Current Transformers
Current Transformers
Catalogue | 2012
           Outdoor instrument
           transformers
            Current transformers
            Voltage transformers
                                 Outdoor instrument
                                                                5
                                 transformers
AMTED302057EN.indd 3
Presentation 6
AMTED302057EN.indd 5
6 AMTED302057EN.indd
AMTED302057EN.indd 7
         The silicon material used on Schneider                      The design of Schneider Electric outdoor instruments transformers was studied
         Electric outdoor transformers is manufactured               in order to:
                                                                     b perform the required behaviours on highest pollution level (level IV as described
         by world known companies.                                   in document IEC815)
         The use of silicon for outdoor electrical                   b perform the required behaviours for ageing, by application of silicon on the sand
         equipment is a process well known in High                   blasted surface of the resin.
         Voltage Industry to prevent flashover and
                                                                     The secondary connections are protected by an enclosure specially designed for
         arcing, especially in severely contaminated                 electrical equipments, in compliance with all major standards (UL, CSA, CE, Lloyds,
         envronments.                                                BV, FI). The materials used is polycarbonate which ensure the resistance to outdoor
         The experience obtained after more than                     conditions.
         25 years of intensive use shows its efficiency              The protection level, according with IEC529 is IP44 standard or higher level on request.
         and reliability, on glass and epoxy isolators.    PE50724
8 AMTED302057EN.indd
                                                            DE58030EN
            b voltage transformers.
            These devices carry out the functions of:
            b reducing the size of value to be measured
            b providing galvanic separation
            b supplying the power needed to process
            the data, or even for the protection device
            to work.
                                                                        Types
                                                                        Instrument transformers are of the following types:
                                                                        Current transformers
                                                                        Connected on the MV network primary circuit, they supply a reduced current value to
                                                                        the secondary circuit, proportional to the network current on which they are installed.
                                                                        Voltage transformers
                                                                        Connected to the MV network primary, they supply the secondary circuit with a reduced
                                                                        voltage value, proportional to the network voltage on which they are installed.
AMTED302057EN.indd 9
                                           Selection guide                                     12
                                           Technical description                               12
                                           Current transformers                                18
                                           7.2 to 24 kV - Type OAM3/N1 - OAM3/N2               18
                                           7.2 to 40.5 kV - Type OAM7/N1 - OAM7/N2 - OAM7/N3   19
AMTED302057EN.indd 11
12 AMTED302057EN.indd
                                        Characteristics (cont.)
                                        Short-time thermal current peak value
                                        This value is standardized from Ith - 1 s at:
                                        b IEC: 2.5 Ith at 50 Hz and 2.6 Ith at 60 Hz
                                        b ANSI: 2.7 Ith at 60 Hz.
                                        Accuracy load
                                        The value of the load on which is based the metered current accuracy conditions.
                                        Accuracy power Pn
                                        Apparent power (VA) that the CT can supply on the secondary for the rated
                                        secondary current for which the accuracy is guaranteed (accuracy load).
                                        Usual value 5 - 7.5 - 10 - 15 VA (IEC).
                                        Accuracy class
                                        Defines the limits of error guaranteed on the transformation ratio and on the phase
                                        shift under the specified conditions of power and current. Classes 0.5 and 1 are used
                                        for metering class P for protection.
                                        Current error ε (%)
                                        Error that the transformer introduces in the measurement of a current when
                                        the transformation ratio is different from the rated value.
                                        Phase shift or phase error ψ (minute)
                                        Difference in phase between the primary and secondary currents, in angle minutes.
