0% found this document useful (0 votes)
54 views6 pages

OsiSense XC XCKP2506P16 Document

This document provides product information for the XCKP2506P16 limit switch. It includes specifications such as its commercialization dates, number of poles, contact type, and environmental resistance. Dimensional drawings and wiring diagrams are also included to illustrate mounting, cable entry points, and electrical connections. The limit switch has a plastic body and multi-directional head, with 1 NC and 1 NO slow-break contact.

Uploaded by

Antonio Isorna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views6 pages

OsiSense XC XCKP2506P16 Document

This document provides product information for the XCKP2506P16 limit switch. It includes specifications such as its commercialization dates, number of poles, contact type, and environmental resistance. Dimensional drawings and wiring diagrams are also included to illustrate mounting, cable entry points, and electrical connections. The limit switch has a plastic body and multi-directional head, with 1 NC and 1 NO slow-break contact.

Uploaded by

Antonio Isorna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Product data sheet XCKP2506P16

Characteristics limit switch XCKP - cat's whisker - 1NC+1NO -


slow - M16

Product Life Status : COMMERCIALIZED


TODAY
APR 20, 2020

End of Commercialization
NOV 30, 2020

Main
Range of product OsiSense XC
Series name Standard format
Product or component Limit switch

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
type
Device short name XCKP
Sensor design Compact
Body type Fixed
Head type Multi-directional head
Material Plastic
Body material Plastic

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Head material Zamak

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Fixing mode By the body
Movement of operating Multi-directional
head
Type of operator Spring return cat''s whisker
Type of approach Multi-directional approach
Number of poles 2
Contacts type and 1 NC + 1 NO
composition
Contact operation Slow-break, break before make
Product Life Status : COMMERCIALIZED

APR 20, 2020

End of Commercialization
NOV 30, 2020

Complementary
Switch actuation By any moving part
Electrical connection Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²
Cable entry 1 entry tapped for M16 x 1.5 cable gland, cable outer diameter: 4…8 mm
Contacts insulation form Zb
Positive opening Without
Minimum torque for tripping 0.13 N.M
Maximum actuation speed 1 M/S
Repeat accuracy 0.1 mm on the tripping points with 1 million operating cycles
Contact code designation A300, AC-15 (Ue = 240 V), Ie = 3 A, Ithe = 10 A conforming to EN/IEC 60947-5-1
appendix A
Q300, DC-13 (Ue = 250 V), Ie = 0.27 A conforming to EN/IEC 60947-5-1
appendix A

Apr 20, 2020


1
[Ui] rated insulation voltage 300 V conforming to UL 508
500 V (pollution degree 3) conforming to IEC 60947-1
300 V conforming to CSA C22.2 No 14
Maximum resistance across terminals 25 MOhm conforming to IEC 60255-7 category 3
[Uimp] rated impulse withstand voltage 6 KV IEC 60664
6 KV IEC 60947-1
Short-circuit protection 10 A cartridge fuse, type gG
Electrical durability 5000000 Cycles, DC-13, 120 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5
conforming to IEC 60947-5-1 appendix C
5000000 Cycles, DC-13, 24 V, 10 W, operating rate <60 cyc/mn, load factor: 0.5
conforming to IEC 60947-5-1 appendix C
5000000 Cycles, DC-13, 48 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5
conforming to IEC 60947-5-1 appendix C
Mechanical durability 5000000 Cycles
Width 31 Mm
Height 65 Mm
Depth 30 Mm
Net weight 0.085 Kg
Terminals description ISO n°1 (13-14)NO
(21-22)NC

Environment
Shock resistance 50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance 25 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
IP degree of protection IP66 conforming to IEC 60529
IP67 conforming to IEC 60529
IK degree of protection IK04 conforming to EN 50102
Electrical shock protection class Class II conforming to IEC 61140
Class II conforming to NF C 20-030
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -40…70 °C
Protective treatment TC
Product certifications CCC
UL
CSA
Standards IEC 60204-1
EN 60947-5-1
IEC 60947-5-1
CSA C22.2 No 14
EN 60204-1
UL 508

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS
Declaration
Mercury free Yes
RoHS exemption information
Yes
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information

Contractual warranty
Warranty 18 months

2
Product data sheet XCKP2506P16
Dimensions Drawings

Dimensions

(1) Tapped entry for M16 x 1.5


(2) 2 elongated holes Ø 4.3 x 6.3 mm on 22 mm centres, 2 holes Ø 4.3 on 20 mm centres.
(3) 2 x Ø 3 holes for support studs, depth 4 mm.

3
Product data sheet XCKP2506P16
Mounting and Clearance

Mounting with Cable Entry

Position of Cable Gland

(1) Recommended
(2) To be avoided

Setting-up

Plunger or Multi-directional Heads

4
Product data sheet XCKP2506P16
Connections and Schema

Wiring Diagram

2-pole NC + NO Break before Make, Slow Break

5
Product data sheet XCKP2506P16
Technical Description

Characteristics of Actuation

Switch Actuation by Any Moving Part

Functionnal Diagram

(1) Closed
(2) Open

You might also like