90% found this document useful (10 votes)
4K views15 pages

LV Protection Relay Seminar

This document discusses protective devices and equipment for low voltage systems. It provides information on: 1) Recommended protective devices for LV equipment include fuses, circuit breakers, and motor circuit protectors. Protection requirements include phase fault, ground fault, overload, short circuit, and arc flash protection. 2) LV equipment includes switchgears, switchboards, motor control centers, panels, transformers, and motors. Circuit breakers can have thermal, magnetic, or thermal-magnetic characteristics. Fuses have inverse time or time-current characteristics. 3) Standards like IEC and ANSI have different symbols and methods for protective devices but cover similar concepts like grounding, short circuit calculation methods, and

Uploaded by

Ciel Aire
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
90% found this document useful (10 votes)
4K views15 pages

LV Protection Relay Seminar

This document discusses protective devices and equipment for low voltage systems. It provides information on: 1) Recommended protective devices for LV equipment include fuses, circuit breakers, and motor circuit protectors. Protection requirements include phase fault, ground fault, overload, short circuit, and arc flash protection. 2) LV equipment includes switchgears, switchboards, motor control centers, panels, transformers, and motors. Circuit breakers can have thermal, magnetic, or thermal-magnetic characteristics. Fuses have inverse time or time-current characteristics. 3) Standards like IEC and ANSI have different symbols and methods for protective devices but cover similar concepts like grounding, short circuit calculation methods, and

Uploaded by

Ciel Aire
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

LV EQUIPMENT PROTECTION

*Recommended to use ETAP (Electrical Simulator and Analysis) ver. 16.1


PROTECTIVE DEVICES (Fuses, ACB, MCCB, MCB, MCP)
*Requirement for PEE:
 Phase Fault Protection
 Protection Coordination
 Ground Fault Protection *MCP – Motor Circuit Protector
 Short Circuit Protection and Voltage Drop
 Overload Protection
 Arc Flash
LV EQUIPMENT
*IEC and ANSI Standard (Differs in Symbols, Methods and Terms)
 Switchgears
Ex: ANSI – Ground
 Switchboards
IEC – Earth
 LV MCC
Short Circuit Calculation Methods
 LV Panels
 Transformers
 Motors SYSTEM VOLTAGE LEVELS (IEC 60038)
 Low Voltage - 1000V
LV CIRCUIT BREAKER CHARACTERISTICS  Medium Voltage - 1000V to 35kV
 High Voltage - 35kV to 230kV
 Thermal (Small MCCBs, MCB)
 Extra High Voltage -245kV to 1200kV
 Magnetic (MCP)
 Thermal-Magnetic (MCCB, MCP)
*Log,Log Graph (Necessary for Coordination)
LV FUSES
 Inverse Characteristic *Inverse – The higher the current Thermal – Overload *Thermal in most MCCB is fixed
the faster it act. Magnetic – Short Circuit
LV-ACB (PCB)
 Short Time Pickup (STPU) *Fuse is reliable because its fast acting PROTECTION CURVES
 Long Time Pickup (LTPU)
 Long Time Delay (LTD) Thermal – Magnetic Magnetic Thermal
 Short Time Delay
 Instantaneous
 Sensor / Plug

AT – Ampere Trip *Only in MCB, MCCB

AF – Ampere Frame *Physical size of the breaker *MCP – L Graph (uses magnetic for short circuit protection only)
*Interchangeability purposes Ex: Fire Pump Motor needs to run even on overload or grounded
conditions (will not run on short circuit condition)
*No Ampere Trip in ACB only Ampere Frame because it can be setup) *Magnetic-Only Circuit Breaker is Rare
Locked Rotor Current: 5x FLA
SAMPLE SWITCHGEAR (ACB)
Ex: 20A Motor FLA
LRA = 5(IFL)
= 5 (20)
= 100 A

*Protection system must be fast enough to protect but not fast enough to
lose coordination

Consider Starting Characteristic of Motor

Notes:

*ACB – Consider location and capability to maintain


*For Safety – selection of rating
*Cross and Latch and Interrupting or Making Rating

*Two Rating of Breaker


-Making
-Breaking

*Adjust design based on actual availability of equipment


SWITCH GEAR PROTECTION
234 for copper (zero resistance @ -234.5°C)
Example Problem: 228 for aluminum

