Vito Tronic
Vito Tronic
Service Instructions
for use by heating contractor
IMPORTANT
Certified as a component part Read and save these instructions
of Viessmann boilers only
for future reference.
Warranty
Information contained in
this and related product
Product documentation documentation must be
Read all applicable documentation read and followed. Failure
before commencing installation. Store to do so renders warranty
documentation near boiler in a readily null and void.
accessible location for reference in the
future by service personnel.
For a listing of
applicable literature,
please see section
entitled “Important
Regulatory and
Installation Requirements.”
2
General information
Safety Terminology
Take note of all symbols and notations intended to draw attention to potential hazards or important product information.
These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
DANGER
Indicates an imminently hazardous
situation which, if not avoided, will
result in death, serious injury or
substantial product / property damage.
WARNING
Indicates an imminently hazardous
situation which, if not avoided, could
result in death, serious injury or
substantial product / property damage.
CAUTION
Indicates an imminently hazardous
situation which, if not avoided, may
result in minor injury or product /
property damage.
IMPORTANT
Helpful hints for installation, operation
or maintenance which pertain to the
product.
5351 338 v1.8
3
Product Information
These instructions are not required for the Vitotronic 100, GC1 used in multi-boiler
systems with the Vitocontrol-S, VD2/CT3/CM2.
4
Index
Page
Installation Mounting the Front Part of the Control Unit (VD2/VD2A/CT3 only) 37
Opening the Control Unit (VD2/VD2A/CT3 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Control and Junction Box Installation Instructions (CM2 only) . . . . . . . . . . . 39
Mounting the Front Part of the Control Unit (CM2 only) . . . . . . . . . . . . . . . . . . . . . . 40
Opening the Control Unit (CM2 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Overview of Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Overview of Electrical Connections (VD2/VD2A/CT3 only) . . . . . . . . . . . . . 43
Overview of Electrical Connections (CM2 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Routing and Strain Relief of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Inserting the Boiler Coding Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Setting of the Fixed High Limit (if required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Setting of the Adjustable High Limit (if required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Sensor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Connection of the Boiler Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Connection of the DHW Tank Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Connection of the Return Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Connection of the Flue Gas Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Connection of the Pumps (VD2/VD2A/CT3 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Connection of the Pumps (CM2 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Connection of Return Mixing Valve or
Isolation/Modulating Valve (VD2/VD2A/CT3 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Connection of Return Mixing Valve or
Isolation/Modulating Valve (CM2 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Making Space for Accessory Adaptors on the Din Rail (CM2 only) . 58
Vitotronic 100, GCI with 30% LTP Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Connection of External Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Connection of External Controls (VD2/VD2A only) . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Connection of External Controls (CT3 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Connection of Combustion Air Device (VD2/VD2A/CT3 only) . . . . . . . 66
Connection of Combustion Air Device (CM2 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Connection of Combustion Air Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Connection of Combustion Air Device on Multiple Boiler Systems 69
Connection of Single Air Device on Multiple Boiler Systems . . . . . . . . 70
Connection of Combustion Air Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Gas Flue Temp. Sensor (Optional for CM2 equipped with
SS Flue Collector) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Connection of Low Water Cut-off Device (VD2/VD2A/CT3 only) 73
Connection of Low Water Cut-off Device (CM2 only) . . . . . . . . . . . . . . . . . . . . . . 74
Connections to Terminal aBÖ (VD2/VD2A/CT3 only) . . . . . . . . . . . . . . . . . . . . . . . . 75
Connection of the Compiled Failure Alarm Indicator
(VD2/VD2A/CT3 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Connection of the Compiled Failure Alarm Indicator (CM2 only) . 77
Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only) 78
Power Supply Connection to Boiler Control (VD2/VD2A/CT3 only) . . 82
Burner Connection, Burner Control Wiring (CM2 only) 83
5351 338 v1.8
5
Start-up Procedure (overview) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6
Heating system types
Overview
7
Heating system types
Circuit Diagram 1
8
Heating system types
Wiring diagram
Wiring of the Therm-Control in heating
systems with heating circuit control units
are not connected to the boiler control
unit via the LON.
Required coding:
Change “4C” to “2” - use the plug-in
connector 20 A1 to close the
downstream mixing valve. Change “0D”
to “1” - the Therm-Control acts on the
mixing valve of the downstream heating
circuits (for Vitotronic 200 and 300,
delivered condition).
9
Heating system types
Circuit Diagram 2
Multi-boiler system with Therm-Control and three-way mixing valve
in conjunction with Vitorond 200, VD2A
Plug aJA Therm-Control temperature gSM2 Mixing valve motor (only for
! Outdoor temperature sensor sensor Vitotronic 300-K)
(only for Vitotronic 300-K) sÖM2 Heating circuit pump, mixing gSM3 Mixing valve motor (only for
?Flow Flow temperature sensor, valve (only for Vitotronic Vitotronic 300-K)
common heating flow (only for 300-K) gSM3 Mixing valve motor, Vitotronic
the Vitotronic 300-K) sÖM3 Heating circuit pump, mixing 200-H
?M2 Flow temperature sensor, valve (only for Vitotronic lÖ Burner
mixing valve (only for the 300-K) (burner stage 2 / mod.)
