U ninterruptib le P ower S upply ( U P S )
NP 2011 / NP 2031 / NP 4011 / NP 4031 / NP 4033 Series
AC S ecured P ower f or I ndustries
Q uality and Reliable System
NP 2011 / 2031 Series
NP 2011 and NP 203 1 series are
designed to offer a cost effective product
with the most advanced technology in
power supply applications. They are
"on-line” double conversion UPS,
designed to protect ac loads from any
disturbances from the ac mains power
supply.
The power conversion to ac stabilised
voltage is monitored by means of IGBT
modules, assuring high performance in
terms of efficiency, harmonic distortion
and voltage stability. The modular and
flexi ble design allows easy configuration
of the system according to the customers
technical requirements.
Options Technical advancements
Parallel redundant operation IGBT technology
H ot standby operation Digital control
Bypass isolation transformer and/ or AC True on-line double coversion
voltage stabilizer
All components accessible from front
Remote monitoring panel
Large charger for use with DC loads and
Software for remote monitoring charging large batteries
Potential free contacts ( AS400) EMI filter
AC distribution Integrated static and manual bypass switches
Ex ternal service bypass switch 110/ 220 VDC battery voltages
Input and output filters Low noise and heat rej ection
Emergency power off ( EPO) Microprocessor controlled LC D mimic and
control
Special meters and alarms
RS23 2 and RS485 communication ports
5 0/ 6 0 H z frequency converter
Communication panel
The standard communication panel offers all the
critical alarms and indications needed. The status
of the UPS is available at a glance thanks to the
integrated graphic and LC D panel alarm and
metering functions in clear tex t and different
languages.
T h e m aj or f eatures are:
Measurements of voltages, currents and
frequency
Startup, operation, alarms and history via LC D
display
Operation mode LED’s
Emergency power off ( EPO) Application
Alarm battery discharged Petrochemical processing plants
Automatic battery test and failure alarm Refineries, offshore platforms
Battery boost charge ( option) Oil and gas pipeline
SNMP interface for remote monitoring and control Power generation plants
via PC
Components standards Equipment standards
Power transformers IEC 7 6 Low voltage assemblies IEC 43 9-1,
IEC 43 9-2,
C ircuit breakers IEC 947 -2 IEC 43 9-3
Switches IEC 947 -3 Semiconductor convertors IEC 146 -1-1,
IEC 146 -1-3 ,
C ontactors IEC 947 -4-1 IEC 146 -2
Fuses IEC 26 9 Degree of protection IEC 5 29
Measuring instruments IEC 5 1-1 Safety ( C E marking) EN 5 0091-1
C apacitors IEC 3 84 Electromagnetic compatibility
( C E making) EN 5 0091-2
NP 2011 - Technical Data
UPS Power Rating
DC/Battery Voltage : 110 Vdc
5 10 15 20 30 40 50
Rectifier Data
Nominal input voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.85 15.7 23 31.4 45.9 62.7 78.5
Inverter Data
Permissible input DC voltage range 95 to 165 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 86 87 88 88 88 89 89
Load power factor range 0.7 lag to 0.7 cap
Phase displacement
Balance load Not applicable
100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation
Synchronisation with mains +/- 2 Hz (Selectable)
Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50
System efficiency (%) 79 81 82 83 83 84 84
Losses at nominal load (KW) 0.9 1.6 2.3 2.9 3.9 5.1 6.4
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous
Permissible inverter output variation
+/- 10%
for bypass switching
Insulation test for 60 sec 2.0 kV
Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4
Audible noise level at 1 meter (dBA) 60 60 60 60 65 65 65
Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600
Weight (Kgs) 340 360 450 490 520 560 620
NP 2011 - Technical Data
UPS Power Rating
DC/Battery Voltage : 220 Vdc
5 10 15 20 30 40 50 60 80 100 120
Rectifier Data
Nominal input voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.8 15.6 27.3 31.2 45.4 62.3 75.3 91 124.3 155.8 175
Inverter Data
Permissible input DC voltage range 176 to 325 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 88 89 91 92 92 92 92 93 93 93 93
