P127 PDF
P127 PDF
P125/P126/P127
Directional/Non-directional Relay
P12y/EN M/E95
Technical Manual
Technical Manual                                                P12y/EN M/E95
                BLANK PAGE
             Pxxx/EN SS/G11
SAFETY SECTION
                                                 Pxxx/EN SS/G11
1. INTRODUCTION 3
                 BLANK PAGE
                                                                               Pxxx/EN SS/G11
1.     INTRODUCTION
       This guide and the relevant equipment documentation provide full information on safe
       handling, commissioning and testing of this equipment. This Safety Guide also includes
       descriptions of equipment label markings.
       Documentation for equipment ordered from Schneider Electric is despatched separately from
       manufactured goods and may not be received at the same time. Therefore this guide is
       provided to ensure that printed information which may be present on the equipment is fully
       understood by the recipient.
       The technical data in this safety guide is typical only, see the technical data section of the
       relevant product publication(s) for data specific to a particular equipment.
                 Before carrying out any work on the equipment the user should be familiar with the
                 contents of this Safety Guide and the ratings on the equipment’s rating label.
       Reference should be made to the external connection diagram before the equipment is
       installed, commissioned or serviced.
       Language specific, self-adhesive User Interface labels are provided in a bag for some
       equipment.
       •     Are familiar with the installation, commissioning, and operation of the equipment and
             of the system to which it is being connected;
       •     Are able to safely perform switching operations in accordance with accepted safety
             engineering practices and are authorised to energize and de-energize equipment and
             to isolate, ground, and label it;
       •     Are trained in the care and use of safety apparatus in accordance with safety
             engineering practices;
                 To ensure that wires are correctly terminated the correct crimp terminal and tool
                 for the wire size should be used.
                 The equipment must be connected in accordance with the appropriate connection
                 diagram.
                 Protection Class I Equipment
                      -   Before energizing the equipment it must be earthed using the protective
                          conductor terminal, if provided, or the appropriate termination of the
                          supply plug in the case of plug connected equipment.
                      -   The protective conductor (earth) connection must not be removed since
                          the protection against electric shock provided by the equipment would be
                          lost.
                      -   When the protective (earth) conductor terminal (PCT) is also used to
                          terminate cable screens, etc., it is essential that the integrity of the
                          protective (earth) conductor is checked after the addition or removal of
                          such functional earth connections. For M4 stud PCTs the integrity of the
                          protective (earth) connections should be ensured by use of a locknut or
                          similar.
                 The recommended minimum protective conductor (earth) wire size is 2.5 mm²
                 (3.3 mm² for North America) unless otherwise stated in the technical data section
                 of the equipment documentation, or otherwise required by local or country wiring
                 regulations.
                 The protective conductor (earth) connection must be low-inductance and as short
                 as possible.
                 All connections to the equipment must have a defined potential. Connections that
                 are pre-wired, but not used, should preferably be grounded when binary inputs
                 and output relays are isolated. When binary inputs and output relays are
                 connected to common potential, the pre-wired but unused connections should be
                 connected to the common potential of the grouped connections.
                 Before energizing the equipment, the following should be checked:
                      -   Voltage rating/polarity (rating label/equipment documentation),
                      -   CT circuit rating (rating label) and integrity of connections,
                      -   Protective fuse rating,
                      -   Integrity of   the   protective   conductor    (earth)   connection   (where
                          applicable),
                      -   Voltage and current rating of external wiring, applicable to the application.
                 Accidental touching of exposed terminals
                 If working in an area of restricted space, such as a cubicle, where there is a risk of
                 electric shock due to accidental touching of terminals which do not comply with
                 IP20 rating, then a suitable protective barrier should be provided.
                 Equipment use
                 If the equipment is used in a manner not specified by the manufacturer, the
                 protection provided by the equipment may be impaired.
                 Removal of the equipment front panel/cover
                 Removal of the equipment front panel/cover may expose hazardous live parts,
                 which must not be touched until the electrical power is removed.
Pxxx/EN SS/G11
6.4   Environment
      The equipment is intended for indoor installation and use only. If it is required for use in an
      outdoor environment then it must be mounted in a specific cabinet or housing which will
      enable it to meet the requirements of IEC 60529 with the classification of degree of
      protection IP54 (dust and splashing water protected).
      Pollution Degree - Pollution Degree 2          Compliance is demonstrated by reference
      Altitude - Operation up to 2000m               to safety standards.
      IEC 60255-27:2005
      EN 60255-27: 2006
Introduction                  P12y/EN IT/E95
MiCOM P125/P126/P127
               INTRODUCTION
Introduction                                         P12y/EN IT/E95
CONTENTS
1. INTRODUCTION 3
5.     MAIN FUNCTIONS                                              7
5.1    Main functions                                              7
5.2    General functions                                           8
P12y/EN IT/E95                          Introduction
                 BLANK PAGE
Introduction                                                                      P12y/EN IT/E95
1.     INTRODUCTION
       The MiCOM P125, P126 & P127 relays have been designed for controlling, protecting and
       monitoring industrial installations, public distribution networks and substations. They can also
       be used as part of a protection scheme for transformers and generator transformers. The
       P125, P126 & P127 relays can also provide back-up protection for HV and EHV transmission
       systems.
P12y/EN IT/E95                                                                      Introduction
5.     MAIN FUNCTIONS
5.1    Main functions
       The following table shows the functions available with the models.
       ANSI
       CODES      FEATURES                                             P125     P126     P127
       50/51P/N   1 phase or earth overcurrent                              •
       50/51      3 phase overcurrent                                              •       •
       50/51N     Earth overcurrent                                                •       •
       64N        Restricted Earth Fault                                    •      •       •
       67P        3 phase directional overcurrent                                          •
       67N        Earth fault directional overcurrent                       •      •       •
       51V        Voltage controlled overcurrent                                           •
       37         3 phase undercurrent                                             •       •
       46         Negative phase sequence overcurrent                              •       •
       27/59      Phase under/over voltage (AND & OR mode)                                 •
       59N        Residual over voltage                                     •      •       •
       32         Directional power (active / reactive, under / over
                                                                                           •
                  power)
       32N        Wattmetric Earth Fault                                    •      •       •
       81U/O      Under/over frequency                                                     •
       81R        Rate of Frequency                                                        •
       49         Thermal overload                                                 •       •
       86         Output relay latching                                     •      •       •
       79         Autoreclose                                                      •       •
       50BF       Circuit breaker failure detection                                •       •
       46BC       Broken conductor detection I2/I1                                 •       •
                  Blocking Logic                                            •      •       •
                  Test of output relays (Maintenance)                       •      •       •
                  CB control Local/remote                                   •      •       •
                  Circuit Breaker Maintenance and Trip Circuit
                                                                                   •       •
                  Supervision
                  Cold load pick up                                                •       •
                  Selective relay scheme logic                                     •       •
                  Inrush blocking                                                          •
                  Switch on to fault (SOTF)                                        •       •
                  Phase rotation                                                           •
                  VT supervision (VTS)                                                     •
                  CT Supervision (CTS)                                                     •
P12y/EN IT/E95                                                                  Introduction
  HANDLING, INSTALLATION
   AND CASE DIMENSIONS
Handling, Installation and Case Dimensions                     P12y/EN IN/E95
CONTENT
1.      GENERAL CONSIDERATIONS                                              3
1.1     Receipt of relays                                                   3
1.2     Electrostatic discharge (ESD)                                       3
3. RELAY MOUNTING 5
4. UNPACKING 6
5. STORAGE 7
6.      CONNECTIONS                                                         8
6.1     Connection of power terminals, and Signals terminals                8
6.2     Communication port RS485                                            9
6.3     RS232 port                                                          9
6.4     IRIG-B connections (P127 option)                                    9
6.4.1   IRIG-B Modulated                                                    9
6.4.2   IRIG-B demodulated                                                 10
6.5     Protective Conductor (Earthing)                                    10
7.      CASE DIMENSIONS                                                    11
7.1     MiCOM P126 & P127                                                  11
7.2     MiCOM P125                                                         11
P12y/EN IN/E95     Handling, Installation and Case Dimensions
                 BLANK PAGE
Handling, Installation and Case Dimensions                                       P12y/EN IN/E95
1.     GENERAL CONSIDERATIONS
                        BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
                        USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
                        GUIDE SFTY/4LM/E11 OR LATER ISSUE, OR THE SAFETY AND
                        TECHNICAL DATA SECTIONS OF THE TECHNICAL MANUAL AND
                        ALSO THE RATINGS ON THE EQUIPMENT RATING LABEL.
3.     RELAY MOUNTING
       Relays are dispatched either individually or as part of a panel/rack assembly.
       If an MMLG test block is to be included it should be positioned at the right-hand side of the
       assembly (viewed from the front). Modules should remain protected by their metal case
       during assembly into a panel or rack.
       If external test blocks are connected to the relay, great care should be taken when using the
       associated test plugs such as MMLB and MiCOM P992 since their use may make hazardous
       voltages accessible. *CT shorting links must be in place before the insertion or removal of
       MMLB test plugs, to avoid potentially lethal voltages.
                NOTE:        When a MiCOM P992 Test Plug is inserted into the MiCOM P991 Test
                             Block, the secondaries of the line CTs are automatically shorted,
                             making them safe.
       For individually mounted relays an outline diagram is supplied in section 6 of this chapter
       showing the panel cut-outs and hole centres.
P12y/EN IN/E95                               Handling, Installation and Case Dimensions
4.    UNPACKING
      Care must be taken when unpacking and installing the relays so that none of the parts is
      damaged or the settings altered. Relays must only be handled by skilled persons. The
      installation should be clean, dry and reasonably free from dust and excessive vibration. The
      site should be well lit to facilitate inspection. Relays that have been removed from their cases
      should not be left in situations where they are exposed to dust or damp. This particularly
      applies to installations which are being carried out at the same time as construction work.
Handling, Installation and Case Dimensions                                      P12y/EN IN/E95
5.     STORAGE
       If relays are not to be installed immediately upon receipt they should be stored in a place
       free from dust and moisture in their original cartons. Where de-humidifier bags have been
       included in the packing they should be retained. The action of the de-humidifier crystals will
       be impaired if the bag has been exposed to ambient conditions and may be restored by
       gently heating the bag for about an hour, prior to replacing it in the carton.
       Dust which collects on a carton may, on subsequent unpacking, find its way into the relay; in
       damp conditions the carton and packing may become impregnated with moisture and the de-
       humifier will lose its efficiency.
       Storage temperature: –25°C to +70°C.
P12y/EN IN/E95                               Handling, Installation and Case Dimensions
6.    CONNECTIONS
6.1   Connection of power terminals, and Signals terminals
                        BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
                        USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
                        GUIDE SFTY/4LM/E11 OR LATER ISSUE, OR THE SAFETY AND
                        TECHNICAL DATA SECTIONS OF THE TECHNICAL MANUAL AND
                        ALSO THE RATINGS ON THE EQUIPMENT RATING LABEL.
      The individual equipment is delivered with sufficient M4 screws and washers to connect the
      relay via insulated crimp ring terminals. The maximum number of crimped terminations, per
      terminal block terminal, is two.
      If necessary, Schneider Electric can provide 4 types of insulated crimp terminals (see below)
      according to the cross sectional area of the wire and the type of terminal. Each reference
      corresponds to a sachet of 100 terminals.
P0166ENc
P0167ENc
      To ensure the isolation of adjacent terminals, and to respect the security and safety
      instructions, an insulated sleeve must be used.
      We recommend the following cable cross-sections:
        Except for the RS485 port(s) all the terminal blocks used for connections, can withstand a
        maximum working voltage of 300V.
        We recommend the auxiliary supply is protected by a NIT or TIA fuse type with a maximum
        breaking capacity of 16A. For safety reasons, never install fuses in current transformers
        circuits. Other circuits must be protected by fuses.
6.2     Communication port RS485
        Connections to RS485 are made using ring terminals. It is recommended that a two core
        screened cable, is used with a maximum total length of 1000 m or a 200nF total cable
        capacitance.
        Typical specification:
        −     Position the BNC adaptor (“+” side on terminal 82) and screw the scre/washer
              assembly (“+” and “GND” sides are marked on the adaptor).
Retaining screw
washer
                                                         spacer
                                                                   P3953ENa
P12y/EN IN/E95                               Handling, Installation and Case Dimensions
7.     CASE DIMENSIONS
7.1    MiCOM P126 & P127
P0077ENb
              NOTE:        For P127 with IRIG-B option with BNC adaptor, add 25 mm to the
                           length.
7.2    MiCOM P125
P0078ENb
              NOTE:        The chassis is normally secured in the case by four screws (Self
                           tapping screws 6x1,4), to ensure good seating. The fixing screws
                           should be fitted in normal service (do not add washers). Do not
                           discard these screws.
P12y/EN IN/E95     Handling, Installation and Case Dimensions
                 BLANK PAGE
User Guide                    P12y/EN FT/E95
                 USER GUIDE
User Guide                                                            P12y/EN FT/E95
CONTENT
2.      MENU                                                                      21
2.1     OP PARAMETERS menu                                                        22
2.2     ORDERS menu                                                               23
2.3     CONFIGURATION menu                                                        24
2.3.1   Submenu General Options                                                   24
2.3.2   Voltage Connections                                                       26
2.3.3   Submenu Transfo. Ratio                                                    27
2.3.4   Submenus to Configure LEDs 5 to 8                                         28
2.3.5   Submenu Logic Inputs Choice: Active High/Low                              32
2.3.6   Submenu Output Relays                                                     32
2.3.7   Submenu Group Select                                                      33
2.3.8   Submenu Alarms                                                            34
2.3.9   Submenu Date                                                              35
2.4     MEASUREMENTS menu                                                         36
2.5     METERING Menu (P127)                                                      39
2.5.1   Submenu “Frequency”                                                       39
2.5.2   Submenu “Currents”                                                        40
2.5.3   Submenu “Voltages”                                                        41
2.5.4   Submenu Powers                                                            42
2.5.5   Submenu Energies                                                          43
2.5.6   Plus and minus signes for power and energy calculation.                   44
P12y/EN FT/E95                                                                       User Guide
3.       WIRING                                                                             93
3.1      Auxiliary Power Supply                                                              93
3.2      Current Measurement Inputs                                                          93
3.3      Digital Inputs                                                                      93
User Guide                               P12y/EN FT/E95
                 BLANK PAGE
User Guide                                                                      P12y/EN FT/E95
        The alarms are presented in reverse order of their detection (the most recent alarm first, the
        oldest last). The user can either acknowledge and clear each alarm from the LCD by using
         or go to the end of the ALARM menu and carry out a general acknowledgement.
                         P125                                              P126/P127
        As can be seen in above figures the case width dimensions differ between the P125 and the
        P126/P127.
        The table shows the case size for the relays.
        The hinged covers at the top and bottom of the relay are shown closed. Extra physical
        protection for the front panel can be provided by an optional transparent front cover; this
        allows read only access to the relays settings and data but does not affect the relays IP
        rating. When full access to the relay keypad is required to edit the settings, the transparent
        cover can be unclipped and removed when the top and bottom hinged covers are open. If
        the lower cover is secured with a wire seal, this will need to be removed. Using the side
        flanges of the transparent cover, pull the bottom edge away from the relay front panel until it
        is clear of the seal tab. The cover can then be moved vertically down to release the two
        fixing lugs from their recesses in the front panel.
1.1.2   Front Panel Description
        MiCOM P125, P126 and P127 relay front panel allows the user to easily enter relay settings,
        display measured values and alarms and to clearly display the status of the relay.
1.1.3.2   Keypad
          The keypad has seven keys divided into two groups:
• Two keys located just under the screen (keys and c).
          Keys  and c are used to read and acknowledge alarms. To display successive alarms,
          press key c. Alarms are displayed in reverse order of their detection (the most recent alarm
          first, the oldest alarm last). To acknowledge the alarms, the user can either acknowledge
          each alarm using  or go to the end of the ALARM menu and acknowledge all the alarms
          at the same time.
          When navigating through submenus, key  is also used to come back to the head line of
          the corresponding menu.
                    NOTE:        To acknowledge a relay latched refer to the corresponding submenu
                                 section.
          They are used to navigate through the different menus and submenus and to do the setting
          of the relay.
          The key  is used to validate a choice or a value (modification of settings).
P12y/EN FT/E95                                                                           User Guide
1.1.4   LEDs
        The LED labels on the front panel are by default written in English, however the user has
        self-adhesive labels available with MiCOM relays on which it is possible to write using a ball
        point pen.
        The top four LEDs indicate the status of the relay (Trip condition, alarm LED, equipment
        failure, auxiliary supply).
        The four lower LEDs are freely programmable by the user and can be assigned to display a
        threshold crossing for example (available for all models) or to show the status of the logic
        inputs.The description of each one of these eight LEDs located in the left side of the front
        view is given hereafter (numbered from the top to bottom from 1 to 8):
LED 1
LED 8 P3951ENa
1.1.5     Description of the two areas under the top and bottom flaps
1.1.5.1   Relay Identification
          Under the top hinged cover there is an adhesive paper label that contains the relay model
          number, serial number, sensitive earth current range, rating information and the Cortec code
          for ordering etc.
          Each item on the label is described below:
1.1.6     Description of rear Terminal Block for P125, P126 & P127
1.1.6.1   Description of rear Terminal Block for P125
Case earth
                                            1       2           29             30
                                            3       4           31             32
                                            5       6           33             34
                                            7       8           35             36
                                            9      10           37             38
                                            11     12           39             40
                                            13     14           41           42
                                            15     16           43           44
                                            17     18           45           46
                                            19     20           47           48
                                            21     22           49           50
                                            23     24           51           52
                                            25     26           53           54
                                            27     28           55           56
13 14 Output 3 41 42
                                  15   16   Common                                  43   44
                                            output 3
                     Input 3      17   18   Output 4                                45   46
                     + terminal
                     Input 3      19   20   Common            Current input         47   48   Current
                     – terminal             output 4          (5A)                            input (5A)
                     Input 4      21   22   Input 1                                 49   50
                     + terminal             + terminal
                     Input 4      23   24   Input 1                                 51   52
                     – terminal             – terminal
                                  25   26   Input 2                                 53   54
                                            + terminal
Case earth
                                       57    58          1         2          29        30
                                       59    60          3         4          31        32
                                       61    62          5         6          33        34
                                       63    64          7         8          35        36
                                       65    66          9         10         37        38
                                       67    68          11        12         39        40
                                       69   70           13        14          41       42
                                       71   72           15        16          43       44
                                       73   74           17        18          45       46
                                       75   76           19        20          47       48
                                       77   78           21        22          49       50
                                       79   80           23        24          51       52
                                       81   82           25        26          53       54
                                       83   84           27        28          55       56
Case earth
Column header
                                       OP
                                               Config.    Measur.   Comm.   Protections   Autom. Ctrl   Records
                                       param
                         Column
                            data
                         settings
P0106ENb
                                                         MENU STRUCTURE
1.3     Password
1.3.1   Password Protection
        Password protection is applicable to most of the relay settings, especially to the selection of
        the various alarm thresholds, trip thresholds, communication parameters, allocation of logic
        inputs and outputs.
        The password consists of four capital characters. When leaving the factory, the password is
        set to AAAA. The user can define any combination of four characters.
        Should the password be lost or forgotten, modification of the stored parameters is blocked. It
        is then necessary to contact the manufacturer or his agent and a stand-by password specific
        to the relay concerned may be obtained.
        The programming mode is indicated with the letter "P" on the right hand side of the display
        on each menu heading. The letter "P" remains present as long as the password is active
        (5 minutes if there is no action on the keypad).
1.3.2   Password Entry
        The input of the password is requested as soon as a modification of a parameter is made for
        any one of the six/eight menus and the submenus. The user enters each of the 4 characters
        and then validates the entire password with .
        After 5 seconds, the display returns to the point of the preceding menu.
        If no key is pressed inside of 5 minutes, the password is deactivated. A new password
        request is associated with any subsequent parameter modification.
P12y/EN FT/E95                                                                           User Guide
        The message NEW PASSWORD OK is displayed to indicate that the new password has
        been accepted.
1.3.4   Change of Setting Invalidation
        The procedure to modify a setting is shown in the next part of this document.
        If during this action it occurs the need to get back to the old setting it is necessary push the
         key before validating the setting change. After this action the following message will
        appear on the LCD for some seconds and the old setting will be maintained.
         UPGRADE
         CANCEL
− microprocessor operation,
                                         Menu’ ALARMS
                                I> PHASE               tI> PHASE
                                     A                      A
                                     A                      A
                                     B                      B
                                     B                      B
                                     C                      C
                                     C                      C
                                     A                      A
                                    AB                     AB
                                    AB                     AB
                                     A                      A
                                    AB                     AB
                                   ABC                    ABC
                                   ABC                    ABC
                                   ABC                    ABC
                                   ABC                    ABC
                                   ABC                    ABC
                                   ABC                    ABC
        Following is a description of the voltage inputs connection for the P127 relay.
        Case A
        2 phase to neutral voltage inputs
        1 residual voltage input
                 VC is then calculated as VC= – (VA+ VB)
        To obtain a correct reading of the input voltage the exact voltage transformer ratio for Ve has
        to be set.
P12y/EN FT/E95                                                                       User Guide
      Case B
      2 phase to phase voltage inputs
                VCA is then calculated as VCA= –(VAB + VBC)
      Case C
      3 phase to phase voltage inputs
      No residual voltage input
                Ve can be calculated as Ve = (VA+ VB+ VC )/3
      •      On the MiCOM P125 relays rear terminals there is one current input rated 1A and one
             current input rated 5A available and one voltage input. On the MiCOM P126 relay rear
             terminals there are four current inputs rated 1A and four current inputs rated 5A
             available and one voltage input. On the MiCOM P127 relay rear terminals there are
             four current inputs rated 1A and four current inputs rated 5A available and three
             voltages input.
      •      By using the Cortec code (see the appropriate section) the user can choose the
             voltage range for voltage inputs for the MiCOM P125 & P126 (one input) and P127
             (three inputs).
      All logic outputs can be programmed to respond to any of the available control or protection
      functions. Logic inputs can be assigned to various control functions.
      All logic digital inputs can be programmed to respond to any of the available control or
      protection functions. Their supply level is the same as the power supply selected of the relay
      by Cortec. They can be supplied in A.C or D.C current by Cortec choice.
      The MiCOM relays are powered either from a DC or an AC auxiliary power supply.
      Any short time voltage interruption (<50ms) is filtered and regulated through the auxiliary
      power supply.
      The front panel enables the user to navigate through the menu to access data, change
      settings, read measurements etc.
      Eight LEDs on the front panel allow a clear and simple presentation of events. The various
      detected alarms are stored and can be displayed on the back-lit LCD.
      No Password is required to read and acknowledge (clear) these alarm messages.
      On their rear terminals the MiCOM P125, P126 & P127 relays have a standard RS485 port
      available. The user can choose, by ordering, the communication protocol ModBus RTU, IEC
      60870-5-103 or DNP3 (when available).
      Using the communication channel RS485, all stored information (measurements, alarms,
      and parameters) can be read and the settings can be modified if this functionality is allowed
      by the chosen protocol.
      Evaluation and modification of this data can be carried out on site with a normal PC and the
      appropriate Schneider Electric software.
      RS485 based communication allows MiCOM P125, P126 & P127 relays to be directly linked
      to a digital control system.
      All the available data is then placed at the disposal of the supervisor and can be processed
      either local or remotely.
User Guide                                                                    P12y/EN FT/E95
2.    MENU
      The menu for the MiCOM P125, P126 & P127 relays is divided into the following sections.
      To access these menus from the default display press .
                     DEFAULT
                       DEFAULT
                             DISPLAY
                               DISPLAY          OP
                                                 OPPARAMETERS
                                                    PARAMETERS
                                                   ORDERS
                                                    ORDERS
                                               CONFIGURATION
                                                CONFIGURATION
                                                MEASUREMENTS
                                                 MEASUREMENTS
                                                  METERING
                                                   METERING
When displayed
                                               COMMUNICATION
                                                COMMUNICATION
                                                PROTECTION
                                                  PROTECTIONGx
                                               x = 1,2 or 1 to 8
                                            (P127)
                                               AUTOMAT.
                                                AUTOMAT.CTRL
                                                         CTRL
                                                 RECORDS
                                                   RECORDS
                                                                   P0003ENe
P12y/EN FT/E95                                                                     User Guide
       Active Group                This window displays the active protection and automatic
                           1       features group.The display value can be 1 or 2 for
                                   P125/P126 and 1 to 8 for P127.
       Input         7654321       Displays the status of the logic Inputs.
       Status        0110110       Logic inputs are numbered from 1 to 4 for P125 and 1 to 7
                                   for P126 and P127. When the indicated status is
                                   - 0 the logic input is inactive,
                                   - 1 the logic input is active.
       Input          CBA98        Displays the status of the logic Inputs 8 to 12, only for P127
       Status          00000       “5 opto-inputs” option (product codes P127xx1 or P127xx3).
      − to send open or close orders to the Circuit Breakers from the front panel. Open and close
        orders are written in the event file. This action generates a “Control Trip” alarm, which can
        be inhibited. If inhibited, the “trip” LED and the “Alarm” LED are not lit if the relay RL1 is
        ordered by a control trip information (affected to an input in the “configuration/inputs”
        submenu).
• ratios for the residual voltage and phase voltage transformers (VT),
        •       The choice to enable alarms functionality as well as self reset on trip or instantaneous
                protection or other function,
               CONFIGURA-                                                      
                TION
                                                                           
               General       (1)    Transfo. ratio           Led 5                  Led 6
                options                                                        
Quadrant 2 Quadrant 1
                                                            V
                                Re (–)                           Re (+)
Quadrant 3 Quadrant 4
                                           Im (–)
                                                                           P3976ENa
           Prot. Freq. Block               Sets the voltage threshold below which frequency
           U<                5V            protection is blocked (1).
                                           Setting range:
                                           – from 5 to 130V, step 0.1 (voltage input range 57 to 130V,
                                           P127xA),
                                           – from 20 to 480V, step 0.1V (voltage input range 220 to
                                           480V, P127xB).
           dF/dt Cycles.nb.                The dF/dt detection (rate of change of frequency) is defined
                                 5         as a calculation of an average frequency variation of the
                                           instantaneous values over a programmable number of
                                           cycles.
                                           This menu (1) adjusts the number of periods to calculate a
                                           dF/dt detection.
                                           (setting range from 1 to 200, step 1).
           dF/dt Validat.nb=               Sets the number of dF/dt detection to validate the dF/dt
                                 4         fault (1).
                                           (setting range from 1 to 12, step 1).
           Inh.Block dF/dt                 If Yes is selected, the measurement of the frequency blocks the
           >20 Hz/s             No         calculation when dF/dt exceeds ± 20Hz/s to avoid noise samples
                                                             (1)
                                           in the calculation ,
                                           No: dF/dt measurement is always used for the calculation.
                                           Setting choice: Yes or No).
The shown measurements are functions of system voltages taken at the relay inputs.
CONFIGURATION
           Line CT sec                    Displays the rated secondary current of the line CT (setting
                              5A          value: 1or 5) (1).
           E/Gnd CT primary               Displays the rated primary current of the earth CT from 1 to
                           5A             9999.
           Line VT primary                Displays the rated primary voltage of the line VT (the rated
                        0.10 kV           voltage input range is given by relay Cortec code) from 0.1
                                          to 1000kV (step 0.01kV).
                                          For the 10-480V model the setting range is from 10 to
                                          480V, in steps of 1V (2).
           Line VT sec                    Displays the rated secondary voltage of the line VT (Cortec
                          100.0 V         code) from 2 to 130V (step 0.1V)
                                          This window is not available for the 10-480V model (2).
P12y/EN FT/E95                                                                               User Guide
        The two following lines are only displayed when the connection mode 2Vpp+Vr or 2Vpn+Vr
        is selected.
         E/Gnd VT primary                    Displays the rated primary voltage of the earth VT (Cortec
                     0.10 kV                 code) from 0.1 to 1000kV (step 0.01kV).
                                             For the 10-480V model the setting range is from 10 to
                                             480V, in steps of 1V (2).
         E/Gnd VT sec                        Displays the rated secondary voltage of the earth VT
                           100.0 V           (Cortec code): from 2 to 130V (step 0.1V).
                                             This window is not available for the 10-480V model (2).
        The following lines are only displayed when the “measurement CT” option is present.
         Line CTm primary                    Displays the rated primary current of the measurement CT,
                         1°A                 from 1 to 9999 (2).
                                             Setting range from 1 to 9999 A (step 1A)
         Line CTm sec                        Displays the rated secondary current of the measurement
                              1°A            CT (setting value: 1or 5) (2).
        (1)   P126 and P127 only.
        (2)   P127 only.
        WARNING:           WITH THE P127 RELAY, NOT ALL MEASUREMENTS CAN BE READ IN
                           THE DIRECT MODE. THESE MEASUREMENTS MUST BE READ IN THE
                           INDIRECT MODE.
        These measurement values are called derived measurements. They depend on the selected
        electrical voltage connection mode.
2.3.4   Submenus to Configure LEDs 5 to 8
        To gain access to the CONFIGURATION menu from the default display press . Then
        press  until the submenu Led is reached.
        To reach the LED configuration submenu press  for Led 5. Press  to reach Led 6, again
        to reach Led 7 and again to reach Led 8.
        The following table lists the protection functions that can be assigned to the LEDs (5 to 8) for
        each MiCOM relay model.
        Directional (P127) or three phase (P126) overcurrent protection
                                                      thresholds
        tI>, tI>>, tI>>>              X         X     Time delayed 1st, 2nd and 3rd phase overcurrent
                                                      thresholds
        tIA>, tIB>, tIC>              X         X     Time delayed first threshold trip on phases A, B, C
        Ie>>>
        tIe>, tIe>>,         X        X         X     Time delayed 1st, 2nd and 3rd earth threshold
        tIe>>>
        Ie>>>>                                  X     Instantaneous derived earth overcurrent threshold
        tIe>>>>                                 X     Time delayed derived earth overcurrent threshold
User Guide                                                                         P12y/EN FT/E95
Thermal protection
Overvoltage protection
Undervoltage protection
CB Fail
Logic inputs
Autoreclose function
Auxiliary timers
t SOTF FUNCTION
                                              thresholds
      tP>, tP>>                         X     Time delayed 1st and 2nd active overpower
                                              thresholds
                                              thresholds
      tP<, tP<<                         X     Time delayed 1st and 2nd active underpower
                                              thresholds
User Guide                                                                       P12y/EN FT/E95
                                                thresholds
       tQ>, tQ>>                           X    Time delayed 1st and 2nd reactive overpower
                                                thresholds
                                                thresholds
       tQ<, tQ<<                           X    Time delayed 1st and 2nd reactive underpower
                                                thresholds
Frequency protection
dF/dt6
Logic Equation
CONFIGURATION
CONFIGURATION
         Voltage Input                   Set choice AC or DC power supply for the digital input. The
                              DC         power supply for any input is the same one as much as the
                                         power supply for the relay.
CONFIGURATION
CONFIGURATION
         Change Group                  Selects the way to active the protection setting group.
                     INPUT             When “Input” is selected, “change set” should be assigned
                                       to a logical input in the ‘AUTOMAT. CTRL / Inputs’ menu.
                                       When “Menu” is selected, the setting group is activated:
                                       – locally by HMI, using “Setting Group” cell,
                                       – remotely, using communications port.
                                       Setting choice: Input or menu
         Setting Group                 Displayed only when “Change group” = Menu.
                              1        This cell is used either to activate locally a specific setting
                                       group or to define which value should be used when remote
                                       group switch command is received.
                                       A local setting change command can be perfomed by
                                       changing this value manually among [1 ; 2] for P125/P126
                                       and among [1; 2 ; 3 ; 4 ; 5 ; 6 ; 7 ; 8] for P127.
                                       On P127, when remote group switch command is received,
                                       settings group will switch form ‘setting Group’ to ‘Target
                                       group’ and vice-versa. On P125/P126, ‘Target group’
                                       doesn’t exist as remote group switch command will switch
                                       from 1 to 2 or 2 to 1 by default.
                                       NOTE:
                                       -   Group will be actived only if no alarm is active
                                       -   Active setting group is available in ‘OP PARAMETERS /
                                           Active group’ cell.
         Target group                  Available on P127 only with setting choices from 0 to 8.
                              2        ‘Target group’ defines the destination setting group. When
                                       remote group switch command is received, settings group
                                       will switch form ‘setting Group’ to ‘Target group’ and vice-
                                       versa.
                                       NOTE:
                                       If “0” is selected and remote group switch command is
                                       sned, the setting group will be switched from ‘Active group’
                                       to 1. Next commands will switch settings group from 1 to 2
                                       and vice-versa.
P12y/EN FT/E95                                                                     User Guide
CONFIGURATION
         Reset Led on             If selected, Reset Led on Fault will insure that only the
         Fault              Yes   latest active alarms/LEDs are present (other will be
                                  removed).
         INH Alarm function ?     Yes: the function will not raise an alarm. Alarm LED stays
                          No      OFF no message will be displayed on the HMI.
                                  No: the function will raise an alarm.
                                  The default value is No (except “Inh Alarm Ctrl Trip”=Yes).
                                  In the inh Alarm sub-menus, when the event is noted as a
                                  time delayed threshold, the alarm is inhibited by the time
                                  delayed threshold and the corresponding instantaneous
                                  threshold (for instance, if “Inh Alarm tU<”= yes, U< and tU<
                                  will not raise an alarm. Note, If one of this function is set to
                                  Yes, the alarm will be inhibited if this one is NOT affected to
                                  RL1.
                                  Refer to the following table for trip list.
User Guide                                                                          P12y/EN FT/E95
         Case
         RL1 assigned to “Ctrl Trip”                                    No         No          Yes       Yes
         “Ctrl trip” alarm inhibited                                    No         Yes          No       Yes
         Result:
         LED trip                                                       Off        Off          On       Off
         LED Alarm                                                   blinking      Off        blinking   Off
         Alarm message on display                                      Yes         No          Yes       No
         Event “EVT_TC_TRIP_X1” generated in the event file            Yes         Yes         Yes       Yes
         Default recorded in the records/faul record menu               No         No          Yes       Yes
         RL1 activated                                                  No         No          Yes       Yes
CONFIGURATION
         Date Format                     Assigns free format date or IEC format date (This operation
                                         is seen from remote).
                   PRIVATE
                                         Select choice: Private or IEC
P12y/EN FT/E95                                                                          User Guide
      To gain access to the MEASUREMENTS menu from the default display, press  then 
      until the header of menu is reached.
      The following table lists the items available in the measurements menu for the P125, P126 &
      P127 relays.
Ia
Ic
                                      Vc                     Vb
                                                 Ib           P03978ENa
                                                                  UBC
                                 ICm                            IBm
                                                            P03978ENa
                                           UCA
− frequency,
          −         measured currents, total harmonics distortion (THD) and total demand distortion
                    (TDD), K Factor, measured harmonics,
METERING
         
                                                                                                 
        Frequency              Currents                             Voltages               Powers       Energies
                                                                                                 
                                                                  
                              Phase A                            Phase A            
                                                                                
                                                                       
                                                                                                           P0792ENa
          The following table lists the items available in the Metering menu for the P127 relay:
2.5.1     Submenu “Frequency”
                                        THDAm = 100% ×
                                                                     IAmh2² + IAmh3² + IAmh4² + …
                                                                                 I1
                                        with I1 = magnitude of fundamental current.
        TDDAm TDDBm TDDCm           %   Displays the percentage of the Total Demand Distortion
                                        (TDD) measured for the current. For phase A:
                                        TDDAm = 100% ×
                                                                     IAmh2² + IAmh3² + IAmh4² + …
                                                                                 IL
                                        with IL = magnitude of the load of the system (set this
                                        value using ‘CONFIGURATION / General options / IAm
                                        TDD denom.’ menu.
                 Iam^Ibm Iam^Icm    °   Displays the angle value between phase IAm and IBm,
                                        or between phase IAm and ICm (Phase B only).
                                                    Ia
                                        Ic               P03978ENa
                                                                     Ib
                                                         ∑ IAmhi² × i²
                                        KAM = 100 ×      i=1
                                                            10
                                                            ∑ IAmhi²
                                                              i =1
                                               THDAm = 100% ×
                                                                    VAm2² + VAm3² + VAm4² + …
                                                                                  V1
                                               with V1 = magnitude of fundamental Voltage.
          Iam ^ Va Iam ^ Vb Iam ^ Vc      °    Displays the angle value between phase IA and voltage
                                               VA, VB or VC.
                                                          Va
Ia
Ic
                                                    Vc                 Vb
                                                          Ib            P03978ENa
                   Ibm ^ Vb Icm ^ Vc      °    Displays the angle value between phase IB and voltage
                                               VB, or between phase IC and voltage VC.
                                                          Va
Iam
Icm
                                                    Vc                  Vb
                                                           Ibm         P03978ENa
                                                                              UBC
                                                  ICm                       IBm
                                                                        P03978ENa
                                                         UCA
          Icm^Uab Ibm^Ubc Ibm^Uca            °    Displays the angle value between phase IC and
                                                  voltage UAB, or between phase IB and voltage UBC
                                                  or UCA, or between phase IC and voltage UCA.
                                                        UAB
                                                               Iam
                                                                           UBC
                                                  Icm                    Ibm
                                                                           P03978ENa
                                                        UCA
          VABmh2 VBCmh2 VCAmh2               %    Displays the magnitude of the 2nd to 10th harmonics of
          to      to      to                      the fundamental voltage.
          VABmh10 VBCmh10 VCAmh10
          See § 2.5.6 to see the convention for the positive (+) or negative (–) sign.
User Guide                                                                        P12y/EN FT/E95
        See § 2.5.6 to see the convention for the positive (+) or negative (–) sign.
P12y/EN FT/E95                                                                      User Guide
2.5.6   Plus and minus signes for power and energy calculation.
        Plus or minus signs are defined as follows:
Reference direction
SOURCE LOAD
Metering point
            ACTIVE POWER: P is positive when the power is from the source to the load
            REACTIVE POWER: Q is positive when the load is inductive.
Im (+)
Quadrant 2 Quadrant 1
                                                             V
                             Re (–)                               Re (+)
Quadrant 3 Quadrant 4
                                            Im (–)
                                                                                P3976ENa
with:
         HMI ?
                           Yes
         Date format                   Choose the format of the date, either PRIVATE or IEC
                        Private        protocol.
                                       Select from: Private or IEC.
         COMM1 (or 2) ?
                           Yes
         Baud Rate                     This cell controls the communication speed between relay
                       19200 bd        and master station.
                                       It is important that both relay and master station are set at
                                       the same speed setting.
                                       Select from: 300, 600, 1200, 2400, 4800, 9600, 19200 or
                                       38400 bd.
         Parity                        Choose the parity in the ModBus data frame.
                          None         Select parity: Even, Odd or None
         Stop Bits                     Choose the number of stop bits in the DNP3.0 frame. Select
                              1        0 or 1 using . Press  to validate your choice.
         Relay Address                 This cell sets the unique address for the relay such that only
                              1        one relay is accessed by master station software.
                                       Select from 1 to 255.
P12y/EN FT/E95                                                                          User Guide
             PROTECTION                                                            
              G1 / G2 …G8
                                                                               
             [67/50/51]       (1)     [67N]E/                  [32] Phase    (2)    [32N] Earth     (1)
             [46] Neg         (1)     [49] Therm     (1)       [37] Under    (1)    [59] Phase (2)
            Seq OC                   OL                      current              Over Voltage
PROTECTION G1
            tI >                            Sets the time delay associated with I>. The setting range
                         150.00 s           is from 0.040 to 150.0s (step 10ms).
User Guide                                                                          P12y/EN FT/E95
            t Reset                         Sets the reset time value from 0 to 100 s (step 10 ms).
                            60 ms
            I> >> >>>                       Interlock of first threshold by the second and third
            Interlock         Yes           thresholds, but only if first threshold trip is set to IDMT.
                                            Setting choice: No, Yes
            TMS                             Sets Time Multiplier Setting (TMS) value for the curve
                            1.000           from 0.025 to 1.5 (step 0,001).
            I> >> >>>                       Interlock of first threshold by the second and third
            Interlock         Yes           thresholds, but only if first threshold trip is set to IDMT.
                                            Setting choice: No, Yes
           Delay Type                           Selects the time delay type associated with I>.
                              DMT               Setting choices are:
                                                - “DMT” (definite minimum time): see a,
                                                - “RI” (electromechanical inverse time curve): section b,- -
                                                IEC-xxx, CO2, CO8, IEEE-XX inverse time delay curve, see
                                                c,
                                                - RECT curve, see section c..
        tIe >                           Sets the time delay associated with Ie>. The setting
                     150.00 s           range is from 0.040 to 150.0s (step 10ms).
        tReset                          Sets the reset time value from 0 to 100s (step 10ms).
                       150.0 s
        t Reset                         Sets the reset time value from 0 to 100s (step 10ms).
                        0.10 s
        Ie> >> >>>                      Interlock of first threshold by the second and third
        Interlock         Yes           thresholds, but only if first threshold trip is set to IDMT.
                                        Setting choice: No, Yes
        TMS                             Sets time multiplier setting (TMS) value for the curve
                        1.000           from 0.025 to 1.5 (step 0.001).
        Ie> >> >>>                      Interlock of first threshold by the second and third
        Interlock         Yes           thresholds, but only if first threshold trip is set to IDMT.
                                        Setting choice: No, Yes
User Guide                                                                            P12y/EN FT/E95
           tReset                        Sets the value for the reset time, from 0 to 100 s, in steps of
                            0.10 s       10ms.
          tIe>>>>                             Set the value for the time delay associated with Ie>>>>
                          0.000 s             from 0.00s to 150.0s (step 0.01s)
          To obtain the power value in W, multiply the selected number by 1W or 5W. Example, for
          100:
− if the secondary of the CT = 1A, the HMI will display “100× 1W” and P> = 100W,
− if the secondary of the CT = 5A, the HMI will display “100× 5W” and P> = 500W.
PROTECTION
PROTECTION
           [32N] Mode :                   Selection of the function mode: “Pe” (wattmetric) or “Ie Cos”
                               Pe         (active component of the earth fault current).
                                          Each Pe and IeCos threshold has its own setting (time
                                          delay, threshold value etc), and the following instructionas
                                          are also valid for the two modes (Pe will change to IeCos>.
           Pe> ?                          Selection of the first alarm threshold function for Pe>.
                               No         These instructions are also valid for IeCos>.
                                          Setting choice: No, Yes
                                          Yes: the first earth wattmetric threshold (Pe> - Ie Cos)
                                          protection window is shown (see § 2.7.4.1)
                                          No: the next window will show the threshold menu “Pe>> ?”
                                          - “IeCos>> ?”).
P12y/EN FT/E95                                                                            User Guide
           Pe>                            Sets the value for the first earth wattmetric threshold Pe>.
                        20 x 1 W          High sensitivity current: 0.001 to 1 In
                                             Input voltage range 2-130V: The setting range is from 0.2
                                             to 20 x Ien W, in steps of 0.02 x Ien W.
                                             Input voltage range 10-480V: The setting range is from 1
                                             to 80 x Ien W, in steps of 0.1 x Ien W.
                                          The setting range for IeCos> is from 0.002 to 1Ien, in steps
                                          of 0.001.
                                          Medium sensitivity current: 0.01 to 8 In
                                             Input voltage range 2-130V: The setting range is from 1
                                             to 160 x Ien W, in steps of 0.1 x Ien W.
                                             Input voltage range 10-480V: The setting range is from 4
                                             to 640 x Ien W, in steps of 0.5 x Ien W.
                                          The setting range for IeCos> is from 0.01 to 8 Ien, in steps
                                          of 0.005.
                                          Low sensitivity current: 0.1 to 40 In
                                             For range 2-130V from 10 to 800 x Ien W, in steps of 1 x
                                             Ien W.
                                             For range 10-480V from 40 to 3200 x Ien W, in steps of 5
                                             x Ien W.
                                          The setting range for IeCos> is from 0.1 to 40 Ien, in steps
                                          of 0.01.
           Delay Type                     Displays threshold delay time type. Setting choices are:
                             DMT          DMT (definite time) RI for the electromechanical inverse
                                          time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time delay
                                          curve and RECT curve.:
           t Pe>                          If “Delay type” = DMT only
                         150.00 s         Sets the value for the time delay associated with Pe> -or
                                          IeCos>), from 0 to 150s (step 10ms).
           K                              If “Delay type” = RI only
                            1.000         Selection of K value for the RI curve from 0.100 to 10 (step
                                          0.005).
           TMS                            If “Delay type” ≠ DMT and RI
                            1.000         Sets the time multiplier setting (TMS) value for the curve
                                          from 0.025 to 1.5 (step 0,001).
           Reset Delay Type               If “Delay type” = IEEE/ANSI only.
                          IDMT            Sets the reset delay time type.
                                          Select between DMT (Definitive Time) and IDMT (Inverse
                                          Time).
                                          If IDMT is selected, “RTMS” menu is displayed.
User Guide                                                                          P12y/EN FT/E95
           Pe>>                          Sets the value for the earth second wattmetric threshold
                        20 x 1 W         Pe>>.
                                         High sensitivity current: 0.001 to 1 In
                                           Input voltage range 2-130V: The setting range is from 0.2
                                           to 20 x Ien W, in steps of 0.02 x Ien W.
                                           Input voltage range 10-480V: The setting range is from 1
                                           to 80 x Ien W, in steps of 0.1 x Ien W.
                                         The setting range for IeCos>> is from 0.002 to 1In, in steps
                                         of 0.001.
                                         Medium sensitivity current: 0.01 to 8 In
                                           Input voltage range 2-130V: The setting range is from 1
                                           to 160 x Ien W, in steps of 0.1 x Ien W.
                                           Input voltage range 10-480V: The setting range is from 4
                                           to 640 x Ien W, in steps of 0.5 x Ien W.
                                         The setting range for IeCos>> is from 0.01 to 8 In, in steps
                                         of 0.005.
                                         Low sensitivity current: 0,1 to 40 In
                                           Input voltage range 2-130V: The setting range is from 10
                                           to 800 x Ien W, in steps of1x Ien W.
                                           Input voltage range 10-480V: The setting range is from
                                           40 to 3200 x Ien W, in steps of 5 x Ien W.
                                         The setting range for IeCos>> is from 0.5 to 40 In, in steps
                                         of 0.01.
           tPe>>                         Sets the value for the second earth wattmetric threshold,
                           1.00 s        from 0 to 150 s (step 10ms).
           tReset                        Sets the value for the reset time from 0 to 100 s, in steps of
                           1.00 s        10ms.
P12y/EN FT/E95                                                                         User Guide
PROTECTION G1
2.7.5.1 Submenu First negative phase sequence overcurrent threshold (I2>) protection
           t I2>>>                    Sets the time delay associated with I2>> from 0 to 150s
                        150.00 s      (step 10ms).
PROTECTION G1
        −          start as soon as the current of one phase is below I< threshold value (OR of the 3
                   phases current),
        −          trip if the current of one phase - at least - remains below this threshold during more
                   than tI<.
        I< starting could be inhibited when CB is open (52a)
PROTECTION G1
            t I<                            Sets the time delay associated with I<, from 0 to 150 s (step
                           150.00 s         10ms).
            I< inhibited on 52A             When Yes is selected, this function inhibits undercurrent
                                            protection on circuit breaker (52A) trip.
                                 No
PROTECTION G1
PROTECTION G1
PROTECTION G1
         In addition to these settings, the user can fully link the autoreclose function to the protection
         function using the menus “PROTECTION G1 / Phase OC” and “PROTECTION/ E/Gnd”.
PROTECTION G1
           Ext CB Fail ?                  Allows the use of a dedicated input (CB FLT) to inform the
                              Yes         autoreclose function of the state of the CB (failed or
                                          operational). This signal has to be assigned to a digital input
                                          by the Automatic Control inputs submenu
                                          Setting choice Yes or No.
                                          Yes: The CB will be declared fault and the autoreclose will
                                          move in the locked status when the Ext. CB Fail time will be
                                          elapsed and the Ext CB Fail will stand active. The Ext. CB
                                          Fail timer will start when the tD will be expired. If during this
                                          time the signal Ext CB Fail will disappear the ARC will
                                          continue with its programmed cycles
                                          No: next window will show the submenu “Ext Block ?”.
           Ext CB Fail Time               If “Ext CB Fail”=Yes option is selected only.
                          1.00 s          Set the value for the external CB failure time delay tCFE.
                                          The Ext. CB Fail timer will start when the tD will be expired.
                                          If during this time the signal Ext CB Fail will disappear, the
                                          ARC will continue with its programmed cycles. Once this set
                                          time has elapsed, the information Ext CB Fail is validated.
                                          Setting range is from 10ms to 600s (step 10ms).
            Time period                         Setting range from 10mn to 1440mn (24h) (step 10mn).
                            10 mn               Sets the temporization for trip activity supervision.
         The 52a signal has to be assigned to a digital input by the inputs submenu in Automatic
         control function. The 52a signal is in accordance with the CB status.
         Within the tD a further time window is active.This time window starts together to the td.It
         expires after 50ms.
         If within this time window a threshold involved in the trip of the CB and in the ARC cycle is
         intermittent the ARC will be lock.
          Dead Time                      Displays setting value of the first cycle dead time (tD1) for
          tD1               0.30 s       the autoreclose function from 0.01 to 300s (step 10ms).
          Dead Time                      As above for the second cycle dead time (tD2).
          tD2       180.00 s
          Dead Time                      As above for the third cycle dead time (tD3).
          tD3       180.00 s
          Dead Time                      Sets the value after a first, second and third trip This dead
          tI>               0.05 s       time is used with an IDMT electromagnetic relay, and starts
          tI>>              0.05 s       when the CB opens. The induction disk returns to its initial
          tI>>>             0.05 s       position during this additional time
                                         Setting range is from 50ms to 600s (step 10ms).
          DeadTime                       As above for IE>, IE>> and IE>>>
          tIe>              0.05 s       Setting range is from 50ms to 600s (step 10ms).
          tIe>>             0.05 s
          tIe>>>            0.05 s
          Reclaim Time                   Set the Reclaimer time value (tR). The reclaim time , starts
          tR         180.00 s            when the CB has closed. Setting range is from 20ms to
                                         600s (step 10ms).
                                         After the reclaim time, if the circuit breaker does not trip
                                         again, the autoreclose function resets; otherwise, the relay
                                         either advances to the next shot that is programmed in the
                                         autoreclose cycle, or, if all the programmed reclose
                                         attempts have been accomplished, it locks out.
                                         If the protection element operates during the reclaim time
                                         following the final reclose attempt, the relay will lockout and
                                         the autoreclose function is disabled until the lockout
                                         condition resets.
          Inhib Time                     The “Inhib Time tI” timer is used to block the autoreclose
          tI                5.00 s       being initiated after the CB is manually closed onto a fault.
                                         The lockout condition can reset by a manual closing after
                                         the "Inhib Time tI".
                                         Setting range from 0.01s to 600s, in steps of 10ms.
           CYCLES              4321        4321 are the cycles associated to the trip on tI> pick up
           tI>                 1101        1201 are the actions to be executed after the tI> time delay
                                           has elapsed:
                                           0 = no action on autorecloser: definitive trip (autoreclose will
                                           move in the lock status),
                                           1 = trip on tI> pick-up, followed by reclosing cycle
                                           2 = no trip on tI> pick-up: and this whatever the setting is in
                                           the “AUTOMAT. CRTL/Trip commands/Trip tI>” menu.
           CYCLES              4321        As above for tI>>.
           tI>>                1101
           CYCLES           4321           4321 are the cycles associated to the trip on tI> pick up
           tAux1            1101           1201 are the actions to be executed after the tI> time delay
                                           has elapsed:
                                           0 = no action on autorecloser: definitive trip (autoreclose will
                                           move in the lock status),
                                           1 = trip on tI> pick-up, followed by reclosing cycle,
                                           2 = no trip on tI> pick-up: and this whatever the setting is in
                                           the “AUTOMAT. CRTL/Trip commands/Trip tI>” menu,
                                           3 = autoreclose without trip (trip order is inhibited and no
                                           trip is performed from autoreclose function).
           CYCLES           4321           As above for tAux2.
           tAux2            1101
PROTECTION G1
           tF1                             Displays setting value for the trip threshold from 0 to 600s
                                  0.00 s   (step 10ms).
User Guide                                                                          P12y/EN FT/E95
PROTECTION G1
          dF/dt1=                        Setting of the 1st frequency variation (∆F) per second (∆t) in
                             1.0 Hz/s    Hz/s with ∆t = 1 period (20ms at 50Hz)
                                         Average value of dF/dt1 will be calculated using the number
                                         of cycles set in the ‘CONFIGURATION / dF/dt Cycles.nb.’
                                         menu.
                                         The value is validated if it is repeted x times (x is set in the
                                         ‘CONFIGURATION / dF/dt Cycles.nb.’ menu).
                                         Setting range; from –10Hz/s to +10Hz/s, step = 0.1Hz/s
P12y/EN FT/E95                                                                               User Guide
              AUTOMAT.                                                            
               CTRL
                                                                              
