VIBROCONTROL 1500
2-channel Monitoring Device for Bearing
  Vibrations, Rolling-element Bearing
       Condition and Temperature
   with Diagnostic Remote Monitoring
 Operating Instructions
VIBROCONTROL 1500                                                                                                                   CONTENT
                                             Table of Contents
                                    VIBROCONTROL 1500
1         Safety advice................................................................................ 5
2         Overview ...................................................................................... 6
2.1       Display and operating elements......................................................................6
2.2       Possible measurement and monitoring tasks .................................................7
2.2.1     Display values ...........................................................................................................................7
2.2.2     Measuring range limits ..............................................................................................................8
2.2.3     Display value and bandwidth .....................................................................................................8
2.2.4     Signal detection .........................................................................................................................8
2.3       General ...........................................................................................................9
2.4       Relay functions ...............................................................................................9
3         Technical Data ........................................................................... 11
4         Installation .................................................................................. 16
4.1      With the installation of the VIBROCONTROL 1500 the following are to be
         observed: ......................................................................................................16
4.1.1     Directions for the installation of the VC-1500 on a top-hat rail ................................................17
4.2       Mounting in an AC-211x protective housing .................................................17
4.2.1     Delivery specifications VIBROCONTROL 1500 unit in a protective housing AC-211x ...........19
5         Connections ............................................................................... 21
5.1       Connection terminal layout - upper terminal strip, 1st row ............................22
5.2       Connection terminal layout - upper terminal strip, 2nd row...........................23
5.3       Connection terminal layout - lower terminal strip .........................................23
5.4       Connection terminal layout - power supply AC-4111 ....................................25
5.5       Sensor connection and sensor monitoring....................................................25
5.6       Connection of sensors ..................................................................................26
6         Switching the instrument ON ...................................................... 28
6.1       Single-channel operation ..............................................................................28
6.2       Two-channel (acceleration-temperature) operation: .....................................28
6.3       Hardware / Firmware version ........................................................................29
© VIBROCONTROL 1500 V12.00 - 09.11.2016                            C 103 845.002                  technical specifications subject to change - 3 -
VIBROCONTROL 1500                                                                                                      CONTENT
7        Operating the VIBROCONTROL 1500 ....................................... 30
7.1      Commissioning the instrument......................................................................30
7.2      Base display .................................................................................................30
7.3      Bargraph with limit value display...................................................................31
7.4      Measuring the temperatures .........................................................................31
7.5      Limit value violation - Display........................................................................32
7.6      Menu-guided instrument dialogue.................................................................32
7.7      Measuring the rolling-element bearing condition ..........................................33
7.7.1    Switching off the automatic reference value determination.....................................................36
7.7.2    General advice for bearing condition analysis.........................................................................37
7.8      Trend display and prognosis.........................................................................38
7.9      Rolling-element bearing condition and temperature - Trend.........................41
7.10     Frequency Analysis.......................................................................................42
7.11     Post-mortem display after a LIM2 violation ...................................................43
7.12     Setting/Editing measurement channel functions - Channel ..........................44
7.12.1   Channel setup - (MONITOR) ..................................................................................................45
7.13     Setting up/Editing the basic functions - Device Setup ..................................51
8        Error messages .......................................................................... 55
9        Function checks and self-diagnosis............................................ 56
10       Accessories................................................................................ 57
10.1     Power supply AC-4111 .................................................................................57
10.2     AC-4601 power supply..................................................................................58
10.3     USB/CAN interfaceconverter AC-4201 .........................................................59
11       User dialogue - Overview ........................................................... 60
12       Maintenance............................................................................... 61
12.1     Calibration.....................................................................................................61
12.2     Cleaning........................................................................................................61
13       Disposal ..................................................................................... 61
14       CE Decleration ........................................................................... 62
© VIBROCONTROL 1500 V12.00 - 09.11.2016                      C 103 845.002               technical specifications subject to change - 4 -
VIBROCONTROL 1500                                                                             Safety advice
1          Safety advice
                          This operating instruction contains information and advice which must be
                          observed during the installation and operation of the VIBROCONTROL 1500.
                          Please read these operating instructions carefully before installing and taking
                          a VIBROCONTROL 1500 into operation!
                          Please read the general safety advice and grounding recommendations before
                          the installation and commissioning!
                          The safety advice and grounding recommendations are separately included
                          with the operating instructions!
                          Intended application
                          VIBROCONTROL 1500 is intended exclusively for measurement, display and
                          monitoring of bearing vibrations, rolling-element bearing condition and
                          temperature in the applications of machine protection and condition-
                          dependent machine maintenance. Operation is only permitted up to 2000
                          meters above sea level!
