Coil Selection

This document contains cooling coil selection sheets for two air handling units. The first unit has a total cooling load of 27 tons and requires a coil with the following specifications: 1/2" diameter, 25 fins high, 70 fins long, with 6 rows and 28 circuits at 12 fins per inch. The second unit has a total cooling load of 12 tons and requires a coil with specifications of: 1/2" diameter, 24 fins high, 54 fins long, with 4 rows and 19.2 circuits at 12 fins per inch. Both coils will be connected on the left hand side.

Uploaded by

Mohsin Shaikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
2K views5 pages

Coil Selection

This document contains cooling coil selection sheets for two air handling units. The first unit has a total cooling load of 27 tons and requires a coil with the following specifications: 1/2" diameter, 25 fins high, 70 fins long, with 6 rows and 28 circuits at 12 fins per inch. The second unit has a total cooling load of 12 tons and requires a coil with specifications of: 1/2" diameter, 24 fins high, 54 fins long, with 4 rows and 19.2 circuits at 12 fins per inch. Both coils will be connected on the left hand side.

Uploaded by

Mohsin Shaikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

COOLING COIL SELECTION SHEET - CHW

Customer : DATE

A.H.U. NO. 1

Latent ( L ) 0 BTU / hr. Outside Air ( OA ) 1730 CFM TOTAL TR = 27.00


Sensible ( S ) 0 BTU / hr. Dehumidified Air ( DA ) 6040 CFM CFM / TR = 224
Total ( T ) 0 BTU / hr. Return Air ( RA ) 4310 CFM B.P. FACTOR= 0.03

Outside (OT) 110 o


F DB 75 o
F WB Water Qty 71.60 USGPM Coil Vel. Limit 500 FPM
Inside ( IT ) 73 o
F DB 55 % RH Water in 45 o
F A.D.P. 52.3 F
o

Coil Lvg (LT ) 53.24 o


F DB o
F WB Water out 54 o
F Contact Factor 0.97

Mixture Temp. (AIR ) : 83.60 o


F DB

1730 F.A. X 110 O.T. + 4310 RA X 73 I.T.


6040 D.A.

LMTD = GTD - LTD 16.70 Ht Lt


LN (GTD / LTD) Coil Size : 5/8 " 30 58
Air Entering 83.60 Coil Lvg 53.24 Coil Size : 1/2" 25 70
Water Out 54 Water In 45 No .Of Coils :
GTD 29.60 LTD 8.24
Actual area each sq. ft.
Coil Area ( CA ) = 6040 D.A. = 12.08 sq. ft. Full half Quarter quarter
Half
500 Air . Vel. No. of Circuits : 20.0 10.0 5.0 per coil
20 10 5
Water Vel. = G.P.M. 71.6 X 1.1 = 3.282 fps Velocity : 3.28 fps
24 No .of circuits

Sensible Heat Ratio ( SHR ) 0.88


Air Entering SH 34 TH 38.18
Air Leaving SH 25 TH 27.92
Difference SH 9 TH 10.26

U.A. Factor (From Catalogue ) : 259.05

No. of Rows = 27 ( TR ) X 12000


LMTD 16.70 X C.A. 12.08 X U.A. 259.05

= 5.25 DIVIDING BY 1.18 FOR 12 FPI) 4.45


Selected = 6 Rows

Notes : For brine circulation apply correction factor for Coil Selected :
specific heat to water quantity. Size :
No. of Coils :
For 12 FPI divide No. of rows by 1.18
Connection on Left Hand Side / Right Hand Side
For 10 FPI, divide no of rows by 1.15
Header Size :
Side of Connection to be as seen while facing
coil from prefilter side Type of coil : DX / CH.W / BRINE

REMARKS :
Coil Size X Ht. X Length X Rows X Ckt X FPI X Type X Connection
1/2" 25 70 6 28 12 CH.W. LHS
DATE : PREPARED BY : RRG CHECKED BY :
COOLING COIL SELECTION SHEET - CHW

Customer : DATE

A.H.U. NO. 2

Latent ( L ) 0 BTU / hr. Outside Air ( OA ) 460 CFM TOTAL TR = 12.0


Sensible ( S ) 0 BTU / hr. Dehumidified Air ( DA ) 4460 CFM CFM / TR = 372
Total (T) 0 BTU / hr. Return Air ( RA ) 4000 CFM B.P. FACTOR= 0.03

Outside (OT) 110 o


F DB 75 o
F WB Water Qty 71.6 USGPM Coil Vel. Limit 500 FPM
Inside ( IT ) 73 o
F DB 55 % RH Water in 45 o
F A.D.P. 55.2 o
F
Coil Lvg (LT ) 55.85 o
F DB o
F WB Water out 54 o
F Contact Factor 0.97