              Trip                  Latch                   Blockin         (1)      Inrush       (3)
                                   Supervision                                     Equations
          Comm.Order                                                             
          delay      (3)
AUTOMAT. CTRL
AUTOMAT. CTRL
        tI>>>
        tIe>, tIe>> or     X    X     X    Time delayed 1st, 2nd or 3rd earth threshold.
        tIe>>>
        tIe>>>>                       X    Time delayed derived earth overcurrent threshold trip.
        tP> or P>>                    X    Time delayed 1st or 2nd active overpower threshold.
        tP> or tP>>                   X    Time delayed 1st or 2nd active power threshold.
        P< or P<<                     X    Instantaneous 1st or 2nd active underpower thresholds.
        tP< or tP<<                   X    Time delayed 1st or 2nd active underpower thresholds.
        Q> or Q>>                     X    Instantaneous 1st or 2nd reactive overpower thresholds.
        tQ> or tQ>>                   X    Time delayed 1st or 2nd reactive overpower thresholds.
        Q< or Q<<                     X    Instantaneous 1st or 2nd reactive underpower thresholds.
        tQ< or tQ<<                   X    Time delayed 1st or 2nd reactive underpower thresholds.
        tPe/IeCos>,        X    X     X    Time delayed 1st or 2nd earth overpower/IeCos (wattmetric)
        tPe/IeCos>>                        threshold.
        tI2>, tI2>>or           X     X    Time delayed 1st, 2nd or 3rd negative phase sequence
        tI2>>>                             overcurrent threshold.
        tThermal θ              X     X    Time delayed thermal overload threshold.
        tI<                     X     X    Time delayed undercurrent threshold.
                                                          st        nd
        tU> or tU>                    X    Time delayed 1 or 2 overvoltage threshold.
                                                          st        nd
        tU< or tU<<                   X    Time delayed 1 or 2           undervoltage threshold.
        Blocking of a protection function can be prevented if “No” is selected in the relevant window.
        Blocking of a protection function can be enabled if “Yes” is selected in the relevant window.
AUTOMAT. CTRL
               TEXT                                 INFORMATION
        I>, I>> or I>>>       Instantaneous 1st, 2nd or 3rd phase overcurrent threshold.
        Ie>, Ie>> or Ie>>>    Instantaneous 1st, 2nd or 3rd earth overcurrent threshold.
        Ie>>>>                Derived earth overcurrent threshold.
        I2>, I2>> or I2>>>    Instantaneous 1st, 2nd or 3rd negative phase sequence
                              overcurrent threshold.
AUTOMAT. CTRL
          Blocking Inrush                    Setting choice Yes: The crossing of the Harmonic H2 ratio
                              Yes            threshold on any phase activates the Inrush Blocking Logic
                                             function instantaneously.
                                             Setting choice No: The crossing of the Harmonic H2 ratio
                                             threshold doesn’t activate the Inrush Blocking logic function.
          Inr. Harmonic 2 Ratio =            Set the value for the 2nd harmonic threshold ratio
                           20%               calculated as a percentage of the fundamental
                                             component from 10 to 35% (step 0.1%). Press  to
                                             validate your choice.
          T Inrush reset =                   Set the value for the Inrush tReset time. This provides a
                                             reset delay of the Inrush Blocking signal (logic state=1)
                             0 ms            once the 2nd harmonic level falls below the set threshold.
                                             The setting range is from 0.0s to 2 s (step 10ms).
          Blocking Inrush Function           Enables or disables Inrush blocking for the function.
                           No                Refer to previous tables for protection functions list.
P12y/EN FT/E95                                                                                User Guide
AUTOMAT. CTRL
Sel1 tI>>> Third trip threshold for phase overcurrent threshold (tI>>>).
Sel1 tIe>> Second trip threshold for earth fault overcurrent (tIe>>).
Sel1 tIe>>> Third trip threshold for earth fault overcurrent (tIe>>>).
The following protection functions can be assigned to output relays using this submenu.
AUTOMAT. CTRL
        With the submenu Inputs it is possible to assign a label or an automation function to each
        logic input (see the following table):
        Label
                         Label description                                               P125 P126 P127
        designation
        Unlatch          Unlocks latched output relays                                    X     X    X
        Blk Log 1        Blocking logic 1                                                 X     X    X
        Blk Log 2        Blocking logic 2                                                       X    X
        52 a             Position of the circuit breaker (open)                                 X    X
        52 b             Position of the circuit breaker (close)                                X    X
        CB FLT           External failure information from the CB                               X    X
        Aux 1 to Aux 4   Assigning external information to inputs Aux1 to Aux4            X     X    X
        Aux 5 to Aux 7   Assigning external information to inputs Aux5 to Aux7                  X    X
        Aux 8 to Aux C Assigning external information to inputs Aux8 to AuxC                         X
                       (optional configuration)
        Strt Dist        Starting of the disturbance recording function                         X    X
        Cold L PU        Cold load pick up assignment                                           X    X
        Log Sel 1        Logic selectivity 1                                                    X    X
        Log Sel 2        Logic selectivity 2                                                    X    X
        Change set       Change of setting group (default setting group 1) when                 X    X
                         the changing group parameter (‘CONFIGURATION /
                         Group select / change group’) is set to input.
        Block_79         Blocking of the autoreclose function [79]                              X    X
        θ Reset          Reset of the thermal state                                             X    X
        Trip Circ        Trip circuit supervision input                                         X    X
        Start t BF       Start CB fail timer from external input                                X    X
        Maint. M         Maintenance Mode ON/OFF change                                   X     X    X
        SOTF             Start the Switch On To Fault automatism                                X    X
                         Local mode condition (if active, any remote operation
        Local                                                                             X     X    X
                         involving the output relays is forbidden)
        Synchro.         Assign a Time synchronisation input                              X     X    X
        LED Reset or     Reset of the "Trip" & "Alarm" leds
                                                                                          X     X    X
        Reset Led
        Ctrl Trip        Assign a control trip function to the input. When                X     X    X
                         activated, it is possible to order output relay(s) affected
                         to the control trip function.
        Ctr Close        Assign a control close function to the input. When active-
                         ted, it is possible to order output relays affected to the CB
                                                                                          X     X    X
                         Close (P126) or control close (P125 or P126) function.
                         For P127, this input can be started by the SOTF feature.
P12y/EN FT/E95                                                                             User Guide
                AUTOMAT.                                                        
                 CTRL
                                                                                 
            Inputs                 …                                           
                                  
                                 
                Input 1             Input 2            ...      Input 8/C         Aux Times
                                                                                 
AUTOMAT. CTRL
           Input 5                        Assigning label Log Sel 1 to logic input 5 (P126 & P127
                        Log Sel 1         only).
                                          To modify see above windows.
           Input 6                        Assigning label Block_79 to logic input 6 (P126 & P127
                        Block_79          only).
                                          To modify see above windows.
           Input 7                        Assigning label Cold L PU to logic input 7 (P126 & P127
                       Cold L PU          only).
                                          To modify see above windows.
           Input 8 …                      Assigning label to logic inputs 8 to 12 (C) (P127 with
           Input C                        optional board only).
                                          To modify see above windows.
           Aux1 Time                      Displays setting value of timer assigned to logic input Aux1
           tAux1     200.00 s             from 0 ms to 200 s, in steps of 10 ms.
         Aux8 Time                        As Aux1 for input Aux 8, Aux 9, Aux 10, Aux 11 and Aux 12.
         tAux8      200.00 s              (optional configuration only).
         …
         Aux C Time
         tAuxC      200.00 s
AUTOMAT. CTRL
AUTOMAT. CTRL
         In the following list, setting choice “Yes” assigns the corresponding function with the
         loading pick-up function:
         Cold Load PU ?                   Cold load pick-up function.
                             No           If Yes is selected, the following menu is displayed:
                                          If No is selected, the cold load pick-up function is inactive.
P12y/EN FT/E95                                                                          User Guide
          Cold Load PU                  Displays scaling value, in percent, for the cold load pick up
          Level        200 %            assigned to the selected thresholds from 20% to 800%
                                        (step 1%).
          Cold Load PU                  Displays delay timer setting (tCL) for the Cold Load Pick-up
          tCL        3600.0 s           function, from 0.1 to 3600s (step 100ms).
2.8.10   Submenu 51V (Overcurrent controlled by voltage transformer control (P127 only))
         The 51V function can be inhibited when a VT fault occurs, using “Automatic Ctrl” / “VT
         Supervision” / “VTS Blocks 51V” menu
          (U< OR V2>) & I>>?            Enable or disable the control of the start of the I>> by U<
                           No           and V2 > stages value. Setting choice: Yes or No
          V2>?                          Assigning the V2> threshold value for the inverse voltage
                           130V         47 for the I>> control. Select from 3V to 200V (step 0.1V).
          (U<< OR V2>>) & I>>>?         Enable or disable the control of the start of the I>>> by U<<
                           No           and V2 >> stages value.Setting choice: Yes or No
          V2>>?                         Assigning the V2>> threshold value for the inverse voltage
                           130V         47 for the I>>> control. Select from 3V to 200V by step of
                                        0.1V.
          VTS Blocks Protections?        The VTS function can be used to block voltage dependent
                          No             functions and to change directional overcurrent into non-
                                         directional functions. Setting choice: Yes or No
                                         Note: all voltage and power protections are blocked if VT
                                         fault occurs.
          VTS Non-dir                    Displayed when “VTS blocks protections?” = Yes, This
          I>                Yes          menu is used to change directional overcurrent in non-
          I>>               Yes          directional function.
          I>>>              Yes          If Yes is selected, the directional overcurrent will be
          Ie>               Yes          changed into a non-directional overcurrent protection
          Ie>>              Yes          function for the corresponding threshold,
          Ie>>>             Yes
          Ie>>>>            Yes          If No is selected, even if VTS.
          tVTS                           Sets the VTS timer. The VTS alarm will occur if VT fault
                            0.0s         occurs during more than the VTS timer.
                                         Setting range is from 0 to 100s, in steps of 10ms.
          Block I>?                                Select the possibility to block the instantaneous signal I> in
                                       Yes         case of circuit breaker failure detection. Setting choice: Yes
                                                   or No
          Block Ie>?                               Select the possibility to block the instantaneous signal Ie>
                                       Yes         in case of circuit breaker failure detection.Setting choice:
                                                   Yes or No
                 AUTOMAT.
                  CTRL
CB Supervision
                                        No                      No                       No
                  TC Supervision              CB Open S'vision        CB Close S'vision        CB Open Alarm ?
                         Yes                        Yes                     Yes                      Yes
                 tTrip Circuit tSUP          CB Open Time            CB Close Time            CB Open NB =
                                         No
                  ΣAmps(n) ?                  n                       t Open Pulse               t Close Pulse
                         Yes
                  ΣAmps(n) ?
AUTOMAT. CTRL
          t Open Pulse                   Displays and sets the tripping pulse time delay, from 0.1 to
                                         5s, (step 10ms).
                          100 ms
          t Close Pulse                  Displays and sets the closing pulse time delay, from 0.1 to
                                         5s (step 10ms).
                          100 ms
         The SOTF function can be set using “Automatic Ctrl” menu, “Trip Command”, “Output relays”
         and “Inputs”submenus.
AUTOMAT. CTRL
          Ctrl close input               Enables/disables the possibility to start the SOTF function
                              Yes/No     by the dedicated logic input “Ctr Close”. This “Ctr Close”
                                         input should be assigned to input 1, 2, 3 or 4 using
                                         “Automat. ctrl/Inputs” menu.
P12y/EN FT/E95                                                                             User Guide
          Front comm. order               Enables/disables the possibility to start the SOTF function
                          Yes/No          by a front port communication order.
          Rear comm. order                Enables/disables the possibility to start the SOTF function
                               Yes/No     with an order sent to the rear port communication.
          Rear2 comm. order               When existing, enables/disables the possibility to start the
                          Yes/No          SOTF function with an order sent to the second rear port
                                          communication.
          TEXT                          Information
          None                          No link/assignment.
          I>, I>> or I>>>               Instantaneous 1st, 2nd or 3rd phase overcurrent threshold.
          tI>, tI>> or tI>>>            Time delayed 1st, 2nd or 3rd phase overcurrent threshold.
          Ie>, Ie>> or Ie>>>            Instantaneous 1st, 2nd or 3rd earth overcurrent threshold.
          tIe>, tIe>> or tIe>>>         Time delayed 1st, 2nd or 3rd earth overcurrent threshold.
          Pe> or Pe>>                   1st and 2nd earth wattmetric alarm threshold.
          tPe> or tPe>>                 Time delayed 1st or 2nd earth wattmetric trip threshold.
          I2>, I2>> or I2>>>            Instantaneous 1st, 2nd or 3rd phase negative sequence
                                        threshold.
          tI2>, tI2>> or tI2>>>         Time delayed negative phase sequence (1st; 2nd or 3rd
                                        threshold).
          θ Alarm                       Thermal alarm output signal.
          θ Trip                        Trip on Thermal overload.
          I<                            Instantaneous undercurrent threshold.
          tI<                           Time delayed undercurrent.
          U> or U>>                     Instantaneous 1st or 2nd overvoltage threshold (P127).
          tU> or tU>>                   Time delayed 1st or 2nd overvoltage threshold (P127).
          U< or U<<                     Instantaneous 1st or 2nd undervoltage threshold (P127).
          tU< or tU<<                   Time delayed 1st or 2nd undervoltage threshold (P127).
          Ue>>>>                        Instantaneous threshold for residual overvoltage.
          tUe>>>>                       Time delayed trip threshold for residual overvoltage.
          tBC                           Time delayed broken conductor.
          79 Trip                       Autoreclose final trip.
          Input1 to Input 7:            Opto input 1 to input 7 status.
User Guide                                                                      P12y/EN FT/E95
       TEXT                        Information
       Input8 to Input C           Opto input 8 to input C status (optional configuration).
       t Aux 1 to tAux 7           Copy of the status of the Logic Input delayed by tAux1 (…
                                   tAux7) time.
       t Aux 8 to tAux C           Copy of the status of the Logic Input delayed by tAux8 to tAux
                                   C time (optional configuration).
       P> or P>>                   Instaneous 1st or 2nd active overpower trip threshold (P127).
       tP> or tP>>                 Time delayed 1st or 2nd active overpower trip threshold (P127).
       P< or P<<                   Instaneous 1st or 2nd active underpower trip threshold (P127).
       tP< or tP<<                 Time delayed 1st or 2nd active underpower trip threshold
                                   (P127).
       Q> or Q>>                   Instaneous 1st or 2nd reactive overpower trip threshold (P127).
       tQ> or tQ>>                 Time delayed 1st or 2nd reactive overpower trip threshold (P127).
       Q< or Q<<                   Instaneous 1st or 2nd reactive underpower trip threshold (P127).
       tQ< or tQ<<                 Time delayed 1st or 2nd reactive underpower trip threshold
                                   (P127).
       F1 to F6                    Instantaneous first to sixth frequency trip threshold (P127).
       tF1 to tF6                  Time delayed first to sixth frequency trip threshold (P127).
       dF/dt1 to dF/dt6            1st to 6th rates of change of frequency.
       VTS                         Instantaneous Voltage Transformer Supervision output signal
                                   (P127).
       CTS                         Instantaneous Current Transformer Supervision signal (P127).
       Ie>>>>                      Derived earth overcurrent threshold.
       tIe>>>>                     Time delayed threshold of derived earth overcurrent
                                   threshold.
       79 i. Lock                  Autoreclose lock activated by the internal process of the
                                   autoreclose (Internal Blocking).
       79 e. Lock                  Autoreclose lock activated by the input “block 79” (External
                                   Blocking).
       tEQU. A to tEQU. H          Results of equations A to H.
       CB Fail                     Circuit Breaker failure.
AUTOMAT. CTRL
Logic Equations
       Equ.A Toperat.                   The time of operation setting is used to set the minimum
                           0.00s        time of truth of the selected conditions before validating the
                                        truth of the logic operation.
                                        Setting choice: from 0 to 600s, step 10ms
       Equ.A Treset.                    The reset time sets a minimum time before the logic
                           0.00s        operation is not true when at least one condition is not true.
                                        Setting choice: from 0 to 600s, step 10ms
P12y/EN FT/E95                                                                           User Guide
          Equation A.00                 Logic signal: Setting Choice: Null and logic signals (see
            =           None            table).
AUTOMAT. CTRL
          tOrder Comm 1                 Sets the duration for the reception of the remote
                           0.1s         “communication order 1” signal.
                                        Setting range from 0s to 600s, in steps of 50ms.
          tOrder Comm 2 0.1s            As above for communication orders 2, 3 and 4.
          tOrder Comm 3 0.1s
          tOrder Comm 4 0.1s
User Guide                                                                          P12y/EN FT/E95
RECORDS
                                                                           
             CB            (1)        Fault Record            Instantane-       Disturb
              Monitoring                                      ous               Record
                                                                               