                                        Characteristics of voltage transformer
                                         Characteristics                                Rated values
                                        Rated voltage (kV)                              7.2       12         17.5     24          36
                                        Insulation level:
                                        b power frequency withstand (kV) 1 min          20        28         38       50          70
                                        b lightning impulse withstand (kV - peak)       60        75         95       125         170
                                        Frequency (Hz)                                  50 - 60
                                        Primary current Ipn (A)                         25 - 50 - 75 - 100 - 200 - 400 - 600 - 1000 -
                                                                                        1200 - 1600 - 2000 - 2500
                                        Short-time thermal current Ith (1 s)            12.5 - 16 - 20 - 25 - 31.5 - 40 - 50 kA
                                                                                        or
                                                                                        40 - 80 - 100 - 200 - 300 x In
                                        Secondary current Isn (A)                       1-5
                                        Accuracy power Pn (VA)                          2.5 - 5 - 7.5 - 10 - 15
AMTED302057EN.indd 13
DE58031EN
                                                                 Metering CT or protection CT
                                                                 We have to choose a CT with characteristics that are suited to its application.
                                                                 Metering CT
                                                                 This requires good accuracy (linearity zone) in an area close to the normal service
                                                                 current; it must also protect metering devices from high currents by saturating earlier.
                                                                 Protection CT
                                                                 This requires good accuracy at high currents and will have a higher precision limit
                                                                 (linearity zone) for protection relays to detect the protection thresholds that they are
                                                                 meant to be monitoring.
14 AMTED302057EN.indd
AMTED302057EN.indd 15
                                                                For example for class 5P the maximum error is y ± 5% at the accuracy limit current
                                                                and y ± 1% at the rated current.
                                                                Standardized classes are 5P and 10P. The choice depends on the application.
                                                                The accuracy class is always followed by the accuracy limit factor.
                                                                Accuracy class according to application
                                                                Application                                                   Class
                                                                Zero sequence protection differential protection              5P
                                                                Impedance relay amperemetric protection                       5P - 10P
16 AMTED302057EN.indd
                                                Selection criteria
                                                1 - Define the primary current Ipn
                                                Use the standard values prescribed by IEC regulations:
                                                10, 12.5, 15, 20, 25, 30, 40, 50, 60, 75 A and their decimal multiples.
                                                2 - Define the short circuit current for 1 second Ith
                                                The short circuit current generally refers to 1 second. Should this current be known
                                                for different time values “t”, calculate the value for 1 second by applying the following
                                                formula:
                                                Ith (for 1 sec.) = Ith x t
                                                e.g.: 25 kA for 3 sec. = 25 x 3 = 43.3 kA for 1 sec.
                                                3 - Calculate the “K” coefficient
                                                This value will be the access key to the various tables
                                                     lth x 1 sec.
                                                K=
                                                          lpn
                                                e.g.: Ipn = 100 A, Ith = 12.5 kA x 1 sec. => K = 12500/100 =125
                                                4 - Position on the table
                                                Enter the “K” column and position on the line corresponding to the K value
                                                immediately above the calculated value.
                                                e.g.: calculated K = 125 = K line =150
                                                5 - Check feasibility
                                                A current transformer is feasible with the specifications indicated in the columns
                                                marked with        .
                                                Remarks:
                                                For protection secondaries the following formula is guaranteed:
                                                ALF x VA = constant K
                                                e.g.: 10 VA / 5 P10 = 10 x 10 = 100
                                                5 VA / 5 P20 = 5 x 20 = 100
                                                WARNING: this equation is only guaranteed during the CTs selection phase.
                                                Terminal markings
          DE52792
AMTED302057EN.indd 17
                                                                                             Characteristics
                                                                                             b Standard reference IEC 60044-1
                                                                                             b Rated highest voltage: 7.2 - 12 - 17.5 - 24 kV
                                                                                             b Rated continous thermal current 1.2 x Ipn
                                                                                             b Frequency 50 or 60 Hz
                                                                                             b Rated secondary current standard 5 or 1A
                                                                                             b For primary current < 800 A Double primary ratio through primary coupling
                                                                                             b For primary current > 800 A Double primary ratio through secondary reconnection
                                                                                             b Value “K=Ith/Ipn” must be fixed in comparison with the smaller rated primary
                                                                                             current ratio
                                                                                             b Creepage distance > 700 mm
                                                                                             b Weight 25 kg.