Load power factor range 0.7 lag to 0.7 cap
Phase displacement
Balance load Not applicable
100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation
Synchronisation with mains +/- 2 Hz (Selectable)
Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50 60 80 100 120
System efficiency (%) 81 83 85 85 86 86 87 88 88 88 88
Losses at nominal load (KW) 0.8 1.4 2.1 2.6 3.6 4.8 6.0 6.6 8.7 10.9 13.0
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous
Permissible inverter output variation
+/- 10%
for bypass switching
Insulation test for 60 sec 2.0 kV
Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4
Audible noise level at 1 meter (dBA) 60 60 60 60 60 65 65 65 65 65 65
Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 550 1100 1100 1100 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600 1600 1900 1900 1900
Weight (Kgs) 350 365 375 395 505 575 600 625 660 700 780
NP 2031 - Technical Data
UPS Power Rating
DC/Battery Voltage : 110 Vdc
5 10 15 20 30 40 50
Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.85 15.7 23 31.4 45.9 62.7 78.5
Inverter Data
Permissible input DC voltage range 95 to 165 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 86 87 88 88 88 89 89
Load power factor range 0.7 lag to 0.7 cap
Phase displacement
Balance load Not applicable
100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation
Synchronisation with mains +/- 2 Hz (Selectable)
Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50
System efficiency (%) 79 81 82 83 83 84 84
Losses at nominal load (KW) 0.9 1.6 2.3 2.9 3.9 5.1 6.4
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous
Permissible inverter output variation
+/- 10%
for bypass switching
Insulation test for 60 sec 2.0 kV
Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4
Audible noise level at 1 meter (dBA) 60 60 60 60 65 65 65
Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600
Weight (Kgs) 340 360 450 490 520 560 620
NP 2031 - Technical Data
UPS Power Rating
DC/Battery Voltage : 220 Vdc
5 10 15 20 30 40 50 60 80 100 120
Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 7.8 15.6 27.3 31.2 45.4 62.3 75.3 91 124.3 155.8 175
Inverter Data
Permissible input DC voltage range 176 to 325 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 88 89 91 92 92 92 92 93 93 93 93
Load power factor range 0.7 lag to 0.7 cap
Phase displacement
Balance load Not applicable
100% unbalance load Not applicable
Voltage transient recovery < = 40msec to within +/- 1% of nominal voltage
Short circuit current (A) 200% 10msec
System Data
Output voltage distortion (THD)
Linear Load < 1.5%
Non-linear Load (CF = 3) < 5%
Output frequency regulation
Synchronisation with mains +/- 2 Hz (Selectable)
Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 50 60 80 100 120
System efficiency (%) 81 83 85 85 86 86 87 88 88 88 88
Losses at nominal load (KW) 0.8 1.4 2.1 2.6 3.6 4.8 6.0 6.6 8.7 10.9 13.0
Overload capacity
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 10 min, 150% continuous
Permissible inverter output variation
+/- 10%
for bypass switching
Insulation test for 60 sec 2.0 kV
Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4
Audible noise level at 1 meter (dBA) 60 60 60 60 60 65 65 65 65 65 65
Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 550 1100 1100 1100 1100 1100
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800
H 1600 1600 1600 1600 1600 1600 1600 1600 1900 1900 1900
Weight (Kgs) 350 365 375 395 505 575 600 625 660 700 780
NP 4011 / NP 4031 Series
NP 4011 / NP 403 are true on-line
double conversion UPS system offering
many advanced features.
NP 4011 / NP 403 are equipped with
microprocessor control, digital communica-
tion for remote supervision, and IGBT
power technology.
Application
IT systems, process control systems
Telecommunications facilities
Instrumentation and control
Systems in power stations
NP 4011 / NP 403 1 have many forms of
Industrial plants communication and interface that are required by
the professional user to ensure total control of the
Air traffic control systems
power environment supplied to the critical load.