                          Any application beyond these is considered as invalid for the system.
                          Reliability
                          VIBROCONTROL 1500 is equipment which is reliable in service and
                          corresponds to the state of the art technology. Every instrument leaves our
                          works in an error-free and safe condition.
                          Any person who is responsible for carrying out the installation and operation
                          of the instrument must have read and understood these operating
                          instructions and especially the safety advice in advance of the installation
                          and operation.
                          With inappropriate handling or non-observance of the operating instructions
                          the working reliability is not guaranteed.
                          Warning Note!
                          In the operating instructions reference is made to possible risks and
                          dangers with the installation and start-up. These references are provided
                          with the following terms:
           Caution
                          A caution draws attention to the fact that in case of neglect of the
                          safety advice the possibility of material damage and personal injury
                          exists.
                          Commissioning tasks
                          Commissioning tasks may only be carried out by authorised and trained
                          technical personnel. The required authorisation is exclusively granted by Brüel
                          & Kjær Vibro.
                          Attached safety instructions for installation, commissioning and
                          disposal must be observed!
© VIBROCONTROL 1500 V12.00 - 09.11.2016          C 103 845.002        technical specifications subject to change - 5 -
VIBROCONTROL 1500                                                                              Safety advice
2          Overview
                          The VIBROCONTROL 1500 is a 2-channel, microprocessor-controlled
                          measurement data acquisition, monitoring and diagnosis instrument.
                          Constant-current powered (CCS) acceleration sensors are used for the
                          vibration measurements.
                          In addition to the measurement of casing vibrations in the frequency ranges
                          10 Hz to 1,000 Hz, a rolling-element bearing condition variable is also
                          calculated for the assessment of rolling-element bearing condition.
                          For the measurement and monitoring of temperatures, of type PT-100
                          temperature sensors may also be applied in addition to the vibration sensors.
                          For operation of the instrument a power supply of 20 to 32 VDC is necessary.
                          The power consumption of the instrument amounts to approx. 6 W .
2.1        Display and operating elements
                          Front view
                          Fig.1: VIBROCONTROL 1500 front view
            Buttons and displays
                            Buttons for switching to individual displays, making a selection within the
            , 
                            menus and entering values
            ESC            Button for return to previous display
            ENTER
                           Button for confirmation of entry and calling up menus.
            MENU
            OK             Green LED for display of the OK-status
            L1             Amber LED for display of L1 status
            L2             Red LED for display of the L2 status
© VIBROCONTROL 1500 V12.00 - 09.11.2016           C 103 845.002        technical specifications subject to change - 6 -
VIBROCONTROL 1500                                                                                   Overview
                          The standard equipment contains:
                          o    Two (2) relays with potential-free switch-over contacts for signaling event
                               messages. The relays are assigned to the set limit values.
                          o    One (1) OK relay with potential-free switch-over contacts for monitoring
                               of the power supply, the functions of the microprocessor system and the
                               connected sensors.
                          o    Two (2) analogue outputs proportional to the casing vibration.
                          o    CAN-Bus interface for data transmission between the VIBROCONTROL
                               1500 and a super-ordinate computer.
                          All setting up tasks are carried out directly at the instrument by entry or
                          selection of parameter values. Setting up is also possible using the
                          VIBROCONTROL 1500 Control-Center-Software.
                          The connections for the power supply, measurement sensors, analogue and
                          contact outputs as well as the CAN-Bus interface are made through plug-in
                          terminal blocks.
2.2        Possible measurement and monitoring tasks
2.2.1      Display values
                          Corresponding to the national and international prescription for evaluation of
                          machine vibrations, the effective (RMS) value of vibration velocity is used for
                          display and monitoring.
                              Display value                        Abbreviation                  Unit
                              Vibration velocity                        v               mm/s            in/s
                          There is also the possibility to display and monitor the value of rolling- element
                          bearing condition; unit of rolling-element bearing condition: BC (Bearing
                          Condition)
                              Rolling-element bearing                BC value                  BC
                              condition                                                    dimensionless
                          Measurement and monitoring of temperature is possible by connecting
                          PT-100 sensors.
                            Temperature                             T                 °C °F
© VIBROCONTROL 1500 V12.00 - 09.11.2016            C 103 845.002       technical specifications subject to change - 7 -
VIBROCONTROL 1500                                                                                      Overview
2.2.2      Measuring range limits
                          The measuring range can, according to the application, be adapted to the
                          machine or monitored plant by a wide range.