          Time Peak       (1)        Rolling        (1)                       
          Value                      Demand
        (1)   P126 and P127 only
2.9.1   Submenu CB Monitoring (P126 & P127 only)
        With the CB Monitoring submenu it is possible to read and clear counter values associated
        with the circuit breaker.
         Σ Amps (n)                         Displays the summation of the current (in Amps or square
         RST = [C]                          Amps) interrupted by the CB. Stored current values for all 3
                                            phases are cleared together. To clear these values, press
                                            .
         Σ Amps (n) IA                      Displays the summation value of the current (in Amps or
                         2 E04              square Amps) for phase A interrupted by the circuit breaker.
RECORD
           Fault Time                      Displays the time when the fault was recorded. The format
                         13:05:23          of the time is hh:mm:ss.
                                           In this example the fault was recorded at 1:05:23 pm.
           Fault Date                      Displays the date when the fault was recorded. The format
                         12/11/01          of the Date is DD/MM/YY.
                                           In this example, the fault was recorded on November 12th
                                           2001.
           Active Set Group                Displays the active setting group (1 or 2).
                                 1
           Faulted Phase                   Displays the phase, where a fault occurred, for the chosen
                      PHASE A              fault record. (NONE, PHASE A, B, C, EARTH).
           Threshold                       Displays the origin of the fault that generated the trip order.
                              -----
           IA^VBC Angle                    Displays the angle between phase A current and phase B to
                              ----°        phase C voltage at the time of the fault (P127 only).
                                           The indication is ----° if the angle cannot be measured.
User Guide                                                                         P12y/EN FT/E95
           IB^VCA Angle                   Displays the angle between phase B current and phase C
                              ----°       to phase A voltage at the time of the fault (P127 only).
                                          The indication is ----° if the angle cannot be measured.
           IC^VAB Angle                   Displays the angle between phase C current and phase A
                              ----°       to phase B voltage at the time of the fault. (P127 only)
                                          The indication is ----° if the angle cannot be measured.
           IN^VN Angle                    Displays the angle between earth current and voltage at the
                              ----°       time of the fault.
                                          The indication is ----° if the angle cannot be measured.
RECORD
RECORD
RECORD
           Time Window                  Selection of the time window during which peak and
                            5 mn        average values are stored. Selet choice: 5mn, 10mn,
                                        15mn, 30mn, or 60mn.
RECORD
           Sub Period                   Set the window of time of the subperiod used to calculate
                            1 mn        rolling average values, from 1mn to 60mn (step 1mn).
           Num of Sub Per               Select the number of sub-period used for the calculation of
                               1        the average of these average values.
User Guide                                                                        P12y/EN FT/E95
3.      WIRING
        The MiCOM P125, P126 & P127 relays have the same terminal layout for common
        elements. The wiring diagram for each model is provided in Appendix 1 of the Technical
        Guide.
3.1     Auxiliary Power Supply
        The auxiliary power supply for the MiCOM P125, P126 & P127 relays can be either direct
        current with a voltage range of 24-60 VDC, 48-250 VDC, 130-250 VDC, or alternative current
        with a voltage of 48-250 VAC/ 50-60 Hz. The voltage range (Ua) is specified on the adhesive
        paper label under the top hinged cover on the front of the relay.
        The auxiliary power supply must only be connected to terminals 33 and 34.
3.2     Current Measurement Inputs
        The MiCOM P125, P126 & P127 relays have up to eight current inputs (2 times 4 earth and
        phase current inputs).
        The nominal current value of the measuring inputs is either 1 Amp or 5 Amp (refer to wiring
        diagram). For the same relay, the user can mix the 1 and 5 Amp inputs between phases and
        earth.
                 NOTE:         All phase inputs must have the same rating (1 or 5 Amps).
3.3     Digital Inputs
        The number of logic inputs depends on the relay model. The relays have programmable
        opto-isolated logic inputs, which may be assigned to any available label or function.
        Digital inputs for each relay model:
        The first logic output (RL0) is dedicated to indicate a relay failure (Watchdog, WD) and is not
        part of this table.
3.5     Communication
3.5.1   RS485 Rear Communication Port
        All MiCOM relays have one RS485 rear communication port by default. The terminals 29-30-
        31-32 are dedicated to the RS485 communication port. An optional RS485 port is available
        on P127.
        See wiring diagrams in chapter P12y/EN CO of the Technical Guide.
P12y/EN FT/E95                                                                           User Guide
P0073ENa
CONTENTS
                 BLANK PAGE
                                                                                                                                                                    1.
                    DEFAULT DISPLAY
                      IA = 1245 A
 Language            Close Order        Earth text       E/Gnd VT primary   Led            Inputs :4321     Fail    654321       Change group    Inst. Self-reset
       ENGLISH                     No                N              5A      Ie>                    ↑↑↑↑     safe re.000000              Input                  No
                                                                            tIe>                                                         Menu
                                                                                                                                                                                                MiCOM P125/P126 & P127
                                                                            Ie>>
 Description         Dist rec start                      E/Gnd VT sec                      Voltage input    Maintenance Mode     Setting group   Reset Led on
                                                                            tIe>>
          P125-0                   No                               5A                               DC                No                    1   Fault       No
                                                                            Ie>>>
                                                                            tIe>>>                                              Input
                                                                                                                      Yes
                                                                            Pe/IeCos>
 Reference                                               E/Gnd primary                                      Relays   65W4321                     INH Alarm tAux1?
                                                                            tPe/IeCos>
         ALST                                                  0.10 kV      Pe/IeCos>>                      CMD       0000000                               No
                                                                            tPe/IeCos>>                    No
                                                                                                                                                                    MiCOM P125 – V12 SOFTWARE
                                                                            Ue>>>>
Software version                                         E/Gnd VT sec                                                                            INH Alarm tAux2?
                                                                            tUe>>>>
          12.A                                                 100.0 V                                                                                      No
                                                                            Input1/2/3/4
                                                                            tAux1/2/3/4
 Frequency                                                                                                                                       INH Alarm tAux3?
        50 Hz                                                                                                                                               Yes
Relay     654321
Status    001011                                                                                                                                 Date
Date
       11/06/07                                                                                                                                  Format Date
                                                                                                                                                         Private
Time
   14 : 15 : 34
                                                                                                                                                                                                                         P12y/EN HI/E95
                                                                                                                                                                                                Page 3/24
                                                DEFAULT DISPLAY
                                                  IA = 1245 A
                                                                                                                                                                                Page 4/24
Trip Commands Latch Relays Blocking Loqic Output Relays Inputs Fault Record Instantaneous
                                                                                     Unlatch
                                                                 Ie >>
                                                                                     Blk Log                      12:05:23:42       13:07:15:53
Trip tPe/IeCos>                             Block tPe/IeCos>     tle >>
                                                                                     Aux 1
               No                                          No    Ie >>>
                                                                                     Aux 2
Trip tPe/IeCos >>                           Block tPe/IeCos >>   tle >>>                                     Fault Date          Date
                                                                                     Aux 3
               No                                          No    Pe/IeCos>                                           09/01/01               09/01/01
                                                                                     Aux 4
                                                                 tPe/IeCos>
                                                                                     Strt Dist
                                                                 Pe/IeCos>>
                                                                                     Changeset               Active Set Group    Origin
                                            Block tUe>>>>        tPe/IeCos>>
Trip tUe>>>>                                                                         Maint. M.                               2                Ie>
                                                        No       Ue>>>>
                No                                                                   Local
                                                                 tUe>>>>
                                                                                     Synchro
                                                                 tAux1                                       Faulted Phase       Length
                                                                                     Led Reset
                                                                 tAux2
                                            Block   tAux1   No                       Ctrl Trip                        EARTH                   57 ms
Trip   tAux1    No                                               tAux3
                                            Block   tAux2   No                       Ctrl Close
Trip   tAux2    No                                               tAux4
Trip   tAux3    No                          Block   tAux3   No   Control trip                                Threshold           Trip
Trip   tAux4    No                          Block   tAux4   No   Control Close                                           I>                   No
                                                                 Active Group            Aux Time
                                                                 Input 1
                                                                 Input 2                                     Magnitude
Ctrl Trip                                                                                                            1200 A
                                                                 Input 3                                                         Disturbance Record
                No
                                                                 Input 4             Aux1 Time
                                                                                     tAux1        0.00   s
                                                                                                             IN Magnitude
                                                                                     tAux2        0.00   s                        Records number
                                                                                     tAux3        0.00   s             103 A
                                                                                                                                              5
                                                                                     tAux4        0.00   s
                                                                                                             VN Magnitude
                                                                                                                      0.00V      Pre-Time
                                                                                                                                               1.3 s
                                                                                                             IN^VN Angle
                                                                                                                     0°          Disturb Rec Trig
                                                                                                                                         ON INST.
                                                                                                                                                                                P12y/EN HI/E95
                                                                                                                                                       Page 5/24
                                                                                                                                                                            2.
                   DEFAULT DISPLAY
                     IA = 1245 A
                                                                                                                                                                                                        Page 6/24
Language                  Close Order        Phase rotation      Line CT primary                        Inputs :7654321       Fail 87654321             Change group
                                                                                    Led
       ENGLISH                          No            A-B-C                  5A                                 ↑↑↑↑↑↑↑       safe re.00000000                   Input
                                                                                    I>
                                                                                    tI>                                                                   Menu
                                                                                    I>>                 Voltage input
Description               Dist rec start     Default Displays    Line CT sec        tI>>                                      Maintenance Mode          Setting group
                                                                                                                    DC
           P126-2                       No   RMS IA IB IC IN                   5A   I>>>                                                  No                            1
                                                                                    tI>>>                                                            Input
                                                                                                                                       Yes
                                                                                    tIA>
Reference                                    Phases/Earth Text   E/Gnd CT primary   tIB>                                      Relays8765W4321
            ALST                                 L1 L2 L3 N                5A                                            No   CMD 000000000
                                                                                    tIC>
                                                                                    Ie>
                                                                                    tIe>
                                                                                                                                                                            MiCOM P126 – V12 SOFTWARE
Time
         14 : 15 : 34                                                                                                                            Software version 12.A
                                                                                                                                                                                                        MiCOM P125/P126 & P127
                                                                                                                                                                                                                                 Menu Content Tables
                                              DEFAULT DISPLAY
                                                IA = 1245 A
                                              IB
 Reset Led on                                         600.00 A             0.0°       RST=[C] 0%                                Parity
 Fault              No                                                                                                                        None
Alarm.Inh. Eq A?
Alarm.Inh. Eq H?
                                                                                                                                                                               P12y/EN HI/E95
                                                                                                                                                      Page 7/24
                                                        DEFAULT DISPLAY
                                                          IA = 1245 A
     PROTECTION G1/G2
                                                                                                                                                                                             Page 8/24
PROTECTION G1/G2
                                                                   [59N] residual
      [49] Therm OL               [37] Under current                                             [79] Autoreclose
                                                                   Over Voltage
                                                                                                                                                                         Menu Content Tables
                                                                                                                         tI>>>       0.05   s
      Iθ>         0.10 In         I<         0.10 In               Ue>>>>      5.0 V             Ext CB Fail ?           tIe>        0.05   s
      Te            1 mn          tI<         0.00s                tUe>>>>     0.00s                               No    tIe>>       0.05   s
      K             1.05                                                                                                 tIe>>>      0.05   s
                                                                                                            Yes
      θTrip       100 %
                                                                  No                             Ext CB Fail Time
No                                I< Inhibited on
                                  52 a            No                                                          1.00 s     Reclaim Time
      θ Alarm                                                                                                            tR           5.00 s
                       No    No                                                             No
                                                       OR / AND
                Yes                                                                          Ext Block
                                                                                                                   Yes   Inhib Time Time
      θ Alarm                                                                                                            tR           5.00 s
                       90%
No                                                                                           Rolling demand ?
                                                                                                           No            Phase Cycles
                                                                                                        Yes                                 4
                                                                                                 Max cycles nb
                                                                                                              10         E/Gnd Cycles
                                                                                                                                            4
                                                                                             Time period
                                                                                                                 10 mn   Cycles      4321
                                                                                                                         tI>         1111
                                                                                       No                                tI>>        1111
                                                                                                                         tI>>>       1111
                                                                                                 Dead Time
                                                                                                                         tIe>        1111
                                                                                                 TD1       5.00 s
                                                                                                                         tIe>>       1111
                                                                                                 TD2       5.00 s
                                                                                                                         tIe>>>      1111
                                                                                                 TD3       5.00 s
                                                                                                                         tPe/IeCos> 1111
                                                                                                 TD4       5.00 s
                                                                                                                         tPe/IeCoss>>1111
                                                                                       No                                tAux1       1111
                                                                                                                         tAux2       1111
                                                                                                                         tAux3       1111
                                                                                                                         tAux4       1111
                                                                                                                                                                         P12y/EN HI/E95
                                                                                                                                                Page 9/24
                                   DEFAULT DISPLAY
                                     IA = 1245 A
 AUTOMAT. CTRL
                                                                                                                                    Page 10/24
Trip Commands         Latch Relays             Blocking Loqic        Logic Select 1/2       Output Relays
                                                                                                                                                             P12y/EN HI/E95
Trip tI>         No    Latch :87654321          Block tI>       No    Sel1 tI >>            Trip      8765432
Trip tI>>        No           00000000          Block tI>>      No                  No                1000100   Trip      8765432
Trip tI>>>       No                             Block tI>>>     No                          I>                            1000100
                                                                                            tl >                CB Alarm
                                                                      Sel 1 tI >>>                              52 Fail
                                                                                            I >>
                                                Block tIe>   No                   No                            CB Fail
 Trip tIe>       No                                                                         tl >>
                                                Block tIe>>  No                                                 CB Close
 Trip tIe>>      No                                                                         I >>>
                                                Block tIe>>> No                                                 tAux1
 Trip tIe>>>     No                                                   Sel1 tle >>           tl >>>
                                                                                    No      tIA>                tAux2
                                                Block tPe/IeCos>                            tIB>                tAux3
 Trip tPe/IeCos>                                               No                           tIC                 tAux4
                No                              Block tPe/IeCos >>    Sel 1 tle >>>         Ie >                tAux5
 Trip tPe/IeCos >>                                             No                 No        tle >               tAux6
                No                                                                          Ie >>               tAux7
                                                                                            tle >>              79 Run
                                                Block tI2>   No       t Sel 1               Ie >>>              79 Trip
 Trip tI2>       No                             Block tI2>>  No                    150 ms   tle >>>             79 int. Lock.
 Trip tI2>>      No    Trip   tAux1    No       Block tI2>>> No                             Pe/IeCos>           79 ext. Lock
 Trip tI2>>>     No    Trip   tAux2    No
                                                                                            tPe/IeCos>          SOFT
                       Trip   tAux3    No
                                                                                            Pe/IeCos>>          Control trip
                       Trip   tAux4    No       Block Thermal θ No
                                                                                            tPe/IeCos>>         Control Close
                       Trip   tAux5    No       Block tI<      No
 Trip Thermal θ No                                                                          I2>                 Active Group
                       Trip   tAux6    No
 Trip tI<       No                                                                          tI2>                Input 1
                       Trip   tAux7    No
                                                                                            I2>>                Input 2
                                                Block tUe>>>>
                                                                                            tI2>>               Input 3
                                                            No
                       Trip SOFT       No                                                   I2>>>               Input 4
 Trip tUe>>>>                                                                               tI2>>>              Input 5
                       Ctrl Trip       No
                 No                                                                         Therm Alarm         Input 6
                                                Block TBrk.Cond                             Therm Trip          Input 7
                      Trip EQUATION A ?                       No                            I<                  Equ. A
Trip Brkn.Cond                     No                                                       tI<                 Equ. B
                 No   …                                                                     Ue>>>>              Equ. C
                      Trip EQUATION H ?         Block   tAux1   No                          tUe>>>>             Equ. D
                                   No           Block   tAux2   No                          Brkn Cond           Equ. E
                                                Block   tAux3   No                                              Equ. F
                                                Block   tAux4   No                                              Equ. G
                                                Block   tAux5   No                                              Equ. H
                                                Block   tAux6   No
                                                Block   tAux7   No
                                                                                                                                    MiCOM P125/P126 & P127
                                                                                                                                                             Menu Content Tables
                            DEFAULT DISPLAY
                              IA = 1245 A
AUTOMAT. CTRL
                                                                                                                  No tOpen Pulse
                                                                                                                              300ms
                                                                                                                                                                                                              P12y/EN HI/E95
                                                                                                                                                                                     Page 11/24
                DEFAULT DISPLAY
                  IA = 1245 A
    RECORDS
                                                                                                                           Page 12/24
                                                                                                                                                    P12y/EN HI/E95
CB Monitoring Fault Record Instantaneous Disturbance Record Time Peak Value Rolling Demand
CB Opening Time          Record Number       Number              Records number       Time Window       Sub Period
          83 ms                      25                      5               5                 5 mn                  1mn
                         IA Magnitude        IN Magnitude
                                  1200 A               103 A
                         IB Magnitude        VN Magnitude
                                   500 A              0.00V
                                                                                                                                                     CONFIGURATION (cont
 OP PARAMETERS                                                ORDERS              CONFIGURATION
                                                                                                                                 (2)                         (1)
                       Time                                                      Phases/Earth Text         Time synchro                E/Gnd VT sec
                              14 : 15 : 34                                             L1 L2 L3 N                    IRIG B                   100.0 kV
                                                                                                     (2)
                                                                                 Iam Tdd denom.            IRIG B                      Line CTm primary
                                                                                             1A                     Modulated                       1A
                                                                                                                                                                                                       Page 13/24
 DEFAULT DISPLAY
   IA = 1245 A
CONFIGURATION                                                                                                                                MEASUREMENTS
                    CONFIGURATION
                                                                                                                                                                         Page 14/24
                                                             Inputs                      Output
                                                                                                                                                                                                  P12y/EN HI/E95
CONFIGURATION                                                                                                     METERING
                   MEASUREMENTS
                Frequency
                       50.00 Hz
                                                                                                                                                      Menu Content Tables
                IA
                IB                                                MAX & AVERAGE       MAX SUBPERIOD     Reclose Stats
                IC                          P
                                                                  RCT=[C]             RST=[C] 0%        RST=[C]
                                                                                                                             MiCOM P125/P126 & P127
                IN                          Q
                Ie>>>>                      S
                I1                          Cos(Phi)
                                                                  Max       IA Rms    MAX SUBPERIOD     Total recloses
                I2
                                                                  Max       IB Rms      IA Rms          Cycle 1 recloses
                                            Energy                Max       IC Rms      IB Rms          Cycle 2 recloses
                                            RST=[C]               Average   IA Rms      IC Rms          Cycle 3 recloses
                RATIO I2 / I1 =
                                                                  Average   IB Rms                      Cycle 4 recloses
                           0%
      3Vpn/                                                       Average   IC Rms
    2Vpn+Vr                       2Vpp+Vr                         Max       UAB Rms
                                            3Ph WHours     Fwd    Max       UBC Rms   ROLLING AVERAGE
                                            3Ph WHours     Rev    Average   UAB Rms                     Total Trip &
     UA                    UAB                                                          IA Rms
                                            3Ph VArHours   Fwd    Average   UBC Rms                     Lockout 0
     UB                    UBC                                                          IB Rms
                                            3Ph VArHours    Rev
     UC                    UCA                                                          IC Rms
                                            3Ph VAHours
     UN                    UN
                                            IN-fn
                Pe
                                            RST=[C]    0.00A
                IeCos
                                            THERMAL STATUS
                IN^VN Angle                 RST=[C] 0%
                IA^IB Angle
                IA^IC Angle
      3Vpn/
    2Vpn+Vr                       2Vpp+Vr
                                                                                                                             Page 15/24
  DEFAULT DISPLAY
    IA = 1245 A
                                           (1)                                                                                                   COMMUNICATION
 MEASUREMENTS
                                                                                                                                                                     Page 16/24
                          METERING
                                                                                                                                                                                              P12y/EN HI/E95
  HMI ?               No                                       No              (1)
                                    COMM1                             COMM2                  [67] Phase OC
               No                                     No                             No
            Yes                                 Yes                            Yes
  Relay Address                                                                              I> ?                           I>> ?
                                                                                                                                                                                                       Menu Content Tables
          MODBUS                                                                                                   No                            No
                                                                                                              Dir / Yes                     Dir / Yes
  Date Format                       Baud rate                         Spont. event. &GI
                                                                                                                                                                              MiCOM P125/P126 & P127
                                                                      Measur. upload                          RI                            RI
                                    Stop Bits                         ASDU 9        Yes
                                                           1                                 K         0.025               K                0.025
                                                                                             tReset     0.00s              tReset           0.00s
                                                                      Measur. upload         I> I>> I>>>                                    IEEE, IEC,
                                    Relay address                                            Interlock    Yes                               RECT or CO
                                                                      Other         Yes
                                                           1
                                                                                                              IEEE, IEC,   TMS            0.025
                                                                                                              RECT or CO   Reset Delay TypeDMT
                                                                      Events + Measur.                                     If reset delay type=IDMT:
                                                                      Blocking     Yes       TMS            0.025          Rtms           0.025
                                                                                             Reset Delay TypeDMT           tReset          0.00s
                                                                                             If reset delay type=IDMT:
                                                                      Command                Rtms           0.025
                                                                      Blocking        Yes    tReset          0.00s
                                                                                             Ie> I>> I>>                   I>>> ?
                                                                                             Interlock         Yes                               No
                              nd                                      Command
 (1) Available with P127 with 2    port optional
                                                                      duration       0.1s                                               Dir / Yes
 configuration
                                                                               to COMM2                                    I>>>      10.00 In
                                                                                                                           If Dir:
                                                                    COMM1 only                                             I>> Torque      0°
                                                                                                                           I>> Trip Zone ± 50.0%
                                                                    IEC60870-5-103 only
                                                                                                                           If Dir or Yes:
                                                                                                                           Delay type        DMT
                                                                                                                                                                                                       P12y/EN HI/E95
                                                                                                                                                                              Page 17/24
DEFAULT DISPLAY
  IA = 1245 A
(G3… G8)
                                                                                                                                           [32] Directional
                                                                                                                                                                                                                          P12y/EN HI/E95
                              No                                  No                               No
 Ie> ?                               Ie>> ?                            Ie>>> ?                          Ie>>>> ?                           P> ?
                    No                                     No                            No                             No                                    No
                  Dir / Yes                           Dir / yes                     Dir/Yes/Peak                     Dir / Yes                   Yes
 Ie>       10.00 In                  Ie>>      10.00 In                Ie>>>            10.00 In        Ie>>>>         1.00 In             P>      10000x1W(1)           P< ?
 If Dir:                             If Dir:                           If Dir:                          If Dir:                            tP>           0.00s                           No
 Ue>          1.0V                   Ue>>                              Ue>               260.0V         Ue>(Ie>>>>) 260.0V
                                                                                                                                    No                                         Yes
 Ie> Torque      0°                  Ie>> Torque     0°                Ie> Torque             0°        Ie>>>> Torque       0°
 Ie> Trip ± 50.0%                    Ie>> Trip                         Ie> Trip         ± 10.0%         Ie>>>> Trip ± 10.0%                P>> ?                         P<          1x1W(2)
 If Dir or Yes:                      If Dir or Yes:                    If Dir or Yes:                   If Dir or Yes:                                        No         tP<           0.00s
 Delay type        DMT               Delay type        DMT             Delay Type          DMT          Delay Type       DMT
                                                                                                                                                 Yes                No
                                                                       tIe>>>             0.00s
                                                                       tReset             0.00s                       DMT                  P>> 10000x1W(1)               P<< ?
                  DMT                                 DMT
                                                                                                                                           tP>>      0.00s                               No
 tIe>             0.00s             tIe>>             0.00s                                             tIe>>>>       0.00s         No                                         Yes
 tReset           0.00s             tReset            0.00s                                             tReset        0.00s
                                                                                                                                           Q> ?
                                                                                                                                                                         P<<         1x1W(2)
                  RI                                  RI                                                             RI                                       No
                                                                                                                                                                         tP<<          0.00s
 K          0.025                   K             0.025                                                                                           Yes               No
                                                                                                        K            0.025
 tReset      0.00s                  tReset        0.00s                                                 tReset       0.00s                 Q> 10000x1W        (1)
                                                                                                                                                                         Q< ?
 Ie> I>> I>>                                                                                                                               tQ>      0.00s                                No
 Interlock     Yes                                IEEE, IEC,                                                          IEEE, IEC,
                                                                                                                                    No                                         Yes
                                                  RECT or CO                                                          RECT or CO
                   IEEE, IEC,                                                                                                              Q>> ?
                   RECT or CO       TMS            0.025                                                TMS            0.025                                             Q<          1x1W(2)
                                                                                                                                                              No
                                    Reset Delay TypeDMT                                                 Reset Delay TypeDMT                                              tQ<           0.00s
TMS            0.025                                                                                                                             Yes
                                    If reset delay type=IDMT:                                           If reset delay type=IDMT:                                   No
Reset Delay TypeDMT
                                    Rtms           0.025                                                Rtms           0.025
If reset delay type=IDMT:                                                                                                                  Q>> 10000x1W(1)               Q<< ?
                                    tReset          0.00s                                               tReset          0.00s
Rtms           0.025                                                                                                                       tQ>>      0.00s                               No
tReset          0.00s
                                                                                                                                    No                                         Yes
Ie> I>> I>>
Interlock         Yes                                                                                                                                                    Q<<         1x1W(2)
                                                                                                                                     (1)                                 tQ<<          0.00s
                                                                                                                                            or 10000x5W
                                                                                                                                            or 40000x1W             No
                                                                                                                                            or 40000x5W                  (2)
                                                                                                                                                                               or 1x5W or 4x1W
                                                                                                                                                                               or 4x5W
                                                                                                                                                                                                 MiCOM P125/P126 & P127
                                                                                                                                                                                                                          Menu Content Tables
     DEFAULT DISPLAY
       IA = 1245 A
                       Pe                         No                          No                         No                               No                            No
                 Pe
                                            Yes                         Yes                        Yes                               OR / AND                     OR / AND
      Pe>
                                                                                                                                                                                 MiCOM P125/P126 & P127
                       No         I2>        25.00 In        Iθ>         0.10 In         I<         0.10 In          U>              260.0 V            U<            5.0 V
                 Yes              Delay type    DMT          Te            1 mn          tI<         0.00s           tU>               0.00s            tU<           0.00s
                                  tI2>(1)      0.00 s        K             1.05                                                                         52a Inhib. U<? No
      Pe>     160.0x1W                                       θTrip       100 %
      Delay Type   DMT       No                                                                                 No
                                                                                         I< Inhibited on                                          No
      tPe>(1)     0.00s                                 No                                                              U>> ?
                                  I2>> ?                                                 52 a            No                                             U<< ?
      tReset      0.04s                                                                                                                   No
                                                  No         θ Alarm                                                                                                    No
                                                                                    No
No                                                                            No                                                     OR / AND
                                            Yes                                                                                                                   OR / AND
      Pe>>                                                             Yes               I< Inhibited on
                                                                                         U<              No          U>>             260.0 V
                       No         I2>>      40.00 In                                                                                                   U<<            5.0 V
                                                             θ Alarm                                                 tU>>              0.00s
               Yes                tI2>>       0.00 s                          90%                   Yes                                                tU<<           0.00s
                                                                                                                No                                     52a Inhib. U<<? No
      Pe>> 160.0x1W          No             Yes         No                               I< Inhibited on
      tPe>>        0.00s                                                                 U<            5.0 V
      tReset       0.04s          I2>>> ?                                                                                                          No
      Pe/IeCos Angle 0°                           No                                No
No
                     IeCos                  Yes
      IeCos>                      I2>>>     40.00 In
                       No         tI2>>>      0.00 s                                                                        (1)      If Delay Type = DMT
                 Yes                                                                                                                 Otherwise, the following
                             No                                                                                                      menus are displayed
      IeCos> 8.000Ien
      Delay Type  DMT
      tIeCos>(1) 0.00s                                                                                                          Delay Type ≠ DMT
      tReset     0.04s
                                                                                                                                                                IEEE, IEC,
No                                                                                                                                                              RECT or CO
                                                                                                                                RI
      tIeCos>>                                                                                                                                   TMS            0.025
                                                                                                               K                0.025
                       No                                                                                                                        Reset Delay TypeDMT
                                                                                                               tReset           0.00s
                 Yes                                                                                                                             If reset delay type=IDMT:
      IeCos>> 8.000Ien                                                                                                                           Rtms           0.025
      tIeCos>>     0.00s                                                                                                                         tReset          0.00s
      tReset       0.04s
No    Pe/IeCos Angle 0°
                                                                                                                                                                                                          P12y/EN HI/E95
                                                                                                                                                                                 Page 19/24
    DEFAULT DISPLAY
      IA = 1245 A
                           (G3… G8)
                                                                                                                                                                                    P12y/EN HI/E95
Trip Commands Latch Relays Blocking Loqic 1 / 2 Inrush blocking Logic Select 1/2
 Trip tI>         No   Trip tUe>>>>No           Latch :87654321     Block tI>        No   Block tUe>>>>              Inrush blocking         Sel1 tI >>
                                                                                                                                                                                            Menu Content Tables
 Trip   tIe>      No    Trip   tF3        No                        Block tIe>       No   Block   tF2      No        ratio =     20.0%                   No
 Trip   tIe>>     No    Trip   tF4        No                        Block tIe>>      No   Block   tF3      No
 Trip   tIe>>>    No    Trip   tF5        No                        Block tIe>>>     No   Block   tF4      No
 Trip   tIe>>>>   No                                                                                                 T Inrush reset          Sel1 tle >>
                        Trip   tF6        No                                              Block   tF5      No
                                                                                                                                  0 ms                     No
                                                                                          Block   tF6      No
                                                                    Block tIe>>>> No
 Trip   tP>       No    Trip   dF/dt1     No
 Trip   tP>>      No                                                                                                 Inrush block. on        Sel 1 tle >>>
                        Trip   dF/dt2     No
 Trip   tP<       No                                                                                                 I>           Yes                    No
                        Trip   dF/dt3     No                        Block tP>        No   Block   dF/dt1   No
 Trip   tP<<      No    Trip   dF/dt4     No                        Block tP>>       No                              I>>          No
                                                                                          Block   dF/dt2   No
 Trip   tQ>       No    Trip   dF/dt5     No                                                                         I>>>         No         Sel 1 tle >>>>
                                                                                          Block   dF/dt3   No
 Trip   tQ>>      No    Trip   dF/dt6     No                                                                         Ie>          Yes                    No
                                                                                          Block   dF/dt4   No
 Trip   tQ<       No                                                Block tPe/IeCos>                                 Ie>>         No
                                                                                          Block   dF/dt5   No
 Trip   tQ<       No                                                                 No                              Ie>>>        No
                                                                                          Block   dF/dt6   No
                        Trip Brkn.Cond No                           Block tPe/IeCos >>                               Ie>>>>       No         t Sel 1
                                                                                     No                              I2>          Yes                     150 ms
 Trip tPe/IeCos> No
 Trip tPe/IeCos >>No                                                                                                 I2>>         No
                        Trip   tAux1      No                                              Block TBrk.Cond            I2>>>        No
                        Trip   tAux2      No                        Block tI2>       No                No
 Trip tI2>        No    Trip   tAux3      No                        Block tI2>>      No                         No
 Trip tI2>>       No    Trip   tAux4      No                        Block tI2>>>     No
 Trip tI2>>>      No    Trip   tAux5      No                                              Block   tAux1 No
                        Trip   tAux6      No                                              Block   tAux2 No
 Trip Thermal θ No      Trip   tAux7      No                        Block Thermal θ No    Block   tAux3 No
 Trip tI<       No      Trip   tAux8(1)   No                        Block tI<       No    Block   tAux4 No
                        Trip   tAux9(1)   No                                              Block   tAux5 No
                        Trip   tAuxA(1)   No                                              Block   tAux6 No
 Trip tU>         No    Trip   tAuxB(1)   No                        Block tU>        No   Block   tAux7 No
 Trip tU>>        No    Trip   tAuxC(1)   No                        Block tU>>       No   Block   tAux8(1) No
                                                                                          Block   tAux9(1) No
                                               tEQU. A ?      No                          Block   tAuxA(1) No
 Trip tU<         No    Trip SOTF         No   …                    Block tU<        No   Block   tAuxB(1) No
 Trip tU<<        No    Ctrl Trip         No   tEQU. H ?      No    Block tU<<       No   Block   tAuxC(1)No
                                                                                                                                                                                            P12y/EN HI/E95
                                                                                                                                                                   Page 21/24
DEFAULT DISPLAY
  IA = 1245 A
     (U< OR V2>)        VTS Alarm ?           CT Supervision ?            CB Fail ?                    TC Supervision ?      Sotf                       Equation                tOrder   Comm   1   0.1s
     & I>>     No                       No                No                          No                           No                       No          A/B/C/D/E/F/G/H         tOrder   Comm   2   0.1s
             Yes                Yes                      Yes                        Yes                           Yes                                                           tOrder   Comm   3   0.1s
                                                                                                       t trip circuit        tSotf                                              tOrder   Comm   4   0.1s
                                                                                                                                                                                                           MiCOM P125/P126 & P127
                                                                                                                                                                                                           Page 23/24
 DEFAULT DISPLAY
   IA = 1245 A
CB Monitoring Fault Record Instantaneous Disturbance Record Time Peak Value Rolling Demand
CB Opening Time        Record Number                        Number              Records number       Time Window       Sub Period
          83 ms                    25                                       5               5                 5 mn                  1mn
CB Closing Time        Fault Time          VAB Magnitude    Hour                Pre-Time                               Num of Sub Per
          100 ms            12:05:23:42             103 A      13:07:15:53                 0.1 s                                    1
                       IC Magnitude
                                 480 A
                                                                                                                                          MiCOM P125/P126 & P127
                                                                                                                                                                   Menu Content Tables
Technical Data           P12y/EN TD/E95
CONTENT
1.       RATINGS                                                                          5
1.1      Power Supply                                                                     5
1.2      Frequency                                                                        5
1.3      Current Inputs                                                                   5
1.4      Measurement Current Inputs (P127 with measurement CT)                            5
1.5      Voltage Inputs                                                                   6
1.6      Logic Inputs                                                                     6
1.6.1    Supply                                                                           6
1.7      Output Relay Characteristic                                                      7
2. MECHANICAL DATA 8
3. INSULATION WITHSTAND 9
4. ELECTRICAL ENVIRONMENT 10
5. ENVIRONMENT 11
6.       EU DIRECTIVE                                                                   12
6.1      EMC compliance                                                                  12
6.2      Product safety                                                                  12
9.       DEVIATION OF MEASUREMENTS                                                      16
9.1      Measurements                                                                    16
9.2      Metering (P127 with measurement CT)                                             16
13. COMMUNICATION 41
15.      CURVES                                                                    43
15.1     General                                                                   43
15.1.1   Inverse Time Curves:                                                      43
15.1.2   Reset Timer                                                               44
15.2     Thermal Overload Curves                                                   45
P12y/EN TD/E95                         Technical Data
                 BLANK PAGE
Technical Data                                                            P12y/EN TD/E95
1.     RATINGS
1.1    Power Supply
1.2 Frequency
1.6.1 Supply
           (**) Logic input recognition time for EA approval. Dedicated filtering on 24 samples (15 ms at
           50 Hz)
Technical Data                                                        P12y/EN TD/E95
       Contact rating
       Contact relay                 Dry contact Ag Ni
       Make current                  Max. 30A and carrry for 3s
       Carry capacity                5A continuous
       Rated Voltage                 250Vac
       Breaking characteristic
       Breaking capacity AC          1500 VA resistive
                                     1500 VA inductive (P.F. = 0.5)
                                     220 Vac, 5A (cos ϕ = 0.6)
       Breaking capacity DC          135 Vdc, 0.3A (L/R = 30 ms)
                                     250 Vdc, 50W resistive or
                                     25W inductive (L/R=40ms)
       Operation time                <7ms
       Durability
       Loaded contact                10000 operation minimum
       Unloaded contact              100000 operation minimum
P12y/EN TD/E95                                                                  Technical Data
2.    MECHANICAL DATA
      Design
      MiCOM P125, P126 and P127 relays are available in a 4U metal case for panel or flush
      mounting.
      The table shows the case size of the different models:
      Weight
      P125 approx.:             3.0 Kg
      P126/7 approx.:           4.0 Kg
      Mounting
      Rack or flush mounting.
      Connections
      Rear (double fast on + M4 screw per connection).
      Full draw-out with automatic CT shorting in the case of the relay.
      Enclosure protection
      Per IEC 60529: 2001:
− IP 50 Protection for the rear and sides of the case against dust,
      −     IP 10 Product safety protection for the rear due to live connections on the terminal
            block.
      Dimensions
      See dimensions diagram (P12y/EN IN chapter).
      PC Interface
      DIN 41652 connector (X6),
      type D-Sub, 9-pin.
Technical Data                                                            P12y/EN TD/E95
3.     INSULATION WITHSTAND
       Dielectric withstand    IEC 60255-5: 2000   2 kVrms 1 minute to earth and between
                                                   independent circuits.
                               IEEE C39.90:1989    1.5kV rms AC for 1 minute,
                                                   (reaffirmed 1994) across normally open
                                                   contacts.
       Impulse voltage         IEC 60255-5: 2000   5 kVp Between all terminals & all terminals
                                                   and case earth.
4.    ELECTRICAL ENVIRONMENT
      High frequency         IEC 60255-22-1:1998   2.5 kV common mode, class 3
      disturbance                                  1 kV differential mode, class 3
      Fast transient         IEC 60255-22-4:2002   Class A
                                                   2 kV 5kHz terminal block comms
                                                   4 kV 2.5kHz all circuits excluding comms.
                             EN 61000-4-4:1995     2 kV 5kHz all circuits excluding power
                             Level 4               supply
                                                   4 kV 5kHz power supply
      Electrostatic          EN 61000-4-2:1995 &   8 kV contact discharge, class 4
      discharge              IEC60255-22-2:1996    15kV air discharge, class 4
      Surge Immunity         EN 61000-4-5:1995 &   4kV common mode, level 4
                             IEC 60255-22-5:2002   2kV differential mode, level 4
      Conducted emissions    EN55022:1998 &        0.15-0.5MHz, 79dBµV (quasi peak)
                             IEC 60255-25:2000     66 dBµV (average)
                                                   0.5-30MHz, 73dBµV (quasi peak)
                                                   60 dBµV (average)
      Radiated emissions     EN55022:1998 &        30-230MHz, 40dBµV/m at 10m
                             IEC 60255-25:2000     measurement distance
                                                   230-1GHz, 47dBµV/m at 10m
                                                   measurement distance
      Conducted immunity     EN 61000-4-6:1996 &   Level 3, 10V rms @ 1kHz 80% am,
                             IEC 60255-22-6:2001   150kHz to 80MHz
      Radiated Immunity      EN 61000-4-3:2002 &   Level 3, 10V/m 80MHz to 1GHz @ 1kHz
                             IEC 60255-22-3:2000   80% am
      Radiated Immunity      EN 61000-4-3:2002     Level 4, 30V/m 800MHz to 960MHz and
      from digital                                 1.4GHz to 2GHz @ 1kHz 80% am
      telephones
                             ANSI/                 35V/m 80MHz to 1GHz @ 1kHz 80% am
                             IEEE C37.90.2:2004    35V/m 80MHz to 1GHz @ 100% pulse
                                                   modulated front face only
      Magnetic field         EN 61000-4-8:1994     Level 5, 100A/m applied continuously,
      immunity                                     1000A/m for 3s
                             EN 61000-4-9:1993     Level 5, 1000A/m
                             EN 61000-4-10:1993    Level 5, 100A/m at 100kHz and 1MHz
      ANSI Surge withstand   IEEE/                 4kV fast transient and 2.5kV damped
      capability             ANSI C37.90.1:2002    oscillatory applied common and
                                                   transverse mode
Technical Data                                                         P12y/EN TD/E95
5.     ENVIRONMENT
       Temperature     IEC 60255-6              Ambient temperature range
                                                Operating temperature range
                                                –25°C to +55°C (or –13°F to +131°F)
                                                Storage and transit
                                                –25°C to +70°C (or –13°F to +158°F)*
                                                Tested as per
                                                IEC 60068-2-1: 2007
                                                -25°C (–13°F) storage (96 hours)
                                                -40°C (–40°F) operation (96 hours)
                                                IEC 60068-2-2: 2007
                                                +85°C (+185°F) (storage (96 hours)
                                                +85°C (+185°F) operation (96 hours)
                                                (*) The upper limit is permissible for a single
                                                    6 hour duration within any 24 hour period.
6.    EU DIRECTIVE
6.1   EMC compliance
                   89/336/EEC
                   93/31/EEC
      Compliance with European Commission EMC Directive.
      Generic standards were used to establish conformity:
      EN50081-2: 1994
      EN60952-2: 1995
6.2   Product safety
                   2006/95/EC
                   (replacing 73/23/EEC from
                   01/2007)
      Compliance with European Commission Low Voltage Directive. Compliance is demonstrated
      by reference to generic safety standards:
9.    DEVIATION OF MEASUREMENTS
9.1   Measurements
      Active Power and Active Energy    Reactive Power and Reactive Energy
      Cos ϕ               Deviation     Sin ϕ                     Deviation
      0.866               < 1.5%        0.866                     < 3%
      0.5                 < 3%          0.5                       < 1.5%
      Measurement                       Accuracy
      Phase current                     <0.2% at IN
      Voltage                           <0.2% at VN
      Power                             <0.5% for Pm, Qm and Sm
      Sampling rate                     1600Hz
Technical Data                                                                    P12y/EN TD/E95
                                                        Setting Range
         [67] Phase OC
                                                  Min          Max         Step
         I> ?                               No or Yes or DIR
         I>                                 0.1 In       25 In        0.01 In
         Delay type                         DT or IDMT (IEC_STI, IEC_SI,
                                            IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                            IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                            RECT curve)
         tI>                                0s           150 s        0.01 s
         I> TMS                             0.025        1.5          0.001
         I> Reset Delay Type                DT or IDMT
         I> RTMS                            0.025        3.2          0.025
         I> tReset                          0.00 s       100 s        0.01 s
         I> I>> I>>>                        No or Yes
         Interlock
         I> Torque angle                    0°           359°         1°
         I> Trip zone                       ±10°         ±170°        1°
         I>> ?                              No or Yes or DIR
         I>>                                0.1 In       40 In        0.01 In
         Delay type                         DT or IDMT (IEC_STI, IEC_SI,
                                            IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                            IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                            RECT curve)
P12y/EN TD/E95                                                                      Technical Data
                                                        Setting Range
         [67] Phase OC
                                                 Min           Max          Step
         tI>>                               0s           150 s         0.01 s
         I>> TMS                            0.025        1.5           0.001
         I>> Reset Delay Type               DT or IDMT
         I>> RTMS                           0.025        3,2           0.025
         I>> tReset                         0.00 s       100 s         0.01 s
         I>> Torque angle                   0°           359°          1°
         I>> Trip zone                      ±10°         ±170°         1°
         I>>> ?                             No or Yes or DIR or Peak
         I>>>                               0.1 In       40 In         0.01 In
         tI>>>                              0s           150 s         0.01 s
         I>>> Torque angle                  0°           359°          1°
         I>>> Trip zone                     ±10°         ±170°         1°
                                                        Setting Range
         [51] Phase OC
                                                 Min           Max          Step
         I> ?                               No or Yes
         I>                                 0.1 In       25 In         0.01 In
         Delay type                         DT or IDMT (IEC_STI, IEC_SI,
                                            IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                            IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                            RECT curve)
         tI>                                0s           150 s         0.01 s
         I> TMS                             0.025        1.5           0.001
         I> Reset Delay Type                DT or IDMT
         I> RTMS                            0.025        3.2           0.025
         I> tReset                          0.00 s       100 s         0.01 s
         I> I>> I>>>                        No or Yes
         Interlock
         I>> ?                              No or Yes
         I>>                                0.5 In       40 In         0.01 In
         Delay type                         DT or IDMT (IEC_STI, IEC_SI,
                                            IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                            IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                            RECT curve)
         tI>>                               0s           150 s         0.01 s
         I>> TMS                            0.025        1.5           0.001
Technical Data                                                                       P12y/EN TD/E95
                                                        Setting Range
         [51] Phase OC
                                                 Min           Max          Step
         I>> Reset Delay Type               DT or IDMT
         I>> RTMS                           0.025        3.2             0.025
         I>> tReset                         0.00 s       100 s           0.01 s
         I>>> ?                             No or Yes or Peak
         I>>>                               0.5 In       40 In           0.01 In
         tI>>>                              0s           150 s           0.01 s
10.3 [67N/50N/51N] Dir./Non-Dir. Earth fault protection (P125, P126 & P127)
                                                        Setting Range
         [67N] Earth OC
                                                 Min           Max          Step
         High sensitivity current set       Cortec code P12-C-X---X
         Ie>                                0.002 Ien    1 Ien           0.001 Ien
         Ie>>                               0.002 Ien    1 Ien           0.001 Ien
         Ie>>>                              0.002 Ien    1 Ien           0.001 Ien
         Ie>>>>                             0.1 Ien      40 Ien          00.01 Ien
         Med. sensitivity current set       Cortec code P12-B-X---X
         Ie>                                0.01 Ien     1 Ien           0.005 Ien
         Ie>>                               0.01 Ien     8 Ien           0.005 Ien
         Ie>>>                              0.01 Ien     8 Ien           0.005 Ien
         Ie>>>>                             0.1 Ien      40 Ien          00.01 Ien
         Low sensitivity current set        Cortec code P12-A-X---X
         Ie>                                0.1 Ien      25 Ien          0.1 Ien
         Ie>>                               0.5 Ien      40 Ien          0.1 Ien
         Ie>>>                              0.5 Ien      40 Ien          0.1 Ien
         Ie>>>>                             0.1 Ien      40 Ien          00.01 Ien
                                                   Setting Range
      [67N] Earth OC
                                            Min           Max        Step
      Delay type                       DT or IDMT (IEC_STI, IEC_SI,
                                       IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                       IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                       RECT curve)
      tIe>                             0s           150 s       0.01 s
      Ie> TMS                          0.025        1.5         0.025
      Ie> Reset Delay Type             DT or IDMT
      Ie> RTMS                         0.025        3.2         0.025
      Ie> tReset                       0.00 s       100 s       0.01 s
      Ie> Ie>> Ie>>>                   No or Yes
      Interlock
      Ie> Torque angle                 0°           359°        1°
      Ie> Trip zone                    ±10°         ±170°       1°
      Input residual voltage with range from 57 to 130V
      Ue>                              1V           260 V       0.1 V
      Input residual voltage with range from 220 to 480V
      Ue>                              4V           960 V       0.5 V
      Ie>> ?                           No or Yes or DIR
      Delay type                       DT or IDMT (IEC_STI, IEC_SI,
                                       IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                       IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                       RECT curve)
      tIe>>                            0s           150 s       0.01 s
      Ie>> TMS                         0.025        1.5         0.025
      Ie>> Reset Delay Type            DT or IDMT
      Ie>> RTMS                        0.025        3.2         0.025
      Ie>> tReset                      0.00 s       100 s         0.01 s
      tIe>>                            0s           150         0.01 s
      Ie>> Torque angle                0°           359°        1°
      Ie>> Trip zone                   ±10°         ±170°       1°
      Ie>> tReset                      0.00 s       100 s         0.01 s
      Input residual voltage with range from 57 to 130V
      Ue>>                             1V           260 V       0.1 V
                                                   Setting Range
       [67N] Earth OC
                                             Min           Max        Step
       Ue>>>                            1V           260 V       0.1 V
       Input residual voltage with range from 220 to 480V
       Ue>>>                            4V           960 V       0.5 V
       Input residual voltage with range from 57 to 130V
       Ue>>                             1V           260 V       0.1 V
## x K W
− if Ien = 1A, the internal relay setting value will be equal to 20 x 1 = 20W.
− if Ien = 5a, the internal relay setting value will be equal to 20 x 5 = 100w.
                                                         Setting range
         [32N] Earth Wattmetric
                                                 Min            Max         Step
         Mode                                Pe or IeCos
         High sensitivity:                   Current input from 0.002 to 1 Ien
         57–130V Input voltage               Cortec code: P12-CAX---X
         Pe> (*)                             0.2xK W       20xK W         0.02xK W
         Pe>> (*)                            0.2xK W       20xK W         0.02xK W
         220–480V Input voltage              Cortec code: P12-CBX---X
         Pe> (*)                             1xK W         80xK W         0.1xK W
         Pe>> (*)                            1xK W         80xK W         0.1xK W
         Med. Sensitivity:                   Current input from 0.01 to 8 Ien
         57–130V Input voltage               Cortec code: P12-BAX---X
         Pe> (*)                             1xK W         160xK W        0.1xK W
         Pe>> (*)                            1xK W         160xK W        0.1xK W
         220–480V Input voltage              Cortec code: P12-BBX---X
Technical Data                                                         P12y/EN TD/E95
                                             Setting range
       [32N] Earth Wattmetric
                                      Min           Max       Step
       Pe> (*)                   4xK W        640xK W      0.5xK W
       Pe>> (*)                  4xK W        640xK W      0.5xK W
       Low sensitivity:          Current input from 0.1 to 40 Ien
       57–130V Input voltage     Cortec code: P12-AAX---X
       Pe> (*)                   10xK W       800xK W      1xK W
       Pe>> (*)                  10xK W       800xK W      1xK W
       220–480V Input voltage    Cortec code: P12-ABX---X
       Pe> (*)                   40xK W       3200xK W     5xK W
       Pe>> (*)                  40xK W       3200xK W     5xK W
       Pe> ?                     No or Yes
       Delay Type                DT or IDMT (IEC_STI, IEC_SI,
                                 IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                 IEEE_MI, IIEEE_VI, IEEE_EI,RI,
                                 RECT curve)
       tPe>                      0s           150 s        0.01 s
       Pe> TMS                   0.025        1.5          0.025
       Pe> Reset Delay Type      DT or IDMT
       Pe> RTMS                  0.025        1.5          0.025
       Pe> tReset                0.00 s       100 s        0.01 s
       Pe>> ?                    No or Yes
       tPe>>                     0s           150 s        0.01 s
       Pe>> tReset               0.00 s       100 s        0.01 s
       High sensitivity IeCos    Cortec code P12-C-X---X
       IeCos>                    0.002 Ien    1 Ien        0.001 Ien
       IeCos>>                   0.002 Ien    1 Ien        0.001 Ien
       Med. sensitivity IeCos    Cortec code P12-B-X---X
       IeCos>                    0.01 Ien     8 Ien        0.005 Ien
       IeCos>>                   0.01 Ien     8 Ien        0.005 Ien
       Low sensitivity IeCos     Cortec code P12-A-X---X
       IeCos>                    0.1 Ien      25 Ien       0.01 Ien
       IeCos>>                   0.5 Ien      40 Ien       0.01 Ien
       IeCos> ?                  Yes or No
       Delay Type                DT or IDMT (IEC_STI, IEC_SI,
                                 IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                 IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                 RECT curve)
       tIeCos>                   0s           150 s        0.01 s
       IeCos> TMS                0.025        1.5          0.025
       IeCos> Reset Delay Type   DT or IDMT
       IeCos> RTMS               0.025        1.5          0.025
       IeCos> tReset             0.00 s       100 s        0.01 s
P12y/EN TD/E95                                                                      Technical Data
                                                       Setting range
         [32N] Earth Wattmetric
                                                Min           Max         Step
         IeCos>> ?                         Yes or No
         tIeCos>>                          0s           150 s        0.01 s
         IeCos> tReset                     0.00 s       100 s        0.01 s
         Pe/IeCos Torque angle             0°           359°         1°
− Undercurrent
                                                       Setting ranges
         [37] Undercurrent
                                                Min            Max        Step
         I< ?                              Yes or No
         I<                                0.1 In       1 In         0.01 In
         tI<                               0s           150 s        0.01 s
         I< Inhibited on 52A               Yes or No
         I< inhibited on U<                Yes or No
         I< inhibited on U<                Yes or No
                                                       Setting ranges
         [46] Neg.Seq. OC
                                                Min            Max        Step
         I2> ?                             No or Yes
         I2>                               0.1 In       25 In        0.01 In
         Delay Type                        DT or IDMT (IEC_STI, IEC_SI,
                                           IEC_VI, IEC_EI, IEC_LTI, C02, C08,
                                           IEEE_MI, IIEEE_VI, IEEE_EI, RI,
                                           RECT curve)
         tI2>                              0s           150s         0.01s
         I2> TMS                           0.025        1.5          0.025
         I2> Reset Delay Type              DT or IDMT
         I2> RTMS                          0.025        1.5          0.025
         I2> tReset                        0.04 s       100 s        0.01 s
         I2>> ?                            No or Yes
         I2>>                              0.5 In       40 In        0.01 In
         tI2>>                             0s           150s         0.01s
Technical Data                                                                    P12y/EN TD/E95
                                                        Setting ranges
         [46] Neg.Seq. OC
                                                 Min           Max         Step
         I2>>> ?                            No or Yes
         I2>>>                              0.5 In       40 In        0.01 In
         tI2>>>                             0s           150s         0.01s
                                            Setting range
         [49] Therm. OL
                                                 Min           Max         Step
         Therm. OL ?                        No or Yes