Mixture Temp. (AIR ) : 76.82 o


F DB

460 F.A. X 110 O.T. + 4000 RA X 73 I.T.


4460 D.A.

LMTD = GTD - LTD 16.10 Ht Lt


LN (GTD / LTD) Coil Size : 5/8 " 36 36
Air Entering 76.82 Coil Lvg 55.85 Coil Size : 1/2" 24 54
Water Out 54 Water In 45 No .Of Coils :
GTD 22.82 LTD 10.85
Actual area each sq. ft.
Coil Area ( CA ) = 4460 D.A. = 8.92 sq. ft. Full half quarter
500 Air . Vel. No. of Circuits : 24.0 12.0 6.0 per coil
19.2 9.6 4.8
Water Vel. = G.P.M. 71.6 X 1.1 = 3.28 fps Velocity : 3.28 fps
24 No .of circuits

Sensible Heat Ratio ( SHR ) 0.88


Air Entering SH 34 TH 38.18
Air Leaving SH 25 TH 27.92
Difference SH 9 TH 10.26

U.A. Factor (From Catalogue ) : 259.05

No. of Rows = 12 ( TR ) X 12000


LMTD 16.10 X C.A. 8.92 X U.A. 259.05

= 3.28 DIVIDING BY 1.18 FOR 12 FPI) 2.78


Selected = 4 Rows

Notes : For brine circulation apply correction factor for Coil Selected :
specific heat to water quantity. Size :
No. of Coils :
For 12 FPI divide No. of rows by 1.18
Connection on Left Hand Side / Right Hand Side
For 10 FPI, divide no of rows by 1.15
Header Size :
Side of Connection to be as seen while facing
coil from prefilter side Type of coil : DX / CH.W / BRINE

REMARKS :
Coil Size X Ht. X Length X Rows X Ckt X FPI X Type X Connection
1/2" 24 54 4 28 12 CH.W. LHS
DATE : PREPARED BY : RRG CHECKED BY :
COOLING COIL SELECTION SHEET - CHW

Customer : DATE

A.H.U. NO. 1

Latent ( L ) 0 BTU / hr. Outside Air ( OA ) 1730 CFM TOTAL TR = 27.00


Sensible ( S ) 0 BTU / hr. Dehumidified Air ( DA ) 6040 CFM CFM / TR = 224
Total (T) 0 BTU / hr. Return Air ( RA ) 4310 CFM B.P. FACTOR= 0.03

Outside (OT) 110 o


F DB 75 o
F WB Water Qty 71.60 USGPM Coil Vel. Limit 500 FPM
Inside ( IT ) 73 o
F DB 55 % RH Water in 45 o
F A.D.P. 52.3 o
F
Coil Lvg (LT ) 53.24 o
F DB o
F WB Water out 54 o
F Contact Factor 0.97

Mixture Temp. (AIR ) : 83.60 o


F DB

1730 F.A. X 110 O.T. + 4310 RA X 73 I.T.


6040 D.A.

LMTD = GTD - LTD 16.70 Ht Lt


LN (GTD / LTD) Coil Size : 5/8 " 30 58
Air Entering 83.60 Coil Lvg 53.24 Coil Size : 1/2" 24 72
Water Out 54 Water In 45 No .Of Coils :
GTD 29.60 LTD 8.24
Actual area each sq. ft.
Coil Area ( CA ) = 6040 D.A. = 12.08 sq. ft. Full half Quarter quarter
Half
500 Air . Vel. No. of Circuits : 20.0 10.0 5.0 per coil
19.2 9.6 4.8
Water Vel. = G.P.M. 71.6 X 1.1 = 3.28 fps Velocity : 3.28 fps
24 No .of circuits

Sensible Heat Ratio ( SHR ) 0.88


Air Entering SH 34 TH 38.18
Air Leaving SH 25 TH 27.92
Difference SH 9 TH 10.26

U.A. Factor (From Catalogue ) : 259.05

No. of Rows = 27 (T)X 12000


LMTD 16.70 X C.A. 12.08 X U.A. 259.05

= 5.2535 DIVIDING BY 1.18 FOR 12 FPI) 4.45


Selected = 6 Rows

Notes : For brine circulation apply correction factor for Coil Selected :
specific heat to water quantity. Size :
No. of Coils :
For 12 FPI divide No. of rows by 1.18
Connection on Left Hand Side / Right Hand Side
For 10 FPI, divide no of rows by 1.15
Header Size :
Side of Connection to be as seen while facing
coil from prefilter side Type of coil : DX / CH.W / BRINE

REMARKS :
Coil Size X Ht. X Length X Rows X Ckt X FPI X Type X Connection
1/2" 24 72 6 28 12 CH.W. LHS
DATE : PREPARED BY : RRG CHECKED BY :