Vitotronic 300-K) sÖ Heating circuit pump Vitotronic aVD/aVH External connections
?M3 Flow temperature sensor, 200-H
mixing valve (only for the sK DHW circulation pump (only
Vitotronic 300-K) for the Vitotronic 300-K) Please refer to the control
? Flow temperature sensor fÖ Power supply, 120 VAC manual for the Vitocontrol-S,
5351 338 v1.8
10
Heating system types
Circuit Diagram 3
Single-boiler system with shunt pump for elevating the return temperature
in conjunction with Vitorond 200, VD2
C C
A1
29
20
T2
21 17B
5 17A
3
143
146
40
41
90
T1
*1
B A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor sL Shunt pump
B Domestic hot water tank % DHW tank temperature sensor fÖ Power supply connection,
C Heating circuit with mixing valve (accessory) 120 VAC
aJ A Temperature sensor T1 fA Burner (1st stage)
aJ B Temperature sensor T2 lÖ Burner (2nd stage/modulating)
sÖ A1 Close mixing valves with aVD Connection of external
external heating circuit equipment (see page 60)
controls aVH Connection of external
sA DHW pump equipment (see page 60)
5351 338 v1.8
*1 On the Vitorond the boiler supply and return are at the rear of the boiler.
11
Heating system types
12
Heating system types
Circuit Diagram 4
Single-boiler system with shunt pump and return valve for elevating the return temperature
in conjunction with Vitorond 200, VD2
C C
A1
29
52
T2
21 17B
5 17A
3
143
146
40
41
90
T1
*1
B A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor fÖ Power supply connection,
B Domestic hot water tank % DHW tank temperature sensor 120 VAC
C Heating circuit with mixing valve (accessory) fA Burner (1st stage)
aJ A Temperature sensor T1 gS A1 Mixing valve motor for raising
aJ B Temperature sensor T2 the return temperature
sA DHW pump lÖ Burner (2nd stage/modulating)
sL Shunt pump aVD Connection of external
equipment (see page 60)
aVH Connection of external
equipment (see page 60)
5351 338 v1.8
*1 On the Vitorond the boiler supply and return are at the rear of the boiler.
13
Heating system types
14
Heating system types
Circuit Diagram 5
Multi-boiler system with shunt pump for elevating the return temperature for each boiler
in conjunction with Vitorond 200, VD2
C C
3 3
17B T2 17B T2
17A 17A
52 A1
52 A1
143
146
143
146
41
41
40
90
29
40
90
29
T1 T1
B A A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor gS A1 Motorized isolation valve
B Domestic hot water tank aJ A Temperature sensor T1 lÖ Burner (2nd stage/modulating)
C Heating circuit with mixing valve aJ B Temperature sensor T2 aVD Connection of external
sL Shunt pump equipment (see page 60)
fÖ Power supply connection, aVH Connection of external
120 VAC equipment (see page 60)
fA Burner (1st stage)
5351 338 v1.8
15
Heating system types
16
Heating system types
Circuit Diagram 6
C C
3 3
17A T1 17A T1
52 A1
52 A1
143
146
143
146
41
41
40
90
40
90
B A A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor lÖ Burner (2nd stage/modulating)
B Domestic hot water tank aJ A Temperature sensor T1 aVD Connection of external
C Heating circuit with mixing valve fÖ Power supply connection, equipment (see page 60)
D Common supply pump 120 VAC aVH Connection of external
fA Burner (1st stage) equipment (see page 60)
gS A1 Motorized isolation valve
5351 338 v1.8
17
Heating system types
18
Heating system types
Circuit Diagram 7
C C
3 3
17A 17A
52 A1
52 A1
143
146
41
143
146
41
40
90
29
40
90
29
T1 T1
B A A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor lÖ Burner (2nd stage/modulating)
B Domestic hot water tank aJ A Temperature sensor T1 aVD Connection of external
C Heating circuit with mixing valve sL Boiler circuit pump equipment (see page 60)
fÖ Power supply connection, aVH Connection of external
120 VAC equipment (see page 60)
fA Burner (1st stage)
gS A1 Return valve
5351 338 v1.8
19
Heating system types
20
Heating system types
Circuit Diagram 8
Multi-boiler system with low-loss header and return valve for elevating the return temperature
in conjunction with Vitorond 200, VD2
C C
3 3
17A 17A
52 A1
52 A1
143
146
41
143
146
41
40
90
29
40
90
29
T1 T1
B A A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor lÖ Burner (2nd stage/modulating)
B Domestic hot water tank aJ A Temperature sensor T1 aVD Connection of external
C Heating circuit with mixing valve sL Boiler circuit pump equipment (see page 60)
D Low-loss header fÖ Power supply connection, aVH Connection of external
120 VAC equipment (see page 60)
fA Burner (1st stage)
gS A1 Return valve
5351 338 v1.8
21
Heating system types
CAUTION
IMPORTANT The boiler circuit pumps on each
boiler must be sized so that their
This circuit diagram represents a supply is at least equal to the
recommendation only. It is the maximum possible total heating
responsibility of the customer and/or circuit supply.
heating contractor to check that this Recommendation: 110%.
recommendation is complete and fully
functional. Three-phase equipment
must be connected via additional
power contactors.
