams and secondary winding
                                                                      data on the inside.
                 Ferroresonance Damping Circuit                        The capacitors are marked with measured
                 All CVTs need to incorporate some kind of            capacitance on the lower insulator flange(s).
                 ferro-resonance damping, since the capaci-
                 tance in the voltage divider, in series with the     Potential Grounding Switch
                 inductance of the transformer and the series         A potential grounding switch can be included
                 reactor, constitutes a tuned resonance cir-          in the EMU.
                 cuit.
                   This circuit can be brought into resonance,        Power Line Carrier (PLC)
                 that may saturate the iron core of the trans-        As an option all CVTs can be equipped with
                 former, by various disturbances in the net-          Carrier Accessories. Modern PLC equip-
                 work. This phenomenon can also overheat              ments are adapted for a wide range of cou-
                 the electromagnetic unit or lead to insulation       pling capacitors. No specific capacitance is
                 breakdown.                                           required. Only minimum capacitance must
                   The CPA and CPB use a damping circuit,             be specified due to choice of frequency.
                 connected in parallel with one of the second-
                 ary windings (see scheme in page J-9).
J-2                                           Edition 5, 2008-03              ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers 	                                  CPA and CPB 72-550 kV
Capacitor Voltage Transformer CPA and CPB (ANSI)
Primary Terminal
The CPA and CPB are normally delivered with an
aluminum NEMA pad, suitable for connecting normal
aluminum cable clamps. Other primary terminals can
be offered on request, such as an aluminum round
stud, Ø=30 mm.
  On request a top plate can be provided and drilled
with four bolt holes 5/8” UNC, on a 5” circle in case a
line trap is to be mounted.
  Maximum static force on the primary terminal is 340
lbf (1,500 N) in all directions. Maximum dynamic force
is 475 lbf (2,100 N.)
(Maximum static/dynamic force is 295/412 lbf for
CPB 800)
  Our design is corona free and corona rings are not
needed, but are available on request.
Secondary Terminal Box and
Secondary Terminals
The transformer is equipped with a secon-dary terminal box, protec-
tion class IP 55. This box is equipped with a
detachable,
undrilled gland plate, which on installation                                     L
can be drilled for cable bushings. The box
is provided with a drain. The transformer
can also be equipped with a larger terminal
box, with space for fuses or micro circuit
breakers and/or protection for power line
carrier equipment.
The secondary terminals normally consist                                             A
of Phoenix standard terminal blocks for
wire cross-section > 3/8” (10 mm²). In the
terminal box are also terminals (d1-d2) for damping circuit, terminals
for the adjustment windings (B1 - B10) and the capacitor low voltage
terminal ”L” (for power line carrier equipment). Terminals d1 - d2 and
B1 - B10 are intended for factory settings and thus located behind a
sealed covering hood to prevent inadvertent reconnection.
  The ”L” terminal must always be grounded
  if no carrier equipment is connected.
Ground Terminals
The transformer is normally equipped with a ground
clamp with a cap of nickel-plated brass, for conduc-
tor # 2 SOL to 500 MCM (diameters 8-16 mm), which
can be moved to either mounting foot. Grounding
terminals for the secondary circuits are placed inside
the terminal box.                                                                        Example
ABB Instrument Transformers — Buyer’s Guide          Edition 5, 2008-03                            J-3
CPA and CPB 72-550 kV	                                             Outdoor Capacitor Voltage Transformers
Installation and Maintenance (ANSI)
                 Unpacking                                           • Control measurements of the EMU
                 Please check the crates and their contents          A simple test is to measure the insulation
                 for damage during transportation upon re-           resistance in mega-ohms (max. test voltage
                 ceipt. Should there be any damage, please           1,000 VDC) of the secondary windings.
                 contact ABB for advice before the goods               Since the high voltage winding of the trans-
                 are handled further. Any damage should be           former is not capacitively graded, a measure-
                 documented (photographed).                          ment of the loss angle (tan delta) will give no
                                                                     significant result.
                 Assembly                                              What is possible, however, is to take an oil
                 The electromagnetic unit and the capacitor          sample, for gas chromatography analysis
                 voltage divider are delivered as one unit for       from the electromagnetic unit to assess its
                 CVTs with system voltages up to 230 kV.             condition.