                                                                                             Selection table
                   No. of secondaries per CT                                             1                                                             2
                   Standard types                                                        OAM3/N1                                                       OAM3/N2
                                                                                                                                                       1st measure secondary
                                                                                                                                                       Cl 0.5 Fs = 10
                                                                                                                                                       VA
                                                                                         Alternatively                                                 5    7.5 10   15    20   20   30   30   30   30   30
                   "K"                   lpn                                             Measure second                Protection                      2nd protection
                   k = lth/lpn           Rated primary current (A)                                                     second                          secondary
                                                                                         Cl 05                         Cl 5P                           Cl 5P
                   lth max 50 kA                                                         Fa = 10                       ALF = 10                        ALF = 10
                   for 1 s                                                               VA                            VA                              VA
                                         SR                    DR                        7.5 10    15   20   30   50   5    7.5 10   15   20   30 50   5    5   5    7.5   5    10   10   15   20   30   50
                                         1000
                                         1200
                                         1250
                                                               500-1000
                                                               600-1200
                   For other characteristics, please consult us.
                                                                                             Dimensions
                                                                                                                                                                                 4 holes
       DE58040EN
M12 x 23
                                                                                 341
                                                                                                               302
                                                                                   333
                                                                                                             294
270
18 AMTED302057EN.indd
                                                                                              Characteristics
                                                                                              b Standard reference IEC 60044-1
                                                                                              b Rated highest voltage: 7.2 - 12 - 17.5 - 24 - 36 - 40.5 kV
                                                                                              b Rated continous thermal current 1.2 x Ipn
                                                                                              b Frequency 50 or 60 Hz
                                                                                              b Rated secondary current standard 5 or 1 A
                                                                                              b For primary current < 800 A Double primary ratio through primary coupling
                                                                                              b For primary current > 800 A Double primary ratio through secondary reconnection
                                                                                              b Value “K=Ith/Ipn” must be fixed in comparison with the smaller rated primary
                                                                                              current ratio
                                                                                              b Creepage distance > 1100 mm
                                                                                              b Weight 35 kg.
                                                                                              Selection table
                      No. of secondaries per CT                                           1                                      2                                   3
                      Standard types                                                      OAM7/N1                                OAM7/N2                             OAM7/N3
                                                                                                                                                                     1st measure
                                                                                                                                                                     secondary
                                                                                                                                                                     Class 0.5
                                                                                                                                                                     Fs = 10
                                                                                                                                                                     VA
                                                                                                                                                                     5 10 15 20 30
                                                                                                                                 1st measure secondary               2nd protection
                                                                                                                                                                     secondary
                                                                                                                                 Class 0.5                        Class 5P
                                                                                                                                 FS = 10                          ALF = 10
                                                                                                                                 VA                               VA
                                                                                          Alternatively                          5 7.5 10 15 20 20 30 30 30 30 30 5 5 7.5 10 15
                      "K"                   lpn                                           Measure second     Protection second   2nd protection secondary         3rd protection
                      k = lth/lpn           Rated primary current (A)                                                                                             secondary
                                                                                          Class 0.5          Class 5P            Class 5P                         Class 5P
                      lth max 50 kA                                                       Fa = 10            ALF = 10            ALF = 10                         ALF = 10
                      for 1 s                                                             VA                 VA                  VA                               VA
                                            SR                    DR                      7.5 10 15 20 30 50 5 7.5 10 15 20 30 50 5   5   5 7.5 5 10 10 15 20 30 50 5    5 7.5 10 15
                      100                   10 - 800              10-20 - 400-800
                      150                   10 - 300              10-20 - 300-600
                      200                   10 - 300              10-20 - 300-600
                      250                   10 - 200              10-20 - 200-400
                      300                   10 - 150              10-20 - 150-300
                      400                   10 - 100              10-20 - 100-200
                      500                   10 - 50               10-20 - 100-200
                                            1000
                                            1200
                                            1250
                                            2000
                                            2500
                                                                  500-1000
                                                                  600-1200
                                                                  750-1500
                                                                  1000-2000
                      For other characteristics, please consult us.
