Calculation Sheet
Calculation Sheet
Flow rates
Average Flow                                            4000.00   m3/day
                                                        166.67    m3/h
Peak factor                                             2.00      m3/h
Peak flow                                               333.33
Peak flow rates                                         8000.00   m
Flow rates for the biological treatment
Max. monthly flow                                       4000.00   m
                                                        166.67    m3/h
INLET CHAMBER
Peak flow                                               8000.00   m3/day
                                                        333.33    m3/h
Max. monthly                                            166.67    m3/h
V
Breadth (B)                                    B        1.50      m
Length (L)                                     L        2.90      m
Water depth                                    d max    1.00      m
Volume                                         V        4.35      m3
check
Retention time at peak flow                           46.98     sec         (0.5-2) min,ECP 2018
                                                                            ,P.1/3
                                                      0.78      min
Retention time at average flow                        93.96     sec
1.57 min
                                                            Q 2
                                                         (     )
Head loss through the screen                              C∗A
                                                     H L=
                                                           2∗g
Head loss coefficient for a clean bar screen                       0.60                 ( 0.3-0.6) ,ECP 2018,P.8/3
                                                 c
                                                                   0.11     m           (0.8-1.4) m,ECP
                                                 HL
                                                                                        2018,P.8/3
Manual Screen
No. manual screen set (set)                      n                 1.00     nos, duty
Flow per screen 100% from total flow                               333.33   m3/h
                                                                   0.09     m3/sec
Bar width                                        s                 10       mm
Frame thickness                                  s'                20       mm
Space between bars                               e                 50       mm
Inclination angle                                                  45       Degree
Velocity in the screen channel Before screens                      0.75     m/sec
                                                 V1
Area of the screen channel                       A'                0.12     m2
Selected screen channel width                    w                 0.63     m
Depth of water at maximum flow                   d                 0.20     m
Manual Screen
No. manual screen set (set)                      n              1.00     nos, duty
Flow per screen 100% from total flow                            333.33   m3/h
                                                                0.09     m3/sec
Bar width                                        s              10.00    mm
Frame thickness                                  s'             20.00    mm
Space between bars                               e              50.00    mm
Inclination angle                                               45.00    Degree
Velocity in the screen channel Before screens                   0.39     m/sec
                                                 V1
Area of the screen channel                       A'             0.24     m2
Selected screen channel width                                   0.59     m
                                                 w
Depth of water at maximum flow                                  0.41     m
                                                 d
GRIT CHAMBER
Average flow                                                       4000.00   m3/day
Hourly average flow                                                166.67    m3/h
Peak flow                                                          333.33    m3/h
No. of grit and grease chamber                                     2.00      nos, duty      n>2 ,ECP 2018 ,P.14/3
                                               n
Peak flow per each chamber                                         166.67    m3/h
                                                                   0.05      m3/s
Depth of water                                 d                   0.60      m              > 0.60m, ECP 2018,P.14/3
Width                                                              0.65      m              W > 2m ,Width to depth
                                               w                                            ratio=( 1-2), ECP
                                                                                            2018,P.14/3
Length                                                             12.00     m              L>7.5 m ,Length to depth
                                               L                                            ratio (20-30), ECP
                                                                                            2017,P.14/3
Area of the each chamber                       A'                  7.80      m2
Volume of each chamber                         V                   4.68      m3
Grit production
Specific grit production rate                                      0.20      m3/1000m3 of   100-250 lit/1000m3/d,
                                               GPR
                                                                             water/d        ECP 2018,P.15/3
Total grit produced at average flow                                0.80      m3/d
Grease production
Grease concentration removed                                  90.00     mg/l      Assumed
Dist. To IFAS
Peak flow                                                     8000.00   m3/day