22
Heating system types
Circuit Diagram 9
C C
21 3
5
143
146
40
41
90
B D A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor fA Burner (1st stage)
B Domestic hot water tank % DHW tank temperature sensor lÖ Burner (2nd stage/modulating)
C Heating circuit with mixing valve (accessory) aVD Connection of external
D Neutralizing unit sA DHW pump equipment (see page 60)
fÖ Power supply connection, aVH Connection of external
120 VAC equipment (see page 60)
5351 338 v1.8
23
Heating system types
24
Heating system types
Circuit Diagram 10
Single-boiler system with several heating circuits and one mixing valve heating circuit
in conjunction with Vitocrossal 300
E
C D
F
A1
20
21
or
3
5
143
146
40
41
90
B G A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor fÖ Power supply connection,
B Domestic hot water tank % DHW tank temperature sensor 120 VAC
C Heating circuit with mixing valve (accessory) fA Burner (1st stage)
D Mixing valve heating circuit sÖ A1 Close mixing valves with lÖ Burner (2nd stage/modulating)
or external heating circuit controls aVD Connection of external
E Underfloor heating circuit with sA DHW pump equipment (see page 60)
mixing valve aVH Connection of external
F Limit thermostat (max. limit) equipment (see page 60)
G Neutralizing unit
5351 338 v1.8
25
Heating system types
26
Heating system types
Circuit Diagram 11
Multi-boiler system with several heating circuits and one mixing valve heating circuit
in conjunction with Vitocrossal 300
C C
3 3
52 A1
52 A1
143
146
143
146
41
41
40
90
40
90
B D A D A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor aVD Connection of external
B Domestic hot water tank fÖ Power supply connection, equipment (see page 60)
C Heating circuit with mixing valve 120 VAC aVH Connection of external
D Neutralizing unit fA Burner (1st stage) equipment (see page 60)
gS A1 Motorized isolation valve
lÖ Burner (2nd stage/modulating)
5351 338 v1.8
27
Heating system types
Possible applications The Vitocrossal 300 is operated with Motorized isolation valve
The cascade and DHW tank control constant boiler water temperature by Connect motorized isolation valve
must be activated by a building means of the boiler control unit. adaptor (Part No. 7134 560) or 24V
automation system. Two-stage or modulating burners can valve adaptor (Part No. 7134 559),
be controlled. installed in connection enclosure, in
parallel.
IMPORTANT The Vitocrossal 300 has two return Use electric junction box if necessary.
connections. The heating circuits
This circuit diagram represents a with the higher return temperature
recommendation only. It is the are connected to the return
responsibility of the customer and/or connection at the top, those with
heating contractor to check that this the lower temperatures to the return
recommendation is complete and fully connection at the bottom.
functional. Three-phase equipment
must be connected via additional Please note:
power contactors. At least 15% of the
take-off from the rated output must
be connected to the return connection
at the bottom.
28
Heating system types
Circuit Diagram 12
Multi-boiler system with several heating circuits, one mixing valve heating circuit and Vitorond with shunt pump
in conjunction with Vitocrossal 300 and Vitorond 200
C C
3
3 17B T2
17A
52 A1
143
146
143
146
41
41
40
90
40
90
29
T1
B D A A
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor gS A1 Motorized isolation valve
B Domestic hot water tank aJ A Temperature sensor T1 lÖ Burner (2nd stage/modulating)
C Heating circuit with mixing valve aJ B Temperature sensor T2 aVD Connection of external
D Neutralizing unit sL Shunt pump equipment (see page 60)
fÖ Power supply connection, aVH Connection of external
120 VAC equipment (see page 60)
fA Burner (1st stage)
5351 338 v1.8
29
Heating system types
Possible applications The Vitocrossal 300 (lead boiler) and The Vitocrossal 300 boilers have
The cascade and DHW tank control the Vitorond lag boilers are operated two return connections. The heating
must be activated by a building with modulating boiler water circuits with the higher return
automation system. temperature and load-dependent temperature are connected to the
sequential control by means of the return connection at the top, those
outdoor-reset logic control system. with the lower temperatures to the
IMPORTANT Two-stage or modulating burners can return connection at the bottom.
be controlled.
This circuit diagram represents a Through the control system which is Please note:
recommendation only. It is the linked via the LON BUS, the boiler At least 15% of the
responsibility of the customer and/or supply temperature which is take-off from the rated output must
heating contractor to check that this established is higher than the be connected to the return
recommendation is complete and fully maximum heating circuit supply connection at the bottom.
functional. Three-phase equipment temperature by an adjustable
must be connected via additional difference. The heating system can The return temperature raising
power contactors. be operated in accordance with a functionality of the Vitorond
separate heating curve. modulating boiler is available as an
accessory or must be provided on
site.
The return temperature is raised by
means of the shunt pump and by
closing the isolation valve.
The temperature sensor T1 activates
the isolation valve. The temperature
sensor T2 switches the shunt pump.
30
Heating system types
Circuit Diagram 13
Multi-boiler system with return valve, several heating circuits and one mixing valve
heating circuit
in conjunction with Vitocrossal 300 and Vitorond 200
C C
3 3
17A
52 A1
143
146
143
146
41
41
40
90
40
90
29
T1
B D A A
31
Heating system types
Possible applications The Vitocrossal 300 (lead boiler) and The Vitocrossal 300 boilers have
For heating circuits with temperature the Vitorond lag boilers are operated two return connections. The heating
differences ≥20 K. with modulating boiler water circuits with the higher return
The cascade and DHW tank control temperature and load-dependent temperature are connected to the
must be activated by a building sequential control by means of the return connection at the top, those
automation system. outdoor-reset logic control system. with the lower temperatures to the
Two-stage or modulating burners return connection at the bottom.
can be controlled.
IMPORTANT Through the control system which is Please note:
linked via the LON BUS, the boiler At least 15 % of the
This circuit diagram represents a supply temperature which is take-off from the rated output must
recommendation only. It is the established is higher than the be connected to the return connection
responsibility of the customer and/or maximum heating circuit supply at the bottom.
heating contractor to check that this temperature by an adjustable
recommendation is complete and fully difference. The heating system can The T1 temperature sensor measures
functional. Three-phase equipment be operated in accordance with a the return temperature.
must be connected via additional separate heating curve. The return valve is activated via the
power contactors. boiler control unit so as to ensure that
the return temperature does not fall
below the minimum value.
32
Heating system types
Single-boiler system with several heating circuits and one mixing valve heating circuit
in conjunction with Vitocrossal 200
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor fÖ Power supply connection,
B Domestic hot water tank % DHW tank temperature sensor 120 VAC
C Heating circuit with mixing valve (accessory) fA Burner
D Mixing valve heating circuit sÖ A1 Close mixing valves with lÖ Burner modulation
or external heating circuit controls aVD Connection of external
E Underfloor heating circuit with sA DHW pump equipment (see page 60)
mixing valve aVH Connection of external
F Limit thermostat (max. limit) equipment (see page 60)
G Neutralizing unit
5351 338 v1.8
33
Heating system types
IMPORTANT
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
heating contractor to check that this
recommendation is complete and fully
functional.
