EasyPact TVS Motor starters, contactors & relays up to 630 A www.schneider-electric.
com
EasyPact TVS 3-pole contactors
CPB100419
CPB100418
CPB100417
Size 1 2 3
Rated operational
A 6 9 12 18 25 32 38 40 50 65
current AC-3
Rated operational
A 20 25 32 36 50 60 70 80
current AC-1
Rated 220/230 V 1.1 2.2 3 4 5.5 7.5 9 11 15 18.5
operational
power 380/400 V 2.2 4 5.5 7.5 11 15 18.5 18.5 22 30
in AC-3
415/440 V kW 2.2 4 5.5 9 11 15 18.5 22 25/30 37
500 V 3 5.5 7.5 10 15 18.5 18.5 22 30 37
660/690 V 3 5.5 7.5 10 15 18.5 18.5 30 33 37
Width mm 45 45.5 56 75
Coil rated operating
voltage 24...440 V AC according to the coil voltage code (see below)
Auxiliary built in
1 NO or 1 NC 1 NO + 1 NC
contact
References (1) LC1E06 LC1E09 LC1E12 LC1E18 LC1E25 LC1E32 LC1E38 LC1E40 LC1E50 LC1E65
(1) Partial, see below. Coil voltage code for 3-pole contactors
24 48 110 220 230 240 380 415 440
LC1E06-300 50 Hz B5 E5 F5 M5 - U5 Q5 N5 R5
60 Hz B6 - F6 M6 - - Q6 - R6
LC1E06-95 50/60Hz B7 E7 F7 M7 P7 - Q7 - -
LC1E400-630 50/60Hz - E7 F7 M7 - U7 Q7 N7 -
Contactor: how to determine the full commercial reference ?
Example:
LC1E 12 10 U 5 ref. LC1E1210U5
5 50 Hz
Coil voltage code 240 V
01 1NC
Auxiliary contact configuration (2)
10 1NO
Rated operation current AC3 12 A
Contactor EasyPact TVS
Example 1: you need a 32 A contactor, 1 NC auxiliary contact, 24 V - 50 Hz
coil C LC1E3201B5
Example 2: you need a 120 A contactor, 1 NC + NO auxiliary contact, 220 V - 50 Hz
coil C LC1E120M5
(2) Example up to LC1E38 For details, please consult page A-3.
Version 6.3 - 1 Jan. 2019
A-1 EasyPact TVS catalog