                   CVTs with higher system voltages, having            The tank of the electromagnetic unit can,
                 more than one CVD part, are delivered with          on request, be equipped with a sampling
                 the bottom unit of the CVD assembled onto           valve, and we can deliver suitable sampling
                 the EMU.                                            equipment. A simpler method is to take the
                   The EMU, with the bottom CVD unit should          oil sample from the oil-filling hole. Sampling
                 be installed first, before the top part(s) of the   intervals will vary, depending on service con-
                 CVD is (are) mounted in place. Lifting instruc-     ditions; generally, no oil analysis should be
                 tions are included in each package.                 necessary during the first 20 years of service.
                   Check that the top and the bottom insulator
                 have the same serial number (for CVDs with          Environmental Aspects
                 more than one capacitor unit).                      Impregnant
                                                                     Both Faradol 810 (the synthetic oil in the
                 Maintenance                                         voltage dividers), and Nynäs NYTRO 10 XN
                 The CPA and CPB are designed for a service          (the standard transformer oil in the electro-
                 life of more than 30 years, and are practically     magnetic unit) are free from PCB and other
                 maintenance-free. We recommend however              strongly harmful substances, and pose a low
                 the following checks and measures.                  impact to the environment.
                 • Visual Check                                      Destruction
                 We recommend a period inspection, to                After draining the oils, they can be burnt in
                 check for oil leakages and also to inspect the      an appropriate plant. In this respect, Faradol
                 insulator for collection of dirt.                   has similar combustion properties as normal
                                                                     mineral oil.
                 • Control measurements of the CVD                     The disposal should be carried out in accor-
                 Since the voltage dividers are permanently          dance with local legal provisions, laws and
                 sealed under slight overpressure it is not          regulations.
                 possible to take oil samples from them.               The porcelain can be deposited after it has
                   Under normal service conditions, no notice-       been crushed.
                 able ageing will occur within the capacitors          The metals in the electromagnetic unit, and
                 (verified by ageing tests). However discrep-        the housings of the voltage divider can be
                 ancies between the secondary voltages in            recycled. Aluminum parts are labeled with
                 parallel phases can be an indication of a           material specification. In order to recycle the
                 fault in a capacitor part of one of the voltage     copper in the windings, the oil-saturated
                 transformers, which is why such a compari-          paper insulation should be burnt.
                 son is recommended. In such a case a fur-             The aluminum in the capacitor elements,
                 ther measurement of the capacitance value           with their combination of foil, paper and
                 is recommended. Readings can be taken               polypropylene film can be reclaimed after the
                 between the top and the ”L” terminal in the         insulation has been burnt; the plastic film will
                 secondary terminal box.                             not emit any harmful substances during this
                                                                     process.
J-4                                           Edition 5, 2008-03             ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                                                CPA and CPB 72-550 kV
Design Data According to ANSI
Number of capacitor units, capacitance, flash-over and creepage distance
(CSA, standard capacitance) (also valid for CCA)
                                                                                  Normal porcelain (min. nom. values)      Porcelain with long
 Type                       Number of                   Standard                  Striking distance   Leaking distance     creepage distance
                          capacitor units              capacitance                      (min.)                             (min. nom. values)
                                                       pF (+10; -5 %)                mm (inches)        mm (inches)
 CPA/CPB 72                          1                      23500                       700 (28)          2200 (86)
 CPA/CPB 123                         1                      14500                       980 (39)         3160 (124)
 CPA/CPB 145                         1                      12600                      1190 (47)         3880 (153)
 CPA/CPB 170                         1                      10500                      1400 (55)         4600 (182)           Offered on request
 CPA/CPB 245                         1                       7500                      1960 (77)         6510 (256)
 CPA/CPB 420                         2                       4700                      3220 (127)        10630 (420)
 CPA/CPB 550                         2                       3500                      4200 (166)        13980 (551)
Number of capacitor units, capacitance, flash-over and creepage distance
(CSB, extra high capacitance) (also valid for CCB)
                                                                                  Normal porcelain (min. nom. values)      Porcelain with long
 Type                       Number of                   Extra high                Striking distance   Leaking distance     creepage distance
                          capacitor units              capacitance                      (min.)                             (min. nom. values)
                                                        pF (+10; -5 %)                mm (inches)        mm (inches)
 CPA/CPB 145                         1                      18900                      1400 (56)         4600 (182)
 CPA/CPB 170                         1                      15700                      1400 (56)         4600 (182)
 CPA/CPB 245                         1                      11300                      2100 (83)         6990 (276)           Offered on request
 CPA/CPB 420                         2                       7100                     3220 (127)        10630 (420)
 CPA/CPB 550                         2                       5200                     4200 (166)        13980 (551)
Test Voltages: ANSI C93.1 - 1999
        Type               Nominal             Max rated             AC test             AC test          BIL          RIV test       RIV level
                           system               voltage             Dry, 1min           Wet, 10 sec    1.2/50 µs       voltage
                           voltage
                             kV L-L1)             kV L-G                   kV                 kV          kV             kV               µV
 CPA/CPB 72                     69                  42                     165               140         350             42              125
 CPA/CPB 123                   115                  70                     265               230         550             70              250
 CPA/CPB 145                   138                  84                     320               275         650             84              250
 CPA/CPB 170                   161                  98                     370               325         750             98              250
 CPA/CPB 245                   230                 140                     525               460         1050            140             250
 CPA/CPB 420                   345                 209                     785               680         1550            209             250
 CPA/CPB 550                   500                 318                     900               780         1800            318             500
Test voltages above are valid for altitudes < 3300 feet above sea level.