                          In the table below the measuring range limits (min. max.) are given dependent
                          upon the characteristic variable = effective (RMS) value of vibration velocity.
                          Sensor :                Vibration acceleration sensor
                          Variable :              Effective value (RMS)
                             Display and monitor value                 Measurement range                  Unit
                                                                        Min          Max
                             Vibration velocity                   0 ... 10      0 ... 200                mm/s
                                                                  0 ... 0.5     0 ... 10                  in/s
                          For the selected measuring range, signals of 4 - 20 mA per sensor
                          proportional to the characteristic variable are available at the analogue
                          outputs.
2.2.3      Display value and bandwidth
                          Acquisition of the measured data is done by vibration acceleration sensors.
                             Display and monitor value                  Bandwidth of the
                                                                        characteristic value
                                                                        formation
                             Vibration velocity                           10 Hz ... 1,000 Hz
                             Rolling-element bearing condition           500 ... 5,000 Hz DFT
2.2.4      Signal detection
                          The output voltage of the measurement sensors is proportional to the
                          measured magnitude of the time signal (vibration acceleration).
                          The following signal detection step is carried out by the VIBROCONTROL
                          1500:
                          Calculation of the effective (RMS) value of vibration velocity from an
                          integration of the vibration acceleration signal.
© VIBROCONTROL 1500 V12.00 - 09.11.2016           C 103 845.002           technical specifications subject to change - 8 -
VIBROCONTROL 1500                                                                                  Overview
2.3        General
                          Independently adjustable limit values are assigned to each measuring
                          channel for the casing vibrations, the rolling-element bearing condition and
                          the temperatures. The setting of the respective limit values is done in the unit
                          of the measurement channel.
                          Two values, which are adjustable over the entire measuring range, are
                          available for signaling a violation of the alarm limit settings. A limit value
                          violation is displayed at the VIBROCONTROL 1500 by means of LEDs and
                          the output of the violation respectively through potential-free relay contacts.
                          In order to prevent false alarms due to spurious, very short-term limit value
                          violations, a relay response lag time can be activated for each limit value of
                          the vibration.
                          The entry of the relay response lag time always take place in seconds units.
                          If a measured value exceeding the assigned limit value is sustained for
                          longer than the given response lag time, the appropriate event message is
                          activated.
                          If the current measured value falls below the limit value during the response
                          lag time, the event message "limit value violated" is deactivated and upon a
                          renewed limit value violation the response lag time count begins again.
2.4        Relay functions
                          VIBROCONTROL 1500 is equipped with a total of three (3) relays.
                          The status of these relays is signaled at the front panel by LED control
                          lamps. The relays are shared by both channels.
                          Note:
                          Short the reset contacts only for a short notice.
           Caution
                          Voltages of a dangerous level may exist at the relay contacts at any
                          time!
                          LIM 1 relay
                          If the current measured value exceeds the set limit value for the RMS value
                          of vibration velocity L1v for longer than the period of the adjusted response
                          lag time T1, the LIM1 relay is activated (closed).
                          The same is valid - however without consideration of a response lag time -
                          during a violation of the limit value of the bearing condition L1BC and a
                          violation of the limit value of temperature L1temp (with the deployment of a
                          vibration sensor with PT-100 sensor or temperature sensor PT-100).
                           The LIM 1 relay is not self-latching and is immediately deactivated
                          (opened) if all L1v, L1BC or L1temp limit value is no longer violated.
© VIBROCONTROL 1500 V12.00 - 09.11.2016          C 103 845.002        technical specifications subject to change - 9 -
VIBROCONTROL 1500                                                                                  Overview
                          LIM 2 relay
                          If the current measured value violates the set limit value for the RMS value of
                          vibration velocity L2v for longer than the period of the adjusted response lag
                          time T2, the LIM2 relay is activated (closed).
                          The same is valid - however without consideration of a response lag time -
                          during a violation of the limit value of the bearing condition L2BC and a
                          violation of the limit value of temperature L2temp (with the deployment of a
                          vibration sensor with PT-100 sensor or temperature sensor PT-100).
                          The LIM 2 relay is self-latching. To reset this condition a reset of the relay
                          or an instrument reset must be carried out.
                          OK relay
                          Monitoring of the power supply, the functions of the microprocessor system
                          and the connected sensors is done by an OK-monitoring function. The display
                          of an existing OK fault is by means of an LED; the output of this signal is
                          by means of a set of potential-free switch-over contacts.
                          With an error-free operation the green LED at the instrument front panel
                          lights up (signaling operational readiness) and the contacts of the OK relay
                          are closed.
