UPS Updated 2018

This document provides information on NP 2011/2031/4011/4031/4033 Series Uninterruptible Power Supply (UPS) systems for industrial applications. The NP 2011 and 2031 models offer a cost-effective and efficient double-conversion online UPS with IGBT technology. They provide stable AC power output and protect loads from grid disturbances. The modular design allows for flexible system configuration. The UPS offers communication, monitoring, and bypass options. It meets various component, equipment, and EMC standards for industrial use. Technical specifications are provided for different power ratings.

Uploaded by

Gerard Govin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
613 views15 pages

UPS Updated 2018

This document provides information on NP 2011/2031/4011/4031/4033 Series Uninterruptible Power Supply (UPS) systems for industrial applications. The NP 2011 and 2031 models offer a cost-effective and efficient double-conversion online UPS with IGBT technology. They provide stable AC power output and protect loads from grid disturbances. The modular design allows for flexible system configuration. The UPS offers communication, monitoring, and bypass options. It meets various component, equipment, and EMC standards for industrial use. Technical specifications are provided for different power ratings.

Uploaded by

Gerard Govin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

U ninterruptib le P ower S upply ( U P S )

NP 2011 / NP 2031 / NP 4011 / NP 4031 / NP 4033 Series

AC S ecured P ower f or I ndustries

Q uality and Reliable System


NP 2011 / 2031 Series

NP 2011 and NP 203 1 series are


designed to offer a cost effective product
with the most advanced technology in
power supply applications. They are
"on-line” double conversion UPS,
designed to protect ac loads from any
disturbances from the ac mains power
supply.
The power conversion to ac stabilised
voltage is monitored by means of IGBT
modules, assuring high performance in
terms of efficiency, harmonic distortion
and voltage stability. The modular and
flexi ble design allows easy configuration
of the system according to the customers
technical requirements.

Options Technical advancements


Parallel redundant operation IGBT technology

H ot standby operation Digital control

Bypass isolation transformer and/ or AC True on-line double coversion


voltage stabilizer
All components accessible from front
Remote monitoring panel
Large charger for use with DC loads and
Software for remote monitoring charging large batteries

Potential free contacts ( AS400) EMI filter

AC distribution Integrated static and manual bypass switches

Ex ternal service bypass switch 110/ 220 VDC battery voltages

Input and output filters Low noise and heat rej ection

Emergency power off ( EPO) Microprocessor controlled LC D mimic and


control
Special meters and alarms
RS23 2 and RS485 communication ports
5 0/ 6 0 H z frequency converter
Communication panel
The standard communication panel offers all the
critical alarms and indications needed. The status
of the UPS is available at a glance thanks to the
integrated graphic and LC D panel alarm and
metering functions in clear tex t and different
languages.

T h e m aj or f eatures are:
Measurements of voltages, currents and
frequency

Startup, operation, alarms and history via LC D


display

Operation mode LED’s

Emergency power off ( EPO) Application


Alarm battery discharged Petrochemical processing plants

Automatic battery test and failure alarm Refineries, offshore platforms

Battery boost charge ( option) Oil and gas pipeline

SNMP interface for remote monitoring and control Power generation plants
via PC

Components standards Equipment standards


Power transformers IEC 7 6 Low voltage assemblies IEC 43 9-1,
IEC 43 9-2,
C ircuit breakers IEC 947 -2 IEC 43 9-3

Switches IEC 947 -3 Semiconductor convertors IEC 146 -1-1,


IEC 146 -1-3 ,
C ontactors IEC 947 -4-1 IEC 146 -2

Fuses IEC 26 9 Degree of protection IEC 5 29

Measuring instruments IEC 5 1-1 Safety ( C E marking) EN 5 0091-1

C apacitors IEC 3 84 Electromagnetic compatibility


( C E making) EN 5 0091-2
NP 2011 - Technical Data

UPS Power Rating


DC/Battery Voltage : 110 Vdc
5 10 15 20 30 40 50
Rectifier Data
Nominal input voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.85 15.7 23 31.4 45.9 62.7 78.5
Inverter Data
Permissible input DC voltage range 95 to 165 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 86 87 88 88 88 89 89
Load power factor range 0.7 lag to 0.7 cap
Phase displacement

Balance load Not applicable


100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation

Synchronisation with mains +/- 2 Hz (Selectable)


Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50
System efficiency (%) 79 81 82 83 83 84 84
Losses at nominal load (KW) 0.9 1.6 2.3 2.9 3.9 5.1 6.4
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous

Permissible inverter output variation


+/- 10%
for bypass switching

Insulation test for 60 sec 2.0 kV


Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4

Audible noise level at 1 meter (dBA) 60 60 60 60 65 65 65


Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600
Weight (Kgs) 340 360 450 490 520 560 620
NP 2011 - Technical Data

UPS Power Rating


DC/Battery Voltage : 220 Vdc
5 10 15 20 30 40 50 60 80 100 120
Rectifier Data
Nominal input voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.8 15.6 27.3 31.2 45.4 62.3 75.3 91 124.3 155.8 175
Inverter Data
Permissible input DC voltage range 176 to 325 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 88 89 91 92 92 92 92 93 93 93 93
Load power factor range 0.7 lag to 0.7 cap
Phase displacement

Balance load Not applicable


100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation

Synchronisation with mains +/- 2 Hz (Selectable)


Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50 60 80 100 120
System efficiency (%) 81 83 85 85 86 86 87 88 88 88 88
Losses at nominal load (KW) 0.8 1.4 2.1 2.6 3.6 4.8 6.0 6.6 8.7 10.9 13.0
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous

Permissible inverter output variation


+/- 10%
for bypass switching

Insulation test for 60 sec 2.0 kV


Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4

Audible noise level at 1 meter (dBA) 60 60 60 60 60 65 65 65 65 65 65


Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 550 1100 1100 1100 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600 1600 1900 1900 1900
Weight (Kgs) 350 365 375 395 505 575 600 625 660 700 780
NP 2031 - Technical Data
UPS Power Rating
DC/Battery Voltage : 110 Vdc
5 10 15 20 30 40 50
Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.85 15.7 23 31.4 45.9 62.7 78.5
Inverter Data
Permissible input DC voltage range 95 to 165 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 86 87 88 88 88 89 89
Load power factor range 0.7 lag to 0.7 cap
Phase displacement

Balance load Not applicable


100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation

Synchronisation with mains +/- 2 Hz (Selectable)


Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50
System efficiency (%) 79 81 82 83 83 84 84
Losses at nominal load (KW) 0.9 1.6 2.3 2.9 3.9 5.1 6.4
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous

Permissible inverter output variation


+/- 10%
for bypass switching

Insulation test for 60 sec 2.0 kV


Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4

Audible noise level at 1 meter (dBA) 60 60 60 60 65 65 65


Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600
Weight (Kgs) 340 360 450 490 520 560 620
NP 2031 - Technical Data
UPS Power Rating
DC/Battery Voltage : 220 Vdc
5 10 15 20 30 40 50 60 80 100 120
Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.8 15.6 27.3 31.2 45.4 62.3 75.3 91 124.3 155.8 175
Inverter Data
Permissible input DC voltage range 176 to 325 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 88 89 91 92 92 92 92 93 93 93 93
Load power factor range 0.7 lag to 0.7 cap
Phase displacement

Balance load Not applicable


100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation

Synchronisation with mains +/- 2 Hz (Selectable)


Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50 60 80 100 120
System efficiency (%) 81 83 85 85 86 86 87 88 88 88 88
Losses at nominal load (KW) 0.8 1.4 2.1 2.6 3.6 4.8 6.0 6.6 8.7 10.9 13.0
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous

Permissible inverter output variation


+/- 10%
for bypass switching

Insulation test for 60 sec 2.0 kV


Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4

Audible noise level at 1 meter (dBA) 60 60 60 60 60 65 65 65 65 65 65


Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 550 1100 1100 1100 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600 1600 1900 1900 1900
Weight (Kgs) 350 365 375 395 505 575 600 625 660 700 780
NP 4011 / NP 4031 Series

NP 4011 / NP 403 are true on-line


double conversion UPS system offering
many advanced features.

NP 4011 / NP 403 are equipped with


microprocessor control, digital communica-
tion for remote supervision, and IGBT
power technology.

Application
IT systems, process control systems

Telecommunications facilities

Instrumentation and control

Systems in power stations


NP 4011 / NP 403 1 have many forms of
Industrial plants communication and interface that are required by
the professional user to ensure total control of the
Air traffic control systems
power environment supplied to the critical load.