ABB Instrument Transformers — Buyer’s Guide                                     Edition 5, 2008-03                                                 J-5
CPA and CPB 72-550 kV	                                                                           Outdoor Capacitor Voltage Transformers
Design Data According to ANSI
(The data in the tables below are ABB standard values. Other data can be offered on request)
  Accuracy
  The CPA is offered for 0.6R or 1.2R relay accuracy class and CPB for 0.3 or 0.6 metering accuracy class. It can be
  supplied with two tapped windings, X and Y, or with three tapped windings X, Y and Z.
      CPA with          Metering                 Relaying                 Winding                      Winding                    Aux. winding           Thermal
      standard        Secondary volt          Secondary volt            X1-X2, X2-X3                 X1-X2, X2-X3                   Optional             burden
      capacitance      115V: Tap V             115V:115/√3V             Y1-Y2, Y2-Y3                 Y1-Y2, Y2-Y3                 Z1-Z3, Z2-Z3
                             Ratio                 Ratio            Class        Burden1)         Class       Burden1
                                                                                                                        )
                                                                                                                               Class    Burden1
                                                                                                                                                  )
                                                                                                                                                            VA
      CPA 72            350/600:1:1            (346/600:1:1)        0.6R         0-200VA          1.2R        0-400VA          1.2R      0-75VA            600
      CPA 123           600/1000:1:1          (577/1000:1:1)        0.6R         0-200VA          1.2R        0-400VA          1.2R      0-75VA            600
      CPA 145           700/1200:1:1          (693/1200:1:1)        0.6R         0-200VA          1.2R        0-400VA          1.2R      0-75VA            600
      CPA 170           800/1400:1:1          (808/1400:1:1)        0.6R         0-200VA          1.2R        0-400VA          1.2R      0-75VA            600
      CPA 245          1200/2000:1:1          (1155/2000:1:1)       0.6R         0-200VA          1.2R        0-400VA          1.2R      0-75VA            600
      CPA 420          1800/3000:1:1          (1732/3000:1:1)       0.6R         0-200VA          1.2R        0-400VA          1.2R      0-75VA            600
      CPA 550          2500/4500:1:1          (2511/4350:1:1)       0.6R         0-200VA          1.2R        0-400VA          1.2R      0-75VA            600
  1) The total simultaneous burden (X+Y+Z) is not to exceed values given for each main winding. All burdens are factory set.
      CPB with           Metering                Relaying                 Winding                      Winding                    Aux. winding           Thermal
      extra high       Secondary volt         Secondary volt            X1-X2, X2-X3                 X1-X2, X2-X3                   Optional             burden
      capacitance       115V: Tap V            115V:115/√3V             Y1-Y2, Y2-Y3                 Y1-Y2, Y2-Y3                 Z1-Z3, Z2-Z3
                                                                                           )                           )                          )
                             Ratio                 Ratio            Class         Burden1         Class       Burden1          Class    Burden1             VA
      CPB 145           700/1200:1:1                  -               0.3         0-200VA          0.6        0-200VA          1.2R      0-75VA            600
      CPB 170           800/1400:1:1                  -               0.3         0-200VA          0.6        0-200VA          1.2R      0-75VA            600
      CPB 245          1200/2000:1:1                  -               0.3         0-200VA          0.6        0-200VA          1.2R      0-75VA            600
      CPB 420          1800/3000:1:1                  -              0.3          0-200VA          0.6        0-200VA          1.2R      0-75VA            600
      CPB 550          2500/4500:1:1                  -              0.3          0-200VA          0.6        0-200VA          1.2R      0-75VA            600
  1) The total simultaneous burden (X+Y+Z) is not to exceed values given for each main winding. All burdens are factory set.