34
Heating system types
Multi-boiler system with several heating circuits and one mixing valve heating circuit
in conjunction with Vitocrossal 200
Plugs
A Boiler with Vitotronic 100, GC1 § Boiler temperature sensor aVD Connection of external
B Domestic hot water tank fÖ Power supply connection, equipment (see page 60)
C Heating circuit with mixing valve 120 VAC aVH Connection of external
D Neutralizing unit fA Burner equipment (see page 60)
gS A1 Motorized isolation valve
lÖ Burner modulation
5351 338 v1.8
35
Heating system types
Possible applications The Vitocrossal 200 is operated with Motorized isolation valve
The cascade and DHW tank control constant boiler water temperature by Connect motorized 120V isolation
must be activated by a building means of the boiler control unit and valve adaptor (Part No. 7511 367)
automation system. the Viessmann fully modulating burner. or 24V valve adaptor (Part No.
7511 366), installed in connection
enclosure, in parallel.
IMPORTANT Use electric junction box if necessary.
36
Installation
1.
7.
8.
3.
5351 338 v1.8
37
Installation
1.
3.
38
Installation
WARNING
Do not bend or kink the capillaries.
Damaging the capillaries leads to
malfunction.
39
Installation
40
Installation
41
Installation
145
17 B
17 A
5 151
3/2 90
15 21
143 52 A1/M1 41
146 20 A1/M1
29
50 150
40
156
156
safety equipment
aBA Safety circuit, potential free
aBH Power supply connection for
accessories
42
Installation
[29]
[20] A1
5351 338 v1.8
43
Installation
44
Installation
1. Run the cables from the connection enclosure into the control unit.
2. Apply strain relief to cables (see below).
OR
45
Installation
CAUTION
For matching the operation of the
control unit to the boiler, the boiler
coding card which is supplied as part
of the standard delivery of the boiler
may be used.
Only use the boiler coding card included with the boiler.
46
Installation
47
Installation
A 75 to 1100°C
2. 167 to 212°F
IMPORTANT
Note the setting of coding address
”06”!
WARNING
If the system is operated in
conjunction with a domestic hot
water tank, ensure that the
maximum permissible domestic
hot water temperature is not
exceeded. If necessary, install a
suitable safety device for this
purpose.
48
Installation
Sensor Connection
17B 17A 3 15
1 2 3 1 2 3 1 2 3 1 2 3
A B C D
ATemperature sensor T2
BTemperature sensor T1
CBoiler temperature sensor
DFlue gas temperature sensor
5351 338 v1.8
49
Installation
Electrical connection
See page 42.
560
400
540
0 20 40 60 80 100 120 140
5351 338 v1.8
50
Installation
The sensor measures the domestic hot Heating systems with domestic hot Electrical connection
water tank temperature. water heating (single-boiler systems See page 42.
only)
The sensor measures the boiler
1. Install the DHW tank temperature water temperature of the boiler.
sensor.
5 The boiler temperature sensor is
See installation instructions installed at the same time as the
for domestic hot water tank boiler insulation.
Electrical connection
620 The sensors are ready to plug in.
Insert the DHW temperature sensor
600 in socket ”5” of the boiler control.
580
Resistance in
560
5351 338 v1.8
400
540
0 20 40 60 80 100 120 140
32 68 104 141 176 212 248 284
DHW temperature in °C / °F
51
Installation
Electrical connection
17A or 17B The sensor is inserted in socket
”17A” or ”17B” on the boiler
control.
Return Resistance
temperature in Ω
in °C / °F
17A or 17B 30 / 86 569
40 / 104 592
60 / 140 643
Technical data
700 Degree of protection: IP 32
Ambient temperature
680 during operation: 0 to + 100°C
32 to + 212°F
during storage and transport:
660 -20 to + 70°C
-4 to + 158°F
640
620
600
580
Resistance in
560
540
5351 338 v1.8
20 30 40 50 60 70 80 90 100
68 86 104 122 140 158 176 194 212
Return temperature in °C / °F
52
Installation
Electrical connection
The sensor is inserted in socket
”15” on the control unit.
660
620
Resistance in Ω
580
540
500
0 40 80 120 160 200 240 280
32 104 176 248 360 392 464 536
5351 338 v1.8
53
Installation
20A1/M1
29
54
Installation
corresponding terminals.
55
Installation
1 120V or 24V Valve Adaptor 1 120V Valve Adaptor 1 24V Valve Adaptor
2 DIN rail in connection enclosure 2 120V valve actuator 2 24V valve actuator
3 aBH Terminals
56
Installation
10 11 12
1 120V or 24V Valve Adaptor 1 120V Valve Adaptor 1 24V Valve Adaptor
2 DIN rail in connection enclosure 2 120V valve actuator 2 24V valve actuator
57
Installation
Making Space for Accessory Adaptors on the DIN Rail (CM2 only)
58
Installation
VD2/VD2A
59
Installation
B
2nd stage burner ON
C External changeover of
staged/modulating burners
B D
Switch on 2nd stage burner Boiler activation, isolation valve
Connect dry contact at terminals ”2” open or closed
and ”3” Connect dry contact at terminals ”2”
143 146 of the plug aVD. and ”3” of the plug aVH.
Contact open:
Two-stage operation. Coding “02: 2”
(modulating burner) must be set.
5351 338 v1.8
Note:
Even if contact is closed, scanning the
type of burner will continue to display
“modulating”.
60
Installation
CAUTION
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler must
be constantly closed.