                                                                                              Dimensions
          DE58041EN
                                                                                                                                              4 holes     8 holes
                                                                                                                                              M12 x 23    M12 x 23
                                                                       432                         393
                                                                         424
                                                                                                 385
270
AMTED302057EN.indd 19
                                           Selection guide                                                  22
                                           Technical description                                            22
                                           Voltage transformers                                             27
                                           Phase-earth 7.2 to 24 kV - Type OVF2n/S1 - OVF2n/S2 - OVF2n/S3   27
                                           Phase-earth 36 kV - Type OVF3n/S1 - OVF3n/S2 - OVF3n/S3          28
                                           Phase-phase 7.2 to 24 kV - Type OVC2/S1 - OVC2/S2                29
                                           Phase-phase 36 kV - Type OVC3/S1 - OVC3/S2                       30
AMTED302057EN.indd 21
Connection of a VT
22 AMTED302057EN.indd
                                        Characteristics (cont.)
                                        Accuracy class
                                        Defines the error limits guaranteed relative to the transformation ratio and the phase
                                        shift under specified conditions of power and voltage.
                                        Voltage error ε (%)
                                        Error that the transformer introduces into the voltage measurement when the
                                        transformation ratio is different from the rated value.
                                        Phase shift or phase error (ψ in minutes)
                                        Phase difference between primary and secondary voltages, in angle minutes.
                                        Rated voltage factor KT
                                        This is the factor, a multiple of the rated primary voltage, which determines the
                                        maximum voltage which the transformer must meet the specified temperature rise
                                        and accuracy recommendations. The maximum operating voltage depends on the
                                        network neutral system and the earthing conditions of the primary winding.
                                        Table of voltage factors KT
                                         Voltage factor           Rated duration          Connection mode Network neutral
                                        1.2                       Continuous              Between phases               Any
                                                                  Continuous              Between the                  Any
                                                                                          star-connected
                                                                                          transformer neutral
                                                                                          point and earth
                                        1.2                       Continuous              Between phase and            DIrectly earthed
                                                                                          earth
                                        1.5                       30 s
                                        1.2                       Continuous              Between phase and            Earthed via a limiting
                                        1.9                       30 s                    earth                        resistor with automatic
                                                                                                                       earthing fault
                                                                                                                       elimination
                                        1.2                       Continuous              Between phase and            Insulated neutral
                                        1.9                       8h                      earth                        without automatic
                                                                                                                       earthing fault
                                                                                                                       elimination
                                        1.2                       Continuous              Between phase and            Earthed via a limiting
                                                                                          earth                        resistance with
                                                                                                                       automatic earthing
                                                                                                                       fault elimination
                                        VT operating characteristics
                                        Operation of a VT is more simple than that of a CT because the secondary voltage
                                        is virtually independent of the load, due to it being connected through a high impedance
                                        (virtually used in an open circuit).
                                        Therefore, the secondary must not be short circuited. Under these conditions
                                        an excessively high current will damage the transformer.
AMTED302057EN.indd 23
                                              VT connections
                                              Several metering connection arrangements are possible (fig. opposite)
                                              b star-connection of 3 transformers: requires 1 isolated MV terminal for each
                                              transformer
                                              b connecting to 2 transformers, so-called V-connection: requires 2 isolated MV
                                              terminals per transformer.
DE58035
Vrsd = 3 • V0 = V1 + V2 + V3
DE58038
24 AMTED302057EN.indd
                                        b Class 0.5 corresponds to an error y ± 0.5% for the rated primary voltage,
                                        with the accuracy load over the secondary.
                                        b Class 1 corresponds to an error y ± 1% in the same conditions.
                                        For a given accuracy class, voltage and phase-shift errors must not exceed
                                        the values indicated in the table opposite.