      CPA/CPB                                 Metering performance                                                    Relaying performance
                                      Ratio                       Perf. ref. Voltage 2)                       Ratio                      Perf. ref. Voltage 2)
      CPA 72                      350/600:1:1                        40.25 kV L-G                         (346/600:1:1)                       69/√3 kV
      CPA 123                    600/1000:1:1                          69 kV L-G                          (577/1000:1:1)                      115/√3 kV
      CPA/CPB 145                700/1200:1:1                         80.5 kV L-G                         (693/1200:1:1)                      138/√3 kV
      CPA/CPB 170                800/1400:1:1                          92 kV L-G                          (808/1400:1:1)                      161/√3 kV
      CPA/CPB 245                1200/2000:1:1                        138 kV L-G                         (1155/2000:1:1)                      230/√3 kV
      CPA/CPB 420                1800/3000:1:1                         207kV L-G                         (1732/3000:1:1)                      345/√3 kV
      CPA/CPB 550                2500/4500:1:1                       287.5 kV L-G                        (2510/4348:1:1)                      500/√3 kV
  2) Application of the “performance reference voltage” between phase and ground will result in 115 V secondary winding having lower ratio.
  Rated burdens
  W = 12.5 VA power factor 0.1, X = 25 VA power factor 0.7, Y = 75 VA power factor 0.85
  YY = 150 VA power factor 0.85, Z = 200 VA power factor 0.85, ZZ = 400 VA power factor 0.85
  Coupling Capacitors
  Coupling capacitors types CCA (standard capacitance) and CCB (extra high capacitance) are intended for power
  line carrier applications. The insulator and capacitor design are identical to capacitor voltage dividers type CSA and
  CSB, but without an intermediate voltage terminal.
  Descriptions of the voltage divider are in the IEC catalog for the CVT.
J-6                                                                     Edition 5, 2008-03                       ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                                                CPA and CPB 72-550 kV
Dimensions
Capacitor Voltage Transformer CPA
                                                   A                     B                 C                D                E
 Type                Number of                    Total              Striking          Height to        Mounting         Ground
                   capacitor units               height              distance          flange *)      hole distance    level height
                                                 mm (in)              mm (in)           mm (in)          mm (in)         mm (in)
 CPA 72                      1                1660 (65”)             700 (28”)         340 (13”)        335 (13”)       740 (29”)
 CPA 123                     1                1940 (76”)             980 (39”)         340 (13”)        335 (13”)       740 (29”)
 CPA 145                     1                 2150 (85”)**)       1190 (47”)**)        340 (13”)       335 (13”)        740 (29”)
 CPA 170                     1                2360 (93”)            1400 (55”)         340 (13”)        335 (13”)       740 (29”)
 CPA 245                     1                2920 (115”)**)       1960 (77”)**)        340 (13”)       335 (13”)        740 (29”)
 CPA 420                     2                4530 (178”)          3220 (127”)         340 (13”)        335 (13”)       740 (29”)
 CPA 550                     2                5510 (217”)          4200 (165”)         340 (13”)        335 (13”)       740 (29”)
* Valid for standard terminal box only. ** Valid for standard capacitance only.
Capacitor Voltage Transformer CPB
                                                       A                    B                C              D               E
 Type                   Number of                    Total              Striking         Height to       Mounting      Ground level
                      capacitor units               height              distance         flange *)     hole distance      height
                                                   mm (in)               mm (in)          mm (in)         mm (in)         mm (in)
 CPB 72                          1               1715 (68”)            700 (28”)         390 (15”)       410 (17”)      790 (31”)
 CPB 123                         1               1995 (79”)            980 (39”)         390 (15”)       410 (17”)      790 (31”)
 CPB 145                         1               2205 (87”)**)        1190 (47”)**)      390 (15”)       410 (17”)      790 (31”)
 CPB 170                         1               2415 (95”)           1400 (55”)         390 (15”)       410 (17”)      790 (31”)
 CPB 245                         1             2975 (123”)**)          2100 (83”)**)      390 (15”)      410 (17”)      790 (31”)
 CPB 420                         2              4585 (181”)          3220 (127”)         390 (15”)       410 (17”)      790 (31”)
 CPB 550                         2              5565 (219”)          4200 (165”)         390 (15”)       410 (17”)      790 (31”)
* Valid for standard terminal box only.
