Motor Starters, Contactors & Relays Up To 630 A Easypact Tvs

This document provides specifications for EasyPact TVS 3-pole contactors from Schneider Electric, including: 1. It lists the available sizes from 1 to 80A for rated operational current in AC-3 and AC-1 applications. 2. It provides the rated operational power in kW for various standard voltages from 220V to 690V. 3. It specifies the width in mm depending on the size of the contactor. 4. It indicates the available coil rated operating voltages from 24V to 440V AC. 5. It notes the standard auxiliary built-in contact is 1 NO or 1 NC, but higher sizes can include 1 NO + 1 NC.

Uploaded by

EdwinApacionado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views1 page

Motor Starters, Contactors & Relays Up To 630 A Easypact Tvs

This document provides specifications for EasyPact TVS 3-pole contactors from Schneider Electric, including: 1. It lists the available sizes from 1 to 80A for rated operational current in AC-3 and AC-1 applications. 2. It provides the rated operational power in kW for various standard voltages from 220V to 690V. 3. It specifies the width in mm depending on the size of the contactor. 4. It indicates the available coil rated operating voltages from 24V to 440V AC. 5. It notes the standard auxiliary built-in contact is 1 NO or 1 NC, but higher sizes can include 1 NO + 1 NC.

Uploaded by

EdwinApacionado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

EasyPact TVS Motor starters, contactors & relays up to 630 A www.schneider-electric.

com

EasyPact TVS 3-pole contactors

CPB100419
CPB100418
CPB100417

Size 1 2 3

Rated operational
A 6 9 12 18 25 32 38 40 50 65
current AC-3

Rated operational
A 20 25 32 36 50 60 70 80
current AC-1

Rated 220/230 V 1.1 2.2 3 4 5.5 7.5 9 11 15 18.5


operational
power 380/400 V 2.2 4 5.5 7.5 11 15 18.5 18.5 22 30
in AC-3
415/440 V kW 2.2 4 5.5 9 11 15 18.5 22 25/30 37

500 V 3 5.5 7.5 10 15 18.5 18.5 22 30 37

660/690 V 3 5.5 7.5 10 15 18.5 18.5 30 33 37

Width mm 45 45.5 56 75

Coil rated operating


voltage 24...440 V AC according to the coil voltage code (see below)

Auxiliary built in
1 NO or 1 NC 1 NO + 1 NC
contact

References (1) LC1E06 LC1E09 LC1E12 LC1E18 LC1E25 LC1E32 LC1E38 LC1E40 LC1E50 LC1E65

(1) Partial, see below. Coil voltage code for 3-pole contactors
24 48 110 220 230 240 380 415 440
LC1E06-300 50 Hz B5 E5 F5 M5 - U5 Q5 N5 R5
60 Hz B6 - F6 M6 - - Q6 - R6
LC1E06-95 50/60Hz B7 E7 F7 M7 P7 - Q7 - -
LC1E400-630 50/60Hz - E7 F7 M7 - U7 Q7 N7 -

Contactor: how to determine the full commercial reference ?


Example:
LC1E 12 10 U 5 ref. LC1E1210U5
5 50 Hz
Coil voltage code 240 V
01 1NC
Auxiliary contact configuration (2)
10 1NO
Rated operation current AC3 12 A
Contactor EasyPact TVS

Example 1: you need a 32 A contactor, 1 NC auxiliary contact, 24 V - 50 Hz


coil C LC1E3201B5
Example 2: you need a 120 A contactor, 1 NC + NO auxiliary contact, 220 V - 50 Hz
coil C LC1E120M5
(2) Example up to LC1E38 For details, please consult page A-3.

Version 6.3 - 1 Jan. 2019