T h e m aj or f eatures are:
Measurements of voltages, currents and
frequency

Startup, operation, alarms and history via LC D


display

Operation mode LED’s

Emergency power off ( EPO)

Alarm battery discharged

Automatic battery test and failure alarm

Battery boost charge ( option)

SNMP interface for remote monitoring and control


via PC
NP 4011 - Technical Data

UPS Power Rating 5 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400

Rectifier Data
Nominal input voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Tolerance + 15%, -10% for Vnom +/- 10%
Nominal input frequency 50 / 60Hz

Inverter Data
Permissible input DC voltage range 285 - 420 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 92 92 92 92 92 92 93 93 93 93 94 94 94 94 95 95
Load power factor range 0.5 lag to 0.5 cap
Phase displacement

Balance load 120 deg +/- 1% 120 deg +/- 1%


100% unbalance load 120 deg +/- 1% 120 deg +/- 4%
Voltage transient recovery < = 50msec to within +/- 2% of nominal voltage
Short circuit current (A) 150% 5sec, 200% 100msec 130% 1min
System Data
Output voltage distortion (THD)
Linear Load < 1% < 3%
Non-linear Load (CF = 3) < 4%
Output frequency regulation

Synchronisation with mains +/- 0.5 / 1 / 2 Hz (Selectable with software)


Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
System efficiency (%) 88 88 88 88 88 90 90 90 90 90 92 92 92 93 93 93
Losses at nominal load (KW) 0.4 0.8 1.2 1.6 2.4 3.2 4.8 6.4 8.0 9.6 9.0 11.2 15.1 16.8 19.6 22.4
Overload capacity

2000% 20 msec
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
180% 1 min

Static bypass switch (SBS) 2000% 20 msec, 200% 1 min, 150% 30 min, 130% continuous 140% continuous

Permissible inverter output variation


+/- 10%
for bypass switching

Insulation test for 60 sec 2.0 kV


Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4

Audible noise level at 1 meter (dBA) 58 58 58 58 58 60 60 61 61 62 70 70 70 63 63 63


Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 550 1100 1100 1100 1100 2200 2200 2200 2200 2200 2200
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000
H 1600 1600 1600 1600 1600 1600 1600 1900 1900 1900 1900 1900 1900 1900 1900 1900
Weight (Kgs) 310 310 310 345 385 440 510 669 712 745 1075 1175 2050 2350 2550 3270
NP 4031 - Technical Data

UPS Power Rating 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400

Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance + 15%, -10% for Vnom +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 13.5 20 26.9 39.8 53.5 80 105 132 158 210 262 324 398 418 520
Inverter Data
Permissible input DC voltage range 285 - 420 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 92 92 92 92 92 93 93 93 93 94 94 94 94 95 95
Load power factor range 0.5 lag to 0.5 cap
Phase displacement

Balance load 120 deg +/- 1% 120 deg +/- 1%


100% unbalance load 120 deg +/- 1% 120 deg +/- 4%
Voltage transient recovery < = 50msec to within +/- 2% of nominal voltage
Short circuit current (A) 150% 5sec, 200% 100msec 130% 1min
System Data
Output voltage distortion (THD)
Linear Load < 1% < 3%
Non-linear Load (CF = 3) < 4%
Output frequency regulation

Synchronisation with mains +/- 0.5 / 1 / 2 Hz (Selectable with software)


Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
System efficiency (%) 88 88 88 88 90 90 90 90 90 92 92 92 93 93 93
Losses at nominal load (KW) 0.8 1.2 1.6 2.4 3.2 4.8 6.4 8.0 9.6 9.0 11.2 15.1 16.8 19.6 22.4
Overload capacity

2000% 20 msec
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
180% 1 min

Static bypass switch (SBS) 2000% 20 msec, 200% 1 min, 150% 30 min, 130% continuous 140% continuous

Permissible inverter output variation


+/- 10%
for bypass switching

Insulation test for 60 sec 2.0 kV


Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4

Audible noise level at 1 meter (dBA) 58 58 58 58 60 60 61 61 62 70 70 70 63 63 63


Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100 1100 1100 2200 2200 2200 2200 2200 2200
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000
H 1600 1600 1600 1600 1600 1600 1900 1900 1900 1900 1900 1900 1900 1900 1900
Weight (Kgs) 310 310 345 385 440 510 669 712 745 1075 1175 2050 2350 2550 3270
NP 4033 Series

NP 403 3 series are three-phase output.


True on-line double conversion UPS system
designed with the most advanced electronic
technology equipped with microprocessor
control, digital communication for remote
supervision, and IGBT power technology.

Application
IT systems, process control systems

Telecommunications facilities

Instrumentation and control


Communication panel
Systems in power stations The standard communication panel offers all the
Industrial plants critical alarms and indications needed. The status of
the UPS is available at a glance thanks to the
Air traffic control systems integrated graphic and LC D panel alarm and
metering functions in clear tex t and different
languages.