Note:
√ *For XLPE: T2=250°C; T1=90°C

CABLE DAMAGE CURVE

Assume Demand Load: MDL = 90A or 100A


MATRIX:
MATRIX:
T (sec) I (A)
T (sec) I (A) (Min) (Max)
0.25 20 kA
1000 500 1 10 kA
0.015 1800
70 1000
PLOT:
Note:
* Directly acting element has tolerance (BAND)
* Band (min and max) PLOT:
* Tolerance is available at product catalog

For conductor protection side:


Use: 70mm2 XLPE (based on catalog)

PLOTTING OF CONDUCTOR (CONSIDERED IN PROTECTION)

ANSI FORMULA: WHERE:


I = ISC (Short circuit, Amps)
( ) ( ) A = Conductor area (Circular mils)
t = Time of short circuit (secs)
IEC FORMULA: T1 = Max operating temp (ex. 75°C)
T2 = Max short circuit temp (ex.150°C)
( ) * ( )+
TRANSFORMER DAMAGE CURVE
 Through Fault Protection Curve Example Problem:
 Reference:
- Through Fault: IEEE C57
- Short Circuit: IEEE C37
- ANSI Transformer Handbook Assume: ACB, Square D Micrologic 3.0
 Check suppliers or catalog (Data can be found at catalogs)

MATRIX:

Graph Point t (sec) (x) multiples @Secondary @Primary


Note: (Not Amps but Multiples)
1 300 3 1506 720
2 100 4 2008 960
Question:
3 20 8 4016 1920
IS 20MVA, 220V Secondary possible?
PLOT:
Consider:
*Band = Range
*ST Band
Short Circuit Current:
*Margin = 1.25%

√ LTPU: 115% ~ 125% of IFL


= 502 (1.2)
~ 600 A

*Primary not more than 125% of
rated primary current.

LSIG SETTING, Sensor = 800A


No, Because Short Circuit current
is too high.


COMBINED LOAD CHARACTERISTIC SHORT CIRCUIT PROTECTION COORDINATION
 Phase Fault Protection
Ex: Motor + Static Loads  Ground Fault Protection

VARIAC DIAGRAM: Copper Loss

TRANSFORMER SHORT CIRCUIT TEST


*Open Circuit Test – Core Loss
*Do not reach Vn because it will short circuit

VRDG = VAPP = IL ZØ

%Z or Percent Impedance
Z or Per-unit Impedance (w/o 100)
ZPER UNIT
Note:
*Considered in Generator:
*Winding = Copperloss or LineLoss = IL2 R
-Max Step Load (Bulk Increase in load)
-Max Rejection of Load (Bulk Decrease in load)
Z=
-Transient Stability

*Inrush current is only from source (ex. Primary energization)


(x8 of current)
*Linear means not direct acted but simulated electronically
DERIVIATION OF √ POWER TRIANGLE

S3Ø = 3 S1Ø
S1Ø = VØIØ

If Wye: If Delta:

VECTOR DIAGRAM ( ) ( )
√ √
√ √

̅̅̅ ̅̅̅̅ ̅̅̅̅̅ ̅̅̅̅ *Wye or Delta do not affect power formula

POWER BASE: (PB)

1. √

2.

3.


4.
√ ( √ )

NOTE:
√ *Voltage should not change ZPER UNIT
*Per-unit is unitless


THREE PHASE FAULT SHORT CIRCUIT FORMULA Example Problem:

√ √ √
( )

( )

LINE TO LINE FAULT


( )

LINE TO GROUND FAULT

NOTE:
*In Solidly Grounded System:
ZOT = ZP-SYS

*In Resistance Grounded System:


ZOT = ZP-SYS + 3Zg
MATRIX For POWERBASE (PB), Use the highest MVA (Utility/Source) @1500MVA

1ST Cycle (Max) 30 Cycles (Min)


Bus VL (kV) Z1 IF3Ø (kA) Z1=Z2 ZOT IFL-L IFL-G IF3Ø * +* +
B1 13.80 9.86 6.36 11.50 10.50 4.76 5.62 5.50
B2 4.16 34.73 5.99 41.50 3152.67 4.35 0.192 5.02 @1500MVAb (POWERBASE)
B3 0.40 147.50 14.70 161.50 120.00 11.61 14.66 13.41 *Convert first to base unit
Sizing of kA and Bus Protection Setting

IMPEDANCE DIAGRAM
[ ]
Z2(-) *just remove power
source
[ ]
*Hila hila method, Z1

[ ]

[ ][ ]

[ ][ ]

[ ][ ]

Z1 - Determine total impedance at Buses


*Use Buses (B1, B2, B3) as reference (hila-hila) then use Ohm’s Law.