5351 338 v1.8
61
Installation
Contact open:
The isolation valve is closed after
approx. 5 minutes (coding address
”2C”).
External override of the burner stages
is not possible, and no minimum
temperature is maintained.
Contact closed:
The 1st stage burner is switched on.
The full load is only switched on to
maintain the minimum temperature
(not with Vitocrossal 300). The
boiler water temperature is limited
by the electronic maximum
temperature limit (coding address
”06”) if this is set below the value
preset on the mechanical adjustable
high limit ”R”.
Contact open:
The 1st stage burner is switched off.
5351 338 v1.8
62
Installation
CAUTION
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler must
be constantly closed.
5351 338 v1.8
63
Installation
Contact open:
The isolation valve is closed after
approximately 5 minutes (coding
address ”2C”).
External override of the burner
stages is not possible, and no
minimum temperature is maintained.
Contact closed:
The 1st stage burner is switched on.
The boiler water temperature is
limited by the electronic maximum
temperature limit (coding address
”06”) if this is set below the value
preset on the mechanical adjustable
high limit ”R”.
Contact open:
The 1st stage burner is switched off.
5351 338 v1.8
64
Installation
CAUTION
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler must
be constantly closed.
5351 338 v1.8
65
Installation
IMPORTANT
Wire BK2 must be connected to
terminal 16 and BK3 to terminal 17 -
DO NOT reverse.
¨ Safety instruction!
5351 338 v1.8
66
Installation
67
Installation
E
1. Disconnect power to control and
burner.
¨ Safety instruction!
Provide disconnect means and
overcurrent protection as required by
local codes.
Note:
Spring return air dampers do not
require field supplied relay.
68
Installation
69
Installation
¨ Safety instruction!
Provide disconnect means and
overcurrent protection as required
by local codes.
70
Installation
¨ Safety instruction!
Provide disconnect means and
overcurrent protection as required
by local codes.
71
Installation
72
Installation
CAUTION
Please note that the diagram at left
is only a simplified conceptual
drawing of a typical low water
cut-off (LWCO) device. Refer to the
manual specific to the device for
interconnection details.
73
Installation
CAUTION
Please note that the diagram shown
is only a simplified conceptual
drawing of a typical low water
cut-off (LWCO) device. Refer to the
manual specific to the device for
interconnection details.
74
Installation
External shut-off
1. Remove jumper between terminals
16 and 17.
2. Connect dry contact.
Controlled switch-off takes place
when the contact is opened.
CAUTION
The terminals should be used for
safety switch-off purposes only (e.g.
through a limit thermostat). See
pages 52 to 59 for details of
controlled switch-off.
During switch-off, there is no frost
WARNING
protection of the heating system and
the boiler is not kept at the minimum
boiler water temperature.
Emergency operation
Move jumper from terminals 16 and 17
to terminals 17 and 18.
A Jumper
B External shut-off (dry contact)
5351 338 v1.8
75
Installation
76
Installation
B
5351 338 v1.8
77
Installation
BK Black
BN Brown
5351 338 v1.8
BU Blue
78
Installation
CAUTION
This is a generic connection drawing
only! Follow the burner
manufacturer’s connection drawings
for Viessmann controls.
Plug connection
located on the
DIN rail. See page
42 for details.
a b
A Control unit fÖ Power supply connection of control aBÖ Plugs for external equipment
(Legend: see wiring diagram) unit 120 VAC a External safety devices
B 2nd stage or modulating *1 fA Burner, 1st stage (remove jumper when connecting)
C Hours counter, stage 1 *1 lÖ Burner, 2nd stage b External controlled switch-off
D Burner fault indicator *1 (remove jumper when connecting)
E Control circuit, stage 1/ aBA Safety circuit. Emergency
5351 338 v1.8
79
Installation
80
Installation
CAUTION
During commissioning check for
correct motor rotation. If motor
rotates in opposite direction than
indicated on the burner, disconnect
power supply and reverse wires BK1
and BK2 on the burner terminals.
81
Installation
82
Installation
A
A To plug-in connection in connection Terminal codes
enclosure
B To burner interface 1,2,3 Control circuit ”2nd stage
burner or modulation controller”
(via two-point controller with
2-stage operation;
via three-point controller with
modulating operation)
1 From burner
2 Modulating down
3 Modulating up/2nd stage ON
BK Black
BN Brown
5351 338 v1.8
BU Blue
83
Start-up
Procedure (overview)
Page
84
Start-up
Steps
Override switch
Information
Confirmation
Basic setting
Display window
F1 T6,3 A
TUV
F2 T6,3 A
Fuses
TUV button
85
Start-up
Steps (continued)
The check is made via the ”TUV button” (see page 85).
86
Start-up
Steps (continued)
3. Integrate the control unit in the LON BUS system Single-boiler system only
Set the LON participant number via See page 115 for coding 1.
coding address ”77” in coding 1
(factory setting: ”77: 1”). Please note:
The same number must not be
assigned twice within a LON BUS
system.
This is only possible when all participants are connected and the control unit is
coded as the error manager (coding ”79: 1”).
Example of single-boiler system with Vitotronic 050 heating circuit controls and Vitocom connected downstream
87
Start-up
Steps (continued)
The participant check is used to verify the communication of the system units
connected to the error manager.
Requirements:
The control unit must be coded as the error manager (coding ”79: 1”)
The LON participant number must be coded in all control units (see page 87)
The participant list must be updated in the error manager (see page 87)
Participant number
Consecutive list number
3. Activate the check with . The arrows in the display will flash
If communication between the two until the check is completed. The
units is verified, the arrows in the display window and all lit buttons of
display window stop flashing. the selected participant flash for
If communication is not verified, the approx. 60 seconds.
display shown on the left appears. Check the LON connection (see page
111).