         Iθ                                 0.1 In       3.2 In       0.01
         Te                                 1 mn         200 mn       1mn
         k                                  1            1,5          0.01
         θ Trip                             50%          200%         1%
         θ Alarm ?                          No or Yes
         θ Alarm                            50%          200%         1%
                                                        Setting ranges
         [27] Phase Undervoltage
                                                 Min           Max         Step
         57–130V Input voltage              Cortec code: P127-AX---X
         U< ?                               No or AND or OR
         U<                                 2V           130 V        0.1 V
         tU<                                0s           600 s        0.01 s
         52a Inhib. U< ?                    Yes or No
         U<< ?                              No or AND or OR
         U<<                                2V           130 V        0.1 V
         tU<<                               0s           600 s        0.01 s
         52a Inhib. U<< ?                   Yes or No
         220–480V Input voltage.            Cortec code: P127-BX---X
         U< ?                               No or AND or OR
         U<                                 10 V         480 V        0.5 V
         tU<                                0s           600 s        0.01 s
         52a Inhib. U< ?                    Yes or No
P12y/EN TD/E95                                                                       Technical Data
                                                        Setting ranges
         [27] Phase Undervoltage
                                                  Min        Max         Step
         U<< ?                              No or AND or OR
         U<<                                10 V         480 V       0.5 V
         tU<<                               0s           600 s       0.01 s
         52a Inhib. U<< ?                   Yes or No
                                                        Setting ranges
         [59] Phase Overvoltage
                                                  Min        Max         Step
         57–130V Input voltage              Cortec code: P127-AX---X
         U> ?                               No or AND or OR
         U>                                 2V           260 V       0.1 V
         tU>                                0s           260 s       0.01 s
         U>> ?                              No or AND or OR
         U>>                                2V           260 V       0.1 V
         tU>>                               0s           600 s       0.01 s
         220–480V Input voltage.            Cortec code: P127-BX---X
         U> ?                               No or AND or OR
         U>                                 10 V         960 V       0.5 V
         tU>                                0s           600 s       0.01 s
         U>> ?                              No or AND or OR
         U>>                                10 V         960 V       0.5 V
         tU>>                               0s           600 s       0.01 s
         (*)    OR      trip caused by one or two or three phase values exceeding the threshold.
                AND     trip caused by three phase values exceeding the threshold.
10.10    Under/over frequency Function (P127)
                                                        Setting ranges
         OP PARAMETERS
                                                  Min        Max         Step
         Frequency                          50 Hz        60 Hz       N.A
         [81] Frequency                     Min          Max         Step
         F1?                                81> or 81< or No
         F1                                 45,1 Hz      64,9 Hz     0.01 Hz
         tF1                                0s           600 s       0.01 s
Technical Data                                                                 P12y/EN TD/E95
                                                       Setting ranges
         OP PARAMETERS
                                                 Min        Max         Step
         F2?                               81> or 81< or No
         F2                                45,1 Hz      64,9 Hz     0.01 Hz
         tF2                               0s           600 s       0.01 s
         F3?                               81> or 81< or No
         F3                                45,1 Hz      64,9 Hz     0.01 Hz
         tF3                               0s           600 s       0.01 s
         F4?                               81> or 81< or No
         F4                                45,1 Hz      64,9 Hz     0.01 Hz
         tF4                               0s           600 s       0.01 s
         F5?                               81> or 81< or No
         F5                                45,1 Hz      64,9 Hz     0.01 Hz
         tF5                               0s           600 s       0.01 s
         F6?                               81> or 81< or No
         F6                                45,1 Hz      64,9 Hz     0.01 Hz
         tF6                               0s           600 s       0.01 s
                                                       Setting ranges
         OP PARAMETERS
                                                 Min        Max         Step
         dF/dt1 ?                          Yes or No
         dF/dt1                            –10Hz/s      +10Hz/s     0.1Hz/s
         dF/dt2 ?                          Yes or No
         dF/dt2                            –10Hz/s      +10Hz/s     0.1Hz/s
         dF/dt3 ?                          Yes or No
         dF/dt3                            –10Hz/s      +10Hz/s     0.1Hz/s
         dF/dt4 ?                          Yes or No
         dF/dt4                            –10Hz/s      +10Hz/s     0.1Hz/s
         dF/dt5 ?                          Yes or No
         dF/dt5                            –10Hz/s      +10Hz/s     0.1Hz/s
         dF/dt6 ?                          Yes or No
         dF/dt6                            –10Hz/s      +10Hz/s     0.1Hz/s
                                                                     Setting ranges
         [32] Directional Power
                                                        Min              Max            Step
         57–130V Input voltage                     Cortec code: P127AA or P127BA or P127CA
         “P>?” or “Q>?” or “P<?” or “Q<?”          Yes or No
         P> or Q> or P< or Q<                      1 W*k (*)     10000 W*k (*) 1 W*k (*)
         Directional angle                         0°            359°             1°
         tP> or tQ> or tP< or tQ<                  0s            150 s            0.01 s
         “P>>?” or “Q>>?” or “P<<?” or “Q<<?” Yes or No
         P>> or Q>> or P<< or Q<<                  1 W*k (*)     10000 W*k (*) 1 W*k (*)
         Directional angle                         0°            359°             1°
         tP>> or tQ>> or tP<< or tQ<<              0s            150 s            0.01 s
         220–480V Input voltage                    Cortec code: P127AB or P127BA or P127CA
         “P>?” or “Q>?” or “P<?” or “Q<?”          Yes or No
         P> or Q> or P< or Q<                      4 W*k (*)     40000 W*k (*) 1 W*k (*)
         Directional angle                         0°            359°             1°
         tP> or tQ> or tP< or tQ<                  0s            150 s            0.01 s
         “P>>?” or “Q>>?” or “P<<?” or “Q<<?” Yes or No
         P>> or Q>> or P<< or Q<<                  4 W*k (*)     40000 W*k (*) 1 W*k (*)
         Directional angle                         0°            359°             1°
         tP>> or tQ>> or tP<< or tQ<<              0s            150 s            0.01 s
                                                        Setting range
         [59] Residual Overvoltage
                                                 Min           Max         Step
         57–130V Input voltage.             Cortec code: P127-AX---X
         Ue>>>> ?                           No or Yes
         Ue>>>>                             1V           260 V          0.1 V
         tUe>>>>                            0s           600 s          0.01 s
         220–480V Input voltage.            Cortec code: P127-BX---X
         Ue>>>> ?                           No or Yes
         Ue>>>>                             5V           960 V          0.5 V
         tUe>>>>                            0s           600 s          0.01 s
Technical Data                                                                    P12y/EN TD/E95
                                 1
                          Ue =     x(UA + UB + UC)
                                 3
                          THE SETTING OF THE Ue THRESHOLDS MUST TAKE THE ABOVE
                          FORMULA IN ACCOUNT.
10.13    Multishot Autoreclose Function (P126 & P127)
         Main shots: 4 independent shots.
         External logic inputs: 6 inputs (CB opened signal, CB closed signal, manual opening
         command, manual closing command, blocking order, cycle activation).
         Internal programmable trigger from phase and earth fault on all re-closing cycles.
         External trigger from logic input.
         Inhibit time on manual closing.
         Programmable dead times and reclaim time setting.
         Maximum CB closing control equal to 5s (+t_Pulse setting).
10.13.1 Multishot Autoreclose Settings
                                                          Setting range
         [79] Autoreclose
                                                  Min            Max       Step
         Autoreclose ?                        Yes or No
         Ext. CB Fail ?                       Yes or No
         Ext. CB Fail time                    0.01 s       600 s       0.01 s
         Aux1 ((I>) ?                         Yes or No
         Aux2 (Ie>) ?                         Yes or No
         Ext Block ?                          Yes or No
         Rolling Demand                       Yes or No
         Max cycles nb                        2            100         1
         Time period                          10mn         24h         10mn
         Dead time
         tD1                                  0.01 s       300 s       0.01 s
         tD2                                  0.01 s       300 s       0.01 s
         tD3                                  0.01 s       600 s       0.01 s
         tD4                                  0.01 s       600 s       0.01 s
         tI>                                  0.05 s       600 s       0.01 s
         tI>>                                 0.05 s       600 s       0.01 s
         tI>>>                                0.05 s       600 s       0.01 s
         tIe>                                 0.05 s       600 s       0.01 s
         tIe>>                                0.05 s       600 s       0.01 s
         tIe>>>                               0.05 s       600 s       0.01 s
         Reclaim time
         tR                                   0.02 s       600 s       0.01 s
         Inhib time
P12y/EN TD/E95                                                                        Technical Data
                                                         Setting range
         [79] Autoreclose
                                                Min           Max           Step
         tI                                0.02 s         600 s         0.01 s
         Phase Cycles                      0              4             1
         E/Gnd Cycles                      0              4             1
         Cycles                            4321           Settings
         tI>                               1111           0 or 1 or 2
         tI>>                              1111           0 or 1 or 2
         tI>>>                             1111           0 or 1 or 2
         tIe>                              1111           0 or 1 or 2
         tIe>>                             1111           0 or 1 or 2
         tIe>>>                            1111           0 or 1 or 2
         tPe/Iecos>                        1111           0 or 1 or 2
         tPe/Iecos>>                       1111           0 or 1 or 2
         tAux1                             1111           0 or 1 or 2
         tAux2                             1111           0 or 1 or 2
        With:
        0 = no action on autorecloser: definitive trip
        1 = trip on pick up of the protection element, followed by reclosing cycle
        2 = no trip on pick up of the protection element also if this has been set in the CRTL/Trip
            commands/Trip menu
10.13.2 Further timing
        Fixed time out for lacking of CB opening signal on trip protection:           2.00 s at 50 Hz
                                                                                      1.67 s at 60 Hz
        Time out for lacking of CB closing signal on close control after dead time:
        tClose Pulse(*): from 0.1 to 5.00 s in steps of 0.01 s
        (*) Setting available in CB monitoring menu.
Technical Data                                                                      P12y/EN TD/E95
       −    all models: tIe>, tIe>>, tIe>>>, tPe/IeCos>, tPe/IeCos>> , tUe>>>>, tAux 1, tAux 2, tAux
            3, tAux 4, Ctrl Trip,
       −    P126 and P127 only, tI> , tI>> , tI>>> , tI2>, tI2>>, tI2>>>, Thermal θ, Brkn. Cond ,
            SOTF, tEQUATION A, tEQUATION B, tEQUATION C ,t EQUATION D , tEQUATION E ,
            tEQUATION F, tEQUATION G, tEQUATION H,
       −    P127 only: tIe>>>>, tP>, tP>>, tU>, tU>>, tU<, tU<<, tF1, tF2 , tF3 , tF4 , tF5 , tF6 ,
            dF/dt1, dF/dt2, dF/dt3, dF/dt4, dF/dt5, dF/dt6, tAux 5, tAux 6, tAux 7, tAux 8, tAux 9,
            tAux A, tAux B, tAux C.
11.2   Latch relays
       Number of relay settable:
       −    all models: tIe>, tIe>>, tIe>>>, tPe/IeCos>, tPe/IeCos>>, tUe>>>>, tAux1, tAux2, tAux3,
            tAux4,
− P126 and P127: tI>, tI>>, tI>>>, tI2>, tI2>>, tI2>>>, tThermal θ, tI<, tBrk. Cond,
       −    P127: tIe>>>>, tP>, tP>>, tP<, tP<<, tQ>, tQ>>, tQ<, tQ<<, tU>, tU>>, tU<, tU<<, tF1 ,
            tF2 , tF3 , tF4 , tF5 , tF6 , dF/dt1, dF/dt2, dF/dt3, dF/dt4, dF/dt5, dF/dt6, tAux5, tAux6,
            tAux7, tAux8, tAux9, tAuxA, tAuxB, tAuxC.
                                            Setting range
       Inrush Block
                                                 Min         Max           Step
       Inrush Block                         Yes or No
       Inrush H2 ration                     10 %        35 %            0,1 %
       Inrush tReset                        0 ms        2s              0,1 s
       Block I>                             No          Yes             Yes or No
       Block I>>                            No          Yes             Yes or No
       Block I>>>                           No          Yes             Yes or No
       Block Ie>                            No          Yes             Yes or No
       Block Ie>>                           No          Yes             Yes or No
       Block Ie>>>                          No          Yes             Yes or No
       Block I2>                            No          Yes             Yes or No
       Block I2>>                           No          Yes             Yes or No
       Block I2>>>                          No          Yes             Yes or No
       Block Ie>>>>                         No          Yes             Yes or No
P12y/EN TD/E95                                                                      Technical Data
                                                        Setting range
         Blocking Inrush
                                                 Min         Max         Step
         Sel1 tI>>                          Yes or No
         Sel1 tI>>>                         Yes or No
         Sel1 tIe>>                         Yes or No
         Sel1 tIe>>>                        Yes or No
         Sel1 tIe>>>>                       Yes or No
         Sel1 tIe>>>>                       Yes or No
         T Sel1                             0s           150s         10ms
         −   all models: Ie>, tIe>, Ie_R>, Ie>>, tIe>>, Ie_R>>, Ie>>>, tIe>>>, Ie_R>>>, Pe/IeCos>,
             tPe/IeCos>, Pe/IeCos>>, tPe/IeCos>>, Ue>>>>, tUe>>>>, tAux1, tAux2, tAux3, tAux4,
             CONTROLTRIP, CONTROLCLOSE, ActiveGroup, Input1, Input2, Input3:, Input4,
         −   P126 and P127: Trip, I>, tI>, I_R>, I>>, tI>>, I_R>>, I>>>, tI>>>, I_R>>>, tIA>, tIB>,
             tIC>, I2>, tI2>, I2>>, tI2>>, I2>>>, tI2>>>, ThermAlarm, ThermTrip, I<, tI<, BrknCond,
             CBAlarm, 52 Fail, CBFail , CB Close , 79 Run, 79 Trip, SOTF, Input5, Input6, Input7,
             t EQU.A, t EQU.B, t EQU.C, t EQU.D, t EQU.E, t EQU.F, t EQU.G, t EQU.H, 79 int.
             Lock, 79 Ext Lock,
         −   P127: Ie>>>>, tIe>>>>, P>, tP>, P>>, tP>>, U>, tU>, U>>, tU>>, U<, tU<, U<<, tU<<,
             F1, tF1, F2, tF2, F3, tF3, F4, tF4, F5, tF5, F6, tF6, dF/dt1, dF/dt2, dF/dt3, dF/dt4,
             dF/dt5, dF/dt6, F.OUT, tAux5, tAux6, tAux7, tAux8, tAux9, tAuxA, tAuxB, tAuxC, VTS,
             CTS, Command1, Command2, Command3, Command4.
11.7     Inputs
11.7.1   Inputs assignation
         Single function or multiple automation functions assignable to 4 (P125) or 7 (P126 and P127)
         logic inputs:
         −     all models: None, Unlatch, Blk Log 1, Aux 1, Aux 2, Aux 3, Aux 4, Maint. M, Man.
               Close, Local, Synchronisation, LED Reset (or reset LED),
         −     P126 and P127: Blk Log 2, 52 a, 52 b, CB FLT, θ Reset, Change set, Log Sel 2, Cold
               L PU, Strt Dist, Block_79, Trip Circ, Start t BF, Ctrl Trip, Ctrl Close,
         −     P127: Aux 5, Aux 6, Aux 7, Aux 8, Aux 9, Aux A, Aux B, Aux C, Log Sel 1.
Technical Data                                                                       P12y/EN TD/E95
                                            Setting range
         Auxiliary timers
                                                  Min         Max             Step
         tAux1                              0             200 s          0.01 s
         tAux2                              0             200 s          0.01 s
         tAux3                              0             200 s          0.01 s
         tAux4                              0             200 s          0.01 s
         tAux5                              0             200 s          0.01 s
         tAux6                              0             200 s          0.01 s
         tAux7                              0             20000 s        0.01 s
         tAux8                              0             20000 s        0.01 s
         tAux9                              0             20000 s        0.01 s
         tAuxA (tAux10)                     0             200 s          0.01 s
         tAuxB (tAux11)                     0             200 s          0.01 s
         tAuxC (tAux12)                     0             200 s          0.01 s
                                            Setting range
         Broken Conductor
                                            Min           Max            Step
         Brkn.Cond ?                        Yes or No
         Ratio I2/I1                        20%           100%           1%
         Brkn.Cond Time tBC                 1s            14400s         1s
                                            Setting range
         Cold Load PU
                                                  Min         Max             Step
         Cold Load PU ?                     Yes or No
         Input?                             Yes or No
         Auto?                              Yes or No
         Cold Load pickup activable with: tI>, tI>>, tI>>>, tIe>, tIe>>, tIe>>>,
         tIe>>>>, tI2>, tI2>>, tI2>>> and/or tTherm
         Cold Load PU level                 20%           800%           1%
         tCL                                0.1s          3600s          0.1s
P12y/EN TD/E95                                                                  Technical Data
                                           Setting range
         51V
                                                 Min       Max        Step
         Voltage range 57-130V
         (U<OR V2>) & I>>                  Yes or No
         V2>                               3V          200V       0.1V
         (U<<OR V2>>) & I>>>               Yes or No
         V2>                               3V          200V       0.1V
         Voltage range 220-480V
         (U<OR V2>) & I>>                  Yes or No
         V2>                               20V         720V       0.5V
         (U<<OR V2>>) & I>>>               Yes or No
         V2>                               20V         720V       0.5V
         VTS Blocks 51V                    Yes or No
         VTS Alarm                         Yes or No
                                           Setting range
         VT Supervision
                                                 Min       Max        Step
         VTS?                              Yes or No
         VTS Alarm                         Yes or No
         VTS Blocks 51V                    Yes or No
         VTS Blocks protection ?           Yes or No
         VTS Non Dir I>, I>>, I>>>, Ie>,   Yes or No
         Ie>>, Ie>>> and/or Ie>>>>
         tVTS                              0s          100s       10ms
                                           Setting range
         CT Supervision
                                                 Min       Max        Step
         CT Supervision                    Yes or No
         Ie>                               0.08 × In   1.0 × In   0.01 × In
         Ue< (P127xA)                      0.5V        22V        0.1V
         Ue< (P127xB)                      2V          88V        0.5V
         tCTS                              0s          100s       0.01s
Technical Data                                                                   P12y/EN TD/E95
                                           Setting range
          CB Fail
                                                 Min          Max        Step
          CB Fail ?                        Yes or No
          I< BF                            0.02 In      1In          0.01 In
          CB Fail Time tBF                 0s           10 s         0.01 s
          Block I>                         Yes or No
          Block Ie>                        Yes or No
                                           Setting range
          TC Supervision
                                                 Min          Max        Step
          TC Supervision ?                 Yes or No
          t trip circuit tSUP              0.1 s        10 s         0.01 s
         (*) Note: The tOpen/Close Pulse is available in the P125 for the Local /Remote functionality.
P12y/EN TD/E95                                                                  Technical Data
                                             Setting range
         SOTF
                                                  Min        Max      Step
         SOTF?                               Yes or No
         t SOTF                              0 ms         500 ms   10ms
         I>>                                 Yes or No
         I>>>                                Yes or No
         Ctrl close input                    Yes or No
         SOTF input                          Yes or No
         HMI closing order                   Yes or No
         [79] closing                        Yes or No
         Front comm. order                   Yes or No
         Rear comm. order                    Yes or No
         Rear2 comm. order                   Yes or No
         Capacity               25 faults
         Time-tag               1 millisecond
         Triggers               Any selected protection alarm and threshold
         Data                   Fault date
                                Protection thresholds
                                Setting Group
                                AC inputs measurements (RMS)
                                Fault measurements
         Disturbance Records
         Triggers               Any selected protection alarm and threshold, logic input, remote
                                command
         Data                   AC input channels
                                digital input and output states
                                frequency value
                                Default value              Setting range
                                                           Min         Max             Step
         Records number         5                          1           5               1
         Pre-Time               0.1s                       0.1         2.9 / 4.9 /     0.1
                                                                       6.9 or 8.9
         Disturb rec Trig       ON TRIP                    ON TRIP or ON INST.
         Trigger                Any selected protection alarm and threshold
                                Logic input
                                Remote command
Technical Data                                                         P12y/EN TD/E95
13.     COMMUNICATION
Type   Relay
                   Physical Link   Connectors Data Rate           Protocol
Port   position
RS485 Rear port    Screened twister Screws or   300 to 38400 baud ModBus RTU, ,
                   pair             snap-on     (programmable)    IEC60870-5-103, DNP3
RS485 Optional 2nd Screened twister Screws or   300 to 38400 baud ModBus RTU,
isolated rear port pair             snap-on     (programmable)    IEC60870-5-103 (option)
RS232 Front port   Screened twister Sub–D 9 pin 300 to 38400 baud ModBus RTU
                   pair             female      (programmable)
                                    connector
P12y/EN TD/E95                                                              Technical Data
15.      CURVES
15.1     General
         Although the curves tend towards infinite when the current approaches Is (general
         threshold), the minimum guaranteed value of the operating current for all the curves with the
         inverse time characteristic is 1.1Is (with a tolerance of ± 0.05Is).
15.1.1   Inverse Time Curves:
         The first stage thresholds for phase (earth) overcurrent can be selected with an inverse
         definite minimum time (IDMT) characteristic. The time delay is calculated with a
         mathematical formula.
         In all, there are eleven IDMT characteristics available.
         The mathematical formula applicable to the first ten curves is:
                ⎛     K           ⎞
         t = T ×⎜              + L⎟
                ⎜ (I I S ) − 1
                          α       ⎟
                ⎝                 ⎠
         Where:
         t         Operation time
         K         Factor (see table)
         I         Value of measured current
         Is        Value of the programmed threshold (pick-up value)
         α         Factor (see table)
         L         ANSI/IEEE constant (zero for IEC and RECT curves)
         T         Time multiplier setting from 0.025 to 1.5
                         1
         t= K ⋅
                              0.236
                   0 .339 −
                              ( )
                               I
                                 Is
         K setting is from 0.10 to 10 in steps of 0.05.
         The equation is valid for 1.1 ≤ I/Is ≤ 20.
P12y/EN TD/E95                                                                        Technical Data
       e⎝ τ
            ⎜⎜ ⎟⎟
                 ⎠   =
                         (I ² − (kxIFLC )² )
                              (I ² − Ip ² )
       Where:
       t                  = Time to trip, following application of the overload current, I
                       ⎛ K² - θ                      ⎞
       t Trip = Te In ⎜⎜                             ⎟
                                                     ⎟
                       ⎝ K ² − θtrip                 ⎠
       Where:
       t Trip             = Time to trip (in seconds)
       Te                 = Thermal time constant of the equipment to be protected (in seconds)
       Iθ>                = Full load current rating given by the national standard or by the supplier
       k                  = Factor associated to the thermal state formula
θ alarm = Initial thermal state. If the initial thermal state = 30% then θ =0.3
       θ trip             = Trip thermal state. If the trip thermal state is set at 100%, then θ trip = 1
       The settings of these parameters are available in the various menus. The calculation of the
       thermal state is given by the following formula:
                                     ²⎡     ⎛ −t ⎞ ⎤         ⎛ −t ⎞
                ⎛ Ieq ⎞                     ⎜ ⎟              ⎜ ⎟
                                      ⎢1− e ⎝ Te ⎠ ⎥ + Θ τ e ⎝ Te ⎠
       Θ τ +1 = ⎜        ⎟
                ⎝ kxIΘ > ⎠            ⎢
                                      ⎣
                                                   ⎥
                                                   ⎦
       θ being calculated every 100ms.
P12y/EN TD/E95                         Technical Data
                 BLANK PAGE
Getting Started          P12y/EN GS/E95
            GETTING STARTED
Getting Started                                                    P12y/EN GS/E95
CONTENT
3.      LOCAL CONNECTION TO A PC                                                7
3.1     Configuration                                                           7
3.1.1   REMOTE connection                                                       7
3.2     Products plugged in the same panel                                      8
3.3     Communication between distant products                                  8
3.4     MiCOM S1 and MiCOM S1 Studio relay communications basics                9
3.5     MiCOM S1 Studio                                                         9
3.5.1   Data Model Management                                                   9
3.5.2   “Quick Connection” to the relay using MiCOM S1 Studio                  12
3.5.3   Create a system                                                        15
3.5.4   Create a new substation                                                16
3.5.5   Create a new voltage level                                             17
3.5.6   Create a new bay                                                       17
3.5.7   Create a new device                                                    18
3.5.8   Open Settings File                                                     19
3.6     MiCOM S1                                                               21
3.6.1   Starting MiCOM S1                                                      21
3.6.2   Open communication link with relay                                     22
3.6.3   Off-line use of MiCOM S1                                               24
3.6.4   MiCOM monitoring                                                       25
3.7     Presentation and analysis of disturbance                               26
                 BLANK PAGE
Getting Started                                                                   P12y/EN GS/E95
        − Modify, for instance, the password or the language (“OP parameters” menu.
2.1.2   Password protection
        Password protection is applicable to most of the relay parameter settings, especially to the
        selection of the various thresholds, time delays, communication parameters, allocation of
        logic inputs and logic outputs.
        The password consists of four capital characters. When leaving the factory, the password is
        set to AAAA. The user can define any combination of four characters.
        Should the password be lost or forgotten, the modification of stored parameters is blocked. It
        is then necessary to contact the manufacturer or his agent and by specifying the serial
        number of the relay, a stand-by password specific to the relay concerned may be obtained.
                 NOTE:         The programming mode is indicated with the letter "P" on the right
                               hand side of the display on each menu heading. The letter "P"
                               remains present as long as the password is active (5 minutes if there
                               is no action on the keypad).
        − Go to the “OP. Parameters” menu by pressing  and then to the “password” menu by
          pressing ,
        − Enter the current password (default password = “AAAA”) and validate with  (this
          operation is not necessary if the password has been entered some minutes ago),
        − Enter the new password character by character, using  and  arrows to change a
          letter (maintain the key pressed to scroll through the letter in the alphabet). Use  and 
          arrows to select another character: a flashing cursor will indicate which character field of
          the password may be entered,
        − Validate using  or cancel using . If the password is correct, the following message is
          displayed on the LCD: PASSWORD OK.
Getting Started                                                                 P12y/EN GS/E95
        As soon as the password has been entered, no setting change will be accepted via the
        remote or local communication port (RS485 or RS232).
        Alternatively, the password can be entered by using the Password window in the
        OP.PARAMETERS menu. This password entry procedure is the same as above.
                  NOTE:         In case of loss of password a back up password can be provided
                                contacting Schneider Electric sale office or factory.
2.1.3   Setting the language
        − Go to the “OP. Parameters” menu by pressing  and then to the “Language” menu by
          pressing , ,
        − Go to the “OP. Parameters” menu by pressing  and then to the “Date” menu by
          pressing  (x9),
        − Set the date using  or  arrow, and validate with  (10/11/08 means November 10th
          2008),
                  NOTE:         When you modify the date, the first digit for the day or the month can
                                be selected according to the second digit. For instance, if 13/09/08 is
                                displayed, you cannot select 33 for the day, or 29 for the month.
− Set the date using or arrow, and validate with (14:21:42 means 2:21:42 pm).
           • Press  or  keys to navigate from a menu heading to another menu heading (refer to
             the figure below),
      DEFAULT DISPLAY
        IA = 1245 A
                                                                              or                    when
                                                                              “Measurement”         displayed
                                                                 G1/G2,
                                                                 G3 to G8 (P127)
3.      LOCAL CONNECTION TO A PC
3.1     Configuration
                                                                                  io
                                                                           S1 Stud
                                                                   MiCOM
P0107ENc
        For a local connection between a PC and the relay, a serial cable with metallic shield should
        be used.
        The wiring of the RS232 cable must be as shown in the following drawing.
P0073ENa
                                                                                             29
                                                                                                                 30
                                                                                             32                  31
shield
RS485 cable
P0253ENa
EARTH
        To Open Data Model manager, click on the icon:                 , select " Schneider Electric "
        then "Data Model Manager" in the "Programs" menu.
                                              Schneider Electric
P12y/EN GS/E95                                                                  Getting Started
      Select the “Add” option to add the new data model then click on the “Next” button.
      The next panel is used to select the model source (CD ROM, local folder or Schneider
      Electric FTP server). Select the model source and click on the “next” button.
1 2
       The Data Model Manager loads data models details, and then displays automatically the
       language selection option panel. Select the menu language(s) and click on the “Next” button.
       The data models panel is displayed. Select the data model for your product (for instance, to
       download P12x data models, open the “Px10/Px20/Px20C/M/Modulex” sub-menu (click on
       “+” then select data model according to your product). When data models are selected, the
       Data Model Manager panel displays the selected models size to download.
                                2
                                                                    3
P12y/EN GS/E95                                                                   Getting Started
Click on “Install button”. The model files are downloaded and updated in the system.
        When installation has been completed, close the Data Model Manager. This Data Model is
        used with MiCOM S1 Studio when a system is opened or created. To open this default
        setting file, refer to § 3.5.8.
                                              Schneider Electric
Getting Started                                                                  P12y/EN GS/E95
Toolbar
Click on the “Quick Connect” button at the top left of the application:
       When a system is opened (or created), the following “device type” window is displayed.
P12y/EN GS/E95                                                          Getting Started
      Upon a successful connection, a dialog will be displayed showing device type, model
      number and plant reference. Options for language, device name and comment are also
      available.
      The device is displayed in the Studio Explorer panel.
Getting Started                                                               P12y/EN GS/E95
        − By default, the window displays the message “create new or open existing system”: click
          on “new” to create a new system.
        − If a system is loaded in the “Studio Explorer” window, right-click on the panel background
          and select New System or select the corresponding icon on Studio Explorer's toolbar.
or
        The following window is displayed: Enter the name of the system, and the path to save the
        system file.
P12y/EN GS/E95                                                                    Getting Started
                 NOTE:        In the Studio Explorer panel, if an item is selected, its properties are
                              displayed in the “Properties” panel.
        Click on “new substation” icon (or select the menu using right-click). The following window is
        displayed:
        The new substation is displayed and the menu bar is updated when a substation is selected.
Getting Started                                                                   P12y/EN GS/E95
                                            Import SCL
                            Create a new voltage level
                  1
                                                              2
2 3
                                                                                   4
Getting Started                                                                   P12y/EN GS/E95
        − If the file is saved or if the relay is not connected: open the Settings folder and open the
          Settings file,
        − If the relay is connected, extract the settings from the relay: click on the “Extract Settings”
          command or right click on the Settings folder.
                                         Extract Settings
P12y/EN GS/E95                                                                  Getting Started
− Select the Model and click on the “Finish” button. The default settings are displayed.
                                  2
Getting Started                                                                    P12y/EN GS/E95
3.6     MiCOM S1
3.6.1   Starting MiCOM S1
                                                              Schneider Electric
P12y/EN GS/E95                                                                     Getting Started
Schneider Electric
Schneider Electric
                 NOTE:        Select the “User Manual” button to read “setting & records” and
                              “Measurement Viewer” description and operating procedures.
       When this has been entered, a prompt for the password appears.
       When these have been entered satisfactorily the relay is then able to communicate with
       MiCOM S1. When a communication link has been established between the PC and a
       MiCOM IED, both are said to be online. Data and information can be directly transferred from
       and to the IED using the menu available under the “DEVICE” menu.
P12y/EN GS/E95                                                                       Getting Started
        For further instruction on how to extract, download and modify settings files, please refer to
        the MiCOM S1 User Manual.
        Select the main function in the right hand window.
        To modify a setting value, double click the corresponding line in the left hand window. It
        opens a setting window.
                                                                                2
3.6.3   Off-line use of MiCOM S1
        As well as being used for the on-line editing of settings, MiCOM S1 can also be used as an
        off-line tool to prepare settings without access to the relay. In order to open a default setting
        file for modification, in the “File” menu, select “New” and then “Settings File…”
Getting Started                                                                  P12y/EN GS/E95
        This brings up a prompt for the relay model type where you can select the correct relay for
        your application:
        Clicking on “OK” will open the default file and you can start to edit settings. For further
        instruction on how to extract, download and modify settings files, please refer to the MiCOM
        S1 User Manual.
3.6.4   MiCOM monitoring
        The monitoring module enables to connect to the front port, retrieve and monitor its
        measurements.
                                                            Schneider Electric
                                                                On line
− In the main page, select the function using the blue arrows ( ),
      − Click on the “presentation and Analysis of Disturbance Recording Data with “Wavewin”
        window.
                                        Schneider
                                            On-li
                                                                              Schneider Electric
                                                                                  On-line
      The Wavewin File Manager is displayed (refer to the Wavewin User’s guide to operate
      Wavewin).
Getting Started                                                            P12y/EN GS/E95
       Depose the four retaining screws in the top and the bottom side of the relay. These screws
       retain the relay to the case.
P12y/EN GS/E95                                                                 Getting Started
      Insert a 3mm screwdriver into the hole situated under the upper hinged cover above the
      LCD:
      Insert the screwdriver into the second hole under the lower hinged cover, and the lower lock
      pin is turned 90° to the right.
      By this turning action, push slightly forward the
      module and extract it by pulling on both sides of the
      front panel.
Getting Started                                                            P12y/EN GS/E95
       − Website: www.schneider-electric.com
P12y/EN GS/E95                         Getting Started
                 BLANK PAGE
Application Guide        P12y/EN AP/E95
         APPLICATION GUIDE
Application Guide                                                         P12y/EN AP/E95
CONTENT
1.       INTRODUCTION                                                                       5
1.1      Protection of Underground and Overhead Lines                                        5
3.       VOLTAGE PROTECTIONS                                                            35
3.1      Setting for the Voltage Connections                                             35
3.2      Consideration on the measurement menu                                           36
3.3      (59N) Zero Sequence Overvoltage Protection (P125, P126 & P127)                  36
3.3.1    Setting Guidelines                                                              36
3.4      (27) Undervoltage Protection (P127)                                             36
3.4.1    Setting Guidelines                                                              37
3.5      (59) Overvoltage Protection (P127)                                              37
3.5.1    Setting Guidelines                                                              38
6.18.2   Settings                                                                        81
6.19     Logic equations (P126 & P127)                                                   82
10.      MEASUREMENTS                                                                   87
10.1     Power and Energy Measurements (P127)                                            87
10.2     Additional measurement CT (P127 optional configuration only)                    88
10.2.1   Frequency                                                                       88
10.2.2   Currents                                                                        89
10.2.3   Voltages                                                                        90
10.2.4   Powers                                                                          90
10.2.5   Energies                                                                        91
10.2.6   Plus and minus signes for power and energy calculation.                         91
13.      CT REQUIREMENTS                                                                95
13.1     Definite time / IDMT overcurrent & earth fault protection                       95
13.2     Instantaneous overcurrent & earth fault protection                              95
13.3     Definite time / IDMT sensitive earth fault (SEF) protection                     95
Application Guide                                                                P12y/EN AP/E95
1.     INTRODUCTION
1.1    Protection of Underground and Overhead Lines
       The secure and reliable transmission and distribution of power within a network is heavily
       dependent upon the integrity of underground cables and overhead lines, which link the
       various sections of the network together. Therefore the associated protection system must
       also provide both secure and reliable operation.
       The most common fault conditions, on underground cables and overhead lines, are short
       circuit faults. These faults may occur between the phase conductors but will most often
       involve one or more phase conductor becoming short-circuited to earth.
       Faults caused by short circuits require the fastest faulted conductor clearance times but at
       the same time allowing for suitable co-ordination with other downstream protection devices.
       Fault sensitivity is an issue common to all voltage levels. For transmission systems, tower-
       footing resistance can be high. Also, high resistance faults might be prevalent where lines
       pass over sandy or rocky terrain. Fast, discriminative faulted conductor clearance is required
       for these fault conditions.
       The effect of fault resistance is more pronounced on lower voltage systems, resulting in
       potentially lower fault currents, which in turn increases the difficulty in the detection of high
       resistance faults. In addition, many distribution systems use earthing arrangements designed
       to limit the passage of earth fault current.
       Earthed methods as such as using resistance, Petersen coil or insulated systems make the
       detection of earth faults arduous. Special protection equipment is often used to overcome
       these problems.
       Nowadays, the supply continuity in the energy distribution is of paramount importance.
       On overhead lines most of faults are transient or semi-permanent in nature.
       In order to increase system availability multi-shot autoreclose cycles are commonly used in
       conjunction with instantaneous tripping elements. For permanent faults it is essential that
       only the faulted section of the network is isolated. High-speed, discriminative fault clearance
       is therefore a fundamental requirement of any protection scheme on a distribution network.
       Power transformers are installed at all system voltage levels and have their own specific
       requirements with regard to protection. In order to limit the damage incurred by a transformer
       under fault conditions, fast clearance of the windings with phase to phase and phase to earth
       faults is a primary requirement.
       Damage to electrical plant equipment such as transformers, cables and lines may also be
       incurred by excessive loading conditions, which leads directly to overheating of the
       equipment and subsequent degradation of their insulation. To protect against such fault
       conditions, protective devices require thermal characteristics too.
       Uncleared faults, arising either from the failure of the associated protection system or of the
       switchgear itself, must also be considered. The protection devices concerned should be
       fitted with logic to deal with breaker failure and relays located upstream must be able to
       provide adequate back-up protection for such fault conditions.
       Other situations may arise on overhead lines, such as broken phase conductors.
       Traditionally, a series fault has been difficult to detect.
       With today's digital technology, it is now possible to design elements, which are responsive
       to such unbalanced system, conditions and to subsequently issue alarm and trip signals.
       On large networks, time co-ordination of the overcurrent and earth fault protection relays can
       often lead to problematic grading situations or, as is often the case, excessive fault
       clearance times. Such problems can be overcome by relays operating in blocked overcurrent
       schemes.
P12y/EN AP/E95                                                                     Application Guide
UAB
IA
UBC
IC IB
                           UCA
                                                                        P0354ENa
        Under system fault conditions, the fault current vector will generally lag its nominal phase
        voltage by an angle dependent on the system X/R ratio.
        It is important that the relay operates with maximum sensitivity for currents lying in this
        region.
Application Guide                                                                               P12y/EN AP/E95
0.5
− Current threshold,
      Fwd: forward
      Rev: reverse
                                                                                       P0356ENb
Application Guide                                                                P12y/EN AP/E95
          Fwd: forward
          Rev: reverse
                                                                                         P0357ENa
         The following figures show the windows where the first phase trip forward and instantaneous
         reverse trip can be assigned to an output relay. The same one is for the 2nd and 3rd stages.
           I> >> >>>                       Interlock of first threshold by the second and third
           Interlock                 Yes   thresholds, but only if first threshold trip is set to IDMT.
                                           Setting choice: No, Yes
         The 2nd and 3rd threshold pickup can suspend 1st threshold output control to save selectivity.
         Below it is shown the trend of the delay trip time of the first threshold in the both cases Yes
         or No.
t t
t_I> t_I>>
t_I>>>
I> t I> t
I>> t I>> t
I>>> t I>>> t
                                                                                                   P0358ENa
Application Guide                                                                          P12y/EN AP/E95
        On the P127 relay, it is possible to set the relay characteristic angle (RCA) or torque angle,
        as it is also called, in the range of 0° to +359° in steps of 1°. The trip boundary zone
        associated to the RCA is settable in the range from ±10° to ±170° in steps of 1°.
        Further information about the setting range for the directional overcurrent protection are
        available in the Technical Data document.
P12y/EN AP/E95                                                                            Application Guide
                                          R1                             R2
                                        P126                           P126
                                        OC/EF                          OC/EF
                                           R3                             R4
                                          P127                           P127
                                                           F
                                         DOC/DEF                        DOC/DEF
                                          OC/EF                          OC/EF
11K
                                 R5
                               P126
                               OC/EF
P0081ENa
                                                                 A
                                                       2,1s
                                                                         51
                                                                                                 0,1s
                                   67                    51            2,1s
                                                                Load
                            F                                                                            B
                                                0,1s
                                                                                   67
                                               Load
                     1,7s                                                        Load                    67
                                                                                          1,7s
                                       67
                                        0,5s
                                                                                           67
                                            Load                                 Load
                        67                                                                                   0,5s
                                               67                                  1,3s
                            E                                 Load                                       C
1,3s 0,9s 67 67
                                                       67                 0,9s
                                                                 D
                                                                                                        P0082ENa
        The 2nd and 3rd threshold pickup can suspend 1st threshold output control to save selectivity
        Below it is shown the trend of the delay trip time of the first threshold in the both cases Yes
        or No.
t t
t_I> t_I>>
t_I>>>
I> t I> t
I>> t I>> t
I>>> t I>>> t
                                                                                                P0358ENa
Application Guide                                                                P12y/EN AP/E95
        Being P127 a three phase directional/non directional relay an overcurrent protection involves
        the P127 used as non directional relay and the P126.
        Some applications can be considered, but for indicative applications it is better to involve the
        blocking logic and selective functions, so an overcurrent application will be shown in the part
        of this TG regarding the blocking logic and selective function.
        The following diagrams show the functionality for each thresholds:
                                                 ≥
                                                                              Inst. I>
P0360ENb
                                                     ≥
                                                                                  Inst. I>>
            IA >>
                                                                                  Trip I>>
            IB >>
                                                     ≥           DT/IDMT
IC >>
≥ Inst. I>>>
IA >>>
                                                        ≥
             IB >>>                                                           Trip I>>>
                                                                    DT
             IC >>>
                                    Backward
                                    tripping zone
           The protection element also provides a non-sensitive area to avoid instability due to small
           asymmetries and unbalances that can generally be present in the network system. This
           condition is represented by the characteristic reproduced below, where the hatched area is
           the tripping zone.
           The tripping zone is limited by the equation Ie +(k x Ue) < (k x 18). (18 is a value derived
           experimentally where stability is guaranteed).
           The K factor is 1, if Ien=1A, 5 if Ien=5A.
 Ie [mA]
     30
             Ue>                                                      Ie [mA]
             Ue>>                                                        100
     25                                                                           Ue>
             Ue>>>                                                                Ue>>
                                                                                  Ue>> >
                               Tripping Zone                              90
     20
                                                                                                     Tripping Zone
                                                                          80
                               Ie + Ue= 18
     15                                                                                              Ie + 5 x Ue= 90
                                                                          60
     10
                                           Ie>                            40
                                           Ie>>                                                               Ie>
      5                                                                                                       Ie>>
                                           Ie>>>                          20                                  Ie>> >
      0         5    10        15     20     25    30                      0
                                                        Ue [V]                      5      10   15      20     25      30
                                                                                                                              Ue [V]
                                                           P0068ENa                                                                P0067ENa
                          Ien=1A                                                                 Ien=5A
           The directional earth fault element needs a suitable voltage supply to provide the necessary
           polarisation. (See the Technical data for further information)
           The polarising signal must be representative of the earth fault condition. As residual voltage
           is generated during earth fault conditions, and this quantity is used to polarise directional
           earth fault elements. The P127 relay can derive this voltage internally from the 3 phase
           voltage inputs when the VT connection option 3Vpn is set. It can also be measured directly
           by a VT transformer when the VT connection option 2Vpp+Vr (two phase to phase) or
           2Vpn+Vr (two phase to neutral) is set.
           The P125 and P126 measures this voltage directly from a broken delta or single VT.
P12y/EN AP/E95                                                                     Application Guide
        The setting ranges for directional/non-directional earth fault and wattmetric protection
        (Pe/IeCos) can be found in the FT and TD chapters of the technical guide.
2.4.2   An application of 67N in an Insulated Systems
        The advantage with an insulated power system is that during a single phase to earth fault
        condition, no high earth fault current will flow. Consequently, it is possible to maintain power
        flow on the system even with an earth fault condition present. However, this advantage is
        offset by the fact that the resultant steady state and transient over-voltages on the healthy
        phases can be very high. In general insulated systems will only be used in low or medium
        voltage networks where it does not prove too costly to provide the necessary insulation
        against such over-voltages.
        Higher system voltages would normally be solidly earthed or earthed via a low impedance.
        Operational advantages may be obtained by the use of insulated systems.
        However, it is still essential that detection of the earth fault condition is achieved. This is not
        possible if standard current operated earth fault protection equipment is used. One possibility
        for earth fault detection is by applying a residual over-voltage protection device. This
        functionality is provided by the MiCOM P125, P126 and P127 relays.
        However, fully discriminative earth fault protection on this type of system can only be
        achieved by earth fault protection element. This protection element is included in directional
        relays MiCOM P125, P126 & P127.
        It is essential that a core balance CT is used for high sensitive earth fault detection. This
        eliminates the possibility of spill current that may arise from slight mismatches between
        residually connected line CTs. It also enables a much lower CT ratio to be applied, thereby
        allowing the required protection sensitivity to be more easily achieved.
Application Guide                                                                     P12y/EN AP/E95
                                  A B C
                                                              Ia1
                                                              Ib1
IR1 -jXc1
                                                                           IH1
                                                              Ia2
                                                              Ib2
IR2 -jXc2
                                                                               IH2
                                                            Ia3
                                                            Ib3
                                                     IH1+IH2+IH3
IR3 -jXc3
                        IR3=-(Ia1+Ib1+Ia2+Ib2)+Ia3+Ib3-(Ia3+Ib3)
                        IR3=-(IH1+IH2)+IH3-IH3                   P0363ENa
       From above figure and the vector diagram below it can be seen that the relays on the
       healthy feeders see the unbalance in the charging currents on their own feeder. The relay on
       the faulted feeder, however, sees the charging current from the rest of the system [IH1 and
       IH2 in this case], with it’s own feeders charging current [IH3] being cancelled out.
UA
UC UB
UAf Vr=3Ve
                                  IH1+IH2    Ib1+Ib2
                       Ia1+Ia2
                           270˚
                                                                    TRIP ZONE
                                   O'                   UBf
                                            IR3=-(IH1+IH2)+IH3-IH3
       Referring to the vector diagram, it can be seen that the C phase to earth fault causes the
       phase voltages on the healthy phases to rise by a factor of        3.
P12y/EN AP/E95                                                                       Application Guide
          The A phase charging current (Ia), is then shown to be leading the resultant A phase voltage
          by 90°. Likewise, the IB phase charging current leads the resultant voltage Vb by 90°.
          The unbalance current detected by a core balance current transformer on the healthy
          feeders can be seen as the vector addition of Ia1 and Ib1 (Ia2 and Ib2), giving a residual
          current which lies at exactly 90° anticipating the polarising voltage (Vr=3Ve).
          The vector diagram indicates that the residual currents on the healthy and faulted feeders,
          IH1& IH2 and IR3 respectively, are in opposite direction to each other (180°). A directional
          element could therefore be used to provide discriminative earth fault protection.
          If the polarising voltage of this element, equal to 3Ve, is shifted through +270°, the residual
          current seen by the relay on the faulted feeder will lie within the operate region (Trip Zone) of
          the directional characteristic. As previously stated, the required RCA setting for the sensitive
          earth fault protection when applied to insulated systems, is 270°.
2.4.3     Wattmetric (Pe) Characteristic
          The P125, P126 and P127 relays include the zero sequence power measurement function.
          They also offer the possibility to choose between a Wattmetric (Pe) protection and IeCos
          (active component of the earth fault current) protection functionality mode.
          The following figure shows the characteristic tripping zone for the wattmetric protection.
Pe/IeCos
Tripping zone
                                                                             Pe> Pe>>
                     5˚                                       5˚             IeCos> IeCos>>
                                                                             Q/IeSin
                                                                                        P0365ENa
          In the following formula the power thresholds in the relay menu are called Pe> & Pe>>.
          The Pe> and Pe>> settings are calculated as:
          Vres x Ires x Cos (f – fc) = 9 x Ve x Ie x Cos (f – fc)
          Where:
                f      = angle between the polarising voltage (Vres) and the residual current
                fc     = relay characteristic angle (RCA/torque angle)
                Vres   = residual voltage
                Ires   = residual current
                Ve     = zero sequence voltage
                Ie     = zero sequence current
2.4.3.1   Setting Guidelines for Pe Thresholds
          The Pe thresholds are displayed in the format: ##.## x Ien W
          In this formula the ##.## setting value is multiplied by the setting value of the Ien.
          The threshold value is expressed in Watt secondary.
          Example: The Pe> threshold is to be set from the relay front panel and the setting value is
                   20W.
Application Guide                                                                   P12y/EN AP/E95
        Ien = 1A, the internal relay setting value will be equal to 20 x 1 = 20W.
        To set the thresholds for the Pe (Wattmetric/IeCos) protection the relay will display the menu
        “Wattmetric Protection \ Pe>” (refer to P12y/EN FT section).
        The same procedure is to be applied for setting the second Pe>> threshold.
        For the settings of the trip delay time see the FT chapter of the TG.
2.4.4   Application Considerations
        The protection Pe> and Pe>> require relay current and voltage connections to be actived.
        The measurement of the Pe depends on the voltage wiring of the relay.
        In case of 3Vpn wiring the Ve will be equal to Ve= 1/3(Va+VB+VC) in the other insertions
        way the applied voltage to the relay is directly used to calculate the Pe.
        Referring to the relevant application diagram for the P125, P126 and P127 relays, it should
        be installed such that its direction for forward operation is 'looking into' the protected feeder
        i.e. away from the busbar, with the appropriate RCA .
        As illustrated in the relay application diagram, it is usual for the earth fault element to be
        driven from a core balance current transformer. This eliminates the possibility of spill current
        that may arise from slight mismatches between residually connected line CTs. It also
        enables a much lower CT ratio to be applied, thereby allowing the required protection
        sensitivity to be more easily achieved.
2.4.5   Iecos protection
        The Iecos protection follows the same concepts of the Pe protection.
        The difference is that the thresholds take in account the active component of the earth fault
        current.
        The setting of the RCA follows the above listed table.
IA
IB
IC
IA+IB+IC = Ie>>>>
Ie = Tank Earth
P3940ENa
      As soon as Ie>>>> threshold is running, the instantaneous output associated with this
      threshold is activated. This output indicates that the protection element has detected an
      earth fault and that the time delay associated with the threshold has started. This time delay
      can be blocked via the logic input "Block Logic" associated with this threshold. If this blocking
      input is activated by an output contact of a downstream relay, the logic that will lead to the
      trip command is then blocked only if the relay that is the closest to the fault can see and
      therefore eliminate the fault. This principle is known as «Blocking logic» or «Blocking». It is
      described in more detail in this document.
Application Guide                                                                                P12y/EN AP/E95
t t
t_I> t_I>>
t_I>>>
I> t I> t
I>> t I>> t
I>>> t I>>> t
P0358ENa
        Flexible connection arrangements allow for phase to phase or phase to ground connection of
        the polarising voltage, a wide range of angle settings allows the relay to operate for Watts or
        Vars, Import or export.
        The VT inputs for the MiCOM P125 relay are rated 57 to 130 Vac or 220 – 480 Vac
        (Selected at time of order) these ranges make the relay suitable for connection to a VT
        secondary or direct connection to a 415V systems.
2.6.2   Relay Connection
        The relay setting angle which is discussed in further detail below allows the user to
        customise the VT connection to suit the primary plant, available VT secondaries and the
        protection philosophy of the customer.
        The VT connection can be made phase to phase or phase to ground using the connection
        table below.
        For simplicity the connection has been made so as a reverse power setting will require an
        angle of 180 degrees.
        One of the possible line CT connection is shown below, The CT input can be connected to
        any available phase CT, (A, B or C).
Application Guide                                                                 P12y/EN AP/E95
Pe/IeCos
Tripping zone
                                                                        Pe> Pe>>
                     5˚                                 5˚              IeCos> IeCos>>
                                                                        Q/IeSin
                                                                                  P0365ENa
P12y/EN AP/E95                                                                   Application Guide
                                                     ⎛ −t ⎞
                                                     ⎜ ⎟
                                                    e⎝ τ ⎠    =
                                                                  (I   2
                                                                           − (k × I FLC )2        )
                                                                            (I   2
                                                                                     − I 2p   )
        Where:
                t          =    Time to trip, following application of the overload current, I
                τ          =    Heating and cooling time constant of the protected plant equipment
                I          =    Largest phase current
                IFLC       =    Full load current rating (relay setting ‘Thermal Trip’)
                k          =    1.05 constant, allows continuous operation up to < 1.05 IFLC
                IP         =    Steady state pre-loading current before application of the overload
        The time to trip varies depending on the load current carried before application of the
        overload, i.e. whether the overload was applied from “hot” or “cold”.
        Curves of the thermal overload time characteristic are given in Technical Data.
2.7.2   Mathematical Formula Applicable to MiCOM Relays:
        The calculation of the Time to Trip is given by:
                       ⎛ Ix 2 − θ           ⎞
        t Trip = Te In ⎜                    ⎟
                       ⎜ Ix 2 − θtrip       ⎟
                       ⎝                    ⎠
        With:
             t Trip    =       Time to trip (in seconds)
             Te        =       Thermal time constant of the equipment to be protected (in seconds)
             Ix        =       Thermal overload equal to Ieq/k Iθ >
             Ieq       =       Equivalent current corresponding to the RMS value of the largest
                               phase current
             Iθ >      =       Full load current rating given by the national standard or by the supplier
             k         =       Factor associated to the thermal state formula
             θ         =       Initial thermal state. If the initial thermal state = 30% then θ = 0.3
             θtrip     =       Trip thermal state. If the trip thermal state is set at 100%, then θ trip = 1
        The settings of these parameters are available in the various menus.
        The calculation of the thermal state is given by the following formula:
                                                                       2⎡          ⎛ −t ⎞ ⎤
                                                                                   ⎜ ⎟
                                                                                                    ⎛ −t ⎞
                                                                                                    ⎜ ⎟
                                                     ⎛ I eq ⎞              ⎢1 − e ⎜⎝ Te ⎟⎠ ⎥ + Θ e ⎜⎝ Te ⎟⎠
                                         Θ τ +1   = ⎜⎜          ⎟
                                                                ⎟          ⎢               ⎥    τ
                                                     ⎝ k × IΘ > ⎠          ⎢⎣              ⎥⎦
        Thermal Trip (θtrip) = Permissible continuous loading of the plant equipment / CT ratio.
        Typical time constant values are given in the following tables.
        The relay setting, ‘Time Constant’, is in minutes.
        Paper insulated lead sheathed cables or polyethylene insulated cables, placed above ground
        or in conduits. The table shows τ in minutes, for different cable rated voltages and conductor
        cross-sectional areas:
        An alarm can be raised on reaching a thermal state corresponding to a percentage of the trip
        threshold. A typical setting might be ‘Thermal Trip’ = 70% of thermal capacity.
2.8     Undercurrent Protection (P126 & P127)
        The undercurrent function [37] makes it possible to detect a loss of load (for example the
        draining of a pump or breakage of a conveyor belt). It uses definite delay time undercurrent
        protection.
        The user can set the following parameters:
        This section describes how negative phase sequence overcurrent protection may be applied
        in conjunction with standard overcurrent and earth fault protection in order to alleviate some
        less common application difficulties.
        −     In certain applications, residual current may not be detected by an earth fault relay
              due to the system configuration. For example, an earth fault relay applied on the delta
              side of a delta-star transformer is unable to detect earth faults on the star side.
              However, negative sequence current will be present on both sides of the transformer
              for any fault condition, irrespective of the transformer configuration. Therefore, a
              negative phase sequence overcurrent element may be employed to provide time-
              delayed back-up protection for any un-cleared asymmetrical fault.
        −     Where fuses protect motors on rotating machines, a blown fuse produces a large
              amount of negative sequence current. This is a dangerous condition for the motor due
              to the heating effects of negative phase sequence current at double frequency. A
              negative phase sequence overcurrent element may be applied to provide efficient
              back-up protection for dedicated motor protection relays.
        −     It may also be required to simply set an alarm at the presence of negative phase
              sequence currents on the system. Operators are then prompted to investigate the
              cause of the unbalance.
        The negative phase sequence overcurrent elements have a current pick up settings I2>,
        I2>>, I2>>>, and are time delayed in operation by the adjustable timers tI2>, tI2>>, tI2>>>.
2.9.1   I2 Thresholds Setting Guidelines
        This protection element includes three thresholds.
        The first threshold can be set as DT or IDMT trip delay time.
        The curves are the same as for the [50/51], [50N/51N] protection.
        The current pick-up threshold (settable in the menu PROTECTION G1/[46] Neg. Seg. OC)
        must be set higher than the normal negative phase sequence current due to the normal load
        unbalance that is always present on the system. This can be set at the commissioning stage,
        making use of the relay measurement function to display the standing negative phase
        sequence current, and apply a setting at least 20% above.
        Where the negative phase sequence element is required to operate for specific un-cleared
        asymmetric faults, a precise threshold setting has to be based on an individual fault analysis
        for that particular system due to the complexities involved. However, to ensure operation of
        the protection element, the current pick-up setting must be set approximately 20% below the
        lowest calculated negative phase sequence fault current for a specific remote fault condition.
        The correct setting of the time delay is vital for this protection element. It should be also seen
        that this element is applied primarily to provide back-up protection to other protective devices
        or to provide an alarm. Therefore, it would be associated with a long delay time.
        It must be ensured that the time delay is set longer than the operating time of any other
        protective device (at minimum fault level) on the system, which may respond to unbalanced
        faults, such as:
                   Healthy CT                                                   Saturated CT
                                                   Protected
                                                     circuit
                       Zm                                                           Zm         A-G
RCT1 RCT2
                                                            IF
                                       R L1                       R L3
                                              VS           R ST
R L2 R R L4
                                                                                  C
                                                          STAB
                                                                                  E/F Input
P0343ENa
         Current setting should be selected for a high impedance element so that the primary current
         reaches its nominal current with a given CT, according to the following equation:
         Is < {(Iop / CTRatio) - n.Ie}
P12y/EN AP/E95                                                                     Application Guide
         It is also possible to determine the maximum inrush current of the CT to reach a specific
         primary operating current with a given relay setting.
         The setting of the stabilising resistor must be calculated according to the above formula,
         where the setting depends on the required stability voltage setting Vs and the relay setting Is.
         Vs k If (RCT+2RL)
            =
         Is        IS
         with:
         K= 1 for Vk/Vs less or equal to 16 and
         K= 1.2 for Vk/Vs > 16.
         So:
                 k If (RCT+2RL)
         RST =
                        Ie>
         with Vk ќ 4.Is.RST (A typical value to ensure the high speed operation for an internal fault).
         CT requirements for High Impedance Restricted Earth Fault Protection
         The High Impedance Restricted Earth Fault element shall remain stable for through faults
         and operate in less than 40ms for internal faults provided that the following equations are
         met in determining CT requirements and the value of the associated stabilising resistor:
                 Rs      =    [k* (If) * (RCT + 2RL)] / IS
                 VK      ≥    4 * Is * Rs
         with:
         K= 1 for Vk/Vs less or equal to 16 and
         K= 1.2 for Vk/Vs > 16.
2.10.4   Use of METROSIL non linear resistors
         Metrosils are used to limit the peak voltage developed by the current transformers under
         internal fault conditions, to a value below the insulation level of the current transformers,
         relay and interconnecting leads, which are normally able to withstand 3KV peak.
         The following formula should be used to estimate the peak transient voltage that could be
         induced by an internal fault. This peak voltage depends on:
− CT ratio
Where:
− Vf: maximum voltage that would be produced if CT saturation did not occur
       V = C.I0.25
       Where:
              −    Vs(rms): RMS value of the sinusoidal voltage applied across the Metrosil.
       This is due to the fact that the current waveform through the Metrosil is not sinusoidal but
       appreciably distorted.
       For satisfactory application of the non-linear resistor (Metrosil), its characteristics should
       comply with the following requirements:
              −    At the relay voltage setting, the non-linear resistor (Metrosil) current should be as
                   low as possible, but no greater than approximately 30mA rms for 1A current
                   transformers and approximately 100mA rms for 5A current transformer.
              −    At the maximum secondary current, the non-linear resistor (Metrosil) should limit
                   the voltage to 1500V rms or 2120V peak for 0.25 second. At higher relay voltage
                   settings, it is not always possible to limit the fault voltage to 1500V rms, so higher
                   fault voltage may have to be tolerated.
       The following tables show the typical types of Metrosil that will be required, depending on
       relay current rating, REF voltage setting etc.
P12y/EN AP/E95                                                                      Application Guide
− At the relay voltage setting, the Metrosil current should be less than 30mA rms.
          −      At the maximum secondary internal fault current, the Metrosil unit should limit the
                 voltage to 1500V rms if possible.
          The Metrosil units normally recommended to be used with 1Amp CTs are shown in the
          following table:
                    NOTE:          Single pole Relay Metrosil Units are normally supplied without
                                   mounting brackets unless otherwise specified by the customer.
          Metrosil units for relays with 5A CT
          These Metrosil units have been designed to comply with the following requirements:
          −      At the relay voltage setting, the Metrosil current should be less than 100mA rms (the
                 actual maximum currents passed by the units shown below their type description)
          −      At the maximum secondary internal fault current the Metrosil unit should limit the
                 voltage to 1500V rms for 0.25 second. At the higher relay settings, it is not possible to
                 limit the fault voltage to 1500V rms, hence higher voltage have to be tolerated
                 ( indicated by * ,** , *** ).
          The Metrosil units normally recommended for the used with 5 Amps CTs and single pole
          relays are shown in the following table:
Amps rms          Up to 200V rms          250V rms              275V rms              300V rms
                  600A/S1/S1213           600A/S1/S1214         600A/S1/S1214         600A/S1/S1223
50A               C= 540/640              C= 670/800            C= 670/800            C= 740/870*
                  35mA rms                40mA rms              50mA rms              50mA rms
                  600A/S2/P/S1217         600A/S2/P/S1215       600A/S2/P/S1215       600A/S2/P/S1196
100A              C= 470/540              C= 570/670            C= 570/670            C= 620/740*
                  35mA rms                75mA rms              100mA rms             100mA rms
                  600A/S3/P/S1219         600A/S3/P/S1220       600A/S3/P/S1221       600A/S3/P/S1222
150A              C= 430/500              C= 520/620            C= 570/670**          C= 620/740***
                  100mA rms               100mA rms             100mA rms             100mA rms
3.     VOLTAGE PROTECTIONS
3.1    Setting for the Voltage Connections
       For the P127, it is important to select the VTs configuration and VT protection in the
       Configuration/ General Options/ VT Connection and VT protection submenu in according to
       the relay wiring for a corrected functionality of the voltage protections.
       Protection thresholds are not automatically converted when the protection mode is modified;
       they are directly expressed into the set protection mode. So, if the protection mode is
       modified, the thresholds have to be recalculated. For example, to keep the same protection
       level when the mode is converted from P-P to P-N, it is necessary to divide thresholds by √3.
       In the above mentioned is menu you will find that for the P127 relay there are three
       configurations of VTs.
       1.   3Vpn (Three phase-neutral connection):
       In this configuration, the relay directly measures Ua, Ub, and Uc and calculates internally the
       zero sequence voltage Ue = (1/3)[Ua+Ub+Uc]. This internal value Ue will be used to be
       compared to the threshold of Ue (the Earth Overvoltage Protection threshold and to evaluate
       the angle with the earth current for the earth fault directional protection). However, none UN
       is displayed in the measurement Menu.
       2.   2Vpn + Vr (Two phase-neutral plus an Open Delta connection):
       In this configuration, the relay directly measures Ua and Ub. The input voltage of phase C of
       the relay (terminals 73-74) which is connected to the summation of the three voltage phases
       is used to be compared to the Ue (The earth Overvoltage Protection function threshold). This
       voltage at C input is considered as Ur and it is displayed in the measurement menu as UN.
       Moreover for the phase Overvoltage and Undervoltage protection functions, the phase C
       voltage value Uc is internally reconstituted using the equation:
       −     Uc = Ua+Ub+Ur. This value will be compared to the U/V or O/V threshold in case of a
             fault in phase C. Uc is not displayed in the measurement menu,
       −     two used for the phase voltage Ua and Uc and the others used in Open delta
             configuration for the Ur.
       BE CAREFUL: IF THE Ur IS MEASURED FROM A SEPARATE TRANSFORMER THE
                   ABOVE RECONSTRUCTION IS NOT VALID AND CAN NOT BE USED.
       3.   2Vpp + Vr (Two phase-phase plus an Open Delta connection):
       The relay directly measures Uab and Ubc, the phase to phase (A-C) voltage value Uca is
       internally reconstituted using the equation Uca=Uab+Ubc.
       The third input of voltage of the relay (terminals 73-74) can be connected to the output of a
       delta transformer or to a dedicated voltage transformer, the measured value can be used to
       compare to the earth overvoltage threshold.
       This voltage is displayed in the measurement menu as UN and it is designed as the earth
       voltage.
       4.   VT Protection:
       This setting is only available for 3VPN or 2VPN+Vr connection:
       −     If “VT Protection” = “Protect P-P”, threshold (P-P voltage) is the P-N threshold
             multiplied by √3 to match to wished physical thresholds. Example: U> flag will be
             activated for measured P-N voltage higher than 57V, if threshold = 100V.
       −     if "VT Protection" = "Protect P-N", set thresholds are P-N voltages, and effective
             thresholds used for protections algorithm are set thresholds multiplied by √3. Example:
             U> flag will be activated for measured P-N voltage higher than 57V, if threshold = 57V.
P12y/EN AP/E95                                                                     Application Guide
        Normally, there will be a relay with a primary protection element employed to detect the earth
        fault condition and to issue a trip command if the fault is non-cleared after a nominal time.
        However, in this instance it would be possible to use a relay with an over-voltage protection
        element as back-up protection. Sufficient would be a single stage of protection, having a
        definite delay time.
3.5.1   Setting Guidelines
        The relay with this type of protection element must be co-ordinated with any other over-
        voltage relay at other locations on the system. This should be carried out in a similar manner
        to that used for grading current operated protection devices.
        The protection element over-voltage has two programmable thresholds and two delay timers,
        tU>, tU>>.
        After a trip command the thresholds will be reset when all phase voltages have fallen below
        95% of setting values.
        The overvoltage protection element, which can be set as OR or AND logic, operates by
        comparing each UAB, UBC and UCA voltage input with the U>, U>> thresholds.
                 NOTE:       If the relay is connected in the mode 3Vpn to control the phase to
                             neutral voltages, the thresholds must be multiplied by   3.
        When OR operating logic is set and one or more voltage has risen above the threshold
        value, the tripping command is sent after the tripping timer has reached the set overtime
        condition.
        When AND operating logic is set and all of the voltage values have risen above the threshold
        value, the tripping command is sent after the tripping timer has reached the set overtime
        condition.
        Information as to the thresholds setting range can be found in the FT and TD parts of the
        technical guide.
Application Guide                                                                     P12y/EN AP/E95
        −     if the voltage level for each phase is below the settable undervoltage blocking value
              (see “Prot. Freq. Block U<” cell),
− if the frequency is out of range: fmeasured > (fn+20Hz) or fmeasured < (fn–20Hz),
                                                                             fii -- 12 - fii -- 32
                                                               df /dti - 1 =
                                                                             ti - 1 - ti - 2
                                                                             fi - fi - 1
                                                              df /dti =
                                                                             ti - ti - 1
                                                                                  fi + 1 - fi
                                                               df /dti + 1 =
                                                                                  ti + 1 - ti
                                                                                                     P0399ENa
        The rates of change of frequency are calculated every cycle based upon zero crossing.
                      NOTE:           To be insensitive to the phase shift and vector jumps, we can reject all
                                      measurements of dF/dt greater than 20Hz/s.
Application Guide                                                                                             P12y/EN AP/E95
    CONFIGURATION
            General Options
               dF/dt Cycles.nb = 3             1            2           3
     dF/dt Cycles.nb
                                  3
    CONFIGURATION
            General Options
                                        At the end of the three instantaneous dF/dt
               dF/dt Validat.nb = 2     measurement cycle, the first average value
                                        is calculated.and compared to the dF/dt
     dF/dt Validat.nb                   threshold set in the 'Protection / [81R] Freq.                      PROTECTION
                                 2      change of rate / dF/dt1' menu.                             [81R] Freq. rate of change
                                                             df/dt1 + df/dt 2 + df/dt3
                                         dF / dtaverage1 =                                               dF/dt 1 =
                                                                         3
     CONFIGURATION
                                                1            2           3                df/dt1         df/dt2         df/dt3