                          In case of a fault the LED is extinguished and the OK relay will be
                          deactivated.
                          This OK relay is active during error-free operation (closed, terminals 33 and
                          34 are connected). W hen a fault occurs these relay contacts open. This relay
                          is self-latching. To reactivate this, a reset of the relay or the instrument is
                          necessary.
                          Instrument Reset
                          Simultaneously pushing both of the buttons  and ENTER/MENU for a
                          period of at least 3 seconds effects a reset and a restart of the instrument.
                          Reset of the self-latching relay
                          A reset of the active (closed) condition of the self-latching relays OK and
                          LIM2 is possible at the RESET input by connecting terminals 25 (RST REL2)
                          and 26 (GND). This reset simultaneously also deletes all error messages.
                          Note:
                          Short the reset contacts only for a short notice.
© VIBROCONTROL 1500 V12.00 - 09.11.2016          C 103 845.002        technical specifications subject to change - 10 -
VIBROCONTROL 1500                                                                               Technical Data
3          Technical Data
                             Power supply                      20 to 32 VDC
                             Current consumption               6 W + 0.25 W
                             Protection class                  IP 20
                             Housing                          Metal
                             Housing dimensions               Appr. 90 x 115 x 75 mm (B x H x D)
                             Weight                           700 g
                             Internal resistance              100 k Ω + 10%
                             Instrument type                   2-channel, switchable to 1-channel version
                             Measurement variable             Vibration velocity mm/s or in/s
                             Measurement ranges                10; 20; 40; 50; 100; 200 mm/s or 0.5, 1; 2;
                                                               2.5; 5; 10 in/s
                             Signal detection                  Effective value (RMS)
                             Frequency ranges                 10 Hz to 1kHz
                             Filter slope                      Acc. to ISO 2373
                                                               60 dB/decade with high pass 10 Hz
                                                               40 dB/decade with low pass 1 kHz
                             Limit values                      Adjustable with push buttons in menu
                             Alert alarm                       LIM 1 (arbitrary in selected measuring
                                                               range)
                             Danger alarm                      LIM 2 (arbitrary in selected measuring
                                                               range)
                             Cable connections:
                             Lower terminal row                Divided terminal rows with terminal blocks,
                                                               plugged into the terminal sockets, max. 2.5
                                                               mm².
                             Upper terminal row                Divided terminal rows with terminal blocks,
                                                               plugged into the terminal sockets,
                                                                        2
                                                               0.14 mm – 1.5 mm².
                                                                     2          2
                             Power supply and                  1 mm – 2,5 mm
                             distribution terminal
                                                                            2            2
                             Cable glands of the               M12: 3.0 mm – 6.5 mm
                             Protective housing                           2          2
                                                               M16: 5.0 mm – 10.0 mm
                             AC-211x
© VIBROCONTROL 1500 V12.00 - 09.11.2016              C 103 845.002        technical specifications subject to change - 11 -
VIBROCONTROL 1500                                                                             Technical Data
                             Sensor:
                             Sensor supply                  5 mA ± 5%
                             Transmission factor            100 mV/g and OFF selectable in menu.
                                                            When selecting OFF in channel B, the
                                                            VIBROCONTROL 1500 operates as a 1-
                                                            channel instrument and the missing sensor
                                                            is then not interpreted as a fault!
                             Transmission factor            Multiplication factor = 0.5 to 1.99; value
                             correction value               adjustable in menu. For measurement
                                                            using acceleration sensors (CCS type)
                                                            whose transmission factor deviates from
                                                            the standard factor of 100 mV/g.
                             Analogue output                4…20 mA, for the RMS value of vibration
                                                            velocity of channel A and channel B,
                                                            proportional to the set measuring range.
                                                            Max. load at the analogue output < 500 Ω .
                             Limit value outputs:           Potential-free contacts
                             Alert alarm                    Potential-free contacts LIM 1,
                                                            Display: amber LED
                             Danger alarm                   Potential-free contacts LIM 2,
                                                            Display: red LED
                             Contact loading:               5A/24 VDC,
                                                            Upon violation of the limit value in channel
                                                            A or B, the corresponding relays LIM1 or
                                                            LIM 2 are activated.
                             OK monitoring                  Function test of the instrument and
                                                            connected sensors
                             Range of OK monitoring         6V + 0.5V ...18V + 0.5 V
                             Display                        Green LED, instrument OK and
                                                            operationally ready
© VIBROCONTROL 1500 V12.00 - 09.11.2016            C 103 845.002        technical specifications subject to change - 12 -