4. To check further participants, follow
the steps described in points 2 and
3.
88
Start-up
Steps (continued)
Set the following coding addresses in See page 117 for coding 2.
coding 2:
”00” System type
”01” Single or multi-boiler system
”02” Burner type
”03” Oil or gas-fired operation
”07” Boiler number
”0C” Return temperature raising
”0d” Therm-Control is effective for ...
”4C” plug sÖ function
”4d” plug sL function
”4E” plug gS function
15 Output 20 ON
16 Output 29 ON
17 Output 52 open
18 Output 52 neutral
19 Output 52 closed
10 DHW pump ON
Check sensors
Scanning of operating status
1. Press . information is activated
5351 338 v1.8
1234567
89
Start-up
Steps (continued)
Please note:
The burner must be adjusted. In order to achieve a wide modulation range, the
minimum output should be set as low as possible (take chimney/flue system into
account).
9. Press .
5351 338 v1.8
90
Start-up
Steps (continued)
10. Set the established values in coding See page 115 for coding 1.
level 1.
Address Setting of
05 the partial output (see point 8) as a percentage proportion of the
max. output; e.g.
partial output: 170 kW
max. output: 210 kW
170 kW x100 % = 81 %
210 kW
08 units and tens digits of the maximum output established in point
4: e.g. max. output: 210 kW – here set: 10
09 hundreds digit of the maximum output established in point 4: e.g.
max. output: 210 kW – here set: 2
0A the basic output (see point 6) as a percentage proportion of the
max. output; e.g.
basic output: 70 kW
max. output: 210 kW
70 kW x100 % = 33 %
210 kW
15 the operating time in seconds established in point 5
Please note:
You will find details of other possible settings in the sections entitled
”Coding 1” and ”Coding 2” (see page 115 and 117).
5351 338 v1.8
91
Scanning service information
92
Scanning service information
93
Scanning service information
Scan 0
0 8 8 8 8
SNVT configuration
0 Auto
1 Tool
0
to Software version
0 0 F Communication coprocessor
to to
9 9 LON participant number
0 Scan 0
Scan 1
1 8 8 8 8
0 0
to to
F F Node address
0
to System number
0 F (only with self-binding)
to
F Subnet address
1 Scan 1
Scan 2
2 8 8 8 8
0 0
to to Software version
5351 338 v1.8
94
Scanning service information
Scan 4
4 8 8 8 8
0
to Software version
F Control unit
0
to Software version
1 F Programming unit
or
2 System type
Free
4 Scan 4
Scan b/d
b 8 8 d 8
Isolation valve
0 Closed
1 Preheating
2 Closing
3 Regulating
4 Opening
5 Open
6 Run-on
d Scan d
Burner
0 OFF
1 1st stage/basic load
2 2nd stage/full load
Free
b Scan b
5351 338 v1.8
95
Scanning service information
Scan L
l 8 8 8 8
0 0 0 Output reduction
or to to (0 to 100 %; 0 = OFF)
1 9 9
Free
L Scan L
Scan o
o 8 8 8 8
Free
Free
0 0
to to
F F Equipment identification code
o Scan o
96
Scanning service information
3 65 °C Boiler temperature ––
6 55 °C Return temperature
17A (1st return temperature
Only displayed if return
temperature sensor is
sensor) connected
9 60 °C Return temperature
17B (2nd return temperature
Only displayed if return
temperature sensor is
sensor) connected
Y Burner hours run The hours run can be reset to
63572 h
1st stage ”0” by pressing D. The hours
run displayed are approximate
values only
YY Burner hours run The hours run can be reset to
09572 h
2nd stage ”0” by pressing D. The hours
run displayed are approximate
values only
YYY Burner starts The number of burner starts
30417 can be reset to ”0” by
pressing D
5351 338 v1.8
97
Scanning service information
Please note:
If a service is carried out before the service display appears, set the coding
address ”24: 1” and then coding address ”24: 0”.
Display Meaning
12 u Time interval
(e.g. 12 months)
reached
98
Troubleshooting
Troubleshooting Steps
Page
Diagnosis 1. Establish fault message or ascertain behaviour of system
Please note:
Retrieve fault codes from the fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
99
Troubleshooting
Diagnosis
1234567
Fault symbol
To retrieve an acknowledged
fault message
Press for approx. 2 seconds; Fault is displayed.
select the acknowledged fault by
pressing the or button.
5351 338 v1.8
100
Troubleshooting
Diagnosis (continued)
101
Troubleshooting
Diagnosis (continued)
b6 Operation at constant temperature Invalid hardware code Check the control software circuit
board and confirm the coding address:
- Enter coding 2 (see page 117
for instructions).
- Change code 8A to 176.
- Confirm coding 92:160
102
Troubleshooting
Diagnosis (continued)
d4 Boiler cools down Fixed high limit has operated Check fixed high limit reset to
25° C (+/- 5.0° C)
Cooler than the high limit set
Check connection at inputs
d6 Controlled operation Fault at ”DE1” in the plug-in
adaptor for external safety ”DE1” to ”DE3”
equipment
103
Troubleshooting
Diagnosis (continued)
All faults which have occurred are stored and can be retrieved by scanning.
The scanning sequence starts with the most recently stored fault code.
2. Access the individual fault codes All stored fault codes can be
by pressing the or button. deleted by pressing .
104
Functional description
Brief description
The boiler water temperature is In conjunction with Therm-Control: Coding addresses which influence
controlled by switching the burner on The set-point boiler water temperature the boiler temperature control
and off. is increased when the temperature falls 02 to 06, 08 to 0b, 13 to 1C.