** Valid for standard capacitance only.
                                                               CPA/CPB
ABB Instrument Transformers — Buyer’s Guide                                   Edition 5, 2008-03                                         J-7
CPA and CPB 72-550 kV	                                                                 Outdoor Capacitor Voltage Transformers
Shipping Data (ANSI)
         Capacitor Voltage Transformers CPA
          Type           Net weight         Oil *)    Shipping weight *                    Shipping dimensions                           Shipping
                          incl. oil *)                    3-pack)                                 3-pack                                  volume
                                                                                                                                          3-pack
                                                                                                    LxWxH                                   Total
                              kg             kg                 kg                                      m                                    m3
          CPA 72              320            73                1085                            1.73x0.74x1.93                               2.51)
          CPA 123             350            74                1185                            1.73x0.74x2.21                               2.81)
          CPA 145             370            76                1255                            1.73x0.74x2.42                               3.11)
          CPA 170             390            78                1320                            1.73x0.74x2.54                               3.31)
          CPA 245             450            82              3 x 635                        3 x (3.11x0.69x0.91)                          3 x 2.02)
          CPA 420             715           127            1735 + 835               2.06x0.90x2.91 + 2.24x1.55x0.80                      5.4 + 2.83)
          CPA 550             815           133         3 x 770 + 1035           3 x (3.35x0.80x1.01) + 2.79x1.55x0.80                3 x 2.7 + 3.54)
         Capacitor Voltage Transformers CPB
          Type           Net weight         Oil *)     Shipping weight                     Shipping dimensions                           Shipping
                          incl. oil *)                        *)                                  3-pack                                  volume
                                                           3-pack                                                                         3-pack
                                                                                                    LxWxH                                   Total
                               kg            kg                 kg                                      m                                    m3
          CPB 72              425            95                1440                            2.06x0.90x2.00                               3.71)
          CPB 123             455            96                1550                            2.06x0.90x2.49                               4.61)
          CPB 145             475            98                1610                            2.06x0.90x2.49                               4.61)
          CPB 170             495           100                1675                            2.06x0.90x2.70                               5.01)
          CPB 245             555           104              3 x 755                        3 x (3.21x0.80x1.01)                          3 x 2.62)
          CPB 420             715           127           1735 + 835                2.06x0.90x2.91 + 2.24x1.55x0.80                      5.4 + 2.83)
          CPB 550             815           133         3 x 770 + 1035           3 x (3.35x0.80x1.01) + 2.79x1.55x0.80                3 x 2.7 + 3.54)
         *) The weights for extra high capacitance CVTs are 5 to 10% higher, but the shipping volumes are the same as for standard capacitance CVTs
         1) Vertical 3-pack
         2) Horizontal 1-pack (normally, due to transport height)
         3) Bottom part vertical 3-pack; top part horizontal 3-pack
         4) Bottom part horizontal 1-pack; top part horizontal 3-pack (normally, due to transport height)
J-8                                                           Edition 5, 2008-03                      ABB Instrument Transformers — Buyer’s Guide
Outdoor Capacitor Voltage Transformers	                                                     CPA and CPB 72-550 kV
Capacitor Voltage Transformer CPA and CPB (ANSI)
Schematic Diagram of Capacitor Voltage Transformer
    H1
                                                                   1
                    BN
    H2
          Ground
	        1. Electromagnetic unit (EMU)
	        2. Primary winding of the intermediate voltage transformer
	        3. Potential grounding switch and choke coil (option)
	        4. Adjustment windings (B1-B10)
	        5. Secondary windings X and Y
	        6. Ferroresonance damping circuit
	        7. Auxiliary winding Z (option)
Option – Carrier Accessories
                                                                         Drain coil available for
                                                                         12, 24 or 48 mH.
ABB Instrument Transformers — Buyer’s Guide         Edition 5, 2008-03                                        J-9
Cable Entry Kits	                                                                                    Roxtec CF 16
Optional - Accessories for cable installations
                    Easy installations for cables                      cables sizes and numbers in the junction
                    A Roxtec CF 16 cable entry kit combines reli-      boxes (as shown below).
                    able sealing of cables in junction boxes with      For other dimensions, please contact ABB,
                    easy installations. Each CF 16 can handle          High Voltage Products, Ludvika, Sweden.
                    several cables through the same opening.