            General Options
               dF/dt Cycles.nb = 3
                                                        dF/dtaverage1                      1               2              3
               dF/dt Validat.nb = 2                                          Validation
P3974ENa
        −        will be validated when dF/dtaverage1 and dfF/dtaverage2 exceed df/dt1 setting value
                 (protection menu).
        −        will not be validated when only one of the average value exceeds df/dt1 setting value.
                      NOTE:           The rate of change of frequency is available when voltage inputs are
                                      connected.
P12y/EN AP/E95                                                                                                                                         Application Guide
P Q
                                                     Trip                                                                                      Tri
                                                            zon                                                                                    p   zo
                                                                  e                                                                                         ne
                                                                                                         Q<
                                                                                                            an
        P<                                                                                                    dQ
             and                                                      Directional                               << T                                             Angle
                   P<<                                                                                              rip
                                                                      Angle                                                zo
                               Trip                                                                                             ne
                                      zon
                                            e
                                                                                                                 2°                  0
                                                0
                         2°
                                                             270                                                                                270
                               90                                                                                     90
                                                                                                  Q                                                                                           P
                                                                          2°
                                                                                                                                                                 2°
                                                    180                                                                                  180
         Directional Active Over / Under protection                                                   Directional Reactive Over / Under protection
                                                                                                                                                                                  P3969ENa
                                                                       “P> “100x 5W” if the secondary of the CT = 5A, and the setting of P> = 500W
Application Guide                                                                               P12y/EN AP/E95
          Example1:
          VT connection = 3Vpn
          CT Ratio = 100A / 1A
          VT Ratio = 2kV / 100V
          I = 10A primary = 100mA secondary injected on the 3 phases,
          V = 1155V primary = 57.7V secondary injected on the 3 phases
          Phase Difference = 0 degrees
          P= 57.7 x 0.1 cos (0) + 57.7x 0.1 cos (0) + 57.7 x 0.1 cos (0) = 17.3 W sec
          or 17.3 x CT Ratio x VT Ratio x K (K= CT 1A or 5A) = 17.5 x 100 X 20 x 1 = 35000 W
          Primary
                                                   P
                                      P" =
                                             3.KI ⋅ KU ⋅ Un
                                                                InTA ⋅ UnTV
                                     P ' = InTA ⋅ UnTV ⋅ P" =                  P
                                                                3.KI ⋅ KU ⋅ Un
where:
where In and Un are respectively the nominal current and voltage to the secondary side
                                                  Q
                                    Q" =
                                             3.KI ⋅ KU ⋅ Un
                                                                 InTA ⋅ UnTV
                                    Q ' = InTA ⋅ UnTV ⋅ Q" =                    Q
                                                                3.KI ⋅ KU ⋅ Uan
P12y/EN AP/E95                                                                  Application Guide
where:
                                          Analogue Input
                              CT Range (A)       VT Range (V)                       P
          P127AA              0.1 – 40           57 – 130           1 – 10000xk W with k = 1 or 5 A
          P127AB                                 220 - 480          4 – 40000xk W with k = 1 or 5 A
          P127BA              0.01 – 8           57 – 130           1 – 10000xk W with k = 1 or 5 A
          P127BB                                 220 - 480          4 – 40000xk W with k = 1 or 5 A
          P127CA              0.002 – 1          57 – 130           1 – 10000xk W with k = 1 or 5 A
          P127CB                                 220 - 480          4 – 40000xk W with k = 1 or 5 A
Application Guide                                                                                    P12y/EN AP/E95
       −              the remaining 10-20% of faults are either non-permanent (arcing fault) or permanent.
       A transient fault is a self-clearing ‘non-damage’ fault. This type of fault can be isolated and
       cleared by the immediate tripping of one or more circuit breakers, and does not recur when
       the line is re-energised. The most common cause of transient faults are lightning, insulator
       flashover clashing conductors and wind blown debris.
       The immediate trip will not clear a non-permanent or permanent fault, and the use of the
       recloser may be necessary to clear it. A small tree branch falling on the line could cause a
       non-permanent fault. Permanent faults could be broken conductors, transformer faults, cable
       faults or machine faults that must be located and repaired before the supply can be restored.
       Most of the time, if the faulty line is immediately tripped, and the fault arc has sufficient time
       to de-ionise, reclose of the circuit breakers will result in the line being successfully re-
       energised. Autoreclose schemes are used to automatically reclose a switching device once a
       time delay has elapsed and starting after the CB has opened.
       On HV and MV distribution networks, the autoreclose function is applied mainly to radial
       feeders where system stability problems do not generally arise. Using the autoreclose
       minimises time of interruption and reduces operating costs.
       Automatic autorecloser allows a substation to operate unattended:the number of visits to
       manually reclose a circuit breaker is substantially reduced. This feature constitutes therefore
       an important advantage for substations supervised remotely.
       On circuits using time graded protection, the automatic autorecloser allows the use of
       instantaneous protection to give a high speed first trip. With fast tripping, the duration of the
       power arc resulting from an overhead line fault is reduced to a minimum, thus lessening the
       chance of damage and to develop the transient fault into a permanent fault.
       Using short time delay protection prevents blowing of fuses and reduces circuit breaker
       maintenance by eliminating pre-arc heating when clearing transient faults.
       The next figure shows an example of 4 autoreclose cycles (maximum numbers of allowed
       cycles) to the final trip (in the following diagram, td1, td2, td3, td4 = dead time 1, 2, 3 and 4
       timers, tr = Reclaim time, O = CB open and C = CB closed).
                 Current
O C O C O C O C O final trip
I threshold
                                                                                                     Time
                           Fault                                                                               P0031ENa
        When short time delay protection is used with autoreclose, the scheme is normally arranged
        to block the instantaneous protection after the first trip. Therefore, if the fault persists after re-
        closing, time-graded protection will give discriminative tripping with fuses or other protection
        devices, resulting in the isolation of the faulted section. However, for certain applications,
        where the majority of the faults are likely to be transient, it is not uncommon to allow more
        than one instantaneous trip before the instantaneous protection is blocked.
        Some schemes allow a number of re-closings and time graded trips after the first
        instantaneous trip, which may result in the burning out and clearance of non-permanent
        faults. Such an approach may also be used to allow fuses to operate in teed feeders where
        the fault current is low.
        Any decision to apply the autoreclose function would be influenced by all data known on the
        frequency of transient faults (for instance feeders which consist partly of overhead lines and
        partly of underground cables). When a significant proportion of the faults are permanent, the
        advantages of autoreclose are small, particularly since re-closing on to a faulty cable is likely
        to aggravate the damage.
5.2     Description of the function
5.2.1   Autorecloser activation
        The autoreclose function is activated using “AUTOMAT. CTRL/ PROTECTION G1” menu.
        The same settings apply for the Menu PROTECTION G2.
        The autoreclose function of the relay is available only if the following conditions are verified:
        −       The auxiliary contact of the CB status 52a must be connected to the relay.
                Refer to the “AUTOMAT. CTRL/Inputs” menu
        −       The trip output relay RL1 must not be latched to the earth and/or phase protection
                function.
                Refer to the “AUTOMAT. CTRL/Latch functions” menu
                   NOTE:         If the auxiliary supply is lost during an autoreclose cycle, the
                                 autoreclose function is totally disabled.
        In addition to Autoreclose settings, the user will be able to fully link the autoreclose function
        to the protection function using the menus “PROTECTION G1/Phase OC” and
        “PROTECTION/E/Gnd”.
5.2.2   Logic Inputs
        The autoreclose function has four inputs that can be assigned to the autoreclose logic.
        These inputs can be opto-isolated inputs configured for that under the “AUTOMAT. CTRL”
        menu. External contacts can then be wired to be used as an input and influence the
        autorecloser scheme. These 4 inputs are:
− Autoreclose in progress,
− The fact that the CB doesn’t open after tBf delay (CB Fail),
P0906ENa
        −     Supply continuity - Large reclaim times can result in unnecessary lockout for transient
              faults.
        −     Fault incidence/Past experience - Small reclaim times may be required where there is
              a high incidence of lightning strikes to prevent unnecessary lockout for transient faults.
        −     Charging time of the spring or resetting of electromagnetical induction disk relay - For
              high speed autoreclose, the reclaim time may be set longer than the spring charging
              time to ensure that there is sufficient energy in the circuit breaker to perform a trip-
              close-trip cycle. For delayed autoreclose, this setting is of no need as the dead time
              can be extended by an extra CB healthy check window time if there is insufficient
              energy in the CB. If there is insufficient energy after the check window time the relay
              will lockout.
        −     Switchgear Maintenance - Excessive operation resulting from short reclaim times can
              mean shorter maintenance periods. A minimum reclaim time of 5s may be needed to
              give sufficient time to the CB to recover after a trip and close before it can perform
              another trip-close-trip cycle.
        The reclaim time must be long enough to allow any time delayed protection leading to
        autoreclose to operate. Failure to do so can cause the autoreclose scheme to reset too soon
        and the reactivation of the instantaneous protection.
        If that were the case, a permanent fault would look like some transient faults, caused by
        continuous autorecloses. Applying a protection against excessive fault frequency lockout is
        an additional precaution that can solve this problem.
        It is possible to obtain short reclaim times to obtain less lockouts of the CB by blocking the
        reclaim time from the protection start signals. If short reclaim times are to be used, then the
        switchgear rating may dictate the minimum reclaim time.
        Sensitive earth fault protection is used to detect high resistance earth faults. The time delay
        of such protections is usually a long time delay, typically about 10-15s. If autoreclose is
        generated by the SEF protection, this timer must be taken into account when deciding the
        value of the reclaim time, if the reclaim time is not blocked by an SEF protection start signal.
        Sensitive earth faults, caused by a broken overhead conductor in contact with dry ground or
        a wood fence are rarely transient faults and may be dangerous to people.
        It is therefore common practice to block the autoreclose using the sensitive earth fault
        protection and lockout the circuit breaker.
        Where motor-wound spring closed circuit breakers are used, the reclaim time must be at
        least as long as the spring winding time for high speed autoreclose to ensure that the
        breaker can perform a trip-close-trip cycle.
        A typical 11/33kV reclaim time is 3-10 seconds, this prevents unnecessary lockout during
        thunderstorms. However, times up to 60-180 seconds maybe used.
Application Guide                                                          P12y/EN AP/E95
          To achieve “autoreclose only” setting, external start should be wired on a digital input. This
          digital input should be assigned to tAux1 and/or tAux2.
          Within Autorecloser menu, both “strip and start” and “inhib trip” should be selected for tAux1
          and/or tAux2.
P12y/EN AP/E95                                                                  Application Guide
To avoid any trip when tAux is ON, ensure that tAux is not selected in trip command menu.
       general dead times of 3 - 10 seconds are normally satisfactory, but there may be special
       cases for which additional time is required to permit the resetting of manual controls and
       safety devices.
       Loss of supply to lighting circuits, such as street lighting may be important for safety reasons
       as intervals of 10 seconds or more may be dangerous for traffic. The main considerations of
       supply interruptions for domestic customers are those of inconvenience.
       An important measurement criterion for many power utilities is the number of minutes lost
       per year to customers, which will be reduced on feeders using autoreclose and will also be
       affected by the dead time settings used.
       For high-speed autoreclose the minimum dead time of the power system will depend on the
       minimum time delays imposed by the circuit breaker during a tripping and re-closing
       operation.
       Since a circuit breaker is a mechanical device, it will have an inherent contact separation
       time. The operating time for a modern circuit breaker is usually within the range of 50 - 100
       ms, but could be longer with older designs.
       After tripping, time must be allowed for the mechanism to reset before applying a closing
       pulse. This resetting time will vary depending on the circuit breaker, but is typically 0.1
       seconds.
       Once the circuit breaker has reset, it can begin to close. The time interval between the
       energizing of the closing mechanism and the making of the contacts is termed the closing
       time. Owing to the time constant of a solenoid closing mechanism and the inertia of the
       plunger, a solenoid closing mechanism may take 0.3 s. A spring-operated breaker, on the
       other hand, can close in less than 0.2 seconds.
       Where high-speed re-closing is required, which is true for the majority of medium voltage
       applications, the circuit breaker mechanism itself dictates the minimum dead time. However,
       the fault de-ionizing time may also have to be considered. High-speed autoreclose may be
       required to maintain stability on a network with two or more power sources. For high-speed
       autoreclose the system disturbance time should be minimized by using fast protection, <50
       ms, such as distance or feeder differential protection and fast circuit breakers <100 ms. Fast
       fault clearances can reduce the required fault arc de-ionizing time.
       For stability between two sources a dead time of <300 ms may typically be required. When
       only considering the CB the minimum system dead time is given by the mechanism reset
       time plus the CB closing time. Thus, a solenoid mechanism will not be suitable for high-
       speed autoreclose as the closing time is generally too long.
       For high-speed autoreclose the fault de-ionizing time may be the most important factor when
       considering the dead time. This is the time required for ionized air to disperse around the
       fault position so that the insulation level of the air is restored. This can be approximated from
       the following formula:
                          ⎛         Vsys ⎞     1
       De-ionizing time = ⎜10.5 +        ⎟×          [s] (Vsys = System voltage in kV)
                          ⎝         34.5 ⎠ frequency
          −     Supply continuity - long reclaim times can result in unnecessary lockout for transient
                faults.
          −     Fault incidence and past experience - short reclaim times may be required where
                there is a high incidence of lightning strikes to prevent unnecessary lockout for
                transient faults.
          −     Spring charging time - for high-speed autoreclose the reclaim time may be set longer
                than the spring charging time to ensure there is sufficient energy in the circuit breaker
                to perform a trip-close-trip cycle. For delayed autoreclose there is no need to set the
                reclaim time longer than the spring charging time as the dead time can be extended
                by an extra CB healthy check window time if there is insufficient energy in the CB. If
                there is insufficient energy after the check window time has elapsed the relay will
                lockout.
          −     Switchgear maintenance - excessive operation resulting from short reclaim times can
                mean shorter maintenance periods. A minimum reclaim time of >5 s may be needed to
                allow the CB time to recover after a trip and close operation before it can perform
                another trip-close-trip cycle. This time will depend on the duty (rating) of the CB.
          −     The reclaim time must be long enough to allow any time-delayed protection initiating
                autoreclose to operate. Failure to do so would result in premature resetting of the
                autoreclose scheme and re-enabling of instantaneous protection.
          −     If this condition arose, a permanent fault would effectively look like a number of
                transient faults, resulting in continuous autoreclose operations unless additional
                measures were taken to overcome this, such as excessive fault frequency lockout
                protection.
          −     A sensitive earth fault protection is usually applied to detect high resistance earth
                faults.
                Usually, a long trip delay time is set, typically 10 - 15 s. This longer time may be taken
                into consideration, if autoreclose is started by an earth fault protection, and when
                deciding on a reclaim time, if the reclaim time is not blocked by a SEF protection start
                signal. Sensitive earth faults, for example, a broken overhead conductor in contact
                with dry ground or a wood fence, is rarely transient and presents great danger to
                persons and animals. It is therefore common practice to block autoreclose by
                operation of sensitive earth fault protection and lockout the circuit breaker.
          −     Where motor-wound spring closed circuit breakers are used, the reclaim time must be
                at least as long as the spring winding time for high-speed autoreclose to ensure that
                the breaker can perform a trip-close-trip cycle.
          We suppose to have the following settings for the protection and the ARC narrow to the
          configuration matrix. All the others have to be compliance with the rules above.
Application Guide                                                                   P12y/EN AP/E95
                       67 protection
       I> ON                  I>> ON
       I> 8 In                I>> 10 In
       tI> 5 sec.             tI>> 0 sec
                    AUTORECLOSE
                    (only the matrix)
       ARC cycles                      4321
       AR init tI>                     0110
       ARC cycles                      4321
       AR init tI>>                    0021
       ARC cycles                      4321
       AR init tI>>>                   0000
       ARC cycles                      4321
       AR init tAux1                   0000
       Number of phase                    1
       cycles
       3.   tD1 in progress.
       4.   tD1 is expired.
       5.   Closing of the CB and start of the tR.
            Due to the setting of the ARC the I>> will start but won’t generate a trip. During the
            delay trip time of the I> the fault will be cleared for the breaking of the fuse or for the
            auto-extintion of the fault.
P12y/EN AP/E95                                                              Application Guide
      The above one is an example to show a basic using of the “2” setting in the ARC function.
Application Guide                                                                  P12y/EN AP/E95
       tReset timer defines the minimum duration of overcurrent threshold inhibition (0-2s, settable).
       This timer starts as soon as operating inrush current threshold picks up:
       − If inrush condition duration is smaller than tReset setting value, selected overcurrent
         function will remain inhibited during tReset,
       − If inrush condition duration is longer than tReset setting value, selected overcurrent
         function will be inhibited as long as inrush condition remains valid.
Under inrush condition, the following selectable protection stages will be blocked:
6.4.3 Principle
                     Second
                    harmonic    Settable
                    restraint   blocking
           Blocking logic 1
           Blocking logic 2
               LEVEL
                                           hold      DELAY
               LEVEL
LEVEL
Settable blocking IE
Settable blocking I2
                                            Inrush
                                                              P0866ENA
Application Guide                                                                                     P12y/EN AP/E95
T<200ms T<200ms
CLP starts
                                                             IA       IB IC
                                            In >
                                                                              - phase A AND phase B AND phase C < 5% In
                                                          ¨P3942ENa           - Phase A > In, in less than 200ms
                                     Internel Virtual
                                    threshold 5% In
                                                                                                           P3942ENa
                                                          T<200ms
P12y/EN AP/E95                                                                     Application Guide
                               Setting
                          Cold load Pick-up
                         52A Actif Selectable
                          In the menu CLP
        Ext. CB 52A
        Position
                        Digital logic Input = 52A        &
6.6      VTS
         The voltage transformer supervision (VTS) feature is used to detect failure of the analog ac
         voltage inputs to the relay. This may be caused by internal voltage transformer faults,
         overloading, or faults on the interconnecting wiring to relays. This usually results in one or
         more VT fuses blowing.
         MiCOM P127 is able to detect a VT loss by using VTS automatism. As soon as VT loss is
         detected, all voltage dependent functions will be blocked, an alarm can be raised and
         directional overcurrent functions might be replaced by non-directional overcurrent functions.
6.6.1    VTS occurrence
         VTS automation uses a fixed logic. A VT fault occurs if at least one of the two following
         conditions is verified:
         −     negative sequence voltage is greather than 0,17*Vn (0,3*Vn for 3Vpn connexion) and
               negative sequence current is smaller than 0,5*In.
         OR
         −     voltage is smaller than 0,1*Vn and current greather than 0,1*In.
         The VT fault disappears as soon as one criteria is not valid anymore.
6.6.2    VTS alarm
         A VTS alarm occurs when a VT fault occurs during more than tVTS.
         VTS Alarm won’t occur if VTS conditions remain valid less than the timer tVTS (settable from
         0 to 100s). If VTS condition remains longer than tVTS, this alarm will be latched until
         HMI/communication reset.
         The “VTS alarm” menu activates or deactivates the alarm message and LED (see diagram
         § 6.7).
6.6.3    VTS Blocks 51V
         This function blocks the overcurrent controlled by voltage transformer (51V) protection (see
         diagram § 6.7, “Automat Ctrl” / “VTS blocks 51V”).
Application Guide                                                                 P12y/EN AP/E95
        −      “VTS Blocks Protections?” submenu will unblock all the non directional overcurrent
               protection, or give the possibility to select individually the non directional overcurrent
               protection(s),
        −      When “VTS Blocks protections?” = yes, the non directional overcurrent protections (for
               I>, I>>, I>>>; Ie>, Ie>>, Ie>>> and Ie>>>> thresholds) can be individually locked or
               unlocked: for instance, if “VTS Non dir I>>” = Yes, when a VT fault occurs, the non
               directional overcurrent protection is available for I>> threshold.
6.6.5   Voltage/Power protection
        If VTS occurs, all voltage and power protection will be blocked:
                                                                Setting range
               Menu text          Default setting                                           step size
                                                           Min                  max
        Automat. Ctrl
        CT Supervision
        CT Supervision ?         No                 Yes / No
        Ie>                      0.08 × In          0.08 × In          1 × In            0.01 × In
        Ue<                      5 / 20 V           0.5 / 2V           22 / 88V          0.1 / 0.5V
        tCTS                     200ms              0s                 100s              10ms
P12y/EN AP/E95                                                                              Application Guide
Ie> CTS
Ue<
          The residual voltage setting, Ue< and the residual current setting, Ie>, should be set to avoid
          unwanted operation during healthy system conditions. For example Ue< should be set to
          120% of the maximum steady state residual voltage. The Ie> will typically be set below
          minimum load current. The time-delayed alarm, tCTS, is generally set to 5 seconds.
6.8       51V (voltage controlled overcurrent) features (P127 only)
          Voltage restrained overcurrent protection is used to clear faults which current is lower than
          the rated through current.
          Indeed, fault currents lower than the rated value cannot be cleared by phase overcurrent
          protection (ANSI codes: 50/51), which, by definition, clears faults which currents are much
          higher than the rated current value.
          The voltage restrained overcurrent function implemented in the MiCOM P127 is used to
          inhibit tripping by the phase overcurrent protection function when the relevant conditions are
          met.
          To this effect, the 51V function uses negative-sequence overvoltage settable values (V2>
          and V2>>), as well as the set threshold values for phase overcurrent (ANSI codes: 50/51)
          - I>> and I>>> - and phase undervoltage (ANSI code: 27) - U< and U<< -.
          When enabling the 51V function, the user selects whether it should inhibit the 2nd stage
          and/or the 3rd stage of the phase overcurrent protection function:
                                                    Automat. Ctrl
                    51V> selection                               51V
                    menu “(U< or V2>)& I>>?”                           (U< or V2>) & I>>
                                                               No
        I>>
                                                                                              I>>
                                                              Yes
        U<
                                   ³1                                  &
        V2>                                        &
                                                               No
        tI>>
                                                                                              tI>>
                                                              Yes
        tU<
                                   ³1                                  &
        tV2>                                       &
                                                   Automat. Ctrl
               51V>> selection                               51V
                                                                    (U<< or V2>>)&I>>>
               menu “(U<< or V2>>)& I>>>?”
                                                               No
        I>>>
                                                                                             I>>>
                                                              Yes
        U<<
                                   ³1                                  &
        V2>>                                       &
                                                               No
       tI>>>
                                                                                             tI>>>
                                                              Yes
       tU<<
                                   ³1                                  &
       tV2>>                                       &
                                             Yes
        VTS                                                                              Automat. Ctrl
                                             No                              VT Supervision
                                                       VTS blocks 51V?
No VTS Alarm?
        VTS
                                             Yes                                           VTS Alarm
                                                                                                         P3963ENa
P12y/EN AP/E95                                                                   Application Guide
P0024ENa
P0024ENa
                                         BLOCKING LOGIC
       The allocations of the "Blocking Logic1 and 2” functions are available in the menu
       AUTOMAT. CTRL/Blocking Logic1 / Blocking Logic2; this logic is initiated by energizing
       the appropriate logic input (Blk Log1 or Blk Log2) selecting in the AUTOMAT.
       CRTL/INPUTS menu.
       This functionality involves all the current and voltage protections available in the relays.
P12y/EN AP/E95                                                                 Application Guide
       MENU TEXT
       CB Monitoring
       CB Opening Time        Displays the CB opening time
       CB Closing Time        Displays the CB closing time
       CB Operations          Displays the number of opening commands executed by the CB
       Σ Amps(n) I1           Displays the summation of the Amps (or square Amps) interrupted by
                              the CB phase A
       Σ Amps(n) I2           Displays the summation of the Amps (or square Amps) interrupted by
                              the CB phase B
       Σ Amps(n) I3           Displays the summation of the Amps (or square Amps) interrupted by
                              the CB phase C
       The above counters in the CB condition monitoring function may be reset to zero, for
       example, following a maintenance inspection and overhaul.
       The circuit breaker condition monitoring counters will be updated every time the CB opens,
       from all the different way. In cases where the breaker is tripped by an external protection
       device it is also possible to update the CB condition monitoring. This is achieved by
       allocating one of the logic inputs or via the communications to accept a trigger from an
       external device.
       The options available for the CB condition monitoring function include the set-up of the
       broken conductor protection element and those features, which can be set to raise an alarm,
       or to lockout the CB.
       All the settings are available in the AUTOMAT. CTRL/CB Supervision menu.
Application Guide                                                                 P12y/EN AP/E95
         The Σ In counter monitors the cumulative severity of the duty placed on the interrupter
         allowing a more accurate assessment of the circuit breaker condition to be made.
         For OCBs, the dielectric withstand of the oil generally decreases as a function of
         Σ I2t. This is where ‘I’ is the fault current broken, and ‘t’ is the arcing time within the
         interrupter tank (not the breaking time). As the arcing time cannot be determined accurately,
         the relay would normally be set to monitor the sum of the broken current squared, by setting
         n = 2.
         For other types of circuit breaker, especially those operating on higher voltage systems,
         practical evidence suggests that the value of n = 2 may be inappropriate. In such
         applications n may be set to 1.
         An alarm in this instance for example may be indicative of the need for gas/vacuum
         interrupter HV pressure testing.
         It is imperative that any maintenance programme must be fully compliant with the switchgear
         manufacturer’s instructions.
6.14.1.2 Setting the Number of Operations Thresholds
         Every operation of a circuit breaker results in some degree of wear for its components. Thus,
         routine maintenance, such as oiling of mechanisms, may be based upon the number of
         operations. Suitable setting of the maintenance threshold will allow an alarm to be raised,
         indicating when preventative maintenance is due.
         Should maintenance not be carried out, the relay can be set to lockout the autoreclose
         function on reaching an operations threshold. This prevents further re-closing when the
         circuit breaker has not been maintained to the standard demanded by the maintenance
         instructions supplied by the switchgear manufacturer.
         Certain circuit breakers, such as oil circuit breakers (OCB) can only perform a specific
         number of fault interruptions before requiring maintenance attention. This is because each
         fault interruption causes carbonising of the oil, degrading its dielectric properties.
6.14.1.3 Setting the Operating Time Thresholds
         Slow CB operation is also indicative of the need for mechanism maintenance. Therefore, an
         alarm is provided and is settable in the range of 100 ms to 5 s. This time is set in relation to
         the specified breaking time of the circuit breaker.
6.15     Circuit Breaker Failure (P126 & P127)
         Following the inception of a fault one or more main protection devices will operate and issue
         a trip output to the circuit breaker(s) associated with the faulted circuit. Operation of the
         circuit breaker is essential to isolate the fault, and prevent damage or further damage to the
         power system.
         For transmission and sub-transmission systems, slow fault clearance can also threaten
         system stability. It is therefore common practice to install circuit breaker failure protection
         [50BF], which monitors that the circuit breaker has opened within a reasonable time. If the
         fault current has not been interrupted following a set time delay from circuit breaker trip
         initiation, breaker failure protection (CBF) will operate.
         CBF operation can be used to back-trip upstream circuit breakers to ensure that the fault is
         isolated correctly. CBF can also operate to reset all start output contacts, by external logic,
         ensuring that any blocks asserted on upstream protection are removed.
P12y/EN AP/E95                                                                     Application Guide
CB Fail Enabled
         Any Trip
                                                                     tBF          CB Fail Alarm
                                  1          S
                                                  Q
         External CBF                        R
         Initiate
CBF Ia<
CBF Ib<
         CBF Ic<
                                                                                             P0428ENa
                                      +
             Electrical panel
2 6
                                                                   -
                                  -
                Circuit breaker
52a
P3966ENa
       Example 2
       In this example both 52a and 52b auxiliary contacts are available; the MiCOM P126 and
       P127 relays monitor the complete trip circuit when the CB is closed and a part of the trip
       circuit when the CB is open.
       In this case it is necessary to insert a resistor R1 in series with 52b, if either the output (RL1)
       trip is latched or it stays involuntarily closed, or a long time trip pulse is programmed (See §
       6.16.2 for R1 calculation). Otherwise, a short circuit of DC trip supply would occur during
       tripping sequence.
       In this example, the protection is limited: the coil is only monitored when CB is closed.
                                                   +
                Electrical panel
2 6
                                   -
                 Circuit breaker
52a
52b
R1
P3967ENa
         Example 3
         In this example both 52a and 52b auxiliary contacts are available, the MiCOM P126 & P127
         relays monitor the complete trip circuit whatever the CB status (CB open or CB closed).
         In this case it is necessary to insert a R1, if either the output (RL1) trip is latched, or it stays
         involuntarily closed, or a long time trip pulse is programmed (See § 6.16.2 for R1
         calculation). Otherwise, a short circuit of DC trip supply would occur during tripping
         sequence.
                                                         +
                     Electrical panel
2 6
                                        -
                                                          R1
                     Circuit breaker
52a
52b
P3968ENa
       1 - Case of example no 2:
       The R1 resistor maximum value (in Ohm) is defined by the following formula:
                                                  0,8 × U a − U min
                                           R1 <                     [Ohm]
                                                        I min
       Where:
       Ua =      Auxiliary voltage value (in this case a DC voltage; range is given on label under the
                 top hinged cover. See table below).
       Umin =    Internal minimum voltage value needed for the opto logic input to operate.
       Imin =    Minimum current value needed for the opto logic input to operate.
                                               PR1 > 2 ×
                                                           (1,2 × U a ) 2 [W]
                                                               R1
       2 - Case of example no 3:
       The R1 resistor maximum value (in Ohm) is defined by the following formula:
                                               0,8 × U a − U min
                                      R1 <                       − R Coil [Ohm ]
                                                     I min
       Where:
       Ua =      Auxiliary voltage value (in this case a DC voltage; range is given on label          under
                 the top hinged cover. See table below).
       Umin =    Internal minimum voltage value needed for the opto logic input to operate.
       Imin =    Minimum current value needed for the opto logic input to operate.
       Rcoil =   Trip coil resistance value.
                                              PR1 > 2 ×
                                                           (1,2 × U a ) 2 [W]
                                                          (R1 + R Coil )
       If the trip contact is latched or temporarily by-passed, the continuous current through the
       tripping coil is:
                                                          (R1 + RCOIL)
                                       ICONTINUOUS =
                                                           1.2 × va
       If the value is above admissible continuous current through the tripping coil, trip contact
       latching must not be made and by-passing trip contact should never be made.
P12y/EN AP/E95                                                                      Application Guide
6.17     Switch onto Fault Protection & Trip on Reclose (SOTF/TOR) (P126 & P127)
6.17.1   General
         Under particular conditions, it can happen that when the feeder is supplied by the closing of
         the CB a fast trip command may be required if a fault is present (Closing on to fault).
         Some faults may be caused by conditions not removed from the feeder after a reclosing
         cycle or a manual trip, or due to earthed clamps left on after maintenance works. In these
         cases, it may be desirable to clear the fault condition in fast time, rather than waiting for the
         trip time delay DMT or IDMT associated with the involved protection.
         In case of manually closing of the CB it can happen to switch on to an existing fault. This is a
         particularly critical situation, because the overcurrent protection would not clear the fault until
         the set operate delay had elapsed. This is another typical case of closing on to fault. Hence it
         is desirable to clear the fault as fast as possible.
         The P126 and P127 relays provide the SOTF/TOR functionality.
         The SOTF acronym means switch on to fault.
         The TOR acronym means trip on recloser.
         The available setting to enable/disable/set the SOTF/TOR (Switch On To Fault/ Trip On
         Reclose) function is written in a submenu of the AUTOMATIC CTRL menu.
         The setting regarding the I>> and I>>> is provided to initiate the SOTF function.
6.17.2   SOTF/TOR description
         When the SOTF/TOR function is enable, it can be initiated by a local manual CB control
         close command detected by the digital input labelled Man.Close, or by a TC (closing
         command by remote via network: Modbus, IEC 60870) or by an automatic reclosing cycle.
         When CB has been closed on some faults caused by lightning or something else, the fault
         detection needs a time period. This is the reason why a 500ms fixed time window after
         initiatialization of the SOTF/TOR function is included.
         When this fixed timer is elapsed and the I>> or I>>> is detected, the settable timer t Sotf
         starts.
         The existence of this settable timer is justified because in some applications selectivity for
         fault occurring in stage two or three is requested.
         Another justification of the SOTF/TOR tripping time delay is for cases where serious
         transient happen and the three poles of the CB do not close at the same time and for those
         cases where the CB may not be closed instantaneously.
         Furthermore, the t SOFT can also be considered a trip delay time that substitutes the trip
         timer of the started threshold such to accelerate the tripping.
         If a trip due to switch on to fault occurs during the reclaim time of the ARC, the trip will be
         definitive and the ARC will move in the blocked status.
         If the I>> and I>>> reset during the settable timer t Sotf the SOTF/TOR function resets.
         The following signals can activate the SOTF/TOR function:
         -   “Ctrl close” logical input,
         -   manual closing ordered by HMI,
         -   command generated by a digital input labelled “SOTF”,
         -   front communication order,
         -   rear communication order,
         -   when existing, second rear communication order,
         -   close ordered by autorecloser,
Application Guide                                                                                                                              P12y/EN AP/E95
                                                                                I>>
                                          0     &
                     Autorecloser                                            Autorecloser
                                                       0
AR selected 0 I>>>
                                          0    &
                    Rear Com order                                                                                      t SOTF
                                                                                                           &
                                                       0
                                          0                                                                            0.. 500 ms
                    Rear Com selected
                                                                                                                       valided by
                                                                                                                         setting
                                          0    &
                    Front Com order
                                                       0
                                          0
                    Front Com selected                                              Monostable
                                                                       OR            500 ms
                                          0
                                                                                                                                        OR     Trip
                    Ctrl Close slected
                                                                                                    tI>> valided by
                                          0     &                                                       setting
                       HMI order
                                                       0
                                          0
                    HMI order selected                                                              tI>>> valided by
                                                                                                         setting
                                                                                                                                    P3939ENa
                      Trip setting            : Threshold type selected in Trip setting
         The trip by SOTF is settable in the AUTOMATIC CTRL/TRIP COMMAND submenu and in
         the AUTOMATIC CTRL/Output relays submenu.
6.18.2   Settings
         In the “AUTOMATIC CTRL/Trip Commands ” menu, TC item uses the “CTRL TRIP” function
         to open the CB.
         In the “AUTOMATIC CTRL/Output relays” menu, the “CTRL TRIP” and “CTRL CLOSE”
         functions are assigned to remotely open and close the CB.
         The CB CLOSE relay can be used for the close command.
         In order to keep the normal functionality, the customer will have to assign both information
         TRIP by protection and Ctrl Trip on (RL1), and to assign both information CLOSE CTRL and
         CB CLOSE on the same auxiliary relay.
         An application of the subject mentioned above is presented below.
         In the following schematic, the customer will have to assign the TRIP and CTRL TRIP to the
         TRIP RELAY, the CB CLOSE and the CTRL CLOSE to the auxiliary relay number two, in
         accordance with setting above.
P12y/EN AP/E95                                                                                 Application Guide
       If the Local input is energised any remote command will be ignored if the Local input is de-
       energised all the remote control will be considered.
DC V+ Local Switch
                P125/P126/P127                                        Remote
                                                    Local trip
                       RL 1
                    Control trip
                                                    Local close
                       RL 2
                    Control close
                        RL 2
                   AR close
                  RL 1
                 Protection trip
                 Input labeled
                 Local
DC V- P0689ENa
                           I<
       tAUX 1(input1)                               &
                                                                              5 sec
                                                                  1                                  Output
                                                                                 10 sec
       tAUX 2(input2)
                                                                                                       P0717ENa
Application Guide                                                               P12y/EN AP/E95
      −      Calculation of the average of the RMS values on a "Rolling Sub Period" period.
      The setting of the width of the period "Rolling Sub Period" is in the "RECORDS/Rolling
      Demand/Sub Period" menu.
      Setting range: from 1 to 60 minutes.
      −      Calculation of the average of these average values (sliding window values) on the
             number of "Num. of Sub Periods" periods
      The setting of the number of Sub Period "Num of Sub Periods" in the "RECORDS/Rolling
      Demand/Num of Sub Per" menu.
      Setting range: from 1 to 24.
      Display of the first result in the MEASUREMENTS menu only after the storage of "Num of
      Sub Periods" periods.
      The 3 phases Rolling average value are displayed:
10.    MEASUREMENTS
       The measurement functions on MiCOM P125, P126 and P127 relays are described in
       chapter User Guide of this Technical Guide.
       Particular attention is to be given to the power and energy measurement.
10.1   Power and Energy Measurements (P127)
       The MiCOM P127 relay provides the measurements function for active and reactive power
       and for active and reactive energy.
       The fundamental value is provided for the derived (calculated) measures.
       The following table lists the shown voltage measurements, according to the VT connection
       (‘CONFIGURATION / General options / VT Connection)
The value for power is calculated in accordance with the following listed table.
       The value for energy is calculated by multiplying the calculated power value by time.
       The calculated energy value is stored in a non-volatile memory (E²PROM) every second, so
       that in case of temporary power supply fault, the previous values calculated can be recalled.
       The MiCOM P127 relay provides, on the display, the measurements of the power and of the
       energy. Both refer to primary values and rely on the CT and VT ratio.
       The maximum active and reactive power value displayed is 9999MW and 9999MVAr.
       The maximum active and reactive energy value displayed is 4200GWh and 4200GVArh.
       The sign of the active and reactive power/energy values is taken according to the diagram
       below.
P12y/EN AP/E95                                                                      Application Guide
         They are in accordance with the wiring diagrams in the chapter P12y/EN CO in this
         Technical Guide.
                                                 +
                                  cos phi                      cos phi
                                  +P                   V       +P
                                  -Q                           +Q
                                                           I
P0100ENa
         When CTm1 and CTm2 phases are connected, “Metering” menu displays frequency, 3-
         phases currents, 3-phases voltage, power and energy measured values.
                   NOTE:        the following explanations are given for phase A. The same equations
                                are applicable to phase B or phase C using (IBm or ICm) and (VBm or
                                VCm).
10.2.1   Frequency
         This menu displays network frequency.
Application Guide                                                                 P12y/EN AP/E95
10.2.2   Currents
         The “Currents” menu displays the magnitude of the measured currents (true RMS value). It
         takes into account the CTm connection (see the previous table) and CTm ratio
         (‘CONFIGURATION / Transfo ratio’).
         MiCOM P127 displays the magnitude of fundamental current, and the magnitude of the
         currents up to the 10th harmonics.
10.2.2.1 Total Harmonic Distortion (THD) and Total Demand Distorsion (TDD)
         Current Harmonic Distortion is measured by phase in several different ways. The first
         method is Total Harmonic Distortion (THD). The MiCOM P127 THD (THD IAm) equation is
         given in the following equation (for phase A):
10
                                     ∑ IAmh²
                                     h=2
         THD IAm = 100% ×
                                           I1
         Note: the denominator I1 is the magnitude of the fundamental current.
         Alternatively, Current Harmonic Distortion can be measured as Total Demand Distortion
         (TDD). Demand Distortion differs from traditional harmonic distortion in that the denominator
         of the distortion equation is a fixed value “IL”. This fixed denominator value is defined as the
         average peak demand, and is set using ‘CONFIGURATION / General options /
         IAm TDD denom.’ cell:
10
                                     ∑ IAmh²
                                     h=2
         TDD IAm = 100% ×
                                          IL
         By creating a measurement that is based on a fixed value, TDD is a "better" measure of
         distortion problems. Traditional THD is determined on the ratio of harmonics to the
         fundamental. While this is acceptable for voltage measurements, where the fundamental
         only varies slightly, it is ineffective for current measurements since the fundamental varies
         over a wide range. Using traditional THD, 30% THD may mean a 1 Amp load with 30%
         Distortion, or a 100 Amp load with 30% Distortion. By using TDD, these same two loads
         would exhibit 0.3%.
10.2.2.2 K Factor
         K-Factor is a measure of the heating effects on transformers. The following equation is used,
         for MiCOM P127, to determine phase A K-Factor, where "h" is the harmonic number and
         "IAmh" is the magnitude of the hth harmonic:
                         10
                         ∑ IAmh² × h²
                         h =1
         K IAm = 100 ×       10
                              ∑ IAmh²
                              h =1
         K-Factor is measured on each of the three phases of amps, however there is no "Total" K-
         Factor. K-Factor, like THD, does not indicate the actual load on a device, since all three of
         these measurements are ratios. Given the same harmonic ratio, the calculated K-Factor for a
         lightly loaded transformer will be the same as the calculated K-Factor for a heavily loaded
         transformer, although the actual heating on the transformer will be significantly different.
P12y/EN AP/E95                                                                         Application Guide
10.2.3   Voltages
         The following table lists the displayed voltage measurements, according to the VT
         connection (‘CONFIGURATION / General options / VT Connection) and / or to the VT
         protection (‘CONFIGURATION / General options / VT Protection).
         The “Voltages” menu displays the magnitude of the measured voltages (true RMS value). It
         takes in account the CTm connection (see the previous table) and CTm ratio
         (‘CONFIGURATION / Transfo ratio’).
         MiCOM P127 displays the magnitude of fundamental voltage, and the magnitude of the
         voltages up to the 10th harmonics.
10.2.3.1 Total Harmonic Distortion (THD)
         Voltage Harmonic Distortion is measured by phase in several different ways. The MiCOM
         P127 equation for phase A Total Harmonic Distortion (THD) is given in the following
         equation:
10
                                    ∑ VAmh²
                                    h=2
         THD VAm = 100% ×
                                          V1
         Note the denominator V1 is the fundamental magnitude. For Individual Harmonic Distortion
         there is no summation, only one component is used in the numerator.
10.2.4   Powers
         The MiCOM P127 displays:
         −         the measured total apparent power (product of the per-element Volts and Amps),
Application Guide                                                                 P12y/EN AP/E95
         −     the three phase displacement power factor (cosine of the angle between the
               fundamental voltage vector and the fundamental current vector): The Total
               Displacement Power Factor measurement is calculated using the "Power Triangle,” or
               the three-phase Fundamental WATTS divided by the three-phase Fundamental VAs.
               The per-phase Fundamental VA measurement is calculated from the product of the
               per-phase Fundamental Amp and Fundamental Volts values. The three-phase
               Fundamental VA measurement is the sum of the per-phase Fundamental VA values
               (Arithmetic VAs).
         See § 10.2.6 to see the convention for the positive (+) or negative (–) sign.
10.2.5   Energies
         Separate values are maintained for both positive and negative Watt-hours (export and import
         powers) and positive and negative VAR-hours (Lagging and leading VARs. These energy
         quantities are calculated every minute from the Total Watts and Total VARs.
         See § 10.2.6 to see the convention for the positive (+) or negative (–) sign.
10.2.6   Plus and minus signes for power and energy calculation.
         Plus or minus signs are defined as follows:
Reference direction
SOURCE LOAD
Metering point
             ACTIVE POWER: P is positive when the power is from the source to the load
             REACTIVE POWER: Q is positive when the load is inductive.
Im (+)
Quadrant 2 Quadrant 1
                                                               V
                               Re (–)                               Re (+)
Quadrant 3 Quadrant 4
                                              Im (–)
                                                                                         P3976ENa
P12y/EN AP/E95                                                      Application Guide
with:
       FAIL               87654321
       SAFE RE.           00100010
       This settings means:
− RL3, 4, 5, 7 & 8: NO
       −     RL6: Inverted (NO but output relays closed when logical state of the signal is going
             down)
       The setting menu for the functionality of the logic outputs is available in the AUTOMAT.
       CTRL menu.
       It is possible to assign a specific function to each output relay except RL1.
       For more details see the chapter User Guide.
P12y/EN AP/E95                                                                   Application Guide
      Maintenance Mode
                                 YES
      When activating this menu (YES), the Alarm led will start flashing and an alarm message will
      appear “MAINTENANCE MODE”. In this case, all output contacts are blocked, no operation
      will take place on these contacts even if a protection threshold associated to one of these
      output contacts is exceeded.
      (If protection threshold is exceeded, all the associated leds will become ON, even the TRIP
      LED, if the threshold is associated to the RL1).
      RELAYS          8765W4321
      CMD              000000000
      This window allows the user to verify the external wiring to the relay output contacts, to do
      this, it is sufficient to assign a 1 to any of the output contacts, this will close the contact and
      the wiring continuity could be verified.
Application Guide                                                               P12y/EN AP/E95
13.    CT REQUIREMENTS
       The CT requirements for the MiCOM P12y relays are given below.
       The current transformer requirements are based on a maximum prospective fault current of
       50 times the relay rated current (In) and the relay having an instantaneous setting of 25
       times rated current (In). The current transformer requirements are designed to provide
       operation of all protection elements.
       Where the criteria for a specific application are in excess of those detailed above, or the
       actual lead resistance exceeds the limiting value quoted, the CT requirements may need to
       be increased according to the formulae in the following sections.
             MODBUS &
         IEC 60870-5-103 &
              DNP 3.0
             DATABASE
              MiCOM P125-P126 – V12
                MiCOM P127 – V13
Communications                        P12y/EN CT/ E95
                         BLANK PAGE
Communications                     P12y/EN CT/ E95
                                MODBUS DATABASE
MiCOM P125/P126 & P127                  Page 1/148
        MODBUS DATABASE
              MiCOM P125-P126 – V12
                   P127 – V13
P12y/EN CT/ E95                       Communications
MODBUS DATABASE
Page 2/148                     MiCOM P125/P126 & P127
                  BLANK PAGE
Communications                                                            P12y/EN CT/E95
                                                                       MODBUS DATABASE
MiCOM P125/P126 & P127                                                         Page 3/148
CONTENT
1.       INTRODUCTION                                                                   5
1.1      Purpose of this document                                                       5
1.2      Glossary                                                                       5
2.       MODBUS PROTOCOL                                                                6
2.1      MODBUS connection technical characteristics                                    6
2.1.1    MODBUS connection parameters                                                   6
2.1.2    Exchanges messages synchronisation                                             6
2.1.3    Message validity check                                                         6
2.1.4    Address                                                                        6
2.2      MODBUS functions available in the protection device                            7
2.3      Description of the ModBus protocol                                             7
2.3.1    Frame size received from the protection device (slave)                         7
2.3.2    Format of frames sent from the relay                                           8
2.3.3    Messages validity check                                                        8
3.       DATABASE ORGANISATION                                                         10
3.1      Product information, remote signalling, measurements                          11
3.1.1    Page 0H - Product information, remote signalling, measurements (part 1)       11
3.1.2    Page 23H – Measurements / P127 with CT of measurement (part 2)                16
3.2      General remote parameters                                                     19
3.2.1    Page 1H - General remote parameters (part 1)                                  19
3.2.2    Page 6H - General remote parameters (part 2)                                  25
3.3      Protection groups parameters                                                  31
3.3.1    Page 2H - Setting group 1 remote parameters                                   31
3.3.2    Page 3H - Setting group 2 remote parameters                                   39
3.3.3    Page 24H - Setting group 1 remote parameters                                  39
3.3.4    Page 26H - Setting group 2 remote parameters                                  39
3.3.5    Page 28H - Setting group 3 remote parameters                                  39
3.3.6    Page 2AH - Setting group 4 remote parameters                                  39
3.3.7    Page 2CH - Setting group 5 remote parameters                                  39
3.3.8    Page 2EH - Setting group 6 remote parameters                                  39
3.3.9    Page 30H - Setting group 7 remote parameters                                  39
3.3.10   Page 32H - Setting group 8 remote parameters                                  39
3.4      Boolean equations                                                             40
3.4.1    Page 5H - Boolean equations parameters                                        40
3.5      Remote controls, device status & time synchronisation                         47
3.5.1    Page 4H - Remote controls                                                     47
P12y/EN CT/E95                                                            Communications
MODBUS DATABASE
Page 4/148                                                         MiCOM P125/P126 & P127
1.    INTRODUCTION
1.1   Purpose of this document
      This document describes the characteristics of the different communication protocols of
      MiCOM P127, P126 and P125 relays (named P12y in this document).
      The available communication protocols on the relay are listed below:
− MODBUS
− IEC 60870-5-103
      −     DNP3
1.2   Glossary
      Ie           : earth fault current measured
      Ue           : residual voltage measured directly by the input terminals on rear panel
      Pe           : earth fault power (Calculated)
      IeCosPhi     : active component of the earth fault current
2.      MODBUS PROTOCOL
        MiCOM P12y relay can communicate by a RS 485 link. The terminals are placed on the rear
        panel (terminals 31 and 32). See the GS document for further information on the wiring. The
        applied ModBus protocol is compliance with the MODBUS RTU.
2.1     MODBUS connection technical characteristics
2.1.1   MODBUS connection parameters
        The different parameters of the MODBUS connection are as follows:
            Mode
            1 start / 8 bits / 1 stop: total 10 bits
            1 start / 8 bits / even parity / 1 stop: total 11 bits
            1 start / 8 bits / odd parity / 1 stop: total 11 bits
            1 start / 8 bits / 2 stop: total 11 bits
            Function Nr.    Data Read       Data Write                 Data Format & Type
        1                  X                             N bits
        2                  X                             N bits
        3                  X                             N words
        4                  X                             N words
        5                                X               1 bit
        6                                X               1 word
        7                  Fast                          8 bits
        8                  X                             Diagnostics counter
        11                 X                             Event counter
        15                               X               N bits
        16                               X               N words
        Slave address:
        The slave address is in the range from 1 to 255. A transmitted frame with a slave address
        equal to 0 is a globally addressed to all installed equipment (broadcast frame).
        Function code:
        The function code returned from the slave in the exception response frame is the code in
        which the most significant bit (bit 7) is forced to 1.
        Error code:
        Among the 8 exception codes of the MODBUS protocol, the protection device manages two:
− Code 03: A value from the data field is unauthorised (incorrect code).
        CRC16:
        The slave calculates the CRC16 value.
                   NOTE:       The slave device does not respond to globally broadcast frames sent
                               out from the master.
2.3.2   Format of frames sent from the relay
        Frame sent (response)
        Slave address:
        The slave address is in the range from 1 to 255.
        Function code:
        Processed MODBUS function (1 to 16).
        Data:
        Contains reply data to master query.
        CRC 16:
        CRC16 value calculated by the slave.
2.3.3   Messages validity check
        When MiCOM P12y relay (slave) receives a master query, it validates the frame:
        −   If the CRC is incorrect, the frame is discarded as invalid. The slave does not reply to the
            request for data. The master must retransmit its request for data. With the exception of
            a broadcast message, this is the only case where the slave does not reply to a request
            for data from the master.
        −   If the CRC is correct but the slave can not process the request for data, it sends an
            exception response to the master.
        Warning frame sent (response)
        Slave number:
        The address range of the slave device is between 1 and 255.
        Function code:
        The function code returned by the relay in the warning frame is the code in which the most
        significant bit (bit 7) is forced to 1.
Communications                                                                  P12y/EN CT/E95
                                                                             MODBUS DATABASE
MiCOM P125/P126 & P127                                                               Page 9/148
      Warning code:
      On the 8 warning codes of the MODBUS protocol, the relay manages two of them:
      CRC16:
      Value of the CRC16 calculated by the slave.
P12y/EN CT/E95                                                                    Communications
MODBUS DATABASE
Page 10/148                                                           MiCOM P125/P126 & P127
3.          DATABASE ORGANISATION
            Application mapping are organised in pages. The characteristics are the following:
                                                                                                                       P125
                                                                                                                               P126
                                                                                                                                       P127
  Address                                                                                                       Def.
                Group                      Description                   Values range   Step   Unit   Format
   (hex)                                                                                                       value
            Product
0000                         Relay description characters 1 and 2        32 - 127       1             F10              •       •       •
            Information
             Remote
0010                         Digital inputs status                                                    F12                  •       •       •
             signals
             Protection
0017                         Information of the threshold status Ie>                                  F16                  •       •       •
             67n
                                                                                                                     P125
                                                                                                                            P126
                                                                                                                                   P127
 Address                                                                                                      Def.
                Group                     Description                 Values range   Step    Unit   Format
  (hex)                                                                                                      value
            Circuit
0028                      CB Supervision status                                                     F43                      •      •
            Breaker
            Remote
0030–0031                Phase A RMS current                                         1      10mA    F18                      •      •
            measurements
004E Module V1 F1 •
004F Module V2 F1 •
0050 Module IA F1 • •
0051 Module IB F1 • •
0052 Module IC F1 • •
0053 Module Ie F1 • • •
                                                                                                                     P125
                                                                                                                            P126
                                                                                                                                   P127
 Address                                                                                                      Def.
               Group                      Description                 Values range   Step    Unit   Format
  (hex)                                                                                                      value
            Energy                                                    from 1 to
0061–0062                   Positive active energy                               9   1      kWh     F18A                            •
            measures                                                  4.200 x 10
                                                                      from 1 to
0063–0064                   Negative active energy                               9   1      kWh     F18A                            •
                                                                      4.200 x 10
                                                                      from 1 to
0065–0066                   Positive reactive energy                             9   1      kVARh   F18A                            •
                                                                      4.200 x 10
                                                                      from 1 to
0067–0068                   Negative reactive energy                             9   1      kVARh   F18A                            •
                                                                      4.200 x 10
006F Reserved
0074 Reserved
0078–0079 Reserved
                                                                                                                  P125
                                                                                                                         P126
                                                                                                                                P127
 Address                                                                                                   Def.
               Group                    Description             Values range     Step    Unit    Format
  (hex)                                                                                                   value
            Boolean
007F                      Boolean equation status                                                F48                      •      •
            equations
            Voltage
0080–0081                 Phase A RMS voltage                                    1      10mV     F18A                            •
            measurement
008B Module Ue F1 • • •
            Power
009C–009D                 Module Pe                                                     CAN      F18A              •      •      •
            measures
                                                                          6
                                                                -999.9 10
009E–009F                 3-Phase Active Power (P)                          6    1      10Watt   F18                             •
                                                                to 999.9 10
                                                                          6
                                                                -999.9 10
00A0–00A1                 3-Phase Re-active Power (Q)                       6    1      10VAR    F18                             •
                                                                to 999.9 10
            Power
00A9–00AA                 Module IeCos                                                           F18A              •      •      •
            measures
                                                                          6
                                                                -999.9 10               10VA
00AB-00AC                 3-Phase Apparent power (S)                        6    1               F18                             •
                                                                to 999.9 10
00B0 Module VB F1 •
00B1 Module VC F1 •
                                                                                                                   P125
                                                                                                                          P126
                                                                                                                                 P127
 Address                                                                                                    Def.
               Group                      Description              Values range    Step    Unit   Format
  (hex)                                                                                                    value
                                                                   -20 000 to 20
00C0        Measurements df/dt                                                     1      mHz/s   F2                             •
                                                                   000
00C6–00DF Reserved
                                                                                                  16 x
00E0–00EF   HMI screen      Copy of HMI screen                     ASCII code
                                                                                                  F10
00F0–00FF                   Reserved
  P12y/EN CT/E95                                                                  Communications
  MODBUS DATABASE
  Page 16/148                                                          MiCOM P125/P126 & P127
                                                                                                          P125
                                                                                                                 P126
                                                                                                                        P127
  Address                                                                                          Def.
                Group                   Description     Values range     Step    Unit    Format
   (hex)                                                                                          value
            IA
2300                      Fondamental                    Float 32bits                    F88                            •
            measurement
230C–2319 Reserve •
231E Reserved •
            IB
2320                      Fondamental                   Float 32bits                     F88                            •
            measurement
232C–2339 Reserve •
233E Reserved •
            IC
2340                      Fondamental                   Float 32bits                     F88                            •
            measurement
                                                                                                    P125
                                                                                                           P126
                                                                                                                  P127
  Address                                                                                    Def.
               Group                  Description   Values range   Step    Unit    Format
   (hex)                                                                                    value
234C–2359 Reserve •
235E Reserved •
236C–2379 Reserve •
                                                                          360°/6
237A                    Angle Va^Ia or Uab^Ic       0-65534        1               F1                                 •
                                                                          5536
237E Reserved •
                                                                                                            P125
                                                                                                                   P126
                                                                                                                          P127
 Address                                                                                             Def.
               Group                   Description         Values range    Step    Unit    Format
  (hex)                                                                                             value
238C–2399 Reserve •
                                                                                  360°/6
239A                    Angle Vb^Ib or Ubc^Ia              0-65534         1               F1                             •
                                                                                  5536
                                                                                  360°/6
239B                    Angle Vb^Iam or Ubc^Iam            0-65534         1               F1                             •
                                                                                  5536
239E Reserved •
23AC–23B9 Reserve •
                                                                                  360°/6
23BA                    Angle Vc^Ic or Uca^Ib              0-65534         1               F1                             •
                                                                                  5536
                                                                                  360°/6
23BB                    Angle Vc^Iam or Uca^Iam            0-65534         1               F1                             •
                                                                                  5536
23BE Reserved •
            Power &
23C0                    Active Power                       Float 32bits                    F88                             •
            Energie
23D4-23FF               Reserved
 Communications                                                                           P12y/EN CT/E95
                                                                                       MODBUS DATABASE
 MiCOM P125/P126 & P127                                                                      Page 19/148
                                                                                                                  P125
                                                                                                                         P126
                                                                                                                                P127
 Address                                                                                                   Def.
                 Group                     Description             Values range   Step    Unit   Format
  (hex)                                                                                                   value
                                                                                                                    P125
                                                                                                                           P126
                                                                                                                                  P127
 Address                                                                                                     Def.
                 Group                        Description           Values range    Step    Unit   Format
  (hex)                                                                                                     value
Ratios VT
0124–0125    Primary phase    57 - 130V operating range             10 –100000      1      10V     F18A     100V                   •
             VT
                              220 - 480V operating range            220 – 480       1      V       F18A     220V                   •
0128 –0129   Primary earth    57 - 130V operating range             10 -100000      1      10V     F18A     100      •     •      •
             VT                                                                                             V
012C Obsolete
DNP3 0-5 4
group 1-2 • •
                                                                                                                      P125
                                                                                                                             P126
                                                                                                                                    P127
 Address                                                                                                       Def.
               Group                     Description                    Values range   Step   Unit   Format
  (hex)                                                                                                       value
                                                                                                                     P125
                                                                                                                            P126
                                                                                                                                   P127
 Address                                                                                                      Def.
               Group                     Description             Values range     Step       Unit   Format
  (hex)                                                                                                      value
part 1
                                                                                                              P125
                                                                                                                     P126
                                                                                                                            P127
 Address                                                                                               Def.
               Group                      Description          Values range   Step    Unit   Format
  (hex)                                                                                               value
part 2
                                                                                                                 P125
                                                                                                                        P126
                                                                                                                               P127
 Address                                                                                                  Def.
              Group                       Description             Values range   Step    Unit   Format
  (hex)                                                                                                  value
01F3 Obsolete
01F4 Obsolete
                                                                                                         P125
                                                                                                                P126
                                                                                                                       P127
 Address                                                                                          Def.
                Group                        Description   Values range   Step   Unit   Format
  (hex)                                                                                          value
0606-060B Reserved
                                                                                                                P125
                                                                                                                       P126
                                                                                                                              P127
 Address                                                                                                 Def.
               Group                      Description           Values range    Step    Unit   Format
  (hex)                                                                                                 value
062F Reserved
0638-063F Reserved
0652 Reserved • • •
                                                                                                                     P125
                                                                                                                            P126
                                                                                                                                   P127
 Address                                                                                                      Def.
                Group                     Description                Values range   Step    Unit    Format
  (hex)                                                                                                      value
                            MODBUS                                   1 - 255
                            IEC 60870-5-103                          1 – 254
DNP3 1 - 59999
066F Reserved
0675-0678 Reserved
067E-0681 Reserved
0684 Reserve
                                                                                                             P125
                                                                                                                    P126
                                                                                                                           P127
 Address                                                                                              Def.
               Group                        Description      Values range   Step    Unit    Format
  (hex)                                                                                              value
06A8                        Ve threshold                                                                                   •
                                     range A                 5 - 220        1      0.1V     F1       50
                                     range B                 20 - 880       5      0.1V     F1       200
                                                                                                                       P125
                                                                                                                              P126
                                                                                                                                     P127
 Address                                                                                                        Def.
              Group                       Description                Values range   Step       Unit   Format
