Gain energy insight and
control with PowerLogic™
PowerLogic PM700
power and energy meters
Compact, cost-effective power and
energy meters
PowerLogic PM700 series power and energy meters offer outstanding
quality, versatility and functionality in a cost-effective, ultra-compact unit.
OEMs, panel builders and customers in industrial, buildings or infrastructure
environments will find the meters ideal for replacing analog meters or for
adding metering to custom panels, switchboards, switchgear, gensets,
motor control centers and UPS systems. The meters are simple to use and
offer large, bright LCD displays. They can be used for stand-alone metering
or seamlessly integrated with PowerLogic power and energy management
systems.
The meters are available in four models with incremental features. All
models offer power, demand, energy, power factor, frequency and THD
measurements, with higher models offering a choice of digital inputs,
outputs, RS-485 communications and alarm functions. Perfect for monitoring
right down to the tool level, the meters’ IEC Class 1 or Class 0.5 certified
accuracy make them suited for many applications.
Typical applications
v Energy savings
v Measure efficiency, reveal opportunities and verify savings
v Sub-bill tenants for energy costs
v Allocate energy costs to departments or processes
v Reduce peak demand surcharges
v Reduce power factor penalties
v Leverage existing infrastructure capacity and avoid over-building
v Energy availability and reliability
v Verify the reliable operation of equipment
v Improve response to power quality-related problems
Features
Cost-effective
Financial management including
accounting and billing v Simple retrofit
v Low initial investment
Ease of use
v Fast setup via display or software
v Compatible with entry-level PowerView software
Facility and energy management
v Bright, easy to read LCD display
High accuracy metering
v IEC62053-22.Class 0.5S energy accuracy (PM750)
v IEC62053-21 Class 1 energy accuracy (PM700, PM700P, PM710)
Operations management including Communications
engineering, planning and maintenance v RS-485 port (PM710, PM750)
v Modbus protocol for integration with power and energy management
software such as PowerLogic ION Enterprise, PowerLogic System
Manager or PowerLogic PowerView
Pulse inputs and outputs
v 2 outputs (PM700P) for kWh or kvarh pulsing
Power generation, transmission v 1 output (PM750) for kWh-pulsing, alarm status or external controlled
and distribution output
v 2 inputs (PM750) for status, alarms or demand input synchronisation
Service entrances and onsite generation
Power mitigation and main power
distribution equipment
Integrated network comprising corporate intranet, Internet, serial, dialup or wireless connections
PM700 series meter front view showing PM700 series meter rear view showing
integrated display. connectors.
PDUs and data servers
Tenants, departments or subcontractors
Processes, lines, machines or
equipment
Typical applications of PowerLogic PM700 series meters within a
PowerLogic power and energy management system
(A) Installation
Mounting Options
96 mm
(3.78 in.) The meters come with an integrated display and can be quickly panel mounted
through a square cutout using two clips with no tools required. A small panel footprint
and shallow 50 mm (1.97 in.) depth behind the mounting surface maximises free
space for other electrical devices inside a switchgear cabinet when mounted on the
50.0 mm 19 mm 96 mm door. This makes the meters suitable for low voltage switchboards, shallow cable
(0.75 in.)
(1.97 in.) (3.78 in.)
compartments or on standalone machines.
92 mm Circuit and control power connections
+0.8 –0.0
(3.62 in.) All models are compatible with low and high voltage 4-wire wye and 3-wire delta
systems and are suitable for three-phase (3P, 3P + N), two-phase and single-phase
(B)
systems. Direct connect inputs up to 480 V ac line-to-line or use voltage (potential)
transformers for higher voltage systems. All models offer a universal AC or DC power
supply.
92 mm
+0.8 –0.0
(3.62 in.)