                                                              333.33    m3/h
Design flow rate                                              250.00    m3/h
V
Breadth (B)                                     B             1.60      m
Length (L)                                      L             3.00      m
Water depth                                     d max         1.50      m
Volume                                          V             7.20      m3
check
Retention time at peak flow                                   1.30      min       (0.5-2) min, ECP 2018
                                                                                  ,P.1/3
Retention time at average flow                          1.73      min           (0.5-2) min, ECP 2018
                                                                                ,P.1/3
IFAS TANK
Influent BOD                                            291.00    mg/l
Influent sBOD                                           174.60    mg/l
Influent TSS                                            241.00    mg/l
Influent VSS                                            192.80    mg/l          TSS/VSS= 0.8
Influent NH4                                            25.00     mg/l
Influent TKN                                            20.00     mg/l
Sludge production
Influent substrate                                                     378.30    mg/l
concentration(So)=biodegradable COD             S0
"bCOD"
Vtotal
Excess sludge
Sludge production including inert matters                     769.32    kg Tss/d
                                             Px, Tss, total
Sludge specific gravity                                       1.01
Sludge concentration                         C2               9000      mg/l
Sludge to be waste                                            84.63     m3/d
Return sludge
MLSS                                                          2000.00   mg/l
Return sludge ratio (RAS)=MLSS/ (C2-MLSS)    RAS              0.29      of total flow
taken                                                         0.50                           (50-100) % , ECP 2019
                                             RAS
                                                                                             ,P50/3
Required return sludge flow                  Q'               3000.00   m3/d
Dist. To FST
Volume                                         V         7.20      m3
check
Retention time at peak flow                              1.30      min                    (0.5-2) min,ECP 2018
                                                                                          ,P.1/3
Retention time at average flow                           1.73      min                    (0.5-2) min,ECP 2018
                                                                                          ,P.1/3
Checks
Retention time at average flow                2.91      hr          (1.5-2) hours , ECP, P.83
                                       t
Retention time at Peak flow            t      1.45      hr          (1.5-2) hours , ECP, P.83
Overflow rate at average flow                 19.26                 (16-28) m3/m2/day, for
                                       OFR                          avg flow, ECP
                                                                    2018,P.3/52 ,
Overflow rate at peak flow                    38.51                 (40-64) m3/m2/day, for
                                       OFR'                         peak flow, ECP
                                                                    2018,P.3/52
Solid loading rate at average flow            2.41                  (5-8) Kg/m2/hr,ECP
                                       SLR
                                                                    2018,P.3/52
Solid loading rate at peak flow               4.81                  (5-8) Kg/m2/hr,ECP
                                       SLR'
                                                                    2018,P.3/52
Weir loading rate at average flow                            55.36     m3/m/day
                                            WLR
Weir loading rate at peak flow                               110.72    m3/m/day
                                            WLR'
V notch weir pitch                                           0.30      m
Weir length for each clarifier                               36.13     m
No. of V notches unit                                        120.43
Selected No. of V notches unit                               120
Excess sludge
Sludge production including inert matters                    769.32    kg Tss/d
                                            Px, Tss, total
Sludge specific gravity                                      1.01
Sludge concentration                        C2               9000      mg/l
Sludge to be waste                                           84.63     m3/d
Return sludge
MLSS                                                         2000
Return sludge ratio                         RAS              0.50      of total flow   RAS=MLSS/ (C2-MLSS)
Required return sludge flow                 Q'               3000      m3/d
Checks
Retention time at peak flow                              0.54        hr
                                                         32.40       min          10-30 min,ECP
                                                                                  2018,P.3/53
Retention time at average flow                           0.72        hr
Thickened Sludge
Thickened sludge solids concentration                       2.00          %                    2-3% for thickened excess
                                                                                               sludge
Sludge specific gravity                                     1.05
Thickened sludge weight                                     461.59        kg TSS/day
Thickened sludge flow                                       21.98         m3/day
Supernatant (sludge liquor) water flow                      130.36        m3/day
Thickener Depth
Thickened sludge depth=Thickened sludge                     0.39          m
flow/Total area                             H thickened
DRYING BEDS