Technical Specification For Current Transformers: Miyaneh Steel Complex
Technical Specification For Current Transformers: Miyaneh Steel Complex
DOCUMENT TITLE :
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 2 of 12
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 3 of 12
                                                                                                     CURRENT TRANSFORMER
                                                                                                                                                                                     1
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                     1.0 GENERAL………………………………………………………………………………
                                                                                                           …….4
                                                                                                     2.0 DESCRIPTION…………………………………………………………………………….....6
                                                                                                     3.0 TERMINOLOGY…………………………………………………………………………...…6
                                                                                                     4.0 STANDARDS…………………………………………………………………………..…….6
                                                                                                     5.0 DESIGN AND CONSTRUCTION…………………………………………………..…..…..6
                                                                                                     6.0 SUBMITTALS………………………………………………………………………….....….9
                                                                                                     7.0 INSPECTION AND TESTS……………………………………………………………..…10
                                                                                                     8.0 SUPERVISION OVER INSTALLATION AND ERECTION……..………….……….….10
                                                                                                     9.0 SPARE PART..…………………… ……………………………………………...……...…11
                                                                                                     10.0 MEASUREMENT AND PAYMENT……………………………………………………..12
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 4 of 12
                                                                                                              1.0           GENERAL
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                              1.1           SCOPE
                                                                                                              This Specification Describes the Minimum requirements for design, inspection and
                                                                                                              testing of outdoor, high voltage (230 KV) current transformers of MIYANEH STEEL
                                                                                                              MAKING PLANT (MIYANEH SMP).
1.2 LANGUAGE
                                                                                                              In the event of any conflict between these specifications, the requisition, drawings,
                                                                                                              codes and standards, the priority shall be given in the following order.
                                                                                                                        a. Purchase order
                                                                                                                        b. Drawings
                                                                                                                        c. This specification
                                                                                                                        d. Codes and standards
                                                                                                              In any case vendor shall refer the matter with Purchaser and obtain clarification
                                                                                                              before proceeding with any work.
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 5 of 12
                                                                                                     The steel making plant to be designed and based on the following site data:
                                                                                                     1.5.1 Ambient temperature
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                     - Registered temperature
                                                                                                     Highest recorded:                                                                                                 +41.8°C
                                                                                                     Lowest recorded:                                                                                                   -25.6°C
                                                                                                     Average recorded:                                                                                                  +14.3°C
                                                                                                     - Design conditions
                                                                                                     Max. Ambient temperature:                                                                                         +20°C
                                                                                                     Min. Ambient temperature:                                                                                         +6.9°C
                                                                                                     1.5.5. Earthquake                                  1
                                                                                                     Earthquake load will be in accordance with the Iranian code of practice for Seismic
                                                                                                     Resistant design of Building, standard 2800 (latest edition). For this project following factor
                                                                                                                                                                                                                                             .shall be applied
                                                                                                     Seismic zone: Region 2 (High Seismic Zone)
                                                                                                                                                                                                                 Design base acceleration: 0.3 G
                                                                                                     Soil: type II
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 6 of 12
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                     2.0 DESCRIPTION
                                                                                                     Current transformers shall mean single phase, oil immersed, self cooled current
                                                                                                     transformers of specified ratings work of this Chapter includes design, manufacture,
                                                                                                     factory testing, transportation and supervision over erection and commissioning of current
                                                                                                     transformers and all their accessories.
                                                                                                     3.0 TERMINOLOGY
                                                                                                     Technical terminology is to be as defined in latest edition of IEC ,50, I.E.E.E 100 and/or
                                                                                                     ANSI C42-100 standards.
                                                                                                     4.0 STANDARDS
                                                                                                     Work of this Chapter shall comply with the requirements of latest edition of IEC, BS,
                                                                                                     DIN,ANSI and NEMA standards within which IEC standard is preferred .
2) A filling plug.
3) A draining valve.
4) A draining cup.
                                                                                                     5)The lower metallic part of the current transformers shall be provided with two earthing
                                                                                                     clamps for suitable size of Cu-conductor so arranged that the earth connection cannot be
                                                                                                     inadvertently removed.
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 7 of 12
                                                                                                     5-2 All details exposed to corrosion shall be made by non-corrosive material, or be hot dip-
                                                                                                     galvanized to a thickness as specified inISO-1461.