The set-point boiler water temperature below the set-point value on the sensor
value is determined by the set-point of the Therm-Control.
supply temperature values of the boiler
circuit (A1), the heating circuits with
mixing valve (from Vitotronic 050) and
the set-point supply temperature value
preset via coding address ”9b” as well
as the set-point domestic hot water
temperature, and is dependent on the
boiler and the heating and control
facilities installed.
Functions
The boiler water temperature is Upper limits of control range Lower limit of control range
measured via a multiple sensor well by Fixed high limit FHL The control unit regulates the boiler
three sensors separately: 110°C / 230°F, can be adjusted to water temperature in normal
Fixed high limit FHL 100°C / 212 or 230°F operation and in the frost protection
(liquid expansion) Adjustable high limit AHL mode according to the boiler
Adjustable high limit AHL 95°C/ 203°F, can be adjusted to concerned (boiler coding card).
(liquid expansion) 100°C / 212°F
Boiler temperature sensor BTS Electronic maximum limit
(change in resistance PT 500) Setting range: 20 to 127°C /
68 to 261°F
The maximum limit for the boiler
water temperature is defined in
coding address ”06”.
Control sequence
105
Functional description
Brief description
The supply temperature of the boiler Coding addresses which influence the
circuit (A1) corresponds to the boiler heating circuit control
water temperature. 55, 56, 58, 5A to 63, 6A, 6b.
Functions
The boiler circuit (A1) is dependent on Upper limit of control range Domestic hot water temperature
the boiler water temperature and its Electronic maximum limit With priority control:
control range limits. Setting range: 1 to 127°C / While the DHW tank is being
34 to 261°F. heated, the set-point supply
Change via coding address ”C6”. temperature value is set to
0°C / 32°F.
Lower limit of control range Without priority control:
Electronic minimum limit The heating circuit control
Setting range: 1 to 127°C / continues to operate as normal
34 to 261°F. with the setpoint value unchanged.
Change via coding address ”C5”.
Brief description
The DHW tank temperature control is a The switching differential is ±2.5°C / coding address ”60”) and space
constant value control. It operates on 4.5°F. heating is switched off (DHW tank
the basis of switching the DHW pump During DHW tank heating, a constant priority control optional).
on and off. maximum boiler water temperature is
set (20°C / 36°F above the set-point
DHW tank temperature, variable via
Functions
Frost protection function Heating with the additional function Additional control facilities
If the domestic hot water temperature takes place daily at the time of the The domestic hot water supply
falls below 10°C / 50°F, the domestic 1st domestic hot water heating can be blocked and released via
hot water DHW tank is heated to period. change-over of the heating program.
20°C / 68°F.
Set-point domestic hot water System with DHW heating
Additional function for domestic hot temperature The functions described above also
water heating The set-point domestic hot water apply in conjunction with DHW
For temporarily increasing the DHW temperature can be set in the range of heatings.
tank temperature at selectable intervals 10 to 60°C / 50 to 140°F. The
→ this provides additional assurance setpoint range can be extended to Set the following codings:
that bacteria are eliminated. 95°C / 203°F via coding address ”4C: 1”, ”4E: 1”, ”55: 3”.
This function is activated when a ”56”.
5351 338 v1.8
106
Functional description
Control sequence
The DHW pump is switched on When the DHW tank has been
immediately (Coding ”61: 1”). heated up, the DHW pump continues
to run (coding ”62: 10”) until
Boiler temperature-dependent switching - the temperature difference
of the DHW pump between the boiler water and
(Coding ”61: 0”): domestic hot water is less than
The circulation pump is switched on 7°C / 13°F or
when the boiler water temperature is - the set-point boiler water
7°C / 13°F higher than the domestic temperature selected through the
hot water temperature. set-point supply temperature of the
boiler circuit is reached
or
- the set-point domestic hot water
temperature is exceeded by
5°C / 9°F.
The max. run-on time is 15 minutes
(selectable via coding address ”62”).
107
Additional information
Overview
Page
System Components
Line voltage motherboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Low-voltage motherboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Power supply unit board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Electronics board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Optolink/override switch board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Programming unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Fuse box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
LON communication module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Boiler coding card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
TUV button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Fixed high limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Adjustable high limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Input module 0 to 10V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Resetting codings to the factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Coding 1
Call up coding level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Codings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Coding 2
Call up coding level 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Reset codings to factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Overview of all codings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Wiring Diagrams
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Low-voltage motherboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Line voltage motherboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Parts List
GCI Series 126
5351 338 v1.8
108
Additional information
Technical Data
System Components
109
Additional information
Power supply unit board, 120 VAC Part No. 7823 991
110
Additional information
For setting:
heating program
set-point values
For displaying:
temperatures
operating status information
faults
LON
D
LON
LON
LON
LON
indicated.
D
1 terminal resistor is inserted on each
of the first and last control unit.
111
Additional information
Fuses
F1
F2
112
Additional information
IMPORTANT
Set the lower limit at least 20°C / 36°F higher than the domestic hot water
temperature, the upper limit at least 15°C / 27°F lower than the fixed high limit.
Adjusting shaft 6 mm / 0.27 inches, flat topped
Adjusting knob pushed onto shaft from front
Capillary 3600 mm / 141.7 inches long
Sensor 3 mm / 0.1inches thick, 180 mm / 7.1inches long
Tests:
Electrical to VDE 0701 standard
5351 338 v1.8
113
Additional information
From software version 7 of Vitocontrol-S, VD2/CT3, the Input Module can be connected (software version via scan 2:
1st digit, display ≥7).
Electronics
B
F1 ON
50mA
(slow)
OFF 1 2 3 4
L1 N S Ö P 1 2 3 1 2 3
40
120 VAC _ +
A
157 144 145
Please note:
Amongst switches 1 to 3, only one switch may be set to ON.
display.