  (hex)                                                                                                        value
06BD       Group           Group number for digital input inactive   1-8            1                 F55      1                      •
           changing
                                                                                                P125
                                                                                                       P126
                                                                                                              P127
 Address                                                                                 Def.
               Group               Description   Values range   Step    Unit   Format
  (hex)                                                                                 value
                                                                                                                    P125
                                                                                                                           P126
                                                                                                                                  P127
 Address                                                                                                     Def.
                Group                     Description               Values range   Step    Unit    Format
  (hex)                                                                                                     value
0205                      K: I>trip time multiplier for RI type     100 -10000     5      0.001    F1       100             •      •
                          curve
10 - 4000 •
10 - 4000 •
0217        Ie> value     0.002 - 1 Ien operating range             2 - 1000       1      1/1000   F1       1000     •      •      •
                                                                                          Ien
021B                      K: Ie> trip time multiplier for RI type   100 -10000     5      0.001    F1       100      •      •      •
                          curve
 P12y/EN CT/E95                                                                        Communications
 MODBUS DATABASE
 Page 32/148                                                             MiCOM P125/P126 & P127
                                                                                                             P125
                                                                                                                    P126
                                                                                                                           P127
 Address                                                                                              Def.
               Group                       Description       Values range   Step    Unit    Format
  (hex)                                                                                              value
0224       Ie>> value      0.002-1 Ien operating range       2 - 1000       1      1/1000   F1       1000     •      •      •
                                                                                   Ien
022A       Ie>>> value     0.002-1 Ien operating range       2 - 1000       1      1/1000   F1       1000     •      •      •
                                                                                   Ien
                                                                                                                     P125
                                                                                                                            P126
                                                                                                                                   P127
 Address                                                                                                      Def.
              Group                       Description                Values range   Step    Unit    Format
  (hex)                                                                                                      value
023E                       K: I2> trip time multiplier for RI type   100-10000      5      1/1000   F1       100             •      •
                           curve
operating range
                                                                                                                       P125
                                                                                                                              P126
                                                                                                                                     P127
 Address                                                                                                        Def.
              Group                       Description                Values range   Step       Unit   Format
  (hex)                                                                                                        value
0255                       K: Pe> trip time multiplier for RI type   100 -10000     5      0.001      F1       100      •      •      •
                           curve
025D       IeCos> value    0.002 - 1 Ien operating range             2 - 1000       1      1/1000     F1       1000     •      •      •
                                                                                           Ien
0261                       K: IeCos> trip time multiplier for RI     100 -10000     5      0.001      F1       100      •      •      •
                           type curve
0266       IeCos>> value   0.002 - 1 Ien operating range             2 - 1000       1      1/1000     F1       1000     •      •      •
                                                                                           Ien
                                                                                                                    P125
                                                                                                                           P126
                                                                                                                                  P127
 Address                                                                                                     Def.
               Group                       Description               Values range   Step    Unit   Format
  (hex)                                                                                                     value
028A                       K: I>> trip time multiplier for RI type   100 -10000     5      0.001   F1       100             •      •
                           curve
0290                       K: Ie>> trip time multiplier for type     100 - 10000    5      0.001   F1       100      •      •      •
                           curve
                                                                                                             P125
                                                                                                                    P126
                                                                                                                           P127
 Address                                                                                              Def.
                Group                        Description     Values range   Step    Unit    Format
  (hex)                                                                                              value
029B-029F Reserved
                                                                                                          P125
                                                                                                                 P126
                                                                                                                        P127
 Address                                                                                           Def.
               Group                        Description   Values range   Step    Unit    Format
  (hex)                                                                                           value
                                                          5510-6490                               ou
                                                                                                  6000
                                                                                                                       P125
                                                                                                                              P126
                                                                                                                                     P127
 Address                                                                                                        Def.
                  Group                     Description               Values range   Step    Unit     Format
  (hex)                                                                                                        value
02E9                          K: Ie>>>> trip time multiplier for RI   100 to 10000   5      1/1000    F1       100                    •
                              curve
  Address                                                                                  Def.
                Group                Description      Values range   Step   Unit Format
   (hex)                                                                                  Value
 0500       Bool Equations   Equation A.00 operator   0-1            1           F70      0
 0501                        Equation A.00 operand    0 - 111        1           F72      0
 0502                        Equation A.01 operator   0-3            1           F71      0
 0503                        Equation A.01 operand    0 - 111        1           F72      0
 0504                        Equation A.02 operator   0-3            1           F71      0
 0505                        Equation A.02 operand    0 - 111        1           F72      0
 0506                        Equation A.03 operator   0-3            1           F71      0
 0507                        Equation A.03 operand    0 - 111        1           F72      0
 0508                        Equation A.04 operator   0-3            1           F71      0
 0509                        Equation A.04 operand    0 - 111        1           F72      0
 050A                        Equation A.05 operator   0-3            1           F71      0
 050B                        Equation A.05 operand    0 - 111        1           F72      0
 050C                        Equation A.06 operator   0-3            1           F71      0
 050D                        Equation A.06 operand    0 - 111        1           F72      0
 050E                        Equation A.07 operator   0-3            1           F71      0
 050F                        Equation A.07 operand    0 - 111        1           F72      0
 0510                        Equation A.08 operator   0-3            1           F71      0
 0511                        Equation A.08 operand    0 - 111        1           F72      0
 0512                        Equation A.09 operator   0-3            1           F71      0
 0513                        Equation A.09 operand    0 - 111        1           F72      0
 0514                        Equation A.10 operator   0-3            1           F71      0
 0515                        Equation A.10 operand    0 - 111        1           F72      0
 0516                        Equation A.11 operator   0-3            1           F71      0
 0517                        Equation A.11 operand    0 - 111        1           F72      0
 0518                        Equation A.12 operator   0-3            1           F71      0
 0519                        Equation A.12 operand    0 - 111        1           F72      0
 051A                        Equation A.13 operator   0-3            1           F71      0
 051B                        Equation A.13 operand    0 - 111        1           F72      0
 051C                        Equation A.14 operator   0-3            1           F71      0
 051D                        Equation A.14 operand    0 - 111        1           F72      0
 051E                        Equation A.15 operator   0-3            1           F71      0
 051F                        Equation A.15 operand    0 - 111        1           F72      0
 0520                        Equation B.00 operator   0-1            1           F70      0
 0521                        Equation B.00 operand    0 - 111        1           F72      0
 0522                        Equation B.01 operator   0-3            1           F71      0
 0523                        Equation B.01 operand    0 - 111        1           F72      0
 0524                        Equation B.02 operator   0-3            1           F71      0
 0525                        Equation B.02 operand    0 - 111        1           F72      0
Communications                                                 P12y/EN CT/E95
                                                            MODBUS DATABASE
MiCOM P125/P126 & P127                                            Page 41/148
 Address                                                                           Def.
            Group           Description      Values range    Step   Unit Format
  (hex)                                                                           Value
0526                Equation B.03 operator   0-3             1           F71      0
0527                Equation B.03 operand    0 - 111         1           F72      0
0528                Equation B.04 operator   0-3             1           F71      0
0529                Equation B.04 operand    0 - 111         1           F72      0
052A                Equation B.05 operator   0-3             1           F71      0
052B                Equation B.05 operand    0 - 111         1           F72      0
052C                Equation B.06 operator   0-3             1           F71      0
052D                Equation B.06 operand    0 - 111         1           F72      0
052E                Equation B.07 operator   0-3             1           F71      0
052F                Equation B.07 operand    0 - 111         1           F72      0
0530                Equation B.08 operator   0-3             1           F71      0
0531                Equation B.08 operand    0 - 111         1           F72      0
0532                Equation B.09 operator   0-3             1           F71      0
0533                Equation B.09 operand    0 - 111         1           F72      0
0534                Equation B.10 operator   0-3             1           F71      0
0535                Equation B.10 operand    0 - 111         1           F72      0
0536                Equation B.11 operator   0-3             1           F71      0
0537                Equation B.11 operand    0 - 111         1           F72      0
0538                Equation B.12 operator   0-3             1           F71      0
0539                Equation B.12 operand    0 - 111         1           F72      0
053A                Equation B.13 operator   0-3             1           F71      0
053B                Equation B.13 operand    0 - 111         1           F72      0
053C                Equation B.14 operator   0-3             1           F71      0
053D                Equation B.14 operand    0 - 111         1           F72      0
053E                Equation B.15 operator   0-3             1           F71      0
053F                Equation B.15 operand    0 - 111         1           F72      0
0540                Equation C.00 operator   0-1             1           F70      0
0541                Equation C.00 operand    0 - 111         1           F72      0
0542                Equation C.01 operator   0-3             1           F71      0
0543                Equation C.01 operand    0 - 111         1           F72      0
0544                Equation C.02 operator   0-3             1           F71      0
0545                Equation C.02 operand    0 - 111         1           F72      0
0546                Equation C.03 operator   0-3             1           F71      0
0547                Equation C.03 operand    0 - 111         1           F72      0
0548                Equation C.04 operator   0-3             1           F71      0
0549                Equation C.04 operand    0 - 111         1           F72      0
054A                Equation C.05 operator   0-3             1           F71      0
054B                Equation C.05 operand    0 - 111         1           F72      0
054C                Equation C.06 operator   0-3             1           F71      0
054D                Equation C.06 operand    0 - 111         1           F72      0
P12y/EN CT/E95                                                 Communications
MODBUS DATABASE
Page 42/148                                           MiCOM P125/P126 & P127
 Address                                                                         Def.
           Group           Description      Values range   Step   Unit Format
  (hex)                                                                         Value
054E               Equation C.07 operator   0-3            1           F71      0
054F               Equation C.07 operand    0 - 111        1           F72      0
0550               Equation C.08 operator   0-3            1           F71      0
0551               Equation C.08 operand    0 - 111        1           F72      0
0552               Equation C.09 operator   0-3            1           F71      0
0553               Equation C.09 operand    0 - 111        1           F72      0
0554               Equation C.10 operator   0-3            1           F71      0
0555               Equation C.10 operand    0 - 111        1           F72      0
0556               Equation C.11 operator   0-3            1           F71      0
0557               Equation C.11 operand    0 - 111        1           F72      0
0558               Equation C.12 operator   0-3            1           F71      0
0559               Equation C.12 operand    0 - 111        1           F72      0
055A               Equation C.13 operator   0-3            1           F71      0
055B               Equation C.13 operand    0 - 111        1           F72      0
055C               Equation C.14 operator   0-3            1           F71      0
055D               Equation C.14 operand    0 - 111        1           F72      0
055E               Equation C.15 operator   0-3            1           F71      0
055F               Equation C.15 operand    0 - 111        1           F72      0
0560               Equation D.00 operator   0-1            1           F70      0
0561               Equation D.00 operand    0 - 111        1           F72      0
0562               Equation D.01 operator   0-3            1           F71      0
0563               Equation D.01 operand    0 - 111        1           F72      0
0564               Equation D.02 operator   0-3            1           F71      0
0565               Equation D.02 operand    0 - 111        1           F72      0
0566               Equation D.03 operator   0-3            1           F71      0
0567               Equation D.03 operand    0 - 111        1           F72      0
0568               Equation D.04 operator   0-3            1           F71      0
0569               Equation D.04 operand    0 - 111        1           F72      0
056A               Equation D.05 operator   0-3            1           F71      0
056B               Equation D.05 operand    0 - 111        1           F72      0
056C               Equation D.06 operator   0-3            1           F71      0
056D               Equation D.06 operand    0 - 111        1           F72      0
056E               Equation D.07 operator   0-3            1           F71      0
056F               Equation D.07 operand    0 - 111        1           F72      0
0570               Equation D.08 operator   0-3            1           F71      0
0571               Equation D.08 operand    0 - 111        1           F72      0
0572               Equation D.09 operator   0-3            1           F71      0
0573               Equation D.09 operand    0 - 111        1           F72      0
0574               Equation D.10 operator   0-3            1           F71      0
0575               Equation D.10 operand    0 - 111        1           F72      0
Communications                                                 P12y/EN CT/E95
                                                            MODBUS DATABASE
MiCOM P125/P126 & P127                                            Page 43/148
 Address                                                                           Def.
            Group           Description      Values range    Step   Unit Format
  (hex)                                                                           Value
0576                Equation D.11 operator   0-3             1           F71      0
0577                Equation D.11 operand    0 - 111         1           F72      0
0578                Equation D.12 operator   0-3             1           F71      0
0579                Equation D.12 operand    0 - 111         1           F72      0
057A                Equation D.13 operator   0-3             1           F71      0
057B                Equation D.13 operand    0 - 111         1           F72      0
057C                Equation D.14 operator   0-3             1           F71      0
057D                Equation D.14 operand    0 - 111         1           F72      0
057E                Equation D.15 operator   0-3             1           F71      0
057F                Equation D.15 operand    0 - 111         1           F72      0
0580                Equation E.00 operator   0-1             1           F70      0
0581                Equation E.00 operand    0 - 111         1           F72      0
0582                Equation E.01 operator   0-3             1           F71      0
0583                Equation E.01 operand    0 - 111         1           F72      0
0584                Equation E.02 operator   0-3             1           F71      0
0585                Equation E.02 operand    0 - 111         1           F72      0
0586                Equation E.03 operator   0-3             1           F71      0
0587                Equation E.03 operand    0 - 111         1           F72      0
0588                Equation E.04 operator   0-3             1           F71      0
0589                Equation E.04 operand    0 - 111         1           F72      0
058A                Equation E.05 operator   0-3             1           F71      0
058B                Equation E.05 operand    0 - 111         1           F72      0
058C                Equation E.06 operator   0-3             1           F71      0
058D                Equation E.06 operand    0 - 111         1           F72      0
058E                Equation E.07 operator   0-3             1           F71      0
058F                Equation E.07 operand    0 - 111         1           F72      0
0590                Equation E.08 operator   0-3             1           F71      0
0591                Equation E.08 operand    0 - 111         1           F72      0
0592                Equation E.09 operator   0-3             1           F71      0
0593                Equation E.09 operand    0 - 111         1           F72      0
0594                Equation E.10 operator   0-3             1           F71      0
0595                Equation E.10 operand    0 - 111         1           F72      0
0596                Equation E.11 operator   0-3             1           F71      0
0597                Equation E.11 operand    0 - 111         1           F72      0
0598                Equation E.12 operator   0-3             1           F71      0
0599                Equation E.12 operand    0 - 111         1           F72      0
059A                Equation E.13 operator   0-3             1           F71      0
059B                Equation E.13 operand    0 - 111         1           F72      0
059C                Equation E.14 operator   0-3             1           F71      0
059D                Equation E.14 operand    0 - 111         1           F72      0
P12y/EN CT/E95                                                 Communications
MODBUS DATABASE
Page 44/148                                           MiCOM P125/P126 & P127
 Address                                                                         Def.
           Group           Description      Values range   Step   Unit Format
  (hex)                                                                         Value
059E               Equation E.15 operator   0-3            1           F71      0
059F               Equation E.15 operand    0 - 111        1           F72      0
05A0               Equation F.00 operator   0-1            1           F70      0
05A1               Equation F.00 operand    0 - 111        1           F72      0
05A2               Equation F.01 operator   0-3            1           F71      0
05A3               Equation F.01 operand    0 - 111        1           F72      0
05A4               Equation F.02 operator   0-3            1           F71      0
05A5               Equation F.02 operand    0 - 111        1           F72      0
05A6               Equation F.03 operator   0-3            1           F71      0
05A7               Equation F.03 operand    0 - 111        1           F72      0
05A8               Equation F.04 operator   0-3            1           F71      0
05A9               Equation F.04 operand    0 - 111        1           F72      0
05AA               Equation F.05 operator   0-3            1           F71      0
05AB               Equation F.05 operand    0 - 111        1           F72      0
05AC               Equation F.06 operator   0-3            1           F71      0
05AD               Equation F.06 operand    0 - 111        1           F72      0
05AE               Equation F.07 operator   0-3            1           F71      0
05AF               Equation F.07 operand    0 - 111        1           F72      0
05B0               Equation F.08 operator   0-3            1           F71      0
05B1               Equation F.08 operand    0 - 111        1           F72      0
05B2               Equation F.09 operator   0-3            1           F71      0
05B3               Equation F.09 operand    0 - 111        1           F72      0
05B4               Equation F.10 operator   0-3            1           F71      0
05B5               Equation F.10 operand    0 - 111        1           F72      0
05B6               Equation F.11 operator   0-3            1           F71      0
05B7               Equation F.11 operand    0 - 111        1           F72      0
05B8               Equation F.12 operator   0-3            1           F71      0
05B9               Equation F.12 operand    0 - 111        1           F72      0
05BA               Equation F.13 operator   0-3            1           F71      0
05BB               Equation F.13 operand    0 - 111        1           F72      0
05BC               Equation F.14 operator   0-3            1           F71      0
05BD               Equation F.14 operand    0 - 111        1           F72      0
05BE               Equation F.15 operator   0-3            1           F71      0
05BF               Equation F.15 operand    0 - 111        1           F72      0
05C0               Equation G.00 operator   0-1            1           F70      0
05C1               Equation G.00 operand    0 - 111        1           F72      0
05C2               Equation G.01 operator   0-3            1           F71      0
05C3               Equation G.01 operand    0 - 111        1           F72      0
05C4               Equation G.02 operator   0-3            1           F71      0
05C5               Equation G.02 operand    0 - 111        1           F72      0
Communications                                                 P12y/EN CT/E95
                                                            MODBUS DATABASE
MiCOM P125/P126 & P127                                            Page 45/148
 Address                                                                           Def.
            Group           Description      Values range    Step   Unit Format
  (hex)                                                                           Value
05C6                Equation G.03 operator   0-3             1           F71      0
05C7                Equation G.03 operand    0 - 111         1           F72      0
05C8                Equation G.04 operator   0-3             1           F71      0
050C9               Equation G.04 operand    0 - 111         1           F72      0
05CA                Equation G.05 operator   0-3             1           F71      0
05CB                Equation G.05 operand    0 - 111         1           F72      0
05CC                Equation G.06 operator   0-3             1           F71      0
05CD                Equation G.06 operand    0 - 111         1           F72      0
05CE                Equation G.07 operator   0-3             1           F71      0
05CF                Equation G.07 operand    0 - 111         1           F72      0
05D0                Equation G.08 operator   0-3             1           F71      0
05D1                Equation G.08 operand    0 - 111         1           F72      0
05D2                Equation G.09 operator   0-3             1           F71      0
05D3                Equation G.09 operand    0 - 111         1           F72      0
05D4                Equation G.10 operator   0-3             1           F71      0
05D5                Equation G.10 operand    0 - 111         1           F72      0
05D6                Equation G.11 operator   0-3             1           F71      0
05D7                Equation G.11 operand    0 - 111         1           F72      0
05D8                Equation G.12 operator   0-3             1           F71      0
05D9                Equation G.12 operand    0 - 111         1           F72      0
05DA                Equation G.13 operator   0-3             1           F71      0
05DB                Equation G.13 operand    0 - 111         1           F72      0
05DC                Equation G.14 operator   0-3             1           F71      0
05DD                Equation G.14 operand    0 - 111         1           F72      0
05DE                Equation G.15 operator   0-3             1           F71      0
05DF                Equation G.15 operand    0 - 111         1           F72      0
05E0                Equation H.00 operator   0-1             1           F70      0
05E1                Equation H.00 operand    0 - 111         1           F72      0
05E2                Equation H.01 operator   0-3             1           F71      0
05E3                Equation H.01 operand    0 - 111         1           F72      0
05E4                Equation H.02 operator   0-3             1           F71      0
05E5                Equation H.02 operand    0 - 111         1           F72      0
05E6                Equation H.03 operator   0-3             1           F71      0
05E7                Equation H.03 operand    0 - 111         1           F72      0
05E8                Equation H.04 operator   0-3             1           F71      0
05E9                Equation H.04 operand    0 - 111         1           F72      0
05EA                Equation H.05 operator   0-3             1           F71      0
05EB                Equation H.05 operand    0 - 111         1           F72      0
05EC                Equation H.06 operator   0-3             1           F71      0
05ED                Equation H.06 operand    0 - 111         1           F72      0
P12y/EN CT/E95                                                 Communications
MODBUS DATABASE
Page 46/148                                           MiCOM P125/P126 & P127
 Address                                                                         Def.
           Group           Description      Values range   Step   Unit Format
  (hex)                                                                         Value
05EE               Equation H.07 operator   0-3            1           F71      0
05EF               Equation H.07 operand    0 - 111        1           F72      0
05F0               Equation H.08 operator   0-3            1           F71      0
05F1               Equation H.08 operand    0 - 111        1           F72      0
05F2               Equation H.09 operator   0-3            1           F71      0
05F3               Equation H.09 operand    0 - 111        1           F72      0
05F4               Equation H.10 operator   0-3            1           F71      0
05F5               Equation H.10 operand    0 - 111        1           F72      0
05F6               Equation H.11 operator   0-3            1           F71      0
05F7               Equation H.11 operand    0 - 111        1           F72      0
05F8               Equation H.12 operator   0-3            1           F71      0
05F9               Equation H.12 operand    0 - 111        1           F72      0
05FA               Equation H.13 operator   0-3            1           F71      0
05FB               Equation H.13 operand    0 - 111        1           F72      0
05FC               Equation H.14 operator   0-3            1           F71      0
05FD               Equation H.14 operand    0 - 111        1           F72      0
05FE               Equation H.15 operator   0-3            1           F71      0
05FF               Equation H.15 operand    0 - 111        1           F72      0
Communications                                                                        P12y/EN CT/E95
                                                                                   MODBUS DATABASE
MiCOM P125/P126 & P127                                                                   Page 47/148
  Address                                                                                                          Def.
                        Group             Description              Values range       Step       Unit Format
   (hex)                                                                                                          Value
 0400            Remote control   Remote control word 1            0 -.65535          1               F9           0
 0401                             Calibration mode                                                                 0
 0402                             Remote control word 2            0 --511            1               F39          0
                                  (single output command)
 0403                             Remote control word 3            0 – 65535          1               F9A          0
 0404                             Remote control word 4            0 – 65535          1               F9B          0
 0405                             Keyboard remote control          Binary             1               F81          0
  Address                                                                                                          Def.
                        Group             Description              Values range       Step       Unit Format
   (hex)                                                                                                          Value
0700                              Relays status                                      1       -       F23          0
                                   Address         Nb      Mask
                Timer                                                          Values range                     Unit
                                    (hex)         bytes    (hex)
With private date format:
Year                              0800       2            FFFF     1994-2093                               Years
Month                             0801       1 (Hi)       FF       1 -12                                   Months
Day                                          1 (Lo)       FF       1 - 31                                  Days
Hour                              0802       1 (Hi)       FF       0 - 23                                  Hours
Minute                                       1 (Lo)       FF       0 - 59                                  Minutes
Milliseconds                      0803       2            FFFF     0 - 59999                               ms
With IEC 60870-5-103 format:
                                  0800       1 (Hi)
Year                                         1 (Lo)       7F       94-99 (1994-1999)                       Years
                                                                   0-93 (2000-2093)
Month                             0801       1 (Hi)       0F       1 - 12                                  Months
Day of the week                              1 (Lo)       E0       1 – 7 (Monday – Sunday)                 Days
Day of the month                             1 (Lo)       1F       1 - 31                                  Days
Season                            0802       1 (Hi)       80       0 - 1 (summer – winter)
Hour                                         1 (Hi)       1F       0 - 23                                  Hours
Date validity                                1 (Lo)       80       0 - 1 (valid – invalid)
Minute                                       1 (Lo)       3F       0 - 59                                  Minutes
Milliseconds                      0803       2            FFFF     0 - 59999                               ms
P12y/EN CT/E95                                                                 Communications
MODBUS DATABASE
Page 48/148                                                        MiCOM P125/P126 & P127
                   NOTE:        The disturbance data pages contain the values of one channel from
                                one given disturbance record.
          Line phase current value (primary value) = value x phase primary CT ratio x √2 / 800
          Earth current values calculation formula
          The formula depends of nominal earth current:
          0.1 to 40 Ien range
          Line earth current value (primary value) = value x earth primary CT ratio x √2 / 800
          0.01 to 8 Ien range
          Line earth current value (primary value) = value x earth primary CT ratio x √2 / 3277
          0.002 to 1 Ien range
          Line earth current value (primary value) = value x earth primary CT ratio x √2 / 32700
     −   Frequency channel:
     Time between two samples in microseconds
     −   Logical channels:
         Logical channel 1 (if MODBUS or DNP3 on rear ports)
Words description:
Code                                                                  MODBUS
                          Event meaning                   Format                            Alarm
(Dec)                                                               address (Hex)
01      Control close (Remote, input, HMI)           F9            013
02      Control trip (Remote, input, HMI)            F9            013
03      Disturbance recording start                  F73
04      Trip output unlatch                          F9            013
05      Settings change                              Address
06      Remote thermal reset                         F9
07      Maintenance Mode                             F9↑↓          0402             Auto
08      Control relay in maintenance mode            F39↑↓         013
09      U<                                           F17↑↓         70               Inhib & Self
10      U<<                                          F17↑↓         71               Inhib & Self
11      Pe/Iecos>                                    F16↑↓         72               Yes & Self
12      Pe/Iecos>>                                   F16↑↓         73               Yes & Self
13      I<                                           F17↑↓         21               Yes & Self
14      I2>                                          F17↑↓         7C               Yes & Self
15      I2>>                                         F17↑↓         7D               Yes & Self
16      I2>>>                                        F17↑↓         7E               Yes & Self
17      θ alarm (Thermal overload)                   F37↑↓         020              Yes
18      U>                                           F17↑↓         76               Yes & Self
19      U>>                                          F17↑↓         77               Yes & Self
20      Ue>>>>                                       F16↑↓         7A               Yes & Self
21      I>                                           F17↑↓         14               Yes & Self
22      I>>                                          F17↑↓         15               Yes & Self
23      I>>>                                         F17↑↓         16               Yes & Self
24      Ie>                                          F16↑↓         17               Yes & Self
25      Ie>>                                         F16↑↓         18               Yes & Self
26      Ie>>>                                        F16↑↓         19               Yes & Self
27      U< trip                                      F17↑↓         70               Inhib
28      U<< trip                                     F17↑↓         71               Inhib
29      Pe/Iecos> trip                               F16↑↓         72               Yes
30      Pe/Iecos>> trip                              F16↑↓         73               Yes
31      I< trip                                      F17↑↓         21               Yes
32      I2> trip                                     F17↑↓         7C               Yes
33      I2>> trip                                    F17↑↓         7D               Yes
34      I2>>> trip                                   F17↑↓         7E               Yes
35      θ trip (Thermal overload)                    F37↑↓         20               Yes
36      U> trip                                      F17↑↓         76               Yes
37      U>> trip                                     F17↑↓         77               Yes
38      Ue>>>> trip                                  F16↑↓         7A               Yes
Communications                                                              P12y/EN CT/E95
                                                                         MODBUS DATABASE
MiCOM P125/P126 & P127                                                         Page 59/148
 Code                                                                 MODBUS
                            Event meaning                  Format                           Alarm
 (Dec)                                                              address (Hex)
39       Reserved
40       Reserved
41       Reserved
42       I> trip                                         F17↑↓      14              Yes
43       I>> trip                                        F17↑↓      15              Yes
44       I>>> trip                                       F17↑↓      16              Yes
45       Ie> trip                                        F16↑↓      17              Yes
46       Ie>> trip                                       F16↑↓      18              Yes
47       Ie>>> trip                                      F16↑↓      19              Yes
48       Trip SOTF                                       F38↑↓      23              Yes
49       X1 trip: t AUX3                                 F13        13
50       X1 trip: t AUX4                                 F13        13
51       Equ. Log. A trip                                F48↑↓      7F              Inhib
52       Equ. Log. B trip                                F48↑↓      7F              Inhib
53       Equ. Log. C trip                                F48↑↓      7F              Inhib
54       Equ. Log. D trip                                F48↑↓      7F              Inhib
55       Broken conductor                                F38↑↓      23              Yes
56       t AUX1 trip                                     F38↑↓      23              Inhib
57       t AUX2 trip                                     F38↑↓      23              Inhib
58       CB Flt or SF6 low (by logical input)            F20↑↓      11              Auto
59       Working time                                    F43↑↓      28              Yes
60       Operation numbers                               F43↑↓      28              Yes
61       Sum of switched square amps                     F43↑↓      28              Yes
62       Trip circuit supervision                        F43↑↓      28              Yes
63       Closing time                                    F43↑↓      28              Yes
64       Reclose successful                              F43↑↓      28              Auto
65       Recloser final trip                             F43↑↓      28
66       Recloser settings error                         F43↑↓      28              Auto
67       Circuit Breaker Failure                         F38↑↓      23              Yes
68       Selective scheme logic 1 (by logical input)     F20↑↓      11
69       Selective scheme logic 2 (by logical input)     F20↑↓      11
70       Blocking logic 1 (by logical input)             F20↑↓      11
71       Blocking logic 2 (by logical input)             F20↑↓      11
72       Setting group change                            F55        11
73       O/O (by logical input)                          F20↑↓      11
74       F/O (by logical input)                          F20↑↓      11
75       All alarms acknowledgement (by logical input)   F20↑↓      11
76       Cold load pick up                               F20↑↓      11
77       Input logic state change                        F12↑↓      10
P12y/EN CT/E95                                                                    Communications
MODBUS DATABASE
Page 60/148                                                            MiCOM P125/P126 & P127
Code                                                                      MODBUS
                           Event meaning                      Format                           Alarm
(Dec)                                                                   address (Hex)
78      X1 trip: θ trip                                  F13           13
79      X1 trip: t I>                                    F13           13
80      X1 trip: t I>>                                   F13           13
81      X1 trip: t I>>>                                  F13           13
82      X1 trip: t Ie>                                   F13           13
83      X1 trip: t Ie>>                                  F13           13
84      X1 trip: t Ie>>>                                 F13           13
85      X1 trip: t Pe/Iecos>                             F13           13
86      X1 trip: t Pe/Iecos>>                            F13           13
87      X1 trip: t U<                                    F13           13
88      X1 trip: t U<<                                   F13           13
89      X1 trip: t I<                                    F13           13
90      X1 trip: t U>                                    F13           13
91      X1 trip: t U>>                                   F13           13
92      X1 trip: t I2>                                   F13           13
93      X1 trip: t I2>>                                  F13           13
94      X1 trip: t I2>>>                                 F13           13
95      X1 trip: t Ue>>>>                                F13           13
96      X1 trip: Broken Conductor                        F13           13
97      X1 trip: Equ. Log. A                             F13           13
98      X1 trip: Equ. Log. B                             F13           13
99      X1 trip: Equ. Log. C                             F13           13
100     X1 trip: Equ. Log. D                             F13           13
101     X1 trip: t AUX1                                  F13           13
102     X1 trip: t AUX2                                  F13           13
103     Output relays command                            F39↑↓         402
104     Front panel single alarm acknowledge
105     All alarms front panel acknowledgement
106     Single alarm remote acknowledgement
107     All alarms remote acknowledgement
108     Major material alarm                             F45↑↓         0F               Yes
109     Minor material alarm                             F45↑↓         0F               Yes
110     Operating Latched Relays status                  F27↑↓         2E               Auto
111     General “Start” protection (IEC 60870-5-103      F95↑↓         0B
        protocol)
112     Recloser in “Service” (IEC 60870-5-103 only)     F43↑↓         28
113     52a by recloser (IEC 60870-5-103 protocol)       Cycle
114     Local parameter setting (password active) -      ↑↓
        (IEC 60870-5-103 protocol)
115     Start timer Breaker failure (by logical input)   F20A↑↓        0D
Communications                                                  P12y/EN CT/E95
                                                             MODBUS DATABASE
MiCOM P125/P126 & P127                                             Page 61/148
 Code                                                     MODBUS
                             Event meaning     Format                           Alarm
 (Dec)                                                  address (Hex)
116      t AUX3 trip                         F38↑↓      23              Inhib
117      t AUX4 trip                         F38↑↓      23              Inhib
118      Manual Close (by logical input)     F20A↑↓     0D
119      X1 trip: SOTF                       F38↑↓      23
120      Local Mode (by logical input)       F20A↑↓     0D
121      I>> Blocked                         F38A↑↓     22
122      I>>> Blocked                        F38A↑↓     22
123      VTS                                 F38A↑↓     22              Auto
124      V2>                                 F38A↑↓     22
125      V2>>                                F38A↑↓     22
126      Recloser int locked                 F43↑↓      28              Auto
127      Recloser in progress                F43↑↓      28
128      Synchronization                     F23
129      Inrush blocking                     F38A↑↓     22
130      P>                                  F38A↑↓     22              Yes & Self
131      P>>                                 F38A↑↓     22              Yes & Self
132      P> trip                             F38A↑↓     22              Yes
133      P>> trip                            F38A↑↓     22              Yes
134      X1 trip: t P>                       F13        13
135      X1 trip: t P>>                      F13        13
136      f1                                  F67↑↓      B5              Yes & Self
137      f2                                  F67↑↓      B6              Yes & Self
138      f3                                  F67↑↓      B7              Yes & Self
139      f4                                  F67↑↓      B8              Yes & Self
140      f5                                  F67↑↓      B9              Yes & Self
141      f6                                  F67↑↓      BA              Yes & Self
142      tf1                                 F67↑↓      B5              Yes
143      tf2                                 F67↑↓      B6              Yes
144      tf3                                 F67↑↓      B7              Yes
145      tf4                                 F67↑↓      B8              Yes
146      tf5                                 F67↑↓      B9              Yes
147      tf6                                 F67↑↓      BA              Yes
148      F out                               F69↑↓      BB              Auto
149      X1 trip: tf1 Trip                   F13        13
150      X1 trip: tf2 Trip                   F13        13
151      X1 trip: tf3 Trip                   F13        13
152      X1 trip: tf4 Trip                   F13        13
153      X1 trip: tf5 Trip                   F13        13
154      X1 trip: tf6 Trip                   F13        13
P12y/EN CT/E95                                                      Communications
MODBUS DATABASE
Page 62/148                                              MiCOM P125/P126 & P127
Code                                                        MODBUS
                           Event meaning        Format                            Alarm
(Dec)                                                     address (Hex)
155     Equ. Log. E trip                      F48↑↓      7F               Inhib
156     Equ. Log. F trip                      F48↑↓      7F               Inhib
157     Equ. Log. G trip                      F48↑↓      7F               Inhib
158     Equ. Log. H trip                      F48↑↓      7F               Inhib
159     X1 trip: Equ. Log. E                  F13        13
160     X1 trip: Equ. Log. F                  F13        13
161     X1 trip: Equ. Log. G                  F13        13
162     X1 trip: Equ. Log. H                  F13        13
163     Comm. IEC-103: Signals&Measurements   F78        0668
        blocking
164     Comm. IEC-103: Commands blocking      F78        0668
165     t AUX5 trip                           F38B↑↓     2F               Inhib
166     t AUX6 trip                           F38B↑↓     2F               Inhib
167     t AUX7 trip                           F38B↑↓     2F               Inhib
168     t AUX8 trip                           F38B↑↓     2F               Inhib
169     t AUX9 trip                           F38B↑↓     2F               Inhib
170     t AUX A trip                          F38B↑↓     2F               Inhib
171     t AUX B trip                          F38B↑↓     2F               Inhib
172     t AUX C trip                          F38B↑↓     2F               Inhib
173     X1 trip: t AUX5                       F13        13
174     X1 trip: t AUX6                       F13        13
175     X1 trip: t AUX7                       F13        13
176     X1 trip: t AUX8                       F13        13
177     X1 trip: t AUX9                       F13        13
178     X1 trip: t AUXA                       F13        13
179     X1 trip: t AUXB                       F13        13
180     X1 trip: t AUXC                       F13        13
181     Start Earth (for IEC-103)
182     Ie>>>>                                F16↑↓      1A               Yes & Self
183     Ie>>>> trip                           F16↑↓      1A               Yes
184     X1 trip: t Ie>>>>                     F13        13
185     Reset LEDs (by logical input)         F20B↑↓     BE
186     CTS                                   F38A↑↓     24               Auto
187     df/dt1                                F94↑↓      BF               Yes
188     df/dt2                                F94↑↓      BF               Yes
189     df/dt3                                F94↑↓      BF               Yes
190     df/dt4                                F94↑↓      BF               Yes
191     df/dt5                                F94↑↓      BF               Yes
192     df/dt6                                F94↑↓      BF               Yes
193     X1 trip: df/dt1 Trip                  F13        13
Communications                                                                 P12y/EN CT/E95
                                                                            MODBUS DATABASE
MiCOM P125/P126 & P127                                                            Page 63/148
 Code                                                                   MODBUS
                          Event meaning                  Format                              Alarm
 (Dec)                                                                address (Hex)
194      X1 trip: df/dt2 Trip                         F13            13
195      X1 trip: df/dt3 Trip                         F13            13
196      X1 trip: df/dt4 Trip                         F13            13
197      X1 trip: df/dt5 Trip                         F13            13
198      X1 trip: df/dt6 Trip                         F13            13
199      Recloser ext locked                          F43↑↓          28               Auto
200      P<                                           F38A↑↓         22               Yes & Self
201      P<<                                          F38A↑↓         22               Yes & Self
202      P< trip                                      F38A↑↓         22               Yes
203      P<< trip                                     F38A↑↓         22               Yes
204      X1 trip: t P<                                F13            13
205      X1 trip: t P<<                               F13            13
206      Q>                                           F38B↑↓         2F               Yes & Self
207      Q>>                                          F38B↑↓         2F               Yes & Self
208      Q> trip                                      F38B↑↓         2F               Yes
209      Q>> trip                                     F38B↑↓         2F               Yes
210      X1 trip: t Q>                                F13            13
211      X1 trip: t Q>>                               F13            13
212      Q<                                           F38B↑↓         2F               Yes & Self
213      Q<<                                          F38B↑↓         2F               Yes & Self
214      Q< trip                                      F38B↑↓         2F               Yes
215      Q<< trip                                     F38B↑↓         2F               Yes
216      X1 trip: t Q<                                F13            13
217      X1 trip: t Q<<                               F13            13
218      Comm order 1                                 F9A            0403
219      Comm order 2                                 F9A            0403
220      Comm order 3                                 F9A            0403
221      Comm order 4                                 F9A            0403
222      “General Trip” (IEC 60870-5-103 protocol)    F95↑↓          0B
223      Trip Phase A (IEC 60870-5-103 protocol)      F17↑↓          14/15/16 or
                                                                     76/77 or 70/71
224      Trip Phase B (IEC 60870-5-103 protocol)      F17↑↓          14/15/16 or
                                                                     76/77 or 70/71
225      Trip Phase C (IEC 60870-5-103 protocol)      F17↑↓          14/15/16 or
                                                                     76/77 or 70/71
226      General reset command                        F9A            0403
Words description:
     CODE                                       DESCRIPTION
 F1         Unsigned integer: numerical data 0 to 65535
 F2         Signed integer: numerical data -32768 to 32767
 F3         Unsigned integer: trip / reset curves type (hex values)
            0       : DMT
            10      : IEC STI
            11      : IEC SI
            12      : IEC VI
            13      : IEC EI
            14      : IEC LTI
            115     : C02
            116     : IEEE MI
            117     : CO8
            118     : IEEE VI
            119     : IEEE EI
            1A      : RECT
            20      : RI
 F4         Unsigned integer: UART Baud rate
            0: 300
            1: 600
            2: 1200
            3: 2400
            4: 4800
            5: 9600
            6: 19200
            7: 38400
 F5         Unsigned integer: Modbus and DNP3 parity bit
            0: none
            1: even
            2: odd
 F6         Unsigned integer: conf. tripping on relay RL1, part 1
            Bit 0: tI>
            Bit 1: tI>>
            Bit 2: tI>>>
            Bit 3: tIe>
            Bit 4: tIe>>
            Bit 5: tIe>>>
            Bit 6: tI<
            Bit 7: θ trip
            Bit 8: broken conductor trip
            Bit 9: AUX 1 trip
            Bit 10: AUX 2 trip
            Bit 11: tI2>
            Bit 12: tPe/Iecos>
            Bit 13: tPe/Iecos>>
            Bit 14: tUe>>>>
            Bit 15: Control trip
P12y/EN CT/E95                                                              Communications
MODBUS DATABASE
Page 70/148                                                     MiCOM P125/P126 & P127
 CODE                                        DESCRIPTION
F6A     Unsigned integer: conf. tripping on relay RL1, part 2
        Bit 0: tU>
        Bit 1: tU>>
        Bit 2: tU<
        Bit 3: tU<<
        Bit 4: t Boolean equation A
        Bit 5: t Boolean equation B
        Bit 6: t Boolean equation C
        Bit 7: t Boolean equation D
        Bit 8: tI2>>
        Bit 9: tI2>>>
        Bit 10: tP >
        Bit 11: tP >>
        Bit 12: Reserved
        Bit 13: AUX 3 trip
        Bit 14: AUX 4 trip
        Bit 15: SOTF/TOR
F6B     Unsigned integer: conf. tripping on relay RL1, part 3
        Bit 0: t Aux 8
        Bit 1: t Aux 9
        Bit 2: t Aux A
        Bit 3: t Aux B
        Bit 4: t Aux C
        Bit 5: df/dt1
        Bit 6: df/dt2
        Bit 7: df/dt3
        Bit 8: df/dt4
        Bit 9: df/dt5
        Bit 10: df/dt6
        Bit 11: tQ>
        it 12: tQ>>
        Bit 13: tQ<
        Bit 14: tQ<<
        Bit 15: Not used
Communications                                                       P12y/EN CT/E95
                                                                  MODBUS DATABASE
MiCOM P125/P126 & P127                                                  Page 71/148
  CODE                                       DESCRIPTION
F7       Unsigned integer: U connection mode
         0: 3Vpn
         2: 2Vpp + Vr
         4: 2Vpn + Vr
F8       Unsigned integer: blocking logic configuration, part 1
         Bit 0: tU>
         Bit 1: tU>>
         Bit 2: tU<
         Bit 3: tU<<
         Bit 4: aux3 trip
         Bit 5: aux4 trip
         Bit 6: t P<
         Bit 7: t P<<
         Bit 8: tI2>>
         Bit 9: tI2>>>
         Bit 10: tP >
         Bit 11: tP >>
         Bit 12: t Q>
         Bit 13: t Q>>
         Bit 14: t Q<
         Bit 15: t Q<<
P12y/EN CT/E95                                                          Communications
MODBUS DATABASE
Page 72/148                                                      MiCOM P125/P126 & P127
 CODE                                        DESCRIPTION
F8B     Unsigned integer: blocking logic configuration, part 3
        Bit 0: tF1
        Bit 1: tF2
        Bit 2: tF3
        Bit 3: tF4
        Bit 4: tF5
        Bit 5: tF6
        Bit 6: Reserve
        Bit 7: Reserve
        Bit 8: tAux 5
        Bit 9: tAux 6
        Bit 10: tAux 7
        Bit 11: tAux 8
        Bit 12: tAux 9
        Bit 13: tAux A
        Bit 14: tAux B
        Bit 15: tAux C
F8C     Unsigned integer: blocking logic configuration, part 4
        Bit 0: df/dt1
        Bit 1: df/dt2
        Bit 2: df/dt3
        Bit 3: df/dt4
        Bit 4: df/dt5
        Bit 5: df/dt6
        Bit 6: reserve
        Bit 7: reserve
        Bit 8: reserve
        Bit 9: reserve
        Bit 10: reserve
        Bit 11: reserve
        Bit 12: reserve
        Bit 13: reserve
        Bit 14: reserve
        Bit 15: reserve
F9      Unsigned integer: remote control 1
  CODE                                          DESCRIPTION
F9A      Previously F50 format
         Unsigned integer: remote control word number 3
         Bit 0: flag sync. harmonic earth current
         Bit 1: LEDs reset
         Bit 2: energy reset
         Bit 3: oldest disturbance acknowledge
         Bit 4: rolling average values reset
         Bit 5: rolling max sub-period values reset
         Bit 6: Communication Order 1
         Bit 7: Communication Order 2
         Bit 8: Communication Order 3
         Bit 9: Communication Order 4
         Bit 10: Not used
         Bit 11: Not used
         Bit 12: SA²n counter reset
         Bit 13: Trips counter reset
         Bit 14: General reset command
         Bit 15: Not used
F9B      Bit 0: Settings group 1 selection
         Bit 1: Settings group 2 selection
         Bit 2: Settings group 3 selection
         Bit 3: Settings group 4 selection
         Bit 4: Settings group 5 selection
         Bit 5: Settings group 6 selection
         Bit 6: Settings group 7 selection
         Bit 7: Settings group 8 selection
F10      Unsigned integer: 2 ASCII characters
 CODE                                       DESCRIPTION
F13     Unsigned integer: logic outputs status
  CODE                                        DESCRIPTION
F14B     Unsigned integer: Rl2 - RL8 output configuration for tAux3 & tAux4
 CODE                                        DESCRIPTION
F15     Unsigned integer: digital inputs configuration, part 1
  CODE                                       DESCRIPTION
F16      Unsigned integer: earth threshold (current, voltage & power) information status
         Bit 0: I>
         Bit 1: tI>
         Bit 2: I>>
         Bit 3: tI>>
         Bit 4: I>>>
         Bit 5: tI>>>
         Bit 6: Ie>
         Bit 7: tIe>
         Bit 8: Ie>>
         Bit 9: tIe>>
         Bit 10: Ie>>>
         Bit 11: tIe>>>
         Bit 12: θ trip
         Bit 13: tI2>
         Bit 14: broken conductor trip
         Bit 15: breaker failure trip
P12y/EN CT/E95                                                     Communications
MODBUS DATABASE
Page 78/148                                                 MiCOM P125/P126 & P127
 CODE                                      DESCRIPTION
F19A    Unsigned integer: leds configuration mask, part 2
        Bit 0: U>
        Bit 1: tU>
        Bit 2: U>>
        Bit 3: tU>>
        Bit 4: U<
        Bit 5: tU<
        Bit 6: U<<
        Bit 7: tU<<
        Bit 8: tI2>>
        Bit 9: tI<
        Bit 10: tI> phase A
        Bit 11: tI> phase B
        Bit 12: tI> phase C
        Bit 13: digital input 6
        Bit 14: digital input 7
        Bit 15: tI2>>>
F19C    Unsigned integer: leds configuration mask, part 4
        Bit 0: I2>
        Bit 1: I2>>
        Bit 2: I2>>>
        Bit 3: I<
        Bit 4: tAux3
        Bit 5: tAux4
        Bit 6: P >
        Bit 7: tP >
        Bit 8: P >>
        Bit 9: tP >>
        Bit 10: VTS
        Bit 11: 51V
        Bit 12: P<
        Bit 13: tP<
        Bit 14: P<<
        Bit 15: tP<<
Communications                                                          P12y/EN CT/E95
                                                                     MODBUS DATABASE
MiCOM P125/P126 & P127                                                     Page 79/148
  CODE                                       DESCRIPTION
F19D     Unsigned integer: leds configuration mask, part 5
         Bit 0: f1
         Bit 1: tf1
         Bit 2: f2
         Bit 3: tf2
         Bit 4: f3
         Bit 5: tf3
         Bit 6: f4
         Bit 7: tf4
         Bit 8: f5
         Bit 9: tf5
         Bit 10: f6
         Bit 11: tf6
         Bit 12: out of frequency
         Bit 13: Q >
         Bit 14: tQ >
         Bit 15: Q >>
F19E     Unsigned integer: leds configuration mask, part 6
         Bit 0: Equ. A
         Bit 1: Equ. B
         Bit 2: Equ. C
         Bit 3: Equ. D
         Bit 4: Equ. E
         Bit 5: Equ. F
         Bit 6: Equ. G
         Bit 7: Equ. H
         Bit 8: tAux 5 (P126-P127).
         Bit 9: tAux 6 (P126-P127).
         Bit 10: tAux 7 (P126-P127).
         Bit 11: tQ>>
         Bit 12: Q<
         Bit 13: tQ<
         Bit 14: Q<<
         Bit 15: tQ<<
F19F     Unsigned integer: leds configuration mask, part 7 (only with p127 optional board)
         Bit 0: t Aux 8.
         Bit 1: t Aux 9
         Bit 2: t Aux A
         Bit 3: t Aux B
         Bit 4: t Aux C
         Bit 5: reserve
         Bit 6: reserve
         Bit 7: reserve
         Bit 8: digital input 8.
         Bit 9: digital input 9.
         Bit 10: digital input A.
         Bit 11: digital input B.
         Bit 12: digital input C
         Bit 13: reserve
         Bit 14: reserve
         Bit 15: reserve
P12y/EN CT/E95                                                      Communications
MODBUS DATABASE
Page 80/148                                                  MiCOM P125/P126 & P127
 CODE                                         DESCRIPTION
F19G    Unsigned integer: leds configuration mask, part 8
        Bit 0: df/dt 1
        Bit 1: df/dt 2
        Bit 2: df/dt 3
        Bit 3: df/dt 4
        Bit 4: df/dt 5
        Bit 5: df/dt 6
        Bit 6: Ie>>>>
        Bit 7: tle>>>>
        Bit 8: CTS
        Bit 9: [79] Ext locked
        Bit 10: reserve
        Bit 11: reserve
        Bit 12: reserve
        Bit 13: reserve
        Bit 14: reserve
        Bit 15: reserve
F20     Unsigned integer: logic inputs data status, part 1
  CODE                                       DESCRIPTION
F20B     Unsigned integer: logical inputs status, part 3
         0: NO
         1: YES
         2: DIR
         3: PEAK
F24B     Unsigned integer: threshold operating mode
         0: NO
         1: AND
         2: OR
F24C     Unsigned integer: 32N protection operating mode
 CODE                                       DESCRIPTION
F27     Unsigned integer: RL1 - RL8 output relays latch configuration and status
        0: no records available
        1: one events record available
        2: two events records available
        3: three events records available
        4: four events records available
        5: five events records available
F31A    Unsigned integer: numbers of default records to display
  CODE                                       DESCRIPTION
F33      Unsigned integer: cold load start thresholds
         Bit 0: tI>
         Bit 1: tI>>
         Bit 2: tI>>>
         Bit 3: tIe>
         Bit 4: tIe>>
         Bit 5: tIe>>>
         Bit 6: θ trip
         Bit 7: tI2>
         Bit 8: tI2>>
         Bit 9: tI2>>>
         Bit 10: tIe>>>>
         Bit 11: Not used
         Bit 12: Not used
         Bit 13: Not used
         Bit 14: Not used
         Bit 15: Not used
F34      Unsigned integer: threshold reset timer type
         0: DMT
         1: IDMT
F35      Unsigned integer: disturbance recording status
         Bit 0: Ie>
         Bit 1: tIe>
         Bit 2: Ie>>
         Bit 3: tIe>>
         Bit 4: Ie>>>
         Bit 5: tIe>>>
         Bit 6: tIe>REV
         Bit 7: tIe>> REV
         Bit 8: tIe>>>REV
         Bit 9: thermal alarm (θ alarm)
         Bit 10: thermal trip (θ trip)
         Bit 11: broken conductor trip
         Bit 12: breaker failure trip
         Bit 13: Ie>>>>
         Bit 14: AUX1 trip
         Bit 15: AUX2 trip
P12y/EN CT/E95                                                            Communications
MODBUS DATABASE
Page 84/148                                                   MiCOM P125/P126 & P127
 CODE                                        DESCRIPTION
F36A    Unsigned integer: non acknowledged memorised alarms flags, part 2
        Bit 0: U<
        Bit 1: tU<
        Bit 2: U<<
        Bit 3: tU<<
        Bit 4: U>
        Bit 5: tU>
        Bit 6: U>>
        Bit 7: tU>>
        Bit 8: Ue>>>>
        Bit 9: tUe>>>>
        Bit 10: recloser internally locked
        Bit 11: recloser successful
        Bit 12: I2>>
        Bit 13: tI2>>
        Bit 14: I2>>>
        Bit 15: tI2>>>
F36C    Unsigned integer: non acknowledged memorised alarms flags, part 4
  CODE                                        DESCRIPTION
F36D     Unsigned integer: non acknowledged memorised alarms flags, part 5
         Bit 0: f1
         Bit 1: tf1
         Bit 2: f2
         Bit 3: tf2
         Bit 4: f3
         Bit 5: tf3
         Bit 6: f4
         Bit 7: tf4
         Bit 8: f5
         Bit 9: tf5
         Bit 10: f6
         Bit 11: tf6
         Bit 12: t Boolean Equation E
         Bit 13: t Boolean Equation F
         Bit 14: t Boolean Equation G
         Bit 15: t Boolean Equation H
F36E     Unsigned integer: non acknowledged memorised alarms flags, part 6
         Bit 0: Q<
         Bit 1: tQ<
         Bit 2: Q<<
         Bit 3: tQ<<
         Bit 4: dfdt 1
         Bit 5: dfdt 2
         Bit 6: dfdt 3
         Bit 7: dfdt 4
         Bit 8: dfdt 5
         Bit 9: dfdt 6
         Bit 10: Recloser externally locked
         Bit 11: Ctrl Trip
         Bit 12: CTS
         Bit 13: Not used
         Bit 14: Not used
         Bit 15: Not used
P12y/EN CT/E95                                                    Communications
MODBUS DATABASE
Page 86/148                                                MiCOM P125/P126 & P127
 CODE                                        DESCRIPTION
F37     Unsigned integer: thermal overload information
  CODE                                      DESCRIPTION
F38B     Unsigned integer: accessory functions, part 3
         Bit 0: tI>>
         Bit 1: tI>>>
         Bit 2: tIe>>
         Bit 3: tIe>>>
         Bit 4: tIe>>>>
         Bits 5 to 15: Reserved
F41      Unsigned integer: remote communication configuration
         5: 5 min
         10: 10 min
         15: 15 min
         30: 30 min
         60: 60 min
P12y/EN CT/E95                                                          Communications
MODBUS DATABASE
Page 88/148                                                      MiCOM P125/P126 & P127
 CODE                                        DESCRIPTION
F43     Unsigned integer
        Bit x =
               0 Æ active when de-energized
               1 Æ active when energized;
        Bit 0: input 1
        Bit 1: input 2
        Bit 2: input 3
        Bit 3: input 4
        Bit 4: input 5
        Bit 5: input 6
        Bit 6: input 7
        Bit 7: input 8 (optional board)
        Bit 8: input 9 (optional board)
        Bit 9: input A (optional board)
        Bit 10: input B (optional board)
        Bit 11: input C (optional board)
        Bits 12 to 15: Reserved
Communications                                                         P12y/EN CT/E95
                                                                    MODBUS DATABASE
MiCOM P125/P126 & P127                                                    Page 89/148
  CODE                                        DESCRIPTION
F48      Unsigned integer: Boolean Equation Status
         Bit 0: Reserved
         Bit 1: t Boolean Equation A
         Bit 2: t Boolean Equation B
         Bit 3: t Boolean Equation C
         Bit 4: t Boolean Equation D
         Bit 5: Temporisation A, B,- or H active
         Bit 6: t Boolean Equation E
         Bit 7: t Boolean Equation F
         Bit 8: t Boolean Equation G
         Bit 9: t Boolean Equation H
         Bits 10 to 15: Reserved
F49      Unsigned integer: calibration status flag
         0: calibration KO
         1: calibration OK
F50      Has been replaced by F9A ( F50 is kept for compatibility reasons
F51      Unsigned integer: digital inputs signal type
         0: DC
         1: AC
F52      Unsigned integer: date and time format
         IEC 60870-5-103:
               0: 9600
               1: 19200
         DNP3.0:
               0: 1200
               1: 2400
               2: 4800
               3: 9600
               4: 19200
               5: 38400
P12y/EN CT/E95                                                              Communications
MODBUS DATABASE
Page 90/148                                                    MiCOM P125/P126 & P127
 CODE                                        DESCRIPTION
F54     Unsigned integer: Digital inputs configuration mode, part 1:
  CODE                                         DESCRIPTION
F56      Unsigned integer: Fail safe and inversion relays
 CODE                                        DESCRIPTION
F61     Unsigned integer: Information on the starting origin of the RL1 trip relay
        01 - Remote X1 trip
        02 - θ trip (Thermal overload)
        03 - I> trip
        04 - I>> trip
        05 - I>>> trip
        06 - Ie> trip
        07 - Ie>> trip
        08 - Ie>>> trip
        09 - I< trip
        10 - Broken conductor trip
        11 - U< trip
        12 - U<< trip
        13 - Pe/Iecos> trip
        14 - Pe/Iecos>> trip
        15 - I2> trip
        16 - I2>> trip
        17 - I2>>> trip
        18 - U> trip
        19 - U>> trip
        20 - Ue>>>> trip
        21 - Aux 1 trip
        22 - Aux 2 trip
        23 - AND Logic equate A trip
        24 - AND Logic equate B trip
        25 - AND Logic equate C trip
        26 - AND Logic equate D trip
        27 - Aux 3 trip
        28 - Aux 4 trip
        29 - SOTF
        30 - P >
        31 - P >>
        32 - f1
        33 - f2
        34 - f3
        35 - f4
        36 - f5
        37 - f6
        38 - AND Logic equate E trip
        39 - AND Logic equate F trip
        40 - AND Logic equate G trip
        41 - AND Logic equate H trip
        42 - t Aux 5 ( P126-7 )
        43 - t Aux 6 ( P126-7 )
        44 - t Aux 7 ( P126-7 )
        45 - t Aux 8 ( P127 with logical inputs 8-12 )
        46 - t Aux 9 ( P127 with logical inputs 8-12 )
        47 - t Aux A ( P127 with logical inputs 8-12 )
        48 - t Aux B ( P127 with logical inputs 8-12 )
        49 - t Aux C ( P127 with logical inputs 8-12 )
        50 - Ie>>>> trip
        51 - P <
        52 - P <<
        53 - Q >
        54 - Q >>
        55 - Q <
        56 - Q <<
        ... See next page
Communications                                                                 P12y/EN CT/E95
                                                                            MODBUS DATABASE
MiCOM P125/P126 & P127                                                            Page 93/148
  CODE                                              DESCRIPTION
F61           Unsigned integer: Information on the starting origin of the RL1 trip relay
(following)
              57 – df/dt1
              58 – df/dt2
              59 – df/dt3
              60 – df/dt4
              61 – df/dt5
              62 – df/dt6
F62           Unsigned integer: LED status (bit = 0 if LED inactive)
              00 - French
              01 - English
              02 - Spanish
              03 - German
              04 - Italian
              05 - Russian
              06 - Polish
              07 - Portuguese
              08 - Dutch
              09 - American
              10 - Czech
              11 - Hungarian
              12 - Greek
              13 – Chinese
              14 - Turkish
              Other - Language by default (product code)
F64           Unsigned integer: Alarms inhibition part 1
 CODE                                        DESCRIPTION
F64A    Unsigned integer: Alarms inhibition part 2
        0: No
        1: Protection under frequency 81<
        2: Protection over frequency 81>
F69     Unsigned integer: frequency measurement status
        Bit 0: F out
        Bit 1: F out because of U min
Communications                                                        P12y/EN CT/E95
                                                                   MODBUS DATABASE
MiCOM P125/P126 & P127                                                   Page 95/148
  CODE                                     DESCRIPTION
F70      Unsigned integer: 1st Operator for Boolean equations
         0: Nothing
         1: NOT
F71      Unsigned integer: Other than 1st Operator for Boolean equations
         0: OR
         1: OR NOT
         2: AND
         3: AND NOT
F72      Unsigned integer: Operand for Boolean equations
         0: NULL
         1: I>
         2: tI>
         3: I>>
         4: tI>>
         5: I>>>
         6: tI>>>
         7: Ie>
         8: tIe>
         9: Ie>>
         10: tIe>>
         11: Ie>>>
         12: tIe>>>
         13: Pe/IeCos>
         14: tPe/IeCos >
         15: Pe/IeCos >>
         16: tPe/IeCos >>
         17: I2>
         18: tI2>
         19: I2>>
         20: tI2>>
         21: I2>>>
         22: tI2>>>
         23: Thermal alarm (Ith>)
         24: Thermal tripping (Ith>>)
         25: I<
         26: tI<
         27: U>
         28: tU>
         29: U>>
         30: tU>>
         31: U<
         32: tU<
         33: U<<
         34: tU<<
         35: Ue>>>>
         36: tUe>>>>
         37: Broken conductor
         38: Tripping 79
         39: tAux1
         40: tAux2
         41: tAux3
         42: tAux4
         43: P>
         44: tP>
         ... See next page
P12y/EN CT/E95                                                         Communications
MODBUS DATABASE
Page 96/148                                                     MiCOM P125/P126 & P127
  CODE                                            DESCRIPTION
F72           Unsigned integer: Operand for Boolean equations
(following)
              45: P>>
              46: tP>>
              47: F1
              48: tF1
              49: F2
              50: tF2
              51: F3
              52: tF3
              53: F4
              54: tF4
              55: F5
              56: tF5
              57: F6
              58: tF6
              59: VTS
              61: tAux 6 ( P126-P127 )
              62: tAux 7 ( P126-P127 )
              63: tAux 8 (P127 with logical inputs 8-12)
              64: tAux 9 (P127 with logical inputs 8-12)
              65: tAux A (P127 with logical inputs 8-12)
              66: tAux B (P127 with logical inputs 8-12)
              67: tAux C (P127 with logical inputs 8-12)
              68: Input 1
              69: Input 2
              70: Input 3
              71: Input 4
              72: Input 5( P126-P127 )
              73: Input 6( P126-P127 )
              74: Input 7( P126-P127 )
              75: Input 8 (P127 with Inputs 8-12)
              76: Input 9 (P127 with Inputs 8-12)
              77: Input A (P127 with Inputs 8-12)
              78: Input B (P127 with Inputs 8-12)
              79: Input C (P127 with Inputs 8-12)
              80: Ie>>>>
              81: tIe>>>>
              82: [79] int. lock
              83: [79] ext. lock
              84: tEquation A
              85: tEquation B
              86: tEquation C
              87: tEquation D
              88: tEquation E
              89: tEquation F
              90: tEquation G
              60: tAux 5 ( P126-P127 )
              91: tEquation H
              92: CB Fail
              93: CTS
              94: df/dt1
              95: df/dt2
              96: df/dt3
              97: df/dt4
              98: df/dt5
              99: df/dt6
              100: P<
              ... See next page
Communications                                                                 P12y/EN CT/E95
                                                                            MODBUS DATABASE
MiCOM P125/P126 & P127                                                            Page 97/148
  CODE                                             DESCRIPTION
F72           Unsigned integer: Operand for Boolean equations
(following)
              101: tP<
              102: P<<
              103: tP<<
              104: Q>
              105: tQ>
              106: Q>>
              107: tQ>>
              108: Q<
              109: tQ<
              110: Q<<
              111: tQ<<
F73           Unsigned integer: Source of the disturbance recording start
              0: None
              1: On trip protection
              2: On instantaneous protection
              3: On communication order
              4: On logic input order
              5: No disturbance
              6: On HMI order
F74           Unsigned integer: Spontaneous event enabling for IEC870-5-103 communication
              0: Logical.
              1: Modulated.
F78           Unsigned integer: IEC870-5-103 communication blocking ( 0 = enabled ; 1 = blocked )
 CODE                                          DESCRIPTION
F79     Unsigned integer: Date-and-time synchronisation origin:
        0: None
        1: IRIG-B, if configured
        2: Logical input, if configured
        3: Communication rear port 1
        4: Communication rear port 2, if option configured
F80     Unsigned integer: Optional board
Only one bit simultaneously. The bit active simulate a pressure on the key.
  CODE                                           DESCRIPTION
F83      Unsigned integer: Inrush blocking configuration
         bit 0: I>
         bit 1: I>>
         bit 2: I>>>
         bit 3: IE>
         bit 4: IE>>
         bit 5: IE>>>
         bit 6: reserved
         bit 7: reserved
         bit 8: reserved
         bit 9: reserved
         bit 10: reserved
         bit 11: I2>
         bit 12: I2>>
         bit 13: I2>>>
         bit 14: IE>>>>
         bit 15: reserved
F84      VT protection
         0: V P-P
         1: V P-N
F85      Phases and Earth labels
 CODE                                        DESCRIPTION
F92     CTS Activation and CTS Mode (Futur use)
        0: CTS inhibited
        1: I2/I1
        2: Null current
        3: I Diff
        4: I Earth
F93     IEC870-5-103 communication: GI selection
        0: Basic GI
        1: Advanced GI
F94     Unsigned integer: df/dt protection flags
        Bit 0: df/dt1
        Bit 1: df/dt2
        Bit 2: df/dt3
        Bit 3: df/dt4
        Bit 4: df/dt5
        Bit 5: df/dt6
F95     IEC870-5-103 communication: Info General Start / General Trip
        Bit 0: General Start
        Bit 1: General Trip
F96     F1 value except if less than 100 ( 1.00% )
        In that case Td demand is equal to Iam Td demand ( modbus address 06D4 )
Communications                                                                 P12y/EN CT/E95
                                                                            MODBUS DATABASE
MiCOM P125/P126 & P127                                                           Page 101/148
        This request may generate an error message with the error code:
                  EVT_NOK(OF):           No record available
                  NOTE:          If there are less than 5 records available, the answer will contain zero
                                 in non-used words.
4.1.3   Service requests
        This request must be sent before uploading the disturbance record channel samples. It
        allows knowing the record number and the channel number to upload.
        It allows also knowing the number of samples in the channel.
        This request may generate an error message with two different error codes:
                  CODE_DEF_RAM(02):                Failure
                  CODE_EVT_NOK(03):                No disturbance record available
4.1.4   Disturbance record upload request
        This request may geberate an error message with two different error codes:
                  CODE_DEP_DATA(04):               The required disturbance data number is greater than
                                                   the memorised number.
                  CODE_SERV_NOK(05):               The service request for disturbance record and
                                                   channel number has not been sent.
4.1.5   Index frame upload request
        This event request may generate an error message with the error code:
              EVT_EN_COURS_ECRIT (5):            An event is being written into the saved RAM.
                 NOTE:         On event retrieval, two possibilities exist regarding the event record
                               acknowledgement:
                               − Automatic event record acknowledgement on event retrieval:
        This event request may generate an error message with the error code:
              EVT_EN_COURS_ECRIT (5):            An event is being written into the saved RAM.
                 NOTE:         This event retrieval does not acknowledge this event.
4.1.8   Modbus request definition used to retrieve the fault records
        Two ways can be followed to retrieve a fault record:
                   NOTE:         On fault retrieval, two possibilities exist regarding the fault record
                                 acknowledgement:
                                 a)   Automatic fault record acknowledgement on event retrieval.
                                      Bit12 of the remote order frame (format F9 – mapping address
                                      0400h) shall be set to 0. On fault retrieval, this fault record is
                                      acknowledged.
                                 b)   Non automatic fault record acknowledgement on fault retrieval:
                                      Bit12 of the remote order frame (format F9 – mapping address
                                      0400h) shall be set to 1. On fault retrieval, this fault record is not
                                      acknowledged.
                                      To acknowledge this fault, another remote order shall be sent to
                                      the relay. Bit 14 of this frame (format F9 – mapping address
                                      0400h) shall be set to 1.
4.1.8.2   Request to retrieve a dedicated fault record
           NOTE:     This fault value retrieval does not acknowledge this fault record.
Communications                          P12y/EN CT/E95
                             IEC 60870-5-103 DATABASE
MiCOM P125/P126 & P127                     Page 105/148
            IEC 60870-5-103
               DATABASE
              MiCOM P125-P126 – V12
                  P127 – V13.A
P12y/EN CT/E95                                 Communications
IEC 60870-5-103 DATABASE
Page 106/148                            MiCOM P125/P126 & P127
                           BLANK PAGE
Communications                                     P12y/EN CT/E95
                                        IEC 60870-5-103 DATABASE
MiCOM P125/P126 & P127                                Page 107/148
CONTENTS
                           BLANK PAGE
Communications                                                               P12y/EN CT/E95
                                                                  IEC 60870-5-103 DATABASE
MiCOM P125/P126 & P127                                                          Page 109/148
        −    Signals&measurements
             blocking active:                           FUN<160>;INF <20>; TYP <1>; COT<1> ↑↓
      −   Group warning
          (Minor hardware alarm):              FUN<160>;INF <46>; TYP <1>; COT<1> ↑↓
      −   Group alarm
          (Major hardware alarm):              FUN<160>;INF <47>; TYP <1>; COT<1> ↑↓
      Start Indications (monitor direction):
      P127 + P126 + P125
P127 only
      −    Signals&measurements
           blocking active:                          FUN<160>;INF <20>; TYP <1>; COT<9>
P127 + P126
      −   Group warning
          (Minor hardware alarm):              FUN<160>;INF <46>; TYP <1>; COT<9>
      −   Group alarm
          (Major hardware alarm):              FUN<160>;INF <47>; TYP <1>; COT<9>
      Start Indications (monitor direction):
      P127 + P126 + P125
Availability
      Each identification message of the relay (ASDU 5) contains the manufacturer name in 8
      ASCII characters (“Schneider Electric”) and 2 free bytes containing: « 127 » or « 126 », or
      « 125 » in decimal format, then 2 free bytes containing the software version number in
      decimal (for ex.: 112 corresponds to “11.C”).
P12y/EN CT/E95                                                                   Communications
IEC 60870-5-103 DATABASE
Page 122/148                                                      MiCOM P125/P126 & P127
− RMS Ia
− RMS Ib
      −   RMS Ic
      P127 only
− RMS Ua
− RMS Ub
− RMS Uc
− P
− Q
− RMS IN,
      −   RMS Un.
      In first ASDU 77, which is a private ASDU,       FUN<168>;INF <209>; TYP <77>; COT<2>
      The following values are stored (in IEEE 32 bits floating-point format):
− I1 (module, unit: V)
− I2 (module, unit: V)
P127 only
− fault Ia ^ Ubc angle (unit= degree, 0 to 360): FUN <243> INF <15>
− fault Ib ^ Uca angle (unit= degree, 0 to 360): FUN <243> INF <16>
− fault Ic ^ Uab angle (unit= degree, 0 to 360): FUN <243> INF <17>
                  BLANK PAGE
Communications                                                          P12y/EN CT/E95
                                                                      DNP3.0 DATABASE
MiCOM P125/P126 & P127                                                    Page 129/148
CONTENT
                  BLANK PAGE
Communications                                                                      P12y/EN CT/E95
                                                                                  DNP3.0 DATABASE
MiCOM P125/P126 & P127                                                                Page 131/148
1.          DNP-3 PROTOCOL
1.1         Purpose of this document
            The purpose of this document is to describe the specific implementation of the Distributed
            Network Protocol (DNP) 3.0 within P12y MiCOM relays.
            P12y uses the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library Version 2.18.
            This document, in conjunction with the DNP 3.0 Basic 4 Document Set, and the DNP Subset
            Definitions Document, provides complete information on how to communicate with P12y via
            the DNP 3.0 protocol.
            This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 2,
            contains many Subset Level 3 features, and contains some functionality even beyond
            Subset Level 3.
1.2         DNP V3.00 Device Profile
            The following table provides a “Device Profile Document” in the standard format defined in
            the DNP 3.0 Subset Definitions Document. While it is referred to in the DNP 3.0 Subset
            Definitions as a “Document,” it is only a component of a total interoperability guide. This
            table,    in    combination     with     the   following should   provide     a    complete
            interoperability/configuration guide for P12y:
− and the Point List Tables provided in Section 4.4 (beginning on page 137).
     DNP V3.00
     DEVICE PROFILE DOCUMENT
     (Also see the Implementation Table in Section 1.3, beginning on page 134).
     Vendor Name: Schneider Electric
     Device Name: SERIAL 20 Platform using the Triangle MicroWorks, Inc. DNP 3.0 Slave
            Source Code Library, Version 2.18.
     Highest DNP Level Supported:                     Device Function:
            For Requests: Level 2                            7       Master
            For Responses: Level 2                           
       Slave
     Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
     Supported (the complete list is described in the attached table):
     For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-
     stop), 07 and 08 (limited quantity), and 17 and 28 (index) are supported in addition to
     request qualifier code 06 (no range – or all points).
     Static object requests received with qualifiers 00, 01, 06, 07, or 08, will be responded with
     qualifiers 00 or 01. Static object requests received with qualifiers 17 or 28 will be
     responded with qualifiers 17 or 28.
     For change-event object requests, qualifiers 17 or 28 are always responded.
     16-bit and 32-bit Analog Change Events with Time may be requested.
     The read function code for Object 50 (Time and Date), variation 1, is supported.
     Maximum Data Link Frame Size (octets):           Maximum Application Fragment Size (octets):
           Transmitted:   292                               Transmitted:   2048
           Received       292                               Received:      2048
     Maximum Data Link Re-tries:                      Maximum Application Layer Re-tries:
          7 None
          