                                                                       Simple maintenance
                    Multidiameter                                      A Roxtec CF 16 can be opened and closed
                    The CF 16 uses adaptable Multidiameter             repeatedly for easy installations and simple
                    technology. This enables cables of a wide          maintenance. Another benefit is a built in
                    range of diameters to be sealed with a per-        spare capacity for possible new cables in the
                    fect fit, even when tolerances and deviations      future.
                    from nominal dimensions are considered.
                    The modules are delivered with a center core       Benefit Summary
                    as a substitute for a cable. This means the        •	Seals several cables and diameters
                    entry kit is adaptable to different cable sizes,   •	Quick and easy installation
                    and to different numbers of penetrations.          •	Cable retention
                                                                       •	Rodent proof
                    Kit Supplied                                       •	IP 66/67
                    The Roxtec CF 16 kits are available in two         •	Halogen-free
                    versions: Each one with a customized set of        •	UL/NEMA 4, 4X, 12, 13
                    sealing modules to suit the most common            •	Fire retardant material UL 94-V0
                    ABB CF 16 junction box kit 1                       ABB CF 16 junction box kit 2
                    Part No.                                           Part No.
                    Roxtec CF 16 Kit 1: Handles maximum                Roxtec CF 16 Kit 2: Handles maximum
                    one 9.5-32.5 mm cable, two 10-25 mm                one 9.5-32.5 mm cable and four 10-25 mm
                    cables and six 3.5-16.5 mm cables.                 cables.
K-1                                              Edition 5, 2008-03           ABB Instrument Transformers — Buyer’s Guide
                                                         s
                                  es r´
                               ot e
                              N omt
                               us
                        C
ABB Instrument Transformers — Buyer’s Guide   Edition 5, 2008-03   K-2
Quality Control and Testing	
Quality Control and Testing
          ABB AB, High Voltage Products is certified by            Type Tests
                                                                   The type tests reports for tests performed on
          Lloyds to fulfill the requirements of ISO 9001.
                                                                   transformers types similar to customer speci-
                                                                   fications are available.
          Bureau Veritas Quality International (BVQI) also
          certifies us for Environmental Management                Routine Tests
          Systems, ISO 14001 and 14024.                            The following tests are performed on each
                                                                   transformer as standard before delivery in
                                                                   accordance with applicable standards:
                    Routine Tests for Current                      Routine Tests for Inductive
                    Transformers IMB                               Voltage Transformers EMF
                    IEC 60044-1 clause 6.2                         IEC 60044-2
                    a	 Verfication of terminal marking and         a	   Verfication of terminal marking and
                    	  polarity                                    	    polarity
                    b	 Power-frequency withstand test on           b	   Power-frequency withstand test on
                    	  primary winding                             	    primary winding
                    c	 Partial discharge measurement               	    (applied test, 75 Hz for one minute)
                    d	 Power-frequency withstand test on           c	   Partial discharge measurement
                    	  secondary windings                          d	   Power-frequency withstand test on
                    e	 Power-frequency withstand test                   secondary windings
                    	  between winding sections                         (applied test 4 kV, 50 Hz for one minute)
                    f	 Inter-turn overvoltage test on secondary    e	   Determination of errors
                       windings
                    g	 Determination of errors                     ABB specific tests
                       (One transformer in each batch is type-     a	 Sealing test
                       tested for accuracy. Remaining units at a   b	 Measurement of no load current I0 at √3
                       reduced number of burdens. Complete            x rated voltage
                       error curves on all transformers must be
                       ordered separately.)                        Other standards
                                                                   The tests described above also fully satisfy
                    IEC 60044-1 clause 6.3                         other standards, such as IEEE.
                    Measurement of capacitance and tan delta
                    ABB specific tests
                    a	 Sealing test
                    b	 Measurement of secondary resistance
                       (sample)
                    c	 Complete excitation curve for each
                       type of core in a transformer. For the
                       remaining transformers all cores are
                       checked at one or two points on the
                       excitation curve.