Input(s) Specifications
Voltage inputs
Nominal full scale (Un): 10 to 277 direct V ac line-to-neutral
10 to 480 V ac direct line-to-line
Up to 1.6 MV with external VT/PT, start of measuring voltage
depends on PT ratio
Metering over-range 1.2 Un (20%)
Input impedance 2 M Ω (Ph-Ph) / 1 M Ω (Ph-N)
Frequency range 45 to 65 Hz
(C)
Current inputs
Nominal current 1 A or 5 A ac
Metering range 5 mA to 6 A ac
Withstand 10 A continuous, 50 A for 10 s per hour, 120 A for 1 s per hour
Load/burden < 0.15 VA
Impedance < 0.1 ohm
Control power
Operating range 100 to 415 V ac ±10%
A. Meter dimensions, showing depth behind panel, 125 to 250 V dc ±20%
and display bezel side and front dimensions. Load/burden 5 VA (ac) or 3 W (dc)
Ride through 100 ms at 120 V ac
B. Meter mounted into square panel cutout.
C. Mounting clips securing meter behind panel.
Front panel display
The anti-glare backlit green LCD is easily read in extreme lighting conditions or
viewing angles. An intuitive navigation with self-guided menus make the meter easy
to use. The large 6-line display offers summary screens that simultaneously present
up to 4 concurrent values, including power and energy values, I/O conditions or alarm
status. Bar chart displays graphically represent system loading and I/O conditions.
Historical and active alarms include timestamps.
Communications
Model PM710 and PM750 meters offer a standard RS-485 communication port that
allows data to be uploaded to software for viewing and analysis. The port offers
2-wire connection, operates at speeds up to 19.2 kbaud, and supports Modbus RTU
protocol.
Software integration
Model PM710 and PM750 meters are compatible with PowerLogic facility-level or
enterprise-wide power and energy management systems. Real-time and min/max
data can be automatically retrieved for analysis at the system level. Compatible with
PowerLogic ION Enterprise, PowerLogic System Manager, PowerLogic PowerView
and PowerLogic Tenant Metering software. Modbus compatibility supports integration
Example screen from PowerLogic ION Enterprise software showing electrical
with building automation, SCADA and other third-party systems.
system diagram with multiple real-time metering points.
Power and energy measurements
Metering is performed by zero-blind sampling all inputs at 32 samples/cycle with
a data update rate of 1 second. The meter offers a range of instantaneous RMS,
power, demand and energy measurements suitable for real-time monitoring, energy
management and sub-billing purposes.
Measurement Accuracy
3-phase and neutral current display Voltage, current, power summary display
Current: per phase, neutral, min/max ±0.4% (PM750)
Current demand: present, peak1 ±0.5% (PM700,700P,PM710)
from 1 A to 6 A
Voltage (line-line, line-neutral): per phase, ±0.3% (PM750)
min/max ±0.5% (PM700, 700P, PM710)
from 50 V to 277 V
Power: real (kW), reactive (kvar), ±0.5% (PM750)
apparent (kVA), per-phase, total ±1% (PM700, PM700P and PM710)
Power demand: present, peak1
Alarm display showing active alarm* Digital inputs and outputs display* Energy: real (kWh), reactive (kvarh), Real: Class 1 as defined by IEC 62053-21
apparent (kVAh), in/out (PM750) (PM700, PM700P, and PM710), Class 0.5S as
defined by IEC 62053-22 (PM750)
Reactive: Class 2 as defined by IEC 62053-23
Signed power factor: total, min/max ±0.0034 for readings from -0.5 to +0.5
Frequency: present, min/max ±0.02 Hz from 45 to 65 Hz
1 Selectable block or sliding demand calculation mode with internal or external (via digital input) demand
synchronisation.
Power factor display*
* Available for model PM750 only.
Power quality analysis
All models offer total harmonic distortion measurement (THD) on voltage and current,
per phase and min/max. The model PM750 can alarm on THD levels.
Type Input / Specifications
output
PM700P 2 digital KY
outputs
3 to 240 V dc or 6 to 240 V ac,
100 mA at 25 °C, derate 0.56
Digital inputs and outputs
mA per °C above 25 °C, 2.41 kV The model PM700P has two solid-state KY outputs dedicated to kWh and kvarh
rms isolation, 30 Ω on-resistance pulsing. The model PM750 has one digital output three operating modes: external
at 100 mA
control (default), alarm (control relay in response to alarm condition) and kWh pulse.
PM750 1 digital KY 8 to 36 V dc, 24 V dc nominal at
output 25 °C, 3.0 kV rms isolation, 28 Ω The PM750 also has two digital inputs featuring two operating modes: normal and
on-resistance at 100 mA demand synchronisation. Use these to trigger alarms or monitor equipment status.