T h e m aj or f eatures are:
Measurements of voltages, currents and
frequency

Startup, operation, alarms and history via LC D


display

Operation mode LED’s

Emergency power off ( EPO)

Alarm battery discharged

Automatic battery test and failure alarm

Battery boost charge ( option)

SNMP interface for remote monitoring and control


via PC
Options
M ultiple system s options
Units of any power rating can be connected in any
configuration

Parallel up to eight systems

H ot and C old standby unlimited systems

Advanced Power Management ( APM) - automated


autostart of systems with an increase in load

Any combination of parallel, hot or cold standby


connected as a single system ( APM)

C ustom er options
12 pulse rectification

Battery and distribution cubicles

Technical advancements C ubicle ratings to IP5 4

IGBT technology Galvanic isolation

Digital control Ex ternal bypass

True on-line double conversion Top cable entry

Progress Battery Management ( PBM) with Battery earth fault monitoring


temperature compensation
Input filters to G5 / 3
Individual phase control of inverter voltage and
current

H igh frequency PWM giving instant respond to


changes in load conditions

Integral static and manual bypass

Low noise and heat rej ection

Safety and protection to meet the highest


industrial demands

Microprocessor controlled LC D mimic and control

RS23 2 and RS485 communication ports

SNMP protocol

Volt free contacts


NP 4033 - Technical Data

UPS Power Rating 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400

Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance + 15%, -10% for Vnom +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 13.5 20 26.9 39.8 53.5 80 105 132 158 210 262 324 398 418 520
Inverter Data
Permissible input DC voltage range 285 - 420 Vdc
Nominal output voltage 380 / 400 / 415 - 690 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 92 92 92 92 92 93 93 93 93 94 94 94 94 95 95
Load power factor range 0.5 lag to 0.5 cap
Phase displacement

Balance load 120 deg +/- 1% 120 deg +/- 1%


100% unbalance load 120 deg +/- 1% 120 deg +/- 4%
Voltage transient recovery < = 50msec to within +/- 2% of nominal voltage
Short circuit current (A) 150% 5sec, 200% 100msec 130% 1min
System Data
Output voltage distortion (THD)
Linear Load < 1% < 3%
Non-linear Load (CF = 3) < 4%
Output frequency regulation

Synchronisation with mains +/- 0.5 / 1 / 2 Hz (Selectable with software)


Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
System efficiency (%) 88 88 88 88 90 90 90 90 90 92 92 92 93 93 93
Losses at nominal load (KW) 0.8 1.2 1.6 2.4 3.2 4.8 6.4 8.0 9.6 9.0 11.2 15.1 16.8 19.6 22.4
Overload capacity

2000% 20 msec
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
180% 1 min

Static bypass switch (SBS) 2000% 20 msec, 200% 1 min, 150% 30 min, 130% continuous 140% continuous

Permissible inverter output variation


+/- 10%
for bypass switching

Insulation test for 60 sec 2.0 kV


Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4

Audible noise level at 1 meter (dBA) 58 58 58 58 60 60 61 61 62 70 70 70 63 63 63


Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100 1100 1100 2200 2200 2200 2200 2200 2200
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000
H 1600 1600 1600 1600 1600 1600 1900 1900 1900 1900 1900 1900 1900 1900 1900
Weight (Kgs) 310 310 345 385 440 510 669 712 745 1075 1175 2050 2350 2550 3270
Application, Standards and Quality

Adapted to your sector’s unique needs


NIKSA UPS systems are primarily designed to meet requirements for applications in the Petrochemical, Oil & Gas,
Power Generation industries and Railways.

Petrochemical Plants Oil and Gas Utilities Railway


Secured and reliable power The global oil and gas Business and public sector With the rigorous environment
continuity is crucial in today’s companies put their trust in us organization require secured within the railway industry, we
industrial and commercial through our successful electrical power, and are understand the demand and
businesses. With our high installation in their pipelines, always seeking to minimize stringent international
quality power supply it can drillings, production and the risk of power failure for standards. Our high quality
protect critical electrical system support operations. Given the business continuity and public power backup equipments are
in the Gas Processing, Liquid strict requirements within the safety. We have proven track capable to maintain the
Nitrogen and Petrochemical oil and gas industries, we are record of supplying to power functionality against wide
processing plants from the well-equipped to meet the generation, transmission, variation in temperature,
damaging effects of power most challenging and hostile distribution and also meeting heavy vibration, and electrical
failure and work disruptions. electrical environment. all the specification in the disruptions.
Utilities industry.

Worldwide recognized standards


Avatec supplies products that are designed and manufactured based on recognized worldwide technical and safety
standards, such as Bureau Veritas, bizSAFE, ABS, Lloyd's Register, Russian Maritime Register, TUV SUD, Under-
writer Laboratories and DNV.