Z2 – Total impedance from reference Bus to utility (No Motor load)

Contribution to utility and motor in Short Circuit (•) @ 1 cycle


Ex. @BUS1

√ √
*No motor contribution at 30 cycles @BUS 3

ZOT (Impedance to ground) Z0B3 = 120

@BUS 1

Z0B1 = 10.5

Fault Currents at 30 Cycles

@BUS 1

@ 30 cycles

√ √

@BUS 2

√ √
( ) ( )
Z0B2 = XT2 + 3ZG



( ) @BUS 2 @BUS 3

Z0B2 = 30 + 3(1040.89)
Z0B2 = 30 + 3122.67
Z0B2 = 3152.67
COMMON PROTECTION CURRENT TRANSFORMER CONCEPT

WHERE: CT POLARITY
50 = Instantaneous Overcurrent • Polarity Mark
51 = Time Delay Overcurrent
= Current Transformer
*S = 5 A (ANSI)
= Primary/Secondary *S = 1 A (IEC)
Current Ratio

= Device 52, Circuit Breaker Threshold (relay reading)

N = Ground Protection * +

( )

(Setting)
SAMPLE DIAGRAM (3 PHASE)

@8 kA Fault (3 Phase)

* +

*Partial Saturation

@7kA Fault (Line to Line)

* +

L-L Fault
*Additional Relay for L-G Fault for “Back-up Protection”
(To delay action)
*By Zero Sequence Current:
= 200/3 A *Inductive kick

* +* +

For Transformer:
(Set to half of reading)
*Multifunction Relay
*87T is recommended for ≥5MVA TF
*Overlapping of Zone
*Bus Differential
ZCT – Usually used for motor feeder
*87 - Differential Protection (Sensitive)
- No Coordination needed
*Differential Relay must be same manufacture date, model, brand
*Insulation Percent
-100%
For Motor: “PROTECTION IS
-133% SCIENCE AND ART”
-177%
-Jimenez, PEE

*References
-IEEE Colored Books
-Stevenson’s
-Schaumm’s Outline

*Restricted Earth Fault


*Full Protection – All Lines
*GIS Switchgear
*Auto Transformer (Big Capacity)
*If has shielding:
SHIELDING > GROUND WIRE > ENTER THE CT
Ungrounded System
> GROUND BUS

*MGB – Main Ground Bus


SAMPLE PROTECTION RELAY SYSTEM TRANSFORMER DIFFERENTIAL

RC – Restraining Coil OC – Operating Coil

*Always consider Polarity: Input


“Away – Away
“Away – Towards”

*Need to maximize protection, not just transformer


*Up to switchgear to protect the cables
Dyn11
*Phase-Shifting Transformer is utilized to
D – Higher Voltage prevent harmonics.
y – Lower Voltage *Delta Configuration – Theoretically has
n – Neutral neutral.
“Agree or Disagree with
11 – O’clock (Phase-Shift) a right reason”

-Jimenez, PEE

*Just re-arrange the wirings to match the phase


Total Current:
@MOTOR:
Total Load: √

Ground Protection: 10 to 30% if IFL of Transformer

Instantaneous/STPU: set according to total load requirements

Ground Setting: 10 to 30% if IFL

@PRIMARY
*use L-L if delta-wye
*Characteristic of motor
starting: √
-Cold Motor If 3Ø fault is one unit: ( )
-Hot Motor
RA51 Setting:
*CLASS 10 – Its trips 10 Pickup 600Max
seconds of starting current.
Set:
*Self-protection up to 1.25
of FL current. * +* + 100 A @4160V, 1040 A @400V
300 A
*Service Factor (SF) – can
overload up to certain EI-IEC (Extremely Inverse)
percentage @ rated
ambient temperature. Where; K = 80, M = Multiple

*Up to 13.41 kA
(Short Circuit)
[ ] Characteristic K
Normal Inverse 0.02 0.14
@TRANSFORMER: Very Inverse 1.0 13.5
Ext. Inverse 2.0 80
* + Long Time 1.0 120

*Allow up to 1.25x *TCC – Time Current Curve


PROTECTION COORDINATION GRAPH

You might also like