2 digital 12 to 36 V dc, 24 V dc nominal,
inputs 12 kΩ impedance, 2.5 kV rms
isolation, max. frequency 25 Hz, Alarm and control functions
response time 10 ms
The PM750 features 15 user-configurable alarms that can be used to trigger on
over and under conditions most commonly found in power systems. Get early
warning of impending problems that could lead to equipment problems or downtime.
Communicate alarms through the RS-485 port for remote monitoring and use the
meter’s digital outputs for control applications to help avoid penalties and perform
General specifications proactive maintenance.
Description Specification
Weight 0.37 kg (0.8 lb)
Safety Europe: e as per IEC 61010-1 i (1). USA and Canada: UL508.
Operating temp. Meter: -5 °C to +60 °C. Display: -10 °C to +50 °C.
Storage temp. Meter and display: -40 °C to +85 °C
Relative humidity 5 to 95% at 50 °C (non-condensing)
Altitude 3000 m maximum
Pollution degree 2
Installation category III, for distribution systems up to 277/480 Vac
Dielectric withstand As per EN 61010, UL508 - double insulated front panel display
IP degree of protection As per IEC 60529: IP52 front display, IP30 meter body
Immunity ESD: IEC 61000-4-2 Level 3, Radiated: IEC 61000-4-3 Level 3, Fast transients: IEC 61000-4-4 Level 3, Impulse waves: IEC 61000-4-5 Level 3
Conducted: IEC 61000-4-6 Level 3, Magnetic field: IEC 61000-4-8 Level 3, Voltage dips: IEC 61000-4-11 Level 3
Emissions Conducted and radiated: e commercial environment/FCC part 15 class B EN 55011, Harmonics: IEC 61000-3-2, Flicker: IEC 61000-3-3
Selection Guide PM700 PM700P PM710 PM750
General
Use on LV and HV systems < < < <
Current accuracy (1 A to 6 A) ±0.5 % ±0.5 % ±0.5 % ±0.4 %
Voltage accuracy (50 V to 277 V) ±0.5 % ±0.5 % ±0.5 % ±0.3 %
“The 2007 award recognizes Schneider Electric for its technological
Energy and power accuracy 1.0 % 1.0 % 1.0 % 0.5 %
advancements and wide product range in the field of power quality (PQ)
Instantaneous rms values and energy management solutions. In total, this is the fourth award that
Current Phases and neutral < < < < Schneider Electric and [recently acquired] Power Measurement have received
from Frost & Sullivan in recognition of achievements in this arena.”
Voltage Ph-Ph, Ph-N < < < < Prithvi Raj, Frost & Sullivan research analyst
Frequency < < < <
Signed power 1
Real < < < <
Reactive < < < <
Apparent < < < <
Power factor Total < < < <
Energy values
Signed real and reactive energy and < < < <
apparent energy
Demand values 2007
Current (present and max.) < < < <
Active, reactive, apparent power < < < <
Setting of calculation mode < < < <
Power quality measurements Bronze winner, 2007 Product of the Year (PM750), Plant Engineering Magazine
Harmonic distortion (current, voltage) < < < <
Data recording
Min/max of instantaneous values < < < <
Display and I/O
Backlit LCD display < < < <
Pulse output - 2 - 1
Pulse input - - - 2
Communication
RS 485 port - - < <
Modbus protocol - - < <
Alarms
Over/under conditions - - - 15
1
Total and per phase
Please contact your local sales representative for ordering information.
Visit www.powerlogic.com for more information on other PowerLogic
products, applications and system solutions.
Schneider Electric
35 Rue Joseph Monier
CS 30323 As standards, specifications and designs develop from time to time, always ask
92506 Rueil Malmaison Cedex for confirmation of the information given in this publication. PowerLogic, ION, ION
Tel : +33 (0)1 41 29 70 00 Enterprise, MeterM@il and Modbus are either trademarks or registered trademarks
Fax : +33 (0)1 41 29 71 00 of Schneider Electric.
www.powerlogic.com Printed on recycled paper
www.schneider-electric.com
Publishing : Schneider Electric
PLSED106037EN ART# 822940 11-2008 Production : Schneider Electric PMC
© 2008 - Schneider Electric - All rights reserved Printing : Imprimerie du Pont de Claix - made in France