                                        Error limits according to the accuracy class
                                        Accuracy class                   Voltage error                    Phase-shift error
                                                                         (ratio) ± %                      ± mm
                                        0.2                              0.2                              10
                                        0.5                              0.5                              20
                                        1                                1.0                              40
                                        Example:
                                        Metering voltage transformer 20 000 / 110 , 50 VA, cl. 0.5
                                                                         3        3
                                        b rated primary voltage 20000 V/3, rated secondary 110 V/3
                                        b accuracy power 50 VA
                                        b accuracy class 0.5. The table of limit error values gives, under the specified
                                        conditions for the accuracy class:
                                        v a primary voltage 80% to 120% of the rated voltage (16 kV to 24 kV)
                                        v a load of between 25% and 100% of the accuracy power, i.e. between
                                        12.5 VA and 50 VA with an inductive power factor of 0.8, the metering errors will be
                                        y ± 0.5% for voltage and y ± 20 min for phase shift.
                                        Example:
                                        Protection voltage transformer 20 000 / 110 , 100 VA, 3P, KT = 1.9 8 h
                                                                          3         3
                                        b the rated primary voltage 20000 V/3, rated secondary 110 V/3
                                        b accuracy power 100 VA
                                        b accuracy class 3P. The table of limit values shows that for:
                                        v a primary voltage of 5% of the rated voltage at KT times the rated voltage,
                                        i.e. 20000 x 5% = 1000 V at 20000 x 1.9 = 38000 V
                                        v a load of between 25% and 100% of the accuracy power, in other words of
                                        between 25 VA and 100 VA with a power factor of 0.8, the metering error will be
                                        y ± 3% in voltage and y ± 120 min in phase shift.
AMTED302057EN.indd 25
                                                                      DE52794
         According to the installation voltage (U) and the type
         of transformer connection:
         b between phase and ground (Upn = U/3)
         b between phase and phase (Upn = U)
         VT accuracy is always guaranteed to be between
         0.8 Upn and 1.2 Upn. Use this information to choose
         standard voltage values.
         2 - Define the rated insulation level
         The rated insulation level should be that immediately
         above the primary voltage level.
         Note: the industrial power frequency test according
         to IEC standards should be carried out by applying
         the formula:
         5 x Upn with a maximum value given by the
         corresponding insulation value.
         3 - Define the secondary voltage Usn
         The standard values are:
         b 100 and 110 divided by 3, for instrument and
         protection Y-connected windings
         b 100 and 110 divided by 3, for residual voltage open
         delta connection.
         4 - Define the frequency
         Values are either 50 or 60 Hz.
         5 - Voltage factor
         It is the factor by which the primary voltage Upn
         should be multiplied in order to determine
         the maximum insulation voltage for the Um device:
         b 1.9 for 8 hours, for insulated pole voltage
         transformers (phase-ground)
         b 1.2 permanent, for insulated pole voltage
         transformers (phase-phase).
         6 - Position on the table
         Enter the column corresponding to the number of
         secondaries and the type of (actual or relative)
         performance simultaneity.
         7 - Check feasibility
         The feasible characteristics are identified by
         the columns with boxes marked:
26 AMTED302057EN.indd
                                                                                           Description
          PE50727
                                                                                           Characteristics
                                                                                           b Standard reference: IEC 60044-2
                                                                                           b Standard primary voltage Upn: 3 - 3.3 - 5 - 5.5 - 6 - 6.6 - 10 - 11 - 13.8 - 15 - 20-
                                                                                           22:3 kV
                                                                                           b Rated insulation level: 7.2 - 12 - 17.5 - 24 kV
                                                                                           b Rated secondary voltage Usn: 100:3 - 100:3 - 110:3 - 110:3 V
                                                                                           b Frequency: 50 or 60 Hz
                                                                                           b Rated voltage factor: 1.9 for 8 hours
                                                                                           b Thermal burden: 300 VA
                                                                                           b Creepage distance > 700 mm
                                                                                           b Weight 35 kg.
