Basler AVR AVC63-7 Manual

This document provides installation, operation, and maintenance instructions for the Basler AVR AVC63-7 voltage regulator. The AVC63-7 is a half-wave voltage regulator designed for 50/60 Hz brushless generators from 100kW to 500kW. It uses solid-state technology to maintain generator line voltage within ±0.25% accuracy from no load to full load. The regulator is small, rugged, and has features like automatic voltage build-up, parallel droop compensation, and overexcitation shutdown.

Uploaded by

Douglas Sobral
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views5 pages

Basler AVR AVC63-7 Manual

This document provides installation, operation, and maintenance instructions for the Basler AVR AVC63-7 voltage regulator. The AVC63-7 is a half-wave voltage regulator designed for 50/60 Hz brushless generators from 100kW to 500kW. It uses solid-state technology to maintain generator line voltage within ±0.25% accuracy from no load to full load. The regulator is small, rugged, and has features like automatic voltage build-up, parallel droop compensation, and overexcitation shutdown.

Uploaded by

Douglas Sobral
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Instruction Manual

Installation • Operation • Maintenance

Basler AVR AVC63-7


AVR AVC63-7 for Basler generator

Ruitai industry Co.,Ltd.


Tel: +86 577 80221899
Fax: +86 577 56667563
Email: sales@china-avr.com
www.china-avr.com

Page 1
AVC63-7
VOLTAGE REGULATOR

Using enhanced technology, the AVC63-7 half wave voltage regulator is


designed for use on 50/60 Hz brushless generators. This encapsulated
regulator is small in size, ruggedly constructed, and incorporates solid
state technology with frequency compensation, automatic voltage build-
up, and parallel droop as standard.

FEATURES
• Integrated circuitry for compact size, simplicity, high reliability.
• Extremely rugged.
FEATURES AND
• Exciter field current 7A continuous, 11.5A forcing. APPLICATIONS
• Regulation accuracy better than ± .25% no load to full load. this page
• Fast response.
• Frequency compensation.
DESCRIPTION AND
• Overexcitation shutdown.
SPECIFICATIONS
• Built-in parallel droop compensation. pages 2 & 3
• EMI suppression.
• Available from stock. INTERCONNECT
DIMENSIONS
DRAWING
• CSA certified.
page 3
• Qualified to the requirements of: page 4
- IEEE C37.90.1 for Surge Withstand Capability.
- ASTM B117-73, Method 711-1C, for Salt Fog.
INSTRUCTION MANUAL
ADDITIONAL INFORMATION DIMENSIONS
page 4
INSTRUCTION MANUAL
Request Publication 9302800990

ROUTE 143, BOX 269 HIGHLAND, ILLINOIS U.S.A. 62249 PHONE 618-654-2341 FAX 618-654-2351
SVP-1
9-96
AVC63-7

DESCRIPTION
The AVC63-7 model of voltage regulator maintains gen- line voltage build-up with a voltage input to the regulator
erator line voltage on brushless generators from 100kW to of at least 6 Vac. Customer accessible stability,
over 500kW in size. The voltage regulator senses genera- underfrequency and range adjusts enable fine tuning of
tor average voltage to maintain a precise regulation band the voltage regulator to the generator in use.
within ±.25 percent. This is accomplished by converting
Figure 1 demonstrates the underfrequency characteris-
a 240 Vac single phase power input to a controlled DC
tics of the voltage regulator during prime mover low
signal to the generator’s exciter field. The solid-state
speed conditions. Customer curve selection matches
voltage build-up circuit will enable automatic generator
the voltage regulator to 50 or 60 Hz systems.

Figure 1 - Frequency Compensation Characteristic

SPECIFICATIONS

2
AVC63-7

SPECIFICATIONS (continued)
DC OUTPUT POWER: 7 Adc at 63 Vdc maximum con- VOLTAGE BUILDUP: Internal provisions for automatic
tinuous, 11.5 Adc at 105 Vdc ten second forcing. voltage buildup from generator residual voltages as
(Forcing with 240 Vac nominal input). low as 6 Vac.

EXCITER FIELD DC RESISTANCE: 9.0 ohms mini- TERMINATIONS: 1/4 “Fast-On” Terminals.
mum; 100 ohms maximum.
POWER DISSIPATION: 35 Watts maximum.
AC POWER INPUT: Operating range: 190-277 Vac
single phase, 50/60 Hz ±10%. Burden 900VA. OPERATING TEMPERATURE: -40°C (-13°F) to
+60°C (+140°F).
SENSING INPUT: 190-240 Vac single phase, 50/60Hz
±10%. Burden <5VA. STORAGE TEMPERATURE: -40°C (-40°F) to +85°C
(+185°F).
VOLTAGE ADJUST RANGE: 170-264 Vac.
VIBRATION: Withstands 1.2 Gs at 5 to 26 Hz; 0.036”
REGULATION ACCURACY: Better than ±.25% no load double amplitude at 27 to 52 Hz; and 5 Gs at 53 to
to full load. 1000 Hz.

RESPONSE TIME: Less than 1.5 cycles for ±5% SHOCK: Withstands up to 15 Gs in each of three
change in sensing voltage. mutually perpendicular axes.

EMI SUPPRESSION: Internal electromagnetic WEIGHT: 10 oz. (0.28 kg) Net.


interference filtering.

PARALLEL COMPENSATION: 5A input from a current


transformer with 10VA burden @ 0.8PF.

Figure 2 - Typical Interconnection Diagram


3
AVC63-7

Figure 3 - Outline Drawing

ROUTE 143, BOX 269, HIGHLAND, ILLINOIS U.S.A. 62249 P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE
PHONE 618-654-2341 FAX 618-654-2351 PHONE (33-3-88) 87-1010 FAX (33-3-88) 87-0808