2. Press D.
114
Additional information
Coding 1
3. Change the value with the or The value is stored and stops flashing
button; press to confirm. for approx. 2 seconds. Then the
address flashes and further addresses
can now be selected with the or
button.
Codings
= Partial output in %
06: 87 Boiler/ Max. limit of boiler water 06: 20 Maximum boiler water temperature limit
burner temperature set to to variable between
87°C / 189°F 06:127 20 and 127°C / 68°F and 261°F
115
Additional information
Coding 1 (continued)
Codings (continued)
116
Additional information
Coding 2
3. Change the value with the or The value is stored and stops
button; flashing for approx. 2 seconds.
press to confirm. Then the address flashes and
further addresses can now be
selected with the or
button.
02: 1 Boiler/ Operation with two-stage 02: 0 Operation with single-stage burner
burner burner 02: 2 Operation with modulating burner
117
Additional information
Coding 2 (continued)
Burner
ON
OFF Time
Set-
point
ERB50 function
04: 1 Values from 6 to 12°C / 11 to 22°F are
set, depending on the heat demand.
Burner
ON
OFF Time
Set-
point
ERB80 function
Values from 6 to 20°C / 11 to 36°F are
04: 2 set, depending on the heat demand.
Burner
ON
OFF
Time
Set-
point
= Partial output in %
*1 The factory setting is determined by the boiler coding card.
118
Additional information
Coding 2 ((continued)
119
Additional information
Coding 2 (continued)
120
Additional information
Coding 2 (continued)
121
Additional information
Coding 2 (continued)
122
Additional information
Coding 2 (continued)
63: 0 DHW Without additional function for 63: 15 Twice per day
domestic hot water heating
63: 0 DHW Without additional function for 63: 1 Additional function: Once per day
domestic hot water heating 63: 2 Every 2 days
to to
63: 14 Every 14 days
68: 8 DHW In conjunction with 2 tank 68: 2 Factor adjustable from 0.2 to 1
temperature sensors with the DHW to per 1 increment = 0.1
heating: 68: 10
Switch-off point of tank heating at
setpoint value x 0.8
69: 7 DHW In conjunction with 2 tank 69: 1 Factor adjustable from 0.1 to 0.9
temperature sensors with the DHW to per 1 increment = 0.1
heating: 69: 9
Switch-on point of tank heating at
setpoint value x 0.7
76: 0 General Without LON communication module 76: 1 With LON communication module;
recognized immediately
76: 2 With Viessmann 2-wire BUS
communication module; recognized
immediately
77: 1 General LON participant number 77: 2 LON participant number selectable
to from 1 to 99
77: 99 Please note:
Each number may be assigned
once only.
78: 1 General LON communication released 78: 0 LON communication blocked
79: 0 General Control unit is not error manager 79: 1 Control unit is error manager
80: 1 General With 5 seconds time delay for fault 80: 0 Without time delay
message 80: 2 Time delay adjustable between
5351 338 v1.8
123
Additional information
Coding 2 (continued)
9d: 0 General Without Input Module 9d: 1 With Input Module 0 - 10V;
0 to 10V will be recognized automatically
124
Additional information
Wiring Diagrams
Overview
A2 Low-voltage motherboard
A3 Line voltage motherboard
A6 Programming unit
A7 Optolink/override switch board
A8 Electronics board
A9 Boiler coding card
A10 LON communication module or
Viessmann 2-wire BUS
communication module
A11 Power supply unit board
A12 Boiler control section
5351 338 v1.8
125
Additional information
Low-voltage motherboard
34--pole
A11
A8
A9
A6
A2
A7
A10
126
Additional information
127
Additional information
floating
ON ON
A11
A3
128
Additional information
129
Additional information
Parts List
GC1 Series
Order No. Serial No. *1
7134 553, 7134 554, 7511 361 7143003
7187096
7248247
Parts
001 Hinges 050 Circuit board (control software) Other Parts (not illustrated)
002 Optic link 051 Diagnostics module (Optolink) 060 Accessory pack (plugs)
004 Adjustable high limit knob 052 Motherboard 061 Coding plug for Vitocrossal 200
005 Fixed high limit cover (control, line voltage) 062 Coding plug for Vitorond 200
006 Dial-stop 110°C / 230°F 054 Circuit board 063 Coding plug for Vitocrossal 300;
008 Support arm (120V power supply) nnn
011 Safety module (wired) 055 Communication module, 080 Installation / Service Instructions
013 Front housing (with Pos. 001) 2-wire BUS Vitotronic 100, GC1
014 Circuit board enclosure 056 LON module 081 Operating Instructions
015 Flip-down cover 065 Burner cable Nr. 41/90 l=3470 Vitotronic 100, GC1
016 Rear housing 067 Sensor (immersion, NI500) 082 Parts List Vitotronic 100, GC1
018 Programming unit 068 Sensor #2 for supply Rating plate
024 Fuse holder cover 074 Harness for programming unit
025 Fuse holder 092 Fuse 6.3A / 250V (10 pack) *1 A 16-digit bar-coded serial no.
030 Fixed high limit is printed on the front housing,
031 Adjustable high limit below the flip-down cover.
037 Switch, 1-pole (FHL test)
038 Switch, 2-pole (power on/off)
042 Sensor #3 for boiler
043 Sensor #5 for domestic hot
water production
049 Motherboard
(control, low voltage)
130
Additional information
Parts List
5351 338 v1.8
131
Additional information
Quick Reference
-40 -40
-35 -31
-25 -13
-20 -4
-18 0
-16 +3
-14 +7
-12 +10
-10 +14
-9 +16
-8 +18
-7 +19
-6 +21
-5 +23
-4 +25
-3 +27
-2 +28
-1 +30
0 +32
+1 +34
+2 +36
+3 +37
+4 +39
+5 +41
+6 +43
+7 +45
+8 +46
+9 +48