L-1                                           Edition 5, 2008-03           ABB Instrument Transformers — Buyer’s Guide
                                                                                       Quality Control and Testing
Test Capibilities in Ludvika                       STL provides a forum for international col-
Our high resource laboratories (high power/      laboration between testing organizations.
high voltage/environmental) in Ludvika are       The membership and supervision of SATS
members of SATS (Scandinavian Associa-           ensures the independency of the laboratory.
tion for Testing of Electric Power Equipment).     We are able to claim that with these testing
SATS is a member of STL                          resources, we are at the forefront in devel-
(Short Circuit Testing Liaison).                 oping new and safe products for the 21st
                                                 century.
Routine Tests for Capacitor                      Routine Tests for Capacitor
Voltage Transformers CPA and CPB                 Voltage Transformers CPA and CPB
                                                 Electromagnetic Unit
IEC 60044-5, § 8.2                               ANSI C93.1-1999, § 6.3
Electromagnetic unit: e, f, g, h, j              *	     Leak test
Capacitor Voltage Divider/Coupling Ca-           2.2.1	 Dielectric test of primary winding, four
pacitor: a, b, c, d, g                                  times performance reference voltage
Capacitor Voltage Transformer: i, j                     (1 min.)
a	 Tightness of capacitor voltage divider 	      *	     Partial discharge measurement
	   (10.1)                                       2.2.3	 Dielectric test on secondary windings
b	 Capacitance and tan delta measurement                and adjustment windings, 4 kV (1 min.)
    at power-frequency (9.2)                     *	     Dielectric test of low voltage terminal,
c	 Power-frequency withstand test (10.2)                10 kV (1 min.)
d	 Measurement of partial discharge              *	     Inspection and measurement of the
    (10.2.3)                                            damping circuit
e	 Verification of terminal markings (10.3)      6	     Verification of terminal marking and
f	 Power-frequency withstand tests on the               polarity.
    electromagnetic unit (10.4)                  5	     Accuracy test
g	 Power-frequency withstand test on low
    voltage terminal (10.2.4)                    Capacitor Voltage Divider/Coupling
h	 Power-frequency withstand tests on            Capacitor
    secondary windings (10.4.2)                  ANSI C93.1-1999, § 6.3
i	 Ferro-resonance check (10.5)                  *	     Leak test
j	 Accuracy check (determinations of             1.1	   Measurement of capacitance and
    errors) (10.6)                                      dissipation factor for each capacitor
                                                        unit before dielectric test
ABB specific tests:                              2.1	   Dielectric test, voltage according to
Electromagnetic Unit                                    table above
	   Tightness test                               *	     Partial discharge test of each capacitor
                                                        porcelain
	   Inspection of damping circuit.               1.2	   Capacitance and dissipation factor
                                                        measurement after dielectric test
                                                 *	     Dielectric test of low voltage terminal
                                                        (1 min.)
                                                 *) ABB-Special quality check
ABB Instrument Transformers — Buyer’s Guide           Edition 5, 2008-03                                       L-2
Inquiry and Ordering Data	
Ordering Data
Current Transformer IMB                                    Voltage Transformer EMF
The following information is required with your            The following information is required with your
order:                                                     order:
•	Quantity                                                  •	Quantity
•	Standard/Customer specification                           •	Standard/Customer specification
•	Frequency                                                 •	Frequency
•	Highest voltage for equipment                             •	Highest voltage for equipment
•	Rated insulation level                                    •	Rated insulation level
Test Voltages                                              Test Voltages
•	Lightning impulse 1.2/50 µs                               •	Lightning impulse 1.2/50 µs
•	Power frequency dry/wet                                   •	Power frequency dry/wet
•	Switching surge 250/2500 µs (For Um ≥ 300 kV, wet)
                                                           Voltages
Currents                                                    •	Ratio (primary and secondary voltages)
•	Ratio (primary and secondary currents)                    •	Reconnection (secondary)
•	Reconnection (primary or/and secondary)                   •	Voltage factor (Vf) and time
•	Rated continuous thermal current (Rf)
•	Short time current, Ith 1 sec (3 sec)                    Burden and Accuracy
•	Dynamic current, Idyn                                     •	Number of secondary winding(s)
                                                            •	For each winding please state:
Burden and Accuracy                                           Connection: Star or broken delta
•	Number of cores                                             Burden/class
•	For each core please state:
	 Burden/class/overcurrent factor                           •	Thermal limit burden (if requested)
Special Requirements                                       Special Requirements
•	Silicone rubber insulator (gray)                          •	Silicone rubber insulator (gray)
•	Creepage distance (ABB standard: 25 mm/kV)                •	Creepage distance (ABB standard: 25 mm/kV)
•	Light gray porcelain (ABB standard: brown)                •	Light gray porcelain (ABB standard: brown)
•	Special primary terminals                                 •	Special primary terminal
•	Special secondary terminals                               •	Special secondary terminals
•	Heater                                                    •	Secondary fuses
•	Secondary overvoltage protection:                         •	Heater
  (spark gaps, protection gaps)                             •	Anodized tank, terminal box and expansion system
•	Anodized tank, terminal box and expansion system          •	1-pack vertical transport (EMF 52-84)
  (IMB 36-170)                                              •	1-pack, horizontal transport (EMF 123-170)
•	1-pack, vertical transport (IMB 36-145)                   •	Other requirements?