 Fixed at 2                                        
    None
          7 Configurable                                      7    Configurable
P12y/EN CT/E95                                                                  Communications
DNP3.0 DATABASE
Page 132/148                                                         MiCOM P125/P126 & P127
 DNP V3.00
 DEVICE PROFILE DOCUMENT
 (Also see the Implementation Table in Section 1.3, beginning on page 134).
 Requires Data Link Layer Confirmation:
   
 Never
   
 Always
   
 Sometimes
   
 Configurable
 Requires Application Layer Confirmation:
   
 Never
   
 Always
   
 When reporting Event Data
   
 When sending multi-fragment responses
   
 Sometimes
   
 Configurable
 Timeouts while waiting for:
 Others:
 Binary input change scanning period:     5ms
 Analog input change scanning period:     1s
 Sends/Executes Control Operations:
 DNP V3.00
 DEVICE PROFILE DOCUMENT
 (Also see the Implementation Table in Section 1.3, beginning on page 134).
 Sends Unsolicited Responses:                   Sends Static Data in Unsolicited Responses:
   
    Never                                      
      Never
   
    Configurable                               
      When Device Restarts
   
    Only certain objects                       
      When Status Flags Change
   
    Sometimes (attach explanation)
   
    ENABLE/DISABLE UNSOLICITED              No other options are permitted.
   
    Function codes supported
 Default Counter Object/Variation:              Counters Roll Over at:
   
