Relay and Timer Specifications
Specifications- 700-HF Relays
Electrical Ratings 700-HF 2 Pole 700-HF 4 Pole
AC 15 @ 700 VA
230V AC AC-1 @ 3000 VA
Inductive V AC
1 Hp @ 240V AC
120V AC 1/2 Hp @ 120V AC
Contacts 12 A @ 30V DC
VDC DC-1 0.5 A @ 110V DC
0.25 A @ 220V DC
AC 12 A @ 250 V AC (per pole)
Resistive
DC 12 A @ 30 V DC (per pole)
AC 80…110% nom voltage
Operating Range
DC 80…110% nom voltage 85…110% nom voltage
AC (50 Hz) 1.5 VA 2 VA
Rated Power
DC 1W 1.3 W
AC 80% nom voltage
Holding Voltage
DC 60% nom voltage
AC 20% nom voltage
Must Drop Out Voltage
DC 10% nom voltage
Insulation Voltage 250V AC
Design Specification/Test Requirements
Pole-to-Pole 2500V AC
Dielectric Withstand Voltage
Contact to Pole 2500V AC
Mechanical
Degree of Protection Open Type (Sockets)
Mechanical Life Operations 20 x 106
Switching Frequency Operations 3600/hr
Coil Voltages See Product Selection
Operating Time at nom voltage Pickup 8 ms 10 ms
at 20 °C Dropout 3 ms 4 ms
Maximum Operating Rate 4 Ops/s
Vibration 15 G
Shock 15 G
Environmental
Operating –40…+70 °C (–40…+268 °F)
Temperature
Storage –50…+80 °C (–89…+176 °F)
Altitude 2000 m (6560 ft)
Construction
Insulating Material Molded High-Dielectric Material
Enclosure Transparent Dust Cover
Contact Material Silver Cad. Oxide
Terminal Markings on Socket In accordance with EN50 0005
Sockets 8-Blade Socket (DPDT) Cat. No. 700-HN116 & 700-HN262, 14-Blade Socket (4PDT) Cat. No. 700-HN139 & 700-HN264
CSA Certified (File No. 229473), UL Recognized (File No. E3125, Guide NLDX2/NLDX8), CE Marked,
Certifications
UL Listed when used with sockets shown above, (File No. E3125, Guide NLDX/NLDX 7), LR Certified, RINA Certified, IMQ Certified
Standards UL 508, CSA 22.2 No. 14, EN-61810-1