                                                                                           Table of options
                      No. of secondaries for VT              1                                  2                                                                      3
                      Standard type                          OVF2n/S1                           OVF2n/S2                                                               OVF2n/S3
                      Application                            Measuring or protection            1st measure                      1st measure or protection             1st 2nd measure or
                                                                                                2nd protection or measure        2nd residual voltage                  protection
                                                                                                                                                                       3rd residual voltage
                      Standard secondary voltage (V)         100:3 or 110:3                     100:3 - 100:3                    100:3 - 100:3                         100:3 or 110:3 and
                                                                                                or 110:3 - 110:3                 or 110:3 - 110:3                      100:3 or 110:3
                      Operation                              -                                  Separate                         Separate                              Simultaneous separate
                      3rd secondary        Accuracy class    -                                  -                                -                                     3P
                                           Output            -                                  -                                -                                     75         50    100
                      2nd secondary        Accuracy class    -                                  0.5 or 1                         3P                                    0.5 or 1
                                           Output            -                                  15    20   30    30    50   75   50        50   75   50    75     100 30          50    75
                      1st secondary        Accuracy class    0.2                0.5             0.2              0.5             0.2                 0.5               0.5
                                           Output            30       40   50   50    75   100 15     20   30    30    50   75   25        30   50   50    75     100 30          50    75
                      For other characteristics, please consult us.
                                                                                           Dimensions
                                                                                                                                                     4 holes 14 x 25              375
          DE58042EN
                                                                                                                321                  312
                                                                                                                                                       280 220 185
49
AMTED302057EN.indd 27
                                                                                       Description
       PE50728
                                                                                       Characteristics
                                                                                       b   Standard reference IEC 60044-2
                                                                                       b   Standard primary voltage Upn: 30 - 33 - 35:3 kV
                                                                                       b   Rated insulation level: 36 kV
                                                                                       b   Rated secondary voltage Usn: 100:3 100:3 110:3 110:3 V
                                                                                       b   Frequency 50 or 60 Hz
                                                                                       b   Rated voltage factor: 1.9 for 8 hours
                                                                                       b   Thermal burden: 450 VA
                                                                                       b   Creepage distance > 1100 mm
                                                                                       b   Weight 45 kg.
                                                                                       Table of options
                   No. of secondaries for VT              1                                 2                                                                    3
                   Standard type                          OVF3n/S1                          OVF3n/S2                                                             OVF3n/S3
                   Application                            Measuring or protection           1st measure                       1st measure or protection          1st 2nd measure or
                                                                                            2nd protection or measure         2nd residual voltage               protection
                                                                                                                                                                 3rd residual voltage
                   Standard secondary voltage (V)         100:3 or 110:3                    100:3 - 100:3                     100:3 - 100:3                      100:3 or 110:3 and
                                                                                            or 110:3 - 110:3                  or 110:3 - 110:3                   100:3 or 110:3
                   Operation                              -                                 Simultaneous                      Separate                           Simultaneous separate
                   3rd secondary      Accuracy class      -                                 -                                 -                                  3P
                                      Output              -                                 -                                 -                                  75         50   100
                   2nd secondary      Accuracy class      -                                 0.5 or 1                          3P                                 0.5 or 1
                                      Output              -                                 15     20   30   30    50   75    50    50   75    50    75      100 30         50   75
                   1st secondary      Accuracy class      0.2                0.5            0.2              0.5              0.2              0.5               0.5
                                      Output              30       40   50   75    100 150 15      20   30   30    50   75    25    40   50    50    75      100 30         50   75
                   For other characteristics, please consult us.
                                                                                       Dimensions
                                               447                                                                                                                      375
       DE58043EN
                                                                                                                                           4 holes 14 x 25              345
                                                                                                                                           4 holes Ø13
                                                                                                                                                                        320
25 max.
28 AMTED302057EN.indd
                                                 Description
          PE58462
                                                 Characteristics
                                                 b   Standard reference IEC 60044-2
                                                 b   Standard primary voltage Upn: 3 - 3.3 - 6 - 6.6 - 10 - 11 - 15 - 20 - 22 - 24 kV
                                                 b   Rated insulation level: 7.2 - 12 - 17.5 - 24 kV
                                                 b   Rated secondary voltage Usn: 100 -100 or 110 -110 V
                                                 b   Frequency 50 or 60 Hz
                                                 b   Rated voltage factor: 1.2 ill.
                                                 b   Thermal burden:
                                                 v   OVC2/S1 = 500 VA
                                                 v   OVC2/S2 = 250 ± 250 VA
                                                 b   Creepage distance phase-ground > 700 mm
                                                 b   Creepage distance phase-phase > 1400 mm
                                                 b   Weight 33 kg.