    Yes
   
    No
P12y/EN CT/E95                                                                                                         Communications
DNP3.0 DATABASE
Page 134/148                                                                                        MiCOM P125/P126 & P127
                                                                             REQUEST                                    RESPONSE
                            OBJECT
                                                                       (Library will parse)                      (Library will respond with)
 Object    Variation                                              Function Codes       Qualifier                  Function         Qualifier
                                       Description                     (dec)
 Number    Number                                                                   Codes (hex)                  Codes (dec)      Codes (hex)
   1           0            Binary Input (Variation 0 is used    1         (read) 00, 01 (start-stop)
                                                                                         06 (no range, or all)
                            to request default variation)
                                                                                         07, 08 (limited qty)
                                                                                         17, 28       (index)
      1          1          Binary Input                         1             (read)    00, 01 (start-stop)     129   (response)   00, 01   (start-stop)
             (default –                                          22                      06 (no range, or all)                      17, 28      (index –
            see note 1)                                                                  07, 08 (limited qty)                                see note 2)
                                                                                         17, 28       (index)
      1          2          Binary Input with Status             1            (read)     00, 01 (start-stop)     129   (response)   00, 01   (start-stop)
                                                                                         06 (no range, or all)                      17, 28      (index –
                                                                                         07, 08 (limited qty)                                see note 2)
                                                                                         17, 28        (index
      2          0          Binary Input Change (Variation 0     1            (read)     06 (no range, or all)
                                                                                         07, 08 (limited qty)
                            is used to request default
                            variation)
      2     1(default –     Binary Input Change without          1            (read)     06 (no range, or all)   129   (response)   17, 28       (index)
           see note 1 for                                                                07, 08 (limited qty)
                            Time
           P120 - P121)
      2          2          Binary Input Change with Time        1            (read)     06 (no range, or all)   129   (response)   17, 28       (index)
             (default –                                                                  07, 08 (limited qty)
            see note 1)
      10         0          Binary Output Status (Variation 0    1            (read)     00, 01 (start-stop)
                                                                                         06 (no range, or all)
                            is used to request default
                                                                                         07, 08 (limited qty)
                            variation)                                                   17, 28       (index)
      10         2          Binary Output Status                 1            (read)     00, 01 (start-stop)     129   (response)   00, 01   (start-stop)
             (default –                                                                  06 (no range, or all)                      17, 28      (index –
            see note 1)                                                                  07, 08 (limited qty)                                see note 2)
                                                                                         17, 28       (index)
      12         1          Control Relay Output Block           3            (select)   00, 01 (start-stop)     129   (response)     echo of request
                                                                 4         (operate)     07, 08 (limited qty)
                                                                 5        (direct op)    17, 28       (index)
                                                                 6 (dir. op, noack)
      20         0          Binary Counter (Variation 0 is       1              (read)   00, 01 (start-stop)
                                                                 7           (freeze)    06 (no range, or all)
                            used to request default variation)
                                                                 8 (freeze noack)        07, 08 (limited qty)
                                                                 9 (freeze clear)        17, 28       (index)
                                                                 10 (frz. cl. Noack)
      20         1          32-Bit Binary Counter                1              (read)   00, 01 (start-stop)     129   (response)   00, 01   (start-stop)
                                                                 7           (freeze)    06 (no range, or all)                      17, 28      (index –
                                                                 8 (freeze noack)        07, 08 (limited qty)                                see note 2)
                                                                 9 (freeze clear)        17, 28       (index)
                                                                 10 (frz. cl. Noack)
      20         2          16-Bit Binary Counter                1              (read)   00, 01 (start-stop)     129   (response)   00, 01   (start-stop)
                                                                 7           (freeze)    06 (no range, or all)                      17, 28      (index –
                                                                 8 (freeze noack)        07, 08 (limited qty)                                see note 2)
                                                                 9 (freeze clear)        17, 28       (index)
                                                                 10 (frz. cl. Noack)
      20         5          32-Bit Binary Counter without        1              (read)   00, 01 (start-stop)     129   (response)   00, 01   (start-stop)
                                                                 7           (freeze)    06 (no range, or all)                      17, 28      (index –
                            Flag
                                                                 8 (freeze noack)        07, 08 (limited qty)                                see note 2)
                                                                 9 (freeze clear)        17, 28       (index)
                                                                 10 (frz. cl. Noack)
      20         6          16-Bit Binary Counter without        1              (read)   00, 01 (start-stop)     129   (response)   00, 01   (start-stop)
                                                                 7           (freeze)    06 (no range, or all)                      17, 28      (index –
                            Flag
                                                                 8 (freeze noack)        07, 08 (limited qty)                                see note 2)
                                                                 9 (freeze clear)        17, 28       (index)
                                                                 10 (frz. cl. Noack)
Communications                                                                                              P12y/EN CT/E95
                                                                                                          DNP3.0 DATABASE
MiCOM P125/P126 & P127                                                                                        Page 135/148
                                                                       REQUEST                                  RESPONSE
                       OBJECT
                                                                 (Library will parse)                    (Library will respond with)
Object   Variation                                          Function Codes      Qualifier                 Function         Qualifier
                                  Description                    (dec)
Number   Number                                                               Codes (hex)                Codes (dec)      Codes (hex)
  21         0         Frozen Counter (Variation 0 is       1          (read)   00, 01 (start-stop)
                                                                                06 (no range, or all)
                       used to request default variation)
                                                                                07, 08 (limited qty)
                                                                                17, 28       (index)
  21         1         32-Bit Frozen Counter                1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  21         2         16-Bit Frozen Counter                1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  21         9         32-Bit Frozen Counter without        1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                       Flag
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  21        10         16-Bit Frozen Counter without        1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                       Flag
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  30         0         Analog Input (Variation 0 is used    1          (read)   00, 01 (start-stop)
                                                                                06 (no range, or all)
                       to request default variation)
                                                                                07, 08 (limited qty)
                                                                                17, 28       (index)
  30         1         32-Bit Analog Input                  1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
          (default –                                                            06 (no range, or all)                       17, 28      (index –
         see note 1                                                             07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  30         2         16-Bit Analog Input                      1      (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  30         3         32-Bit Analog Input without Flag     1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  30         4         16-Bit Analog Input without Flag     1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28       (index)
  32         0         Analog Change Event (Variation       1          (read)   06 (no range, or all)
                                                                                07, 08 (limited qty)
                       0 is used to request default
                       variation)
  32         1         32-Bit Analog Change Event           1          (read)   06 (no range, or all)    129   (response)   17, 28        (index)
          (default –                                                            07, 08 (limited qty)
                       without Time
         see note 1)
  32         2         16-Bit Analog Change Event           1          (read)   06 (no range, or all)    129   (response)   17, 28        (index)
                                                                                07, 08 (limited qty)
                       without Time
  32         3         32-Bit Analog Change Event with      1          (read)   06 (no range, or all)    129   (response)   17, 28        (index)
                                                                                07, 08 (limited qty)
                       Time
  32         4         16-Bit Analog Change Event with      1          (read)   06 (no range, or all)    129   (response)   17, 28        (index)
                                                                                07, 08 (limited qty)
                       Time
  50         0         Time and Date                        1          (read)   00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
                                                                                06 (no range, or all)                       17, 28      (index –
                                                                                07, 08 (limited qty)                                 see note 2)
                                                                                17, 28         (index)
  50         1         Time and Date                        1         (read)    00, 01 (start-stop)      129   (response)   00, 01   (start-stop)
          (default –                                        2         (write)   06 (no range, or all)                       17, 28      (index –
         see note 1)                                                            07    (limited qty=1)                                see note 2)
                                                                                08       (limited qty)
                                                                                17, 28         (index)
  52         2         Time Delay Fine                                                                   129   (response)   07       (limited qty)
                                                                                                                                         (qty = 1)
  60         0         Class 0, 1, 2, and 3 Data            1          (read)   06 (no range, or all)
1.4.2    Binary Output Status Points and Control Relay Output Blocks
         The following table lists both the Binary Output Status Points (Object 10) and the Control
         Relay Output Blocks (Object 12). Binary Output Status points are not included in class 0
         polls.
1.4.3    Counters
         The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21).
         When a freeze function is performed on a Binary Counter point, the frozen value is available
         in the corresponding Frozen Counter point.
         Binary Counters and Frozen Counters are not included in class 0 polls.
         P125 do not support binary Counters and Frozen Counters.
 Binary Counters
 Static (Steady-State) Object Number: 20
 Change Event Object Number:            not supported
 Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack)
                                        9 (freeze and clear), 10 (freeze and clear, noack)
 Static Variation reported when variation 0 requested:   5 (32-Bit Binary Counter without Flag
 Change Event Variation reported when variation 0 requested: none-not supported
 Frozen Counters
 Static (Steady-State) Object Number: 21
 Change Event Object Number:              not supported
 Request Function Codes supported:        1 (read)
 Static Variation reported when variation 0 requested:   9 (32-Bit Frozen Binary without Flag)
 Change Event Variation reported when variation 0 requested: none-not supported
 P126    P127
 Point   Point                                Name/Description                             Data type
 Index   Index
 0       0       Max RMS current phase A (A/100)                                      D1
 1       1       Max RMS current phase B (A/100)                                      D1
 2       2       Max RMS current phase C (A/100)                                      D1
 3       3       Average RMS current phase A (A/100)                                  D1
 4       4       Average RMS current phase B (A/100)                                  D1
 5       5       Average RMS current phase C (A/100)                                  D1
 6       6       CB operation number                                                  D2
 7       7       sa2n ia                                                              D3
 8       8       sa2n ib                                                              D3
 9       9       sa2n ic                                                              D3
 10      10      Total number of autoreclosure cycle                                  D2
 11      11      Number of cycles 1                                                   D2
 12      12      Number of cycles 2                                                   D2
 13      13      Number of cycles 3                                                   D2
 14      14      Number of cycles 4                                                   D2
 15      15      Definitive Tripping number                                           D2
 16      16      Number of closing order                                              D2
 17      17      Rolling demand(average) RMS phase A (A/100)                          D1
 18      18      Rolling demand(average) RMS phase B (A/100)                          D1
 19      19      Rolling demand(average) RMS phase C (A/100)                          D1
 20      20      Maximum RMS phase A (after a new initialization) (A/100)             D1
 21      21      Maximum RMS phase B (after a new initialization) (A/100)             D1
 22      22      Maximum RMS phase C (after a new initialization) (A/100)             D1
         23      Positive active energy (kWh/100)                                     D1
         24      Negative active energy (kWh/100)                                     D1
         25      Positive reactive energy (kVARh/100)                                 D1
         26      Negative reactive energy (kVARh/100)                                 D1
         27      Max RMS voltage phase A (V/100)                                      D1
         28      Max RMS voltage phase B (V/100)                                      D1
         29      Max RMS voltage phase C (V/100)                                      D1
         30      Average RMS voltage phase A (V/100)                                  D1
         31      Average RMS voltage phase B (V/100)                                  D1
         32      Average RMS voltage phase C (V/100)                                  D1
         33      Apparent energy (kVAh/100)                                           D1
Communications                                                                          P12y/EN CT/E95
                                                                                      DNP3.0 DATABASE
MiCOM P125/P126 & P127                                                                    Page 145/148
 Analog Inputs
 Static (Steady-State) Object Number: 30
 Change Event Object Number: 32
 Request Function Codes supported:        1 (read)
 Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
 Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
 Time)
 Change Event Scan Rate:         The scan rate for analog input change events is fixed at 1s
                                                                                                        Initial
                                                                                          Change
 P125    P126    P127                                  Scaling and Units                               Change
                                            Initial                                        Event
 Point   Point   Point   Name/Description              (representation of   Valid Range              Event Class
                                            Value                                          Dead-
 Index   Index   Index                                32767 – see above)                              (1, 2, 3 or
                                                                                           band
                                                                                                        none)
   0      0       0      Active Group         1             32767              1à2           1             1
          1       1      Magnitude IA         0              40 In           0 to 40 In   0.02 In         3
          2       2      Magnitude IB         0              40 In           0 to 40 In   0.02 In         3
          3       3      Magnitude IC         0              40 In           0 to 40 In   0.02 In         3
   1      4       4      Magnitude IN         0             40 IEn          0 to 40 IEn   0.02 IEn        3
          5       5      rms IA              0A            327.67A              0 to                      3
                                                                             40000000       2%
                                                                               A/100
          6       6      rms IB              0A            327.67A              0 to                      3
                                                                             40000000       2%
                                                                               A/100
          7       7      rms IC              0A            327.67A              0 to                      3
                                                                             40000000       2%
                                                                               A/100
   2      8       8      rms IN              0A            327.67A              0 to                      3
                                                                             40000000       2%
                                                                               A/100
                  9      rms VA              0V            327.67V              0 to                      3
                                                                            500000000       2%
                                                                               V/100
                  10     rms VB              0V            327.67V              0 to                      3
                                                                            500000000       2%
                                                                               V/100
                  11     rms VC              0V            327.67V              0 to                      3
                                                                            500000000       2%
                                                                               V/100
   3      9       12     rms VN              0V            327.67V              0 to                      3
                                                                            500000000       2%
                                                                               V/100
                  13     Magnitude VA         0           260V G1*           0 to 260V     0.5V           3
                                                          960V G2*           0 to 960V      2V
P12y/EN CT/E95                                                                              Communications
DNP3.0 DATABASE
Page 146/148                                                                 MiCOM P125/P126 & P127
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported:        1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
Time)
Change Event Scan Rate:         The scan rate for analog input change events is fixed at 1s
                                                                                                          Initial
                                                                                             Change
P125    P126    P127                                    Scaling and Units                                Change
                                             Initial                                          Event
Point   Point   Point    Name/Description               (representation of   Valid Range               Event Class
                                             Value                                            Dead-
Index   Index   Index                                  32767 – see above)                               (1, 2, 3 or
                                                                                              band
                                                                                                          none)
                 14     Magnitude VB           0           260V G1*          0 to 260V        0.5V           3
                                                           960V G2*          0 to 960V         2V
                 15     Magnitude VC           0           260V G1*          0 to 260V        0.5V          3
                                                           960V G2*          0 to 960V         2V
 4       10      16     Magnitude VN           0           260V G1*          0 to 260V        0.5V          3
                                                           960V G2*          0 to 960V         2V
         11      17     Thermal State         0%            32767%           0 to 65535        10           3
 5       12      18     Frequency              0           327,67 Hz           45Hz to        1Hz           3
                                                                              65 Hz and
                                                                             99.99Hz ==
                                                                               ERROR
         13      19     Magnitude I2           0              40 In           0 to 40 In     0.1 In         3
         14      20     Magnitude I1           0              40 In           0 to 40 In     0.1 In         3
                 21     Magnitude V2           0           260V G1*           0 to 260V       0.5V          3
                                                           960V G2*           0 to 960V        2V
                 22     Magnitude V1           0           260V G1*           0 to 260V       0.5V          3
                                                           960V G2*           0 to 960V        2V
                 23     RMS active 3-phase     0           327.67kW          -9.999 E8 to                   3
                        power                                                  9.999 E8       2%
                                                                                kW/100
                 24     RMS reactive 3-        0           327.67kVAr        -9.999 E8 to                   3
                        phase power                                            9.999 E8       2%
                                                                               kVAr/100
 6       15      25     Harmonic power Pe      0            327.67 W         -9.999 E8 to                   3
                                                                               9.999 E8       2%
                                                                                W/100
 7       16      26     Harmonic power         0            327.67 A         -9.999 E8 to                   3
                        IeCos                                                  9.999 E8       2%
                                                                                 A/100
 8       17      27     Angle Ie ^ Ue          0             32767            0 to 360 °       1°           3
                 28     3-phase CosPhi         0                             -100 to 100                    3
                                                                               (1/100)         2
         18      29     Tripping Time          0            327.67s          0 to 10.00s     10 ms          3
         19      30     Closing Time           0            327.67s          0 to 10.00s     10 ms          3
         20      31     Fault number           0             32767           0 to 65535        1            2
         21      32     group                  0             32767              1 to 2      each new        2
                                                                                              fault
         22      33     Fault phase            0             32767            0 to 8 (F1)   each new        2
                                                                                              fault
         23      34     Fault origin           0             32767               0 to       each new        2
                                                                                  29          fault
                                                                                 (F2)
         24      35     Fault magnitude        0              40 In           0 to 40 In    each new        2
                                                                                              fault
         25      36     Fault magnitude IA     0              40 In           0 to 40 In    each new        2
                                                                                              fault
         26      37     Fault magnitude IB     0              40 In           0 to 40 In    each new        2
                                                                                              fault
         27      38     Fault magnitude IC     0              40 In           0 to 40 In    each new        2
                                                                                              fault
         28      39     Fault magnitude IN     0             40 IEn          0 to 40 IEn    each new        2
                                                                                              fault
                 40     Fault magnitude VA     0           260V G1*           0 to 260V     each new        2
                                                           960V G2*           0 to 960V       fault
Communications                                                                             P12y/EN CT/E95
                                                                                         DNP3.0 DATABASE
MiCOM P125/P126 & P127                                                                       Page 147/148
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported:        1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
Time)
Change Event Scan Rate:         The scan rate for analog input change events is fixed at 1s
                                                                                                            Initial
                                                                                              Change
P125    P126    P127                                      Scaling and Units                                Change
                                               Initial                                         Event
Point   Point   Point    Name/Description                 (representation of   Valid Range               Event Class
                                               Value                                           Dead-
Index   Index   Index                                    32767 – see above)                               (1, 2, 3 or
                                                                                               band
                                                                                                            none)
                  41    Fault magnitude VB       0           260V G1*           0 to 260V     each new         2
                                                             960V G2*           0 to 960V       fault
                  42    Fault magnitude VC       0           260V G1*           0 to 260V     each new        2
                                                             960V G2*           0 to 960V       fault
         29       43    Fault magnitude Ue       0           260V G1*           0 to 260V     each new        2
                                                             960V G2*           0 to 960V       fault
                  44    Fault angle IA ^ UBC     0            32767             0 to 360 °    each new        2
                                                                                                fault
                  45    Fault angle IB ^ UCA     0             32767            0 to 360 °    each new        2
                                                                                                fault
                  46    Fault angle IC ^ UAB     0             32767            0 to 360 °    each new        2
                                                                                                fault
         30       47    Fault angle Ie ^ Ue      0             32767            0 to 360 °    each new        2
                                                                                                fault
                  48    RMS apparent power       0           327.67kVA         -9.999 E8 to                   3
                                                                                 9.999 E8       2%
                                                                                 kVA/100
         31       49    Angle Ia ^ Ib            0             32767            0 to 360 °      1°            3
         32       50    Angle Ia ^ Ic            0             32767            0 to 360 °      1°            3
                  51    Angle Ia ^ Va            0             32767            0 to 360 °      1°            3
                        Or Angle Ia ^ Uab
                  52    Angle Ia ^ Vb            0             32767            0 to 360 °      1°            3
                        Or Angle Ia ^ Ubc
                  53    Angle Ia ^ Vc            0             32767            0 to 360 °      1°            3
                        Or Angle Ia ^ Uca
         33       54    Angle Ia ^ Ue            0             32767            0 to 360 °      1°            3
        Format:
        F1:
        0: None, 1: Phase A, 2: Phase B, 4: Phase C, 3: Phase AB, 5: Phase AC, 6: Phase BC, 7:
        Phase A B C, 8: Earth.
        F2:
        0: Null, 1: Remote trip, 2: thermal overload, 3: tI>, 4: tI>>, 5: tI>>>, 6: tIN>, 7: tIN>>, 8:
        tIN>>>, 9: tI<, 10: broken conductor, 11: tU<, 12: tU<<, 13: Pe/Iecos>, 14: Pe/Iecos>>, 15:
        tI2>, 16: tI2>>, 17: tI2>>>, 18: tU>, 19: tU>>, 20: tUN>>>>, 21: tAux1, 22: tAux2, 23: tEqu.A,
        24: tEqu.B, 25: tEqu.C, 26: tEqu.D, 27:tAux3, 28: tAux4, 29: SOTF, 30: tP>, 31: tP>>, 32:
        tF1, 33: tF2, 34: tF3, 35: tF4, 36: tF5, 37: tF6, 38: tEqu.E, 39: tEqu.F, 40: tEqu.G, 41: tEqu.H.
P12y/EN CT/E95                        Communications
DNP3.0 DATABASE
Page 148/148                   MiCOM P125/P126 & P127
                  BLANK PAGE
Commissioning and Maintenance   P12y/EN CM/E95
      COMMISSIONING AND
      MAINTENANCE GUIDE
Commissioning and Maintenance                       P12y/EN CM/E95
CONTENT
4.      SETTING CHECK                                           10
4.1     Settings                                                10
4.2     Measurements                                            10
4.2.1   MiCOM P125                                              10
4.2.2   MiCOM P126                                              11
4.2.3   MiCOM P127                                              11
4.3     Thresholds validation                                   12
4.3.1   MiCOM settings                                          12
4.3.2   Earth current and neutral voltage test                  15
4.4     Final checks                                            19
5.      MAINTENANCE                                             20
5.1     Equipment failure                                       20
5.1.1   Minor fault                                             20
5.1.2   Major fault                                             20
5.1.3   Hardware and software faults                            20
P12y/EN CM/E95                          Commissioning and Maintenance
      •     Extracting the settings applied to the relay using the appropriate setting software
            (preferred method),
                                        P1                                S1
                                        P2                                S2
                               Other ends
                           of electrical cables
                                                                        P0041ENa
                                        P1              S1               _
                                                                + mA
                           +
                           _
P2 S2
P0043ENa
                                                         OP. PARAMETERS/Inputs
                 Input          MiCOM P12x models
                                                             Satuts. cell value
              Opto input 1                                        7654321
                                 P125, P126, P127
            22-24 Terminals                                       0000001
              Opto input 2                                        7654321
                                 P125, P126, P127
            26-28 Terminals                                       0000010
              Opto input 3                                        7654321
                                 P125, P126, P127
            17-19 Terminals                                       0000100
              Opto input 4                                        7654321
                                 P125, P126, P127
            21-23 Terminals                                       0001000
              Opto input 5                                        7654321
                                    P126, P127
            25-27 Terminals                                       0010000
              Opto input 6                                        7654321
                                    P126, P127
            58-60 Terminals                                       0100000
              Opto input 7                                        7654321
                                    P126, P127
            57-59 Terminals                                       1000000
             Opto input 8                                         CBA98
                                        P127 (1)
            61-62 terminals                                       00001
             Opto input 9                                         CBA98
                                        P127 (1)
            64-62 terminals                                       00010
             Opto input 10                                        CBA98
                                        P127 (1)
            63-62 terminals                                       00100
             Opto input 11                                        CBA98
                                        P127 (1)
            66-62 terminals                                       01000
             Opto input 12                                        CBA98
                                        P127 (1)
            65-62 terminals                                       10000
      (1)
            Available only for P127 “5 opto-inputs” option (product codes P127xx1 or P127xx3).
            “Input COM – terminal” 62 is the common terminal for inputs 8 to 12.
Commissioning and Maintenance                                                   P12y/EN CM/E95
                                                                         OP. PARAMETERS/Relay
             OUTPUT RELAYS                  MiCOM P125 range
                                                                             Status. cell value
       WD Relay Terminals 35-37            P125, P126 and P127                  Normal close
       RL 1 Change over type.
       Terminals:                          P125, P126 and P127                   00000001
       2 Common -4 NC-6 NO
       RL 2 Change over type.
       Terminals:                          P125, P126 and P127                   00000010
       8 Common -10 NC-12 NO
       RL 3 Terminals 14-16                P125, P126 and P127                   00000100
       RL 4 Terminals 18-20                P125, P126 and P127                   00001000
       RL 5 Terminals 1-3                  P125, P126 and P127                   00010000
       RL 6 Terminals 7-8                  P125, P126 and P127                   00100000
       RL 7 Terminals 9-11                     P126 and P127                     01000000
       RL 8 Terminals 13-15                    P126 and P127                     10000000
4.      SETTING CHECK
        The setting checks must ensure that all relay settings have been correctly applied to the
        relay for the specific application.
        Transfer the setting file to the relay using a laptop PC running the appropriate software via
        the RS232 front port or the RS485 rear port.
        This is the preferred setting transfer method, because it is faster and there are fewer margins
        for errors.
        If the setting software is not used, the relay settings must be checked manually via the relay
        front panel interface.
        The commissioning checks are as follows:
        1.    Settings verify and delivery to customer,
        2.    Validation of the measurements,
        3.    Validation of the thresholds and associated timers.
4.1     Settings
        Log the settings on the commissioning test sheets.
4.2     Measurements
        The MiCOM P125 P126 P127 relays measure phase and earth currents, phase (phase to
        phase) voltage, zero sequence voltage as a True RMS value up to the 10th harmonics. The
        value(s) indicated take account of the phase and/or earth CT ratio and VT ratio.
        WARNING:        MiCOM P125 P126 P127 RELAYS HAVE 1 AND 5 A CURRENT INPUTS,
                        AND 57 –130V OR 220 – 480V VOLTAGE INPUT.
                        CHECK THAT THE INJECTED CURRENT AND VOLTAGE ARE
                        COMPATIBLE WITH THE SELECTED RANGE.
        •     Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
              value shown on the LCD taking in account the relevant nominal current.
        •     Apply earth voltage to 39-40 terminals and verify in measurements menu the UN value
              shown on LCD.
        •     Log the results to the Commissioning test sheets (Applied value and relay value
              displayed).
Commissioning and Maintenance                                                  P12y/EN CM/E95
• Note the select phase and earth CTs ratio and neutral VT ratio.
        •    Apply current to input terminals 49-50 (In=1A) or 41-42 (In=5A) and verify the IA value
             shown on the LCD.
        •    Apply current to input terminals 51-52 (In=1A) or 43-44 (In=5A) and verify the IB value
             shown on the LCD.
        •    Apply current to input terminals 53-54 (In=1A) or 45-46 (In=5A) and verify the IC value
             shown on the LCD.
        •    Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
             values on the LCD in relay measurement menu.
        •    Apply earth voltage to 73-74 terminals and verify the UN values on the LCD in relay
             measurement menu.
        •    Log the results to the Commissioning test sheets (Applied values and relay values
             displayed).
4.2.3   MiCOM P127
        •    Note the select phase and earth CTs ratio, phase voltage VTs ratio and neutral
             voltage VTs ratio.
        •    Apply current to input terminals 49-50 (In=1A) or 41-42 (In=5A) and verify the IA value
             shown on the LCD.
        •    Apply current to input terminals 51-52 (In=1A) or 43-44 (In=5A) and verify the IB value
             shown on the LCD.
        •    Apply current to input terminals 53-54 (In=1A) or 45-46 (In=5A) and verify the IC value
             shown on the LCD.
        •    Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
             values on the LCD in relay measurement menu.
        •    Apply voltage to inputs terminals 69-70 and 71-72 and verify the UAB and UBC values
             in relay measurement menu on the LCD.
        •    Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
             value in relay measurement menu on the LCD.
        •    Apply voltage to inputs terminals 73-74 and verify the UN value in relay measurement
             menu on the LCD.
        Log the results to the Commissioning test sheets (Applied values and relay values
        displayed).
P12y/EN CM/E95                                             Commissioning and Maintenance
                            Configuration Menu
                              Transfo. Ratio
          E/Gnd CT primary           1A
          E/Gnd CT Sec               1A
          E/Gnd VT primary           0.100 kV
          E/Gnd VT Sec               100.0 V
                             Protection Menu
          Ie>                        Yes
          Ie>                        1 Ien
          tIe>                       DT or IDMT or RI
          tIe> (if DT)               10 s
          Curve (if IDMT)            IEC VI or IEEE VI
          TMS value (if IDMT)        1
          K value (if RI)            1
          Ue>>>>                     10 V
          tUe>>>>                    10 s
                            Automation Menu
          TRIP tIe>                  YES
          TRIP tUe>>>>               YES
Commissioning and Maintenance                            P12y/EN CM/E95
                            Configuration menu
                              Transfo. Ratio
          Line CT primary            1A
          Line CT Sec                1A
          E/Gnd CT primary           1A
          E/Gnd CT Sec               1A
          E/Gnd VT primary           0.100 kV
          E/Gnd VT Sec               100.0 V
                            Protection Menu G1
          I>                         Yes
          I>                         1 In
          tI>                        DT or IDMT or RI
          tI>                        (if DT) 10 s
          Curve (if IDMT)            IEC VI or IEEE VI
          TMS value (if IDMT)        1
          K value (if RI)            1
          Ie>                        Yes
          Ie>                        1 In
          tIe>                       DT or IDMT or RI
          tIe> (if DT)               20 s
          Curve (if IDMT)            IEC VI or IEEE VI
          TMS value (if IDMT)1       K value (if RI)1
          Ue>>>>                     10V
          tUe>>>>                    10 s
                             Automation Menu
          TRIP tI>                   YES
          TRIP tIe>                  YES
          TRIP tUe>>>>               YES
P12y/EN CM/E95                                           Commissioning and Maintenance
                            CONFIGURATION
                             General Options
                                 2Vpp+Vr
                              Transfo. Ratio
          Line CT primary            1A
          Line CT Sec                1A
          E/Gnd CT primary           1A
          E/Gnd CT Sec               1A
          Line VT primary            0.100 kV
          Line VT Sec                100.0 V
          E/Gnd VT primary           0.100 kV
          E/Gnd VT Sec               100.0 V
                            Protection Menu G1
          I>                         Yes
          I>                         1 In
          tI>                        DT or IDMT or RI
          tI> (if DT)                10 s
          Curve (if IDMT)            IEC VI or IEEE VI
          TMS value (if IDMT)        1
          K value (if RI)            1
          U>                         Yes
          U>                         20V
          tU>                        10 s
          Ie>                        Yes
          Ie>                        1 In
          tIe>                       DT or IDMT or RI
          tIe> (if DT)               20 s
          Curve (if IDMT)            IEC VI or IEEE VI
          TMS value (if IDMT)1       K value (if RI)=1
          Ue>>>>                     10 V
          tUe>>>>                    10 s
                             Automation Menu
          TRIP tI>                   YES
          TRIP tU>                   YES
          TRIP tIe>                  YES
          TRIP Ue>>>>                YES
Commissioning and Maintenance                                                     P12y/EN CM/E95
          •     Supply the relay, inject current and voltage with magnitude greater then Ie> and
                Ue>>>> setting value.
          •     If the time delay tIe> is short, gradually increases injection current up to the value of
                the Ie> threshold.
          •     If the time delay tIe> is long, inject 0.95 x I threshold and check that there is no
                tripping. Then inject 1,1 x Ie threshold and check the trip.
          •     Gradually decreases the injected current and record the value of the drop out Ie>
                threshold.
• Checks:
• Ie>, tIe>
          •     Supply the relay inject a current equal to 2 x Ie> threshold into one of the earth current
                inputs. Repeat the operation for various current values (n x Ie threshold with n ranging
                from 4 to 10, for example). Check that the values measured correspond to those
                indicated in the table below (for TMS=1).
P12y/EN CM/E95                                                Commissioning and Maintenance
IEC curves
IEEE/ANSI curves
Checks:
          •     If the time delay tI> is short, gradually increase the injection current up to the value of
                the I> threshold.
          •     If the time delay tI> is long, inject 0.95 x I threshold and check that there is no tripping.
                Then inject 1,1 x I threshold and check the trip.
          •     Gradually decrease the injected current and record the value of the drop out off (I>
                threshold).
Commissioning and Maintenance                                                     P12y/EN CM/E95
Checks:
      •     Apply a current into one of the phases and measure the time delay tI> by pre-setting
            the current above the I> threshold (I injected > 2 x I threshold).
      •     Apply a current onto one of the phases and measure the time delay tI> by pre-setting
            the current above the I> threshold (I injected > 10 x I threshold).
      Checks:
      •     Alarm message on the LCD display for I> after that the setting trip delay time is
            expired.
• Alarm LED flashes > after that the setting trip delay time is expired.
• Trip LED on after that the setting trip delay time is expired.
• I> threshold LED on (if programmed) > after that the setting trip delay time is expired.
• Trip output closes > after that the setting trip delay time is expired.
      •     I> threshold output closes (if programmed) > after that the setting trip delay time is
            expired.
      Delay type: Inverse time (IDMT)
      Used threshold for this test:
• I>, tI>
      •     Supply the relay, inject a current equal to 2 x I> threshold into one of the earth current
            inputs. Repeat the operation for various current values (n x Ie threshold with n ranging
            from 4 to 10, for example). Check that the values measured correspond to those
            indicated in the table below (for TMS=1).
      IEC curves
IEEE/ANSI curves
RI electromechanical curve
          For other injected current values, compare the values found with the theoretical values
          calculated according to the formula of the curves.
                    NOTE:       Equations of IEC, IEEE/ANSI and RI curves are given in chapter
                                P12y/EN TD of this Technical Guide.
          Checks:
          •     If tU> time delay is short, gradually raise the injection voltage up to the value of U>
                threshold.
          •     If U> time delay is long, inject 0.95 x U> threshold setting and check there is no trip.
                Then inject 1.1 x U> threshold setting and check the trip output is close.
          •     Gradually lower the injected current and note the value of the drop out U> threshold.
Commissioning and Maintenance                                                  P12y/EN CM/E95
Checks:
      •    Alarm message on the LCD display for U> after that the setting trip delay time is
           expired.
• Alarm LED flashes after that the setting trip delay time is expired.
• Trip LED on, after that the setting trip delay time is expired.
• U> threshold LED on (if programmed) > after that the setting trip delay time is expired.
• Trip output closes U> after that the setting trip delay time is expired..
      •    U> threshold output closes (if programmed) after that the setting trip delay time is
           expired.
4.4   Final checks
      1.   Remove all test or temporary shorting leads, etc… If it is necessary to disconnect any
           of the external wiring from the relay in order to perform the wiring verification tests, it
           should be ensured that all connections are replace in accordance with the relevant
           external connection or scheme diagram.
      2.   If a MMLG test block is installed, remove the MMLB01 test plug and replace the
           MMLG cover so that the protection is put into service.
      3.   For MiCOM P126 and P127 models, ensure that all event, fault and disturbance
           records, alarm and LEDs have been reset before leaving the relay.
      4.   If the relays are in a new installation or the circuit breaker has been just maintained,
           the circuit breaker maintenance and current counters should be zero. These counters
           (only P126 & P127) have to be reset using relevant command in RECORD/CB
           Monitoring menu (refer to User Guide).
P12y/EN CM/E95                                               Commissioning and Maintenance
5.      MAINTENANCE
5.1     Equipment failure
        MiCOM P125, P126 and P127 relays are full digital and permanent self-diagnosing. Any
        failure of software or hardware elements is instantly detected. As soon as an internal fault is
        detected, depending on its type (minor or major), an alarm message is displayed as a priority
        on the front panel LCD before the fault LED is illuminated (fixed or flashing) and the
        watchdog relay is closed (if the fault is a major one).
        The watchdog facility provides two output relay contacts, one normally open and one
        normally closed that are driven by the processor board. These are provided to give an
        indication that the relay is in a healthy state.
        An equipment failure (major or minor) cannot be acknowledged on the front panel (using the
        dedicated tactile button keypad). Only the disappearance of the cause will acknowledge the
        fault and hence reset the fault LED.
5.1.1   Minor fault
        Regarded by the MiCOM P125, P126 and P127 relays as a minor fault is a communication
        failure. If the communication is in fault, MiCOM P125, P126 and P127 protection and
        automation modules are not affected.
        Message:
        "COMM.ERROR":          Communication fault
        Cause:
        Hardware or software failure of the communication module.
        Action:
        Withdraw the active part and return it to the factory for repair.
        Alternative:
        If communication is not used, disable communication in the COMMUNICATION menu
        (Communication ? = No).
5.1.2   Major fault
        Major fault for MiCOM P125, P126 and P127 relays are all software and hardware failures
        except the communication faults. As soon as this type of failure is detected, the watchdog
        (WD) is closed and all operations are stopped (protection, automation, communication).
5.1.3   Hardware and software faults
        Messages:
        "DEFAULT SETTING": Indication that the relay is running with default setting
        "SETTING ERROR": Failure in the setting
        " CALIBRATION ERROR.": Calibration zone failure
        "CT ERROR": Analogue channel failure
        Cause:
        Hardware or software failure
        Action:
        Restart the protection software.
        If the software fault still remain after restart, withdraw the active part and return the module
        to the factory for repair.
Commissioning and Maintenance                                                  P12y/EN CM/E95
        The case and the rear terminals blocks have been designed to facilitate removal of the
        MiCOM P12x relay should replacement or repair become necessary without disconnect the
        scheme wiring.
                 NOTE:        The MiCOM relays have integral current transformer shorting switches
                              which will close when the active part is removed from the case.
        Remove the upper and lower flap without exerting excessive force. Remove the external
        screws. Under the upper flap, turn the extractor with a 3 mm screwdriver and extract the
        active part of the relay by pulling from the upper and lower notches on the front panel of the
        MiCOM relay.
        The reinstall the repaired or replacement relay follow the above instruction in reverse,
        ensuring that no modification has been done on the scheme wiring.
5.2.2   Replacing the complete relay
        To remove the complete relay (active part and case) the entire wiring must be removed from
        the rear connector.
        Before working at the rear of the relay, isolate all current supplies to the MiCOM relay and
        ensure that the relay is no more powered.
        WARNING:        NEVER OPEN CIRCUIT THE SECONDARY CIRCUIT OF A CURRENT
                        TRANSFORMER SINCE THE HIGH VOLTAGE PRODUCED MAY BE
                        LETHAL AND COULD DAMAGE INSULATION.
        Remove all wiring (communication, logic inputs, outputs, auxiliary voltage, current inputs).
        Disconnect the relay earth connection from the rear of the relay.
        Remove the screws used to fasten the relay to the panel, rack, etc… .These are the screws
        with the larger diameter heads that are accessible when the upper and lower flaps are open.
        Withdraw the relay from the panel, rack, etc… carefully because it will be heavy due to the
        internal transformers.
        To reinstall the repaired or replacement relay follow the above instructions in reverse,
        ensuring that each terminal block is relocated in the correct position and case earth,
        communication are replaced.
        Once reinstallation is complete the relay should be recommissioned using the instruction in
        sections 1 to 4 inclusive of this chapter.
5.3     Problem solving
5.3.1   Password lost or not accepted
        Problem:
        Password lost or not accepted
        Cause:
        MiCOM P125, P126 and P127 relays are supplied with the password set to AAAA.
        This password can be changed by the user (refer OP PARAMETERS menu).
P12y/EN CM/E95                                               Commissioning and Maintenance
          Action:
          There is an additional unique recovery password associated to the relay which can be
          supplied by the factory or service agent, if given details of its serial number (under the upper
          flap of the front panel). With this serial number, contact your Schneider Electric local dealer
          or Schneider Electric After Sales Dept.
5.3.2     Communication
5.3.2.1   Values measured locally and remotely
          Problem:
          The measurements noted remotely and locally (via RS485 communication) differ.
          Cause:
          The values accessible on the front face via the Measurement menu are refreshed every
          second. Those fed back via the communication and accessible by the Schneider Electric
          Setting software generally have skeletal refreshing frequencies. If the refreshing frequency of
          the supervision software differs from that of MiCOM P125, P126 and P127 relays (1s), there
          may be a difference between indicated values.
          Action:
          Adjust the frequency for refreshing the measurements of the supervision software or of the
          setting software to 1 second.
5.3.2.2   MiCOM relay no longer responds
          Problem:
          No response from MiCOM P125, P126 and P127 relays when asked by the supervision
          software without any communication fault message.
          Cause:
          Mainly, this type of problem is linked to an error in the MiCOM P125, P126 and P127
          communication parameters.
          Action:
          Check MiCOM P125, P126 and P127 communication parameters (data rate, parity, etc.) are
          in accordance with the supervision settings.
          Check MiCOM P125, P126 and P127 network address.
          Check that this address is not used by another device connected on the same LAN.
          Check that the other devices on the same LAN answer to supervision requests.
5.3.2.3   A remote command is not taken in account
          Problem:
          The communication between the relay and the PC is correct, but the relay does not accept
          any remote command or file downloading.
          Cause:
          Generally this is due to the fact that the relay is in programming situation. This means that
          the password is active.
          Action:
          Check that the password is not active in the relay since the last 5 minutes.
Connections and Wiring Diagrams   P12y/EN CO/E95
          CONNECTIONS AND
          WIRING DIAGRAMS
Connections and Wiring Diagrams               P12y/EN CO/E95
CONTENT
                 BLANK PAGE
Connections and Wiring Diagrams                                                    P12y/EN CO/E95
Case earth
                                 1       2           29             30
                                 3       4           31             32
                                 5       6           33             34
                                 7       8           35             36
                                 9      10           37             38
                                 11     12           39             40
                                 13     14           41         42
                                 15     16           43         44
                                 17     18           45         46
                                 19     20           47         48
                                 21     22           49         50
                                 23     24           51         52
                                 25     26           53         54
                                 27     28           55         56
                                                                                                      35
                  C            B                                                                             Watch Dog
                  Phase rotation                   ~/ + 33                              WD            37
                                                                                                      36
                                         Auxiliary Voltage                                            4
                  A B C                                                                                      Programmable tripping output
                                                    ~/ _ 34                             RL1           6
                                                                                                      2
                                                                                                      10
 Trip direction
                      P1                                  55                            RL2           12
                                                                                                             Programmable output
                                   S1                                                                 8
                                                     1A                                               14
                                                          56   32N   50N   51N          RL3                  Programmable output
                                                                                                      16
                                                          47                                          18
                                                                                        RL4                  Programmable output
                                                               67N   59N                              20
                                                     5A
                                                          48                                          3
                                                                                        RL5                  Programmable output
                                                                                                      1
                                                                                                      7
                                                                                        RL6                  Programmable output
                                                                                                      5
                                                               MiCOM
                                   A    da                                                            22
                                                                                                             Programmable input L1
                                                                                                      24
                                                                                                      26
                                                                                                             Programmable input L2
                                                               P125
                                   B                                                                  28
                                                                                                      17
                                                                                                             Programmable input L3
                                                                                                      19
                                                                                                      21
                                   C                      40                                                 Programmable input L4
                                                                                                      23
N dn 39
                                                                                                  _   31
                                                                                                      RS485
                                                                                                      Communication Port
                                                                                                  +   32
                                                                                                           *terminating resistor for the last
                                                                                                           relay to be connected between 30-32
                                                                                                                                                P0074ENc
Connections and Wiring Diagrams                                                                  P12y/EN CO/E95
Case earth
                                57     58         1       2           29           30
                                59     60         3       4           31           32
                                61     62         5       6           33           34
                                63     64         7       8           35           36
                                65     66         9       10          37           38
                                67     68        11       12          39           40
                                69     70        13       14              41       42
                                71     72        15       16              43       44
                                73     74        17       18              45       46
                                75     76        19       20              47       48
                                77     78        21       22              49       50
                                79     80        23       24              51       52
                                81     82        25       26              53       54
                                83     84        27       28              55       56
                    C                   B
                        Phase rotation
                                                                                                           35
                    A B C                                                                                  37
                                                              ~/ + 33                            WD
                                                                                                           36
                                                   Auxiliary Voltage                                       4
                                                              ~/ _ 34
                   P1                                                                            RL1       6
                                                                    49                                     2
                          S1                                                                               10
                                                               1A          50    51    32N
                                                                    50                           RL2       12
                          P1                                        51                                     8
                                                                                                           14
                               S1                                                      51N       RL3
                                                               1A         67N    50N                       16
                                                                    52                                     18
                                                                    53                          RL4
                                   P1                                                                      20
                                                                           37    46    49
                                        S1                                                                 3
                                                               1A                               RL5
                                                                                                           1
                                                                    54
                                                                          59N    79    BC
  Trip direction
                                                                                                           7
                                                                    55                          RL6
                          P1                                                                               5
                                             S1                                                            9
                                                               1A         50BF   TCS            RL7
                                                                    56                                     11
                                                                                                           13
                                                                    41                          RL8
                                                                                                           15
                                                               5A                                          22
                                                                    42
                                                                                                           24    Programmable inputL1
                                                                    43
                                                                                                           26
                                                               5A                                                Programmable inputL2
                                                                    44                                     28
                                                                                                           17
                                                                    45
                                                                                                                 Programmable inputL3
                                                                                                           19
                                                               5A                                          21
                                                                    46
                                                                         MiCOM
                                                                                                                 Programmable inputL4
                                                                                                           23
                                                                    47
                                                                                                           25
                                                               5A                                                Programmable inputL5
                                                                                                           27
                                                                         P126
                                                                    48                                     58
                                                                                                                 Programmable inputL6
                                             Ad    a                                                       60
                                                                                                           57
                                                                                                                 Programmable inputL7
                                                                                                           59
                                             B
                                                                                                                   Case earth connection
                                                                                                           29      Communication cable shield
                                                                                                           30
                                             C                      73                                          Terminal RS485
                                                                                                       _   31
                                                                                                               RS485
                                             N    dn                74                                         Communication
                                                                                                       +   32
                                                                                                                                  P0075ENb
Connections and Wiring Diagrams                                                                    P12y/EN CO/E95
Case earth
Protection CT Measurement CT
Watchdog (4)
                                                                                                                Output 1
                                                   Example with phases A
                                                   and B connected
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
                                                                                                                Input 11
                       50       51          67
                                                                                                                Input 12
67N 37 46
49 79 46BC
                         50BF        TC S
                                                                             Terminals "30/32" and "78/80" to
                                                                             be connected at the end of
                                                                             RS485 bus.
                       59       59N         27
81 81R 32
                                                                                               IRIG B
                       CTS
                                                                                               Modulated
                                 = optional
                                                                                                 IRIG B
                                                                                                 Unmo-
                                                                                                 dulated
                                                                                                                               P0076ENe
Connections and Wiring Diagrams                                                     P12y/EN CO/E95
                                                                                C
                                                                        A
                                                                            B
                                                                C
                                                        A
                                                            B
                            Measurement CT connection
                                                                            C
                                                                    A
                                                                        B
                            (optional)
                                                                                           P3947ENb
P12y/EN CO/E95                                    Connections and Wiring Diagrams
                                    Auxiliary
                                    voltage
Phase rotation
                                                           MiCOM
                                                          P126/P127
                                                                                P0101ENa
Connections and Wiring Diagrams                                      P12y/EN CO/E95
                                        Auxiliary
                                        voltage
Phase rotation
                                                              MiCOM
                                                             P126/P127
                                                                                P0102ENa
P12y/EN CO/E95            Connections and Wiring Diagrams
                 BLANK PAGE
Commissioning Test and Record Sheet   P12y/EN RS/E95
      COMMISSIONING TEST
       AND RECORD SHEET
Commissioning Test and Record Sheet                 P12y/EN RS/E95
CONTENT
1.       COMMISSIONING TEST                                      5
1.1      Relay identification                                    5
1.2      Commissioning test record                               5
1.3      Auxiliary supply control                                5
1.4      Measurements and analogue inputs control                6
1.5      Phase overcurrent protection test                       6
1.6      Phase under current protection test                     7
1.7      Earth over current protection test                      7
1.8      Directional earth fault overcurrent                     8
1.9      Earth Fault Wattmetric protection test                  9
1.10     Over/Under Phase voltage protection test                9
1.11     Residual voltage protection test                       10
1.12     Autoreclose basic test                                 10
1.12.1   ARC test procedure with tI>                            12
1.12.2   ARC test procedure with tIe>                           12
                 BLANK PAGE
Commissioning Test and Record Sheet                                         P12y/EN RS/E95
1.    COMMISSIONING TEST
                        BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
                        USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
                        GUIDE SFTY/4LM/D11 OR LATER ISSUE, OR THE SAFETY AND
                        TECHNICAL DATA SECTION OF THE TECHNICAL MANUAL AND ALSO
                        THE RATINGS ON THE EQUIPMENT RATING LABEL.
       Commissioning date:
       Engineer:
       Substation:
       Circuit:
       Network nominal frequency:
       MiCOM relay model:                 P125             P126         P127
       Serial number:
       Rated current In:
       Rated current Ien:
       Rated Voltage primary:
       Rated Voltage secondary:
       Auxiliary voltage Uaux:
       Communication protocol:
       Language:
• Set in the configuration menu in the submenu Transfo Ratio as shown below.
          Type and setting threshold                  Value         Delay Time             Trip value     Drop value
          in In                                       applied in In Setting                in In          in In
          I>:                                   A     0.2 x I>          1s
      Type and setting threshold                     Value         Delay Time          Measured           Drop value in
      in In                                          applied in In Setting             Trip Delay         In
                                                                                       time
      I>:                                       A          2 x I>              1s
      Type and setting threshold                     Value         Delay Time          Trip value in Drop value in
      in In                                          applied in In Setting             In            In
      I>>:                                      A         0.5x I>>             1s
Commissioning Test and Record Sheet                                         P12y/EN RS/E95
       Type and setting threshold          Value         Delay Time   Measured         Drop value in
       in In                               applied in In Setting      Trip Delay       In
                                                                      time
       I>>:                         A        2.5x I>>        1s
       Type and setting threshold          Value         Delay Time   Trip value in Drop value in
       in In                               applied in In Setting      In            In
       I>>>:                        A        0.5xI>>>        1s                    s
       Type and setting threshold          Value         Delay Time   Measured         Drop value in
       in In                               applied in In Setting      Trip Delay       In
                                                                      time
       I>>>:                        A        2.5xI>>>        1s                    s
       Type and setting threshold          Value         Delay Time   Trip value in Drop value in
       in In                               applied in In Setting      In            In
       I<:                          A        0.2 x I<        1s                    s               s
       Type and setting threshold          Value         Delay Time   Measured         Drop value in
       in In                               applied in In Setting      Trip Delay       In
                                                                      time
       I<:                          A        0.2 x I<        1s                    s               s
       Type and setting threshold       Value          Delay Time     Trip value in Drop value in
       in Ien                           applied in Ien Setting        In            In
       Ie>:                             0.2 x Ie>       1s
       Type and setting threshold       Value          Delay Time     Measured         Drop value in
       in Ien                           applied in Ien Setting        Trip Delay       In
                                                                      time
       Ie>:                             2 x Ie>         1s
       Type and setting threshold       Value          Delay Time     Trip value in Drop value in
       in Ien                           applied in Ien Setting        In            In
       Ie>>:                            0.2x Ie>>       1s
       Type and setting threshold       Value          Delay Time     Measured         Drop value in
       in Ien                           applied in Ien Setting        Trip Delay       In
                                                                      time
       Ie>>:                            2 x Ie>>        1s
P12y/EN RS/E95                                       Commissioning Test and Record Sheet
      Type and setting threshold            Value          Delay Time   Trip value in Drop value in
      in Ien                                applied in Ien Setting      In            In
      Ie>>>:                                0.5 x Ie>>>   1s
      Type and setting threshold            Value          Delay Time   Measured      Drop value in
      in Ien                                applied in Ien Setting      Trip Delay    Ien, Ue, R
                                                                        time
      Ie>>>:                                2 x Ie>>>     1s
      Type and setting current stage      Value          Delay Time     Measured      Drop value
      in Ien, Ue> in Volt, in degrees for applied in In, Setting        Trip Delay    for Ien, Ue,
      the torque angle and the trip zone in Volt and                    time          Torque
                                          the angles in                               angle, and
                                          degrees                                     trip zone
      Ie>:                                  0.5 x Ie>
      Ue>:10V                               2 x 10V
                                                          1s
      Torque angle: 0°                      0°
      Trip Zone: +/- 90°                    +/-85°
      Type and setting current stage        Value                                     Drop value
      in Ien, the Ue> in Volt and in        applied in In,              Measured      for Ien, Ue,
                                                           Delay Time
      degrees the torque angle and the      in Volt and                 Trip Delay    Torque
                                                           Setting
      trip zone                             the angles in               time          angle, and
                                            degrees                                   trip zone
      Ie>:                                  2 x Ie>
      Ue>:10V                               80V
                                                          1s
      Torque angle: 0°                      0°
      Trip Zone: +/- 90°                    +/-85°
Commissioning Test and Record Sheet                                          P12y/EN RS/E95
       Type and setting Pe stage are in    Value          Delay Time   Measured      Drop value
       watt referred to the secondary.     applied in In, Setting      Trip Delay    for Ien, Ue,
       The setting value depends on the    in Volt and                 time          Torque
       set nominal Ien current (1A).       the angles in                             angle, and
                                           degrees                                   trip zone
                                           0.5 x
                                           Ien=0.5A
       Pe>: 20W
                                           Ue=45V
                                                          tPe>=1s
                                           Ue^Ie =0°
       ϕc = 0°
       Note: Change the angle between Ue^Ie and verify the trip and drop off of the Pe stage and
       the value of the Pe in the measurement menu.
                                           Value
       Type and setting threshold                         Delay Time   Trip value in Drop value in
                                           applied in
       in Volt                                            Setting      Volt          Volt
                                           Volt
       U>:                                 2xU>           1s
                                           Value                       Measured
       Type and setting threshold                         Delay Time                 Drop value in
                                           applied in                  Trip Delay
       in Volt                                            Setting                    Volt
                                           Volt                        time
       U>:                                 2xU>           1s
                                           Value
       Type and setting threshold                         Delay Time   Trip value in Drop value in
                                           applied in
       in Volt                                            Setting      Volt          Volt
                                           Volt
       U<:                                 0.2 x U <      1s
                                           Value                       Measured
       Type and setting threshold                         Delay Time                 Drop value in
                                           applied in                  Trip Delay
       in Volt                                            Setting                    Volt
                                           Volt                        time
       U<<:                                0.2 x U <<     1s
P12y/EN RS/E95                                      Commissioning Test and Record Sheet
                                              Value
       Type and setting threshold                          Delay Time     Trip value in Drop value in
                                              applied in
       in Volt                                             Setting        Volt          Volt
                                              Volt
       Ue>>>>:                                2 x Ue>>>>   1s
                                              Value                       Measured
       Type and setting threshold                          Delay Time                      Drop value in
                                              applied in                  Trip Delay
       in Volt                                             Setting                         Volt
                                              Volt                        time
       Ue>>>>:                                2 x Ue>>>>   1s
      In the below table are listed the setting to have a corrected functionality of the 79 function.
      The output relay, the digital input and the led assigne are free.
      The indicating setting are those used for internal test.
      In the output relay none other functionality can be assigned to the relay CB Close.
                    NOTE:         To execute the ARC test you have to connect an external relay for the
                                  monitoring the CB status (52a OFF when the CB is open, ON when
                                  CB is closed). Further the flowing of the current to the relay must be
                                  interrupted when the 52a is OFF; CB is open.
1.12.1   ARC test procedure with tI>
− Close the CB and inject current the led 7 lights for 0.2 s,
− …………………………………….
         −       When we are to the td 4 when the CB close and after 1 sec the tI> trip the 79 trip and
                 Recl Blocked will be actived. 4 shots was done.
1.12.2   ARC test procedure with tIe>
− Close the CB and inject the Ie current, the led 7 lights for 0.2 s,
         −       After 1 sec the CB does not open and tDx does not start none led will be light,
         This result is corrected because to the Ie was imposed the setting “2”.
         Commissioning Engineer:
         Date:
         Remarks
Commissioning Test and Record Sheet                                        P12y/EN RS/E95
                             Password:
                             Reference:
                      Software version:
Frequency: 50 Hz 60 Hz
P125
P126
                                                         P127
         model.
         O = Optional
         Line CT Primary                          •      •                        A
         Line CT Secondary                        •      •           1A           5A
         E/Gnd CT Primary                  •      •      •                        A
         E/Gnd CT Secondary                •      •      •           1A           5A
         Line VT primary                                 •                        V
         Line VT sec                                     •                        V
         E/Gnd VT primary                  •      •      •                        V            Not visible
         E/GNnd VT secondary               •      •      •                        V            Not visible
         Line CTm primary                                •                        A            Not visible
         Line CTm sec                                    •                        A            Not visible
P126
P127
                Functions
                                                             Yes          Yes          Yes          Yes
         I>                                •      •
tI> • •
I>> • •
tI>> • •
I>>> • •
tI>>> • •
tIA> • •
tIB> • •
tIC> • •
Ie> • • •
tIe> • • •
Ie>> • • •
tIe>> • • •
Ie>>> • • •
tIe>>> • • •
Ie>>>> •
tIe>>>> •
P> •
         tP>                                      •
Commissioning Test and Record Sheet                                    P12y/EN RS/E95
P125
P126
                                        P127
              Functions
                                               Yes     Yes     Yes        Yes
       P>>                              •
tP>> •
P< •
tP< •
P<< •
tP< •
Q> •
tQ> •
Q>> •
tQ>> •
Q< •
tQ< •
Q<< •
tQ< •
Pe/IeCos> • • •
tPe/IeCos> • • •
Pe/IeCos>> • • •
tPe/IeCos>> • • •
I2> • •
tI2> • •
I2>> • •
tI2>> • •
I2>>> • •
tI2>>> • •
Therm. Trip • •
I< • •
tI< • •
U> •
tU> •
U>> •
tU>> •
U< •
tU< •
U<< •
tU<< •
       Ue>>>>             •      •      •
P12y/EN RS/E95                                 Commissioning Test and Record Sheet
P125
P126
                                       P127
             Functions
                                              Yes     Yes       Yes    Yes
       tUe>>>>           •      •      •
F1 •
tF1 •
F2 •
tF2 •
F3 •
tF3 •
F4 •
tF4 •
F5 •
tF5 •
F6 •
tF6 •
F Out •
dF/dt1 •
dF/dt2 •
dF/dt3 •
dF/dt4 •
dF/dt5 •
dF/dt6 •
F. out •
Brkn. Cond • •
CB Fail • •
VTS •
CTS •
Input 1 • • •
Input 2 • • •
Input 3 • • •
Input 4 • • •
Input 5 • •
Input 6 • •
Input 7 •
       Input 8                         O
       Input 9                         O
       Input A                         O
       Input B                         O
Commissioning Test and Record Sheet                                                             P12y/EN RS/E95
P125
P126
                                                P127
              Functions
                                                            Yes         Yes               Yes      Yes
         Input C                                O
         79 Run                          •      •
79i Blocked • •
79e. Blocked • •
tAux1 • • •
tAux2 • • •
tAux3 • •
tAux4 • •
tAux5 •
tAux6 •
tAux7 •
         tAux8                                  O
         tAux9                                  O
         tAuxA                                  O
         tAuxB                                  O
         tAuxC                                  O
         tSOTF                           •      •
tEQU. A • • •
tEQU. B • • •
tEQU. C • • •
tEQU. D • • •
tEQU. E • • •
tEQU. F • • •
tEQU. G • • •
tEQU. H • • •
           = ↓,      =↑
         Inputs (P125 only)                         3               2             1
         Voltage input DC                       DC                           AC
P12y/EN RS/E95                                       Commissioning Test and Record Sheet
← P125 →
← P125 →
         HMI ?                    YES                     NO
         Relay address
         HMI ?                    Private                 IEC
         COMM1 ?                  YES                     NO
         Baud rate
         Parity                  Even           Odd              None
         Stop bits                0                       1
         Relay address
         Spont. event & GI A11   None           Private only
                                 IEC only       All
         GI select.               Basic                   Advanced
         Measur. upload ASDU      YES                     NO
         3.4
         Measur. upload ASDU 9    YES                     NO
         Measur. upload Other     YES                     NO
         Events + Measur.         YES                     NO
         Blocking
         Command Blocking         YES                     NO
         Command timeout                              s
         COMM1 ?                  YES                     NO
         Baud rate
         Parity                  Even           Odd              None
         Stop bits                0                       1
         Relay address
         Spont. event & GI A11   None          Private only
                                 IEC only      All
         GI select.               Basic                   Advanced
         Measur. upload ASDU      YES                     NO
         3.4
         Measur. upload ASDU 9    YES                     NO
         Measur. upload Other     YES                     NO
         Events + Measur.         YES                     NO
         Blocking
         Command Blocking         YES                     NO
Commissioning Test and Record Sheet                                                    P12y/EN RS/E95
G1 G2 G3 G4 G5 G6 G7 G8
tI> s
           K
           t Reset                                                                 s
           I> >> >>> Interlock                          Yes                            No
           TMS
           Reset Delay Type                     DMT                    IDMT             Not displayed
           Rtms                                                                         Not displayed
           tReset                                           s                           Not displayed
           I> >> >>> Interlock                          Yes                            No
P12y/EN RS/E95                                       Commissioning Test and Record Sheet
tI> s
           K
           t Reset                                                     s
           TMS
           Reset Delay Type                 DMT                 IDMT            Not displayed
           Rtms                                                                 Not displayed
           tReset                                        s                      Not displayed
           Ie>                                                       Ien
           Ue>                                         V                     Not displayed
           Ie> Torque                                     °                  Not displayed
           Ie> Trip Zone                                  °                  Not displayed
           tIe>                                                       s
           tReset                                                     s
           K
           t Reset                                                    s
           Ie> >> >>> Interlock                     Yes                    No
           TMS
           Reset Delay Type                   DMT             IDMT           Not displayed
           Rtms                                                              Not displayed
           tReset                                      s                     Not displayed
           Ie> >> >>> Interlock                     Yes                    No
P12y/EN RS/E95                                    Commissioning Test and Record Sheet
             tIe>                                                    s
             tReset                                                  s
             K
             t Reset                                                 s
             TMS
             Reset Delay Type              DMT               IDMT           Not displayed
             Rtms                                                           Not displayed
             tReset                                   s                     Not displayed
            tIe>                                                   s
            tReset                                                 s
            K
            t Reset                                                s
            TMS
            Reset Delay Type               DMT             IDMT           Not displayed
            Rtms                                                          Not displayed
            tReset                                  s                     Not displayed
P12y/EN RS/E95                               Commissioning Test and Record Sheet
         Pe>>? or
         IeCos>> ?                     YES                          NO: Last menu
         I2>> ?                                                NO:
                                  YES
                                                            Next menu I2>>>?
         I2>>                                 In                    Not displayed
         tI2>>                                S                     Not displayed
         I< ?                                      YES                 NO
         I<                                                       In
         tI<                                                       s
         Inhibition I< on 52A                      YES                 NO
         Inhibition I< on U< (P127)                YES                 NO
         Inhibition I< on U< (P127)                                V
                                            AND              OR                No:
         U> ?
                                                                            Next menu: U>>?
         U>                                              V              Not displayed
         tU>                                             s              Not displayed
                                            AND              OR                No:
         U>> ?
                                                                            Last menu
         U>>                                             V              Not displayed
         tU>>                                            s              Not displayed
Commissioning Test and Record Sheet                                    P12y/EN RS/E95
                                            AND               OR            No:
          U< ?
                                                                         Next menu: U>>?
          U<                                            V               Not displayed
          tU<                                           s               Not displayed
          52a Inhib. U< ?                   AND              OR         Not displayed
                                            AND               OR            No:
          U<< ?
                                                                         Last menu
          U<<                                           V               Not displayed
          tU<<                                          s               Not displayed
          52a Inhib. U<< ?                  AND              OR         Not displayed
          [79] Autoreclose ?                                                NO
                                            YES
                                                                         Last menu
          Ext CB Fail ?                                                     NO
                                            YES
                                                                         Next menu: Ext Block?
          Ext CB Fail Time                                          ms
          Ext Block ?                       YES                             NO
          Rolling demand ?                  YES                             NO
          Max cycle nb
          Time period                                          mn
          Dead Time tD1                                         s
          Dead Time tD2                                         s
          Dead Time tD3                                         s
          Dead Time tD4                                         s
          Dead Time tI>                                         s
          Dead Time tI>>                                        s
          Dead Time tI>>>                                       s
          Dead Time tIe>                                        s
          Dead Time tIe>>                                       s
          Dead Time tIe>>>                                      s
          Reclaim time tR                                       s
          Inhib Time tI                                         s
          Phase Cycles                       1            2                3          4
E/Gnd Cycles 1 2 3 4
                                                              Cycles
                                       4              3                     2             1
tI>
tI>>
tI>>>
tIe>
tIe>>
tIe>>>
tPe/IeCos>
tPe/IeCos>>
tAux 1
          tAux 2
Commissioning Test and Record Sheet                                    P12y/EN RS/E95
                                           Fx                 Fx =            tFx
                               No          81>         81<    Hz *           ms *
              [81] F1                                        _______        _______
                           dF/dtx ?        dF/dtx =
                               Yes           Hz/s*
           [81R] dF/dt1                    _______
Trip tI>>
Trip tI>>>
        Trip tIe>
        Trip tIe>>
        Trip tIe>>>
        Trip tIe>>>
Trip tP>
Trip tP>>
Trip tP<
Trip tP<<
Trip tQ>
Trip tQ>>
Trip tQ<
Trip tQ<<
        Trip tPe/IeCos>
        Trip tPe/IeCos>>
        Trip tI2>
Trip tI2>>
Trip tI2>>>
        Trip Thermal θ
        Trip tU>
Trip tU>>
Trip tU<
Trip tU<<
        Trip tUe>>>>
        Trip tF1
Trip tF2
Trip tF3
Trip tF4
Trip tF5
        Trip tF6
Commissioning Test and Record Sheet                P12y/EN RS/E95
Trip dF/dt2
Trip dF/dt3
Trip dF/dt4
Trip dF/dt5
Trip dF/dt6
       Trip tAux 1
       Trip tAux 2
       Trip tAux 3
       Trip tAux 4
       Trip tAux 5
Trip tAux 6
Trip tAux 7
Trip SOTF
       Ctrl Trip
       Trip tEQU A
       Trip tEQU B
       Trip tEQU C
       Trip tEQU D
       Trip tEQU E
       Trip tEQU F
       Trip tEQU G
       Trip tEQU H
P12y/EN RS/E95                                           Commissioning Test and Record Sheet
← P125 →
        tThermal θ
        tI<
        tU>
        tU>>
        tU<
        tU<<
        tUe>>>>
        tF1
        tF2
Commissioning Test and Record Sheet                          P12y/EN RS/E95
       tThermal θ
       tI<
       tU>
       tU>>
       tU<
       tU<<
       tUe>>>>
       tF1
       tF2
       tF3
       tF4
       tF5
       tF6
       dF/dt1
       dF/dt2
       dF/dt3
       dF/dt4
       dF/dt5
       dF/dt6
       tBrk. Cond
       tAux1
       tAux2
       tAux3
       tAux4
       tAux5
       tAux6
       tAux7
       tAux8 (option)
       tAux9 (option)
       tAuxA (option)
Commissioning Test and Record Sheet                                 P12y/EN RS/E95
                                P123
               Function
                                 Yes
        I>
        I>>
        I>>>
        Ie>
        Ie>>
        Ie>>>
        Ie>>>>
        I2>
        I2>>
        I2>>>
        • = available                                           ← P125 →
        O = Option (P127)                                           ← P126 / P127 →
                                                        RL2 RL3 RL4 RL5 RL6 RL7 RL8
P125
P126
                                                 P127
                  Function
                                                        Yes   Yes   Yes   Yes   Yes    Yes   Yes
        Trip                              •      •
        I>                                •      •
        tI>                               •      •
        I_R>                              •      •
        I>>                               •      •
        tI>>                              •      •
        I_R>>                             •      •
        I>>>                              •      •
        tI>>>                             •      •
        I_R>>>                            •      •
        tIA>                              •      •
        tIB>                              •      •
        tIC>                              •      •
        Ie>                        •      •      •
        tIe>                       •      •      •
        Ie_R>                      •      •      •
        Ie>>                       •      •      •
        tIe>>                      •      •      •
        Ie_R>>                     •      •      •
        Ie>>>                      •      •      •
        tIe>>>                     •      •      •
        Ie>>>>                                   •
        tIe>>>>                                  •
        Ie_R>>>                    •      •      •
        P>                                       •
        tP>                                      •
        P>>                                      •
        tP>>                                     •
        P<                                       •
        tP<                                      •
        P<<                                      •
P12y/EN RS/E95                           Commissioning Test and Record Sheet
      • = available                                     ← P125 →
      O = Option (P127)                                     ← P126 / P127 →
                                                RL2 RL3 RL4 RL5 RL6 RL7 RL8
P125
P126
                                         P127
                Function
                                                Yes   Yes    Yes   Yes   Yes   Yes   Yes
       tP<<                              •
       Q>                                •
       tQ>                               •
       Q>>                               •
       tQ>>                              •
       Q<                                •
       tQ<                               •
       Q<<                               •
       tQ<<                              •
       Pe/IeCos>           •      •      •
       tPe/IeCos>          •      •      •
       Pe/IeCos>>          •      •      •
       tPe/IeCos>>         •      •      •
       I2>                        •      •
       tI2>                       •      •
       I2>>                       •      •
       tI2>>                      •      •
       I2>>>                      •      •
       tI2>>>                     •      •
       ThermAlarm                 •      •
       ThermTrip                  •      •
       I<                         •      •
       tI<                        •      •
       U>                                •
       tU>                               •
       U>>                               •
       tU>>                              •
       U<                                •
       tU<                               •
       U<<                               •
       tU<<                              •
       Ue>>>>              •      •      •
Commissioning Test and Record Sheet                                   P12y/EN RS/E95
       • = available                                     ← P125 →
       O = Option (P127)                                     ← P126 / P127 →
                                                 RL2 RL3 RL4 RL5 RL6 RL7 RL8
P125
P126
                                          P127
                 Function
                                                 Yes   Yes   Yes   Yes   Yes    Yes   Yes
       tUe>>>>:             •      •      •
       F1                                 •
       tF1                                •
       F2                                 •
       tF2                                •
       F3                                 •
       tF3                                •
       F4                                 •
       tF4                                •
       F5                                 •
       tF5                                •
       F6                                 •
       tF6                                •
       F.OUT                              •
       dF/dt1                             •
       dF/dt2                             •
       dF/dt3                             •
       dF/dt4                             •
       dF/dt5                             •
       dF/dt6                             •
       BrknCond                    •      •
       CBAlarm                     •      •
       52 Fail                     •      •
       CBFail                      •      •
       CB Close                    •      •
       tAux1                •      •      •
       tAux2                •      •      •
       tAux3                •      •      •
       tAux4                •      •      •
       tAux5                              •
tAux6 •
       tAux7                              •
P12y/EN RS/E95                             Commissioning Test and Record Sheet
      • = available                                       ← P125 →
      O = Option (P127)                                       ← P126 / P127 →
                                                  RL2 RL3 RL4 RL5 RL6 RL7 RL8
P125
P126
                                           P127
                  Function
                                                  Yes   Yes    Yes   Yes   Yes   Yes   Yes
       tAux8                               O
       tAux9                               O
       tAuxA                               O
       tAuxB                               O
       tAuxC                               O
       79 Run                       •      •
       79 Trip                      •      •
       79 int. Lock                 •      •
       79 ext. Lock                 •      •
       SOTF                         •      •
       CONTROLTRIP           •      •      •
       CONTROLCLOSE          •      •      •
       ActiveGroup           •      •      •
       Input1 :              •      •      •
       Input2                •      •      •
       Input3 :              •      •      •
       Input4                •      •      •
       Input5                       •      •
       Input6                       •      •
       Input7                       •      •
       Input8                              O
       Input8                              O
       InputA                              O
       InputB                              O
       InputC                              O
       VTS                                 •
       CTS                                 •
       t EQU.A                      •      •
       t EQU.B                      •      •
       t EQU.C                      •      •
       t EQU.D                      •      •
       t EQU.E                      •      •
Commissioning Test and Record Sheet                                  P12y/EN RS/E95
       • = available                                    ← P125 →
       O = Option (P127)                                    ← P126 / P127 →
                                                RL2 RL3 RL4 RL5 RL6 RL7 RL8
P125
P126
                                         P127
              Function
                                                Yes   Yes   Yes   Yes   Yes    Yes   Yes
       t EQU.F                    •      •
       t EQU.G                    •      •
       T EQU.H                    •      •
       Command1                          •
       Command2                          •
       Command3                          •
       Command4                          •
P12y/EN RS/E95                                           Commissioning Test and Record Sheet
           • = available                                ← P125 →
           O = Option.                                    ← P126 / P127 →            ← option P127 →
                                                                            Inputs
P125
P126
                                             P127
                   Function
                                                    1    2   3     4   5    6   7    8   9   A   B   C
           None                •      •      •
           Unlatch             •      •      •
           Blk Log 1           •      •      •
           Blk Log 2                  •      •
           52 a                       •      •
           52 b                       •      •
           CB FLT                     •      •
           Aux 1               •      •      •
           Aux 2               •      •      •
           Aux 3               •      •      •
           Aux 4               •      •      •
           Aux 5                             •
           Aux 6                             •
           Aux 7                             •
           Aux 8                             O
           Aux 9                             O
           Aux A                             O
           Aux B                             O
           Aux C                             O
           Strt Dist                  •      •
           Cold L PU                  •      •
           Log Sel 1                  •      •
           Log Sel 2                  •      •
           Change Set                 •      •
           Block_79                   •      •
           θ Reset                    •      •
           Trip Circ                  •      •
           Start t BF                 •      •
           Maint. M            •      •      •
           SOTF                       •      •
Local • • •
           Synchro.            •      •      •
           Led Reset or
                               •      •      •
           Reset Led
Commissioning Test and Record Sheet                                                     P12y/EN RS/E95
           • = available                                 ← P125 →
           O = Option.                                     ← P126 / P127 →              ← option P127 →
                                                                            Inputs
P125
P126
                                              P127
                 Function
                                                     1    2   3     4   5   6       7   8    9   A   B   C
           Ctrl Trip            •      •      •
           Ctr Close            •      •      •
2.5.9.2 tAux
           Ratio I2/I1                                                          %
P12y/EN RS/E95                                 Commissioning Test and Record Sheet
Ue< V
          tCTS                                                    s
P12y/EN RS/E95                               Commissioning Test and Record Sheet
          TC Supervision?                            YES              NO
          T trip circuit t SUP                                    s
          CB Open S'vision                           YES              NO
          CB Open Time                                         ms
          CB Close S'vision                          YES              NO
          CB Close Time                                        ms
          CB Open Alarm?                             YES              NO
          CB Open NB
          Σ Amps(n)?                                 YES              NO
          Σ Amps(n)
t Open Pulse ms
          t Close Pulse                                        ms
Commissioning Test and Record Sheet                                         P12y/EN RS/E95
2.5.17 SOTF
          SOTF?                                          YES                 NO
          t SOTF                                                     ms
          I>> ?                                          YES                 NO
          I>>> ?                                         YES                 NO
          Ctrl close input                               YES                 NO
          SOTF input                                     YES                 NO
          HMI closing order                              YES                 NO
          [79] closing                                   YES                 NO
          Front comm. order                              YES                 NO
          Rear comm. order                               YES                 NO
          Rear2 comm. order                              YES                 NO
tCommand1 s
tCommand1 s
tCommand1 s
          tCommand4                                              s
P12y/EN RS/E95                      Commissioning Test and Record Sheet
         CB Monitoring Time                              s
         CB Closing Time                                 s
         Σ Amps (n) IA
         Σ Amps (n) IB
         Σ Amps (n) IC
         Record Number
         Fault Time                                  :   :
         Fault date                              /       /
         Active Set Group       1            2
         Faulted phase          None         Phase A         Phase B
                                             Phase C         Earth
         Threshold
         Magnitude                                       A
         IA Magnitude                                    A
         IB Magnitude                                    A
         IC Magnitude                                    A
         IN Magnitude                                    A
         VAB Magnitude (P127)                            V
         VBC Magnitude (P127)                            V
         VCA Magnitude (P127)                            V
         VN Magnitude                                    V
         IA^VBC Angle                                    °
         IB^VCA Angle                                    °
         IC^VAB Angle                                    °
         IN^VN Angle                                     °
Commissioning Test and Record Sheet                                      P12y/EN RS/E95
             Number                 1     2          3             4           5
             Hour                                        :     :
             Date                                    /         /
             Origin
             Length                                            s
             Trip                       YES                                NO
             Pre-Time                                          s
             Post-Time                                         s
             Disturb rec Trig           On trip                            On inst.
Time Window mn
             Sub Period                                      mn
             Num of Sub Per.
RECORDS
Fault Record
Disturb Record
• VT Connection: 3Vpn
• Line CT primary: 1A
• Line CT secondary: 1A
• E/Gnd CT primary: 1A
• E/Gnd CT secondary: 1A
          •     ON
          •     1 In
          •     Characteristic                      IDMT
          •     Curve                               IEC_SI (Standard Inverse)
          •     TMS                                 0.025
          •     Reset time delay                    0.04 s
          Inject current of 0.95 In into the A phase input. Increase the current in 0.01In steps, pausing
          for 2.5s between each step, until the relay operates. The current must then be reduced in the
          same manner until the protection resets.
          Repeat the above tests for all phases.
          Repeat the above test for other overcurrent stages taking in account that the delay time for
          nthe second and third threshold is DMT (t=0s). Make the test before on I>> after on I>>>.
3.7.1.1   Pass Criteria
          For the relay to pass it shall operate as detailed below.
          Delay trip IDMT (inverse time only for I>):
          •     Is                                  1 In
          •     Characteristic                      DT / IDMT
          •     Curve                               IEC_SI (Standard Inverse)
          •     TMS                                 1.0
          •     Time Delay                          1s
          •     Directionality                      Non-directional
          •     Reset time delay                    0s
          Enable stage 1 overcurrent and prepare the tests set so that A phase current can be
          instantaneously applied at 2In and 10In respectively. Measure the operating times of the
          relay start and trip contacts. Repeat the test with the element set to IDMT. Repeat the test
          with the element disabled and verify that no start or trip elements operate.
          Repeat the above testing for all phases and stages (with the exception of IDMT which is only
          for the first stage).
P12y/EN RS/E95                                            Commissioning Test and Record Sheet
          •     DT operating time
          •     1.0s ±2%
          •     IDMT operating time
          •     10.07s ±2% at 2 Ies
          •     2.999s ±2% at 10 Ies
3.7.5     Directional earth fault overcurrent protection
3.7.5.1   Neutral sensitivity test
          Object:
          The following tests verify that the relay directional earth fault elements operate at the set
          thresholds and boundary trip zone.
          Wirng scheme: 3Vpn for the voltage, Holmgreen insertion for the currents. The Ie current is
          the output common of the phase current inputs.
          Test with the following relay settings:
• E/GND Primary 5A
• E/GND Secondary 5A
• Characteristic IDMT
• TMS 1
• Ue 1V
• Directionality Directional
• VT connection 3Vpn
• Characteristic DT
• Is 0.2 Ien
The operating boundary shall be within ±3° of the relay characteristic angle ±45°.
• Characteristic DT / IDMT
• TMS 1.0
• Time Delay 1s
• Directionality Non-directional
          •     Is                                  1 Ien
          Enable stage 1 of Earth Fault protection and prepare the tests set so that Ie current can be
          instantaneously applied at 2 Ies and 10 Ies respectively. Measure the operating times of the
          relay start and trip contacts. Repeat the test with the element set to IDMT. Repeat the test
          with the element disabled and verify that no start or trip elements operate.
          Repeat the above testing for all stages (IDMT is only for the first stage).
3.7.8.1   Pass Criteria
          For the relay to pass it shall operate as detailed below.
          DT operating time
          •     1.0s ±2%
          IDMT operating time:
• VT connection 3Vpn
• Characteristic DT
• Is 1 In
The operating boundary shall be within ±3° of the relay characteristic angle ±80°.
          •     Inject: Ua=57.7V, Ub= 57.7V, Uc=57.7V with these values the Ue is equal to 0.
          Inject the Ia phase current with displacement 0° with Ua to have the following ratios Pe/Pe>:
          2, 3, 4
         •     I2>                                 0.1In
         Apply three phase currents to the relay at a magnitude of In. Step change the A phase
         current to a magnitude of 0.5In. Verify that the fault record indicates that the negative
         sequence overcurrent has started.
         Repeat the above testing with the time delay set to 0s. The fault record should now indicate
         trips.
3.7.11.1 Pass Criteria
         For the relay to pass it shall operate as detailed above.
3.7.12   Thermal overload
         Object:
         The following tests verify that thermal overload starts and trips applied to the relay operate
         correctly.
         Test with the following relay settings:
• K 1
         •     θ Trip                              100%
         Configure the test set to apply 3 phase balanced current to the relay.
         Reset the thermal time state of the relay. Inject three phase 0.55 In to the relay and measure
         the operating time of the contact. Verify that the fault record indicates that the thermal
         overload alarm has operated followed by a thermal overload trip after 107 s ±2%.
3.7.12.1 Pass Criteria
         For the relay to pass it shall operate as detailed above.
3.8      Voltage Protection (only P127)
         The voltage protection 27 and 59 compare the line voltage to the setting elements of each
         protection.
3.8.1    Under voltage
         Object:
         The following tests verify that under voltage starts and trips applied to the relay operate
         correctly.
         Test with the following relay settings:
• Mode OR
• Characteristic DT
         •     DT                                  30s
P12y/EN RS/E95                                            Commissioning Test and Record Sheet
          •     U<                                  50V
          Enable stage 1 over voltage and apply rated three phase voltages (57.7V per phase) to the
          relay. After 2s reduce the phase A voltage and phase B voltage to 20V. Measure the
          operating times of the relay start and trip contacts. Repeat the test with the element disabled
          and verify that no start or trip elements operate.
          Repeat the above tests for stage 2 under voltage.
3.8.3     Over voltage
          Object:
          To verify that over voltage starts and trips applied to the relay operate correctly.
          Test with the following relay settings:
• Mode OR
• Characteristic DT
          •     DT                                  10s
3.8.4     Phase to neutral over voltage element
          Test with the following relay settings:
          •     U>100V
          Enable stage 1 and apply three phase voltages (50V per phase) to the relay. After 1s
          increase the phase A voltage and phase B voltage to 60V. Measure the operating times of
          the relay start and trip contacts. Repeat the test with the element disabled and verify that no
          start or trip elements operate.
          Repeat the above testing for stage 2 overvoltage.
3.8.5     Residual over voltage
          Object:
          The following tests verify that residual over voltage starts and trips applied to the relay are
          recorded as fault records.
          Test with the following relay settings:
• Ue>>>> 10V
+ Vdc
52a
                                         2      6    Trip
                                                     order             Opto-
                                                                       input
MiCOM P126/P127
                                                             - Vdc
                                                                                   P0096ENa
        •      Characteristic                       DT
        •      Time Delay                           0s
        •      Directionality                       Non-directional
        •      Reset time delay                     0s
        •      Is (I>)                              1 In
        CBF:
        •      Time Delay                           0s
        •      I<BF                                 0.5 In
        •      tBF                                  5s
P12y/EN RS/E95                                            Commissioning Test and Record Sheet
          The relay shall be configured with trip commands relay assigned to t_I>, with relay 2
          assigned to CB fail function and with relay 2 assigned as latched.
          Enable stage 1 overcurrent and apply three phase currents to the relay at 0.8 In for 1s;
          instantaneously increase the currents applied to the ABC phase inputs to 2 In for 7s. Verify
          after the increase that tat the relays number 2 change in the status display windows to level
          1 after 5s.
3.9.2.1   Pass Criteria
          For the relay to pass it shall operate as detailed above.
3.9.3     Cold load pick-up
          Test with the following relay settings:
          Cold load pick-up:
• t_I> Yes
• Level 200%
          •     tCL                                 5.0 s
          Overcurrent:
• Characteristic DT
• Time Delay 2s
• Directionality Non-directional
          •     Is (I>)                             1In
          Inputs:
          •     Input 1                             Cold L PU
          Apply three phase currents to the relay at a magnitude of 1.5 In and supply the input 1.
          Verify after 8 sec the trip of the overcurrent is recrided as a fault record.
3.9.3.1   Pass Criteria
          For the relay to pass it shall operate as detailed above.
3.9.4     Broken Conductor
          Object:
          The following tests verify that a broken conductor condition causes the relay to operate
          correctly.
          Test with the following relay settings:
• Characteristic DT
     HARDWARE/SOFTWARE
     VERSION HISTORY AND
        COMPATIBILITY
        P125 P126 V12
           P127 V13
Hardware/Software Version   P12y/EN VC/E95
History and Compatibility
MiCOM P125/P126/P127             Page 1/28
CONTENTS
1. INTRODUCTION 3
2. MiCOM P125 4
3. MiCOM P126 9
4.    MiCOM P127                        17
P12y/EN VC/E95                Hardware/Software Version
                                History and Compatibility
Page 2/28                      MiCOM P125/P126/P127
                 BLANK PAGE
Hardware/Software Version                                                     P12y/EN VC/E95
History and Compatibility
MiCOM P125/P126/P127                                                                  Page 3/28
1. INTRODUCTION
HARDWARE INSTALLED
        E.g.: W W Y Y N N N
        - W = Week 01 To 52
        - Y = Year (19)94 To (20)93
        - N = Product Arrang. 001 To 999
P12y/EN VC/E95                                                    Hardware/Software Version
                                                                    History and Compatibility
Page 4/28                                                          MiCOM P125/P126/P127
2.      MiCOM P125
          P125 – Serial number – Hardware Correlation
          Serial Number                                    Hardware installed
          Phase 1                                          HARDWARE VERSION 4
          Phase 2                                          HARDWARE VERSION 5
V10.D    08/2006   V10.D software is equivalent to V6.H software based on V2.13            Hard 5
                   the phase II hardware redesign (Hard 4)
                       Software changes implemented in this version
                   - None.
Hardware/Software Version                                                             P12y/EN VC/E95
History and Compatibility
MiCOM P125/P126/P127                                                                          Page 7/28
3.      MiCOM P126
         P126 - Serial number – Hardware Correlation
         Serial Number                                 Hardware installed
         Phase 1                                       HARDWARE VERSION 4
         Phase 2                                       HARDWARE VERSION 5
V10.D    08/2006   V10.D software is equivalent to v6.H software based          V2.13     Hard 5
                   on the phase II hardware redesign (Hard 4).
                      Software changes implemented in this version
                   - None.
P12y/EN VC/E95                                                               Hardware/Software Version
                                                                               History and Compatibility
Page 14/28                                                                    MiCOM P125/P126/P127
4.      MiCOM P127
         P127 - Serial number – Hardware Correlation
         Serial Number                                 Hardware installed
         Phase 1                                       HARDWARE VERSION 4
         Phase 2                                       HARDWARE VERSION 5
V10.D    08/2006   V10.D software is equivalent to v6.H software based V2.13               Hard 5
                   on the phase II hardware redesign (Hard 4).
                      Software changes implemented in this version
                   - None.
Hardware/Software Version                                                            P12y/EN VC/E95
History and Compatibility
MiCOM P125/P126/P127                                                                        Page 23/28
                 BLANK PAGE
                                                                  © 2010 Schneider Electric. All rights reserved.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone:   +33 (0) 1 41 29 70 00
Fax:     +33 (0) 1 41 29 71 00
www.schneider-electric.com       Publishing: Schneider Electric
Publication: P12x/EN T/E95                            11/2010