                                                                                                     5-3 Current transformer shall be equipped with a secondary terminal box with necessary
                                                                                                     holes for cable connections. The terminal box shall be spacious enough to allow
                                                                                                     connection of necessary connecting leads, and short-circuiting of the current transformer's
                                                                                                     secondary terminals, to be carried out comfortably.
                                                                                                     The terminal box shall be accessible when the current transformer is in operation and also
                                                                                                     be provided with rain-protected, net covered, breather holes. The terminal box shall be
                                                                                                     provided with earthing copper bar suitable for earthing of secondary windings and cable
                                                                                                     shields. The copper wire shall be earthed directly.
                                                                                                     5-4 Current transformers using oil impregnated paper as the insulant may be of the bar,
                                                                                                     single or multi-turn primary. Adequate precautions shall be taken to ensure that a uniform
                                                                                                     stress distribution is achieved throughout the paper insulation. After processing, the
                                                                                                     insulation shall be virtually free of moisture and trapped air.
                                                                                                     Details of the proposed methods of processing, drying and filling the current transformer,
                                                                                                     stating time of drying, degree of vacuum, etc. shall be submitted for the approval of the
                                                                                                     Engineer. Each current transformer shall be impregnated and filled with oil of the grade
                                                                                                     specified in IEC-296.
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 8 of 12
                                                                                                     5-5 The oil-immersed current transformers shall be of the hermatically sealed type
                                                                                                     equipped with bellowes or gas cushion expansion device, the latter case is not acceptable
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                     for top core design. Inner insulation shall be satisfactorily and permanently protected
                                                                                                     against moisture. Associated packings shall be resistant to sun, air, oil and water. Current
                                                                                                     transformers shall be designed without wheels.
                                                                                                     5-6 Full coordination shall be provided between protection current transformers and
                                                                                                     relevant protective relays performance considering transient conditions during initial faults
                                                                                                     and following high speed auto-reclose faults.
                                                                                                     5-7 The precautions taken in the design of the primary windings, to prevent the
                                                                                                     mechanical and thermal stresses, set up on short circuits, from causing a breakdown in
                                                                                                     the transformer, shall be shown on the drawings submitted by the manufacturer.
                                                                                                     5-9 For the multi-ratio tappings a label shall be provided indicating clearly the connections
                                                                                                     required for all ratios.These connections shall also be shown on all connection diagrams.
                                                                                                     5-10 Current transformers shall be mechanically dimensioned for stresses arising from
                                                                                                     tensile forces and movement in connections as well as for short circuit and earthquake
                                                                                                     forces as specified elsewhere in these specifications.
                                                                                                     5-11 The primary terminals shall be designed in accordance with the Technical
                                                                                                     Specification for the design of HV terminals. Insulators shall be manufactured and tested
                                                                                                     according to Ch. bus work.
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                           Page: 9 of 12
                                                                                                     5-12 The type and quality of finish shall be as specified in Chapter MISC. part of these
                                                                                                     specifications.
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                     6.0 SUBMITTALS
                                                                                                     6.1 Calculation Sheets
                                                                                                     Submit four (4) copies of all calculations to establish adequacy of the current transformers
                                                                                                     selected , in any respect, for the specified duties under all power system operation
                                                                                                     conditions (from normal to the most severe fault conditions envisaged) in accidence with
                                                                                                     general section.
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE
                                                                                                                                 MIYANEH
                                                                                                                                 MME    ELCO STEEL
                                                                                                                                             MMTE  COMPLEX
                                                                                                                                   Steel Making Plant Project
                                                                                                                                      ASCOTEC            MMAH
                                                                                             DOCUMENT TITLE                                             :Document No                                       .Rev
                                                                                                                                 :Designer Document NO                                                                             DATE: NOV. 2009
                                                                                            NISCO                                                                             MISP1301ETS003               2-1
ECHNICAL SPECIFICATION for
CURRENT TRANSFORMERS                                                                                                        :Project Document NO                         MWES1U43E000030012                                          Page: 10 of 12
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                     Mandatory spare parts shall be provided as per relevant schedule of prices for this chapter
                                                                                                     The tenderer shall recommend and additional spare parts considered necessary.
C:\Documents and Settings\All Users\Documents\sub-2-9-88\88.8.30\spec ct rev2\spec CT.doc
                                                                                                       Confidential: This document discloses proprietary information. It may not be reproduced nor disclosed any person, nor used for any purpose, except with the written
                                                                                                       .permission of MMTE