                                                 Table of options
                                                  No. of secondaries for VT                 1                             2
                                                  Standard type                             OVC2/S1                       OVC2/S2
                                                 Application                                Measuring or protection       1 for measure or
                                                                                                                          protection (1st sec.)
                                                                                                                          1 for protection (2nd sec.)
                                                 Standard secondary voltage (V)             100 or 110                    100 - 100 or 110 - 110
                                                 Operation                                  -                             Simultaneous
                                                 2nd secondary        Accuracy class        -                             0.5 or 1     0.5 or 1
                                                                      Output                -                             15      25   30    50    100
                                                 1st secondary        Accuracy class        0.2                 0.5       0.2          0.5
                                                                      Output                25    50     50     75    100 15      25   30    50    100
                                                 Feasibility
                                                 For other characteristics, please consult us.
                                                 Dimensions
          DE58044EN
                                                                                                                                375
                                                                                                  4 holes 14 x 25               345
                                                                                                  4 holes Ø13                   320
                                                                                                                                436
                                                     109       53
AMTED302057EN.indd 29
                                          Description
       PE50730
                                          Characteristics
                                          b   Standard reference IEC 60044-2
                                          b   Standard primary voltage Upn: 30 - 33 - 35 kV
                                          b   Rated insulation level: 36 kV
                                          b   Rated secondary voltage Usn: 100-100 or 110-110 V
                                          b   Frequency: 50 or 60 Hz
                                          b   Rated voltage factor: 1.2 ill.
                                          b   Thermal burden:
                                          v   OVC3/S1 500 VA
                                          v   OVC3/S2 250 ± 250 VA
                                          b   Creepage distance phase-ground > 900 mm
                                          b   Creepage distance phase-phase > 1560 mm
                                          b   Weight 43 kg.
                                          Table of options
                                           No. of secondaries for VT                 1                           2
                                           Standard type                             OVC3/S1                     OVC3/S2
                                          Application                                Measuring or protection     1 for measure or
                                                                                                                 protection (1st sec.)
                                                                                                                 1 for protection (2nd sec.)
                                          Standard secondary voltage (V)             100 or 110                  100 - 110 or 110 - 110
                                          Operation                                  -                           Simultaneous
                                          2nd secondary        Accuracy class        -                           0.5 or 1   0.5 or 1
                                                               Output                -                           15    20   30    50      100
                                          1st secondary        Accuracy class        0.2               0.5       0.2        0.5
                                                               Output                25    50     50   75    100 15    20   30    50      100
                                          Feasibility
                                          For other characteristics, please consult us.
                                          Dimensions
       DE52799
30 AMTED302057EN.indd
Ordering informations 32
AMTED302057EN.indd 31
         Order form                                                            Tick the appropriate box   X    and fill in these          the needed value
                                                                                        : boxes for double primary voltage
         Common characteristics
         Type                                                                                                                                                     Quantity
Frequency 50 Hz 60 Hz
Number of secondaries 1 2 3
         CT’s specifications
         Primary
         Rated short time current                                                                                       (kA)                                          (kA)
Rated primary current 1st rated (A) 2nd rated (A) 3rd rated (A)
         Secondary
                                              1st secondary                                   2nd secondary                                    3rd secondary
Accuracy class
Security factor (FS) / accuracy limit factor (ALF) (FS / ALF) (FS / ALF) (FS / ALF)
         VT’s specifications
         Primary
         Phase type                                                                                       Phase / ground                                 Phase / phase
Rated primary voltage 1st rated (kV) 2nd rated (kV) 3rd rated (kV)
         Secondary
                                              1st secondary                                   2nd secondary                                    3rd secondary
Accuracy class
Simultaneous operation
Separate operation
         Options accessories
         Routine test                                                                                                           French            English                 Spanish
32 AMTED302057EN.indd
AMTED302057EN.indd 33
34 AMTED302057EN.indd
AMTED302057EN 01-2012