•	Horizontal transport (IMB 36-145)
•	Other?                                                   Additional Requirements
                                                            •	Ambient temperature
Additional Requirements                                     •	Height above sea level if >1000 m
•	Capacitive voltage tap                                      Please state “normal” system and test voltages
•	Adapter (for replacing old type IMB)                        according to actual standard when ≤1000 m a.s.l.
•	Ambient temperature                                       •	Other requirements?
•	Height above sea level if >1000 m
  Please state “normal” system and test voltages
  according to actual standard when ≤1000 m a.s.l.
•	Other requirements?
M-1                                              Edition 5, 2008-03             ABB Instrument Transformers — Buyer’s Guide
	                                                                                      Inquiry and Ordering Data
Ordering Data
Capacitor Voltage Transformer                                Coupling Capacitor
CPA and CPB                                                  CCA and CCB
The following information is required with your              The following information is required with your
order:                                                       order:
•	Quantity                                                   •	Quantity
•	Standard/Customer specification                            •	Standard/Customer specification
•	Frequency                                                  •	Frequency
•	Highest voltage for equipment                              •	Highest voltage for equipment
•	Rated insulation level                                     •	Rated insulation level
Test Voltages                                                Test Voltages
•	Lightning impulse 1.2/50 µs                                •	Lightning impulse 1.2/50 µs
•	Power frequency dry/wet                                    •	Power frequency dry/wet
•	Switching surge 250/2500 µs (For Um ≥ 300 kV, wet)         •	Switching surge 250/2500 µs (For Um ≥ 300 kV, wet)
Voltages                                                     Special Requirements
•	Ratio (primary and secondary voltages)                     •	Silicone rubber insulator (gray)
•	Reconnection (secondary)                                   •	Creepage distance (ABB standard: 25 mm/kV)
•	Voltage factor (Vf) and time                               •	Light gray porcelain (ABB standard: brown)
                                                             •	Special primary terminal
Burden and Accuracy
•	Number of secondary winding (s)                            Additional Requirements
•	For each winding please state:                             •	Capacitance - high or extra high
  Connection: Star or broken delta                           •	Ambient temperature
  Burden/class                                               •	Height above sea level if >1000 m
                                                               Please state “normal” system and test voltages
•	Thermal limit burden (if requested)                          according to actual standard when ≤1000 m a.s.l.
                                                             •	Other requirements?
Special Requirements
•	Silicone rubber insulator (gray)
•	Creepage distance (ABB standard: 25 mm/kV)
•	Light gray porcelain (ABB standard: brown)
•	Special primary terminal
•	Special secondary terminals
•	Secondary fuses
•	Heater
•	Protection for PLC equipment  
•	Horizontal transport
•	Other requirements?
Additional Requirements
•	Capacitance - high or extra high
•	Ambient temperature
•	Height above sea level if >1000 m
  Please state “normal” system and test voltages
  according to actual standard when ≤1000 m a.s.l.
•	Other requirements?
ABB Instrument Transformers — Buyer’s Guide          Edition 5, 2008-03                                           M-2
                                                                                                                   © Copyright 2008 ABB. All rights reserved. Catalogue publication 1HSM9543 42-00en, Outdoor Instrument Transformers Buyer’s Guide, Edition 5, 2008-03
                                  NOTE: ABB AB is working continuously to improve the products. We therefore
                                  reserve the right to change designs, dimensions and data without prior notice.
ABB AB
High Voltage Products
SE-771 80 LUDVIKA, Sweden
Phone +46 240 78 20 00
Fax +46 240 78 36 50
E-mail: instr.transf@se.abb.com
Internet: http://www.abb.com