T h e m aj or f eatures are:
Measurements of voltages, currents and
frequency
Startup, operation, alarms and history via LC D
display
Operation mode LED’s
Emergency power off ( EPO)
Alarm battery discharged
Automatic battery test and failure alarm
Battery boost charge ( option)
SNMP interface for remote monitoring and control
via PC
NP 4011 - Technical Data
UPS Power Rating 5 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
Rectifier Data
Nominal input voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Tolerance + 15%, -10% for Vnom +/- 10%
Nominal input frequency 50 / 60Hz
Inverter Data
Permissible input DC voltage range 285 - 420 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 92 92 92 92 92 92 93 93 93 93 94 94 94 94 95 95
Load power factor range 0.5 lag to 0.5 cap
Phase displacement
Balance load 120 deg +/- 1% 120 deg +/- 1%
100% unbalance load 120 deg +/- 1% 120 deg +/- 4%
Voltage transient recovery < = 50msec to within +/- 2% of nominal voltage
Short circuit current (A) 150% 5sec, 200% 100msec 130% 1min
System Data
Output voltage distortion (THD)
Linear Load < 1% < 3%
Non-linear Load (CF = 3) < 4%
Output frequency regulation
Synchronisation with mains +/- 0.5 / 1 / 2 Hz (Selectable with software)
Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 5 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
System efficiency (%) 88 88 88 88 88 90 90 90 90 90 92 92 92 93 93 93
Losses at nominal load (KW) 0.4 0.8 1.2 1.6 2.4 3.2 4.8 6.4 8.0 9.6 9.0 11.2 15.1 16.8 19.6 22.4
Overload capacity
2000% 20 msec
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
180% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 1 min, 150% 30 min, 130% continuous 140% continuous
Permissible inverter output variation
+/- 10%
for bypass switching
Insulation test for 60 sec 2.0 kV
Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4
Audible noise level at 1 meter (dBA) 58 58 58 58 58 60 60 61 61 62 70 70 70 63 63 63
Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 550 1100 1100 1100 1100 2200 2200 2200 2200 2200 2200
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000
H 1600 1600 1600 1600 1600 1600 1600 1900 1900 1900 1900 1900 1900 1900 1900 1900
Weight (Kgs) 310 310 310 345 385 440 510 669 712 745 1075 1175 2050 2350 2550 3270
NP 4031 - Technical Data
UPS Power Rating 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance + 15%, -10% for Vnom +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 13.5 20 26.9 39.8 53.5 80 105 132 158 210 262 324 398 418 520
Inverter Data
Permissible input DC voltage range 285 - 420 Vdc
Nominal output voltage 1 Ph + N x 100 / 110 / 120 - 220 / 230 / 240 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 92 92 92 92 92 93 93 93 93 94 94 94 94 95 95
Load power factor range 0.5 lag to 0.5 cap
Phase displacement
Balance load 120 deg +/- 1% 120 deg +/- 1%
100% unbalance load 120 deg +/- 1% 120 deg +/- 4%
Voltage transient recovery < = 50msec to within +/- 2% of nominal voltage
Short circuit current (A) 150% 5sec, 200% 100msec 130% 1min
System Data
Output voltage distortion (THD)
Linear Load < 1% < 3%
Non-linear Load (CF = 3) < 4%
Output frequency regulation
Synchronisation with mains +/- 0.5 / 1 / 2 Hz (Selectable with software)
Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
System efficiency (%) 88 88 88 88 90 90 90 90 90 92 92 92 93 93 93
Losses at nominal load (KW) 0.8 1.2 1.6 2.4 3.2 4.8 6.4 8.0 9.6 9.0 11.2 15.1 16.8 19.6 22.4
Overload capacity
2000% 20 msec
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
180% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 1 min, 150% 30 min, 130% continuous 140% continuous
Permissible inverter output variation
+/- 10%
for bypass switching
Insulation test for 60 sec 2.0 kV
Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4
Audible noise level at 1 meter (dBA) 58 58 58 58 60 60 61 61 62 70 70 70 63 63 63
Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100 1100 1100 2200 2200 2200 2200 2200 2200
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000
H 1600 1600 1600 1600 1600 1600 1900 1900 1900 1900 1900 1900 1900 1900 1900
Weight (Kgs) 310 310 345 385 440 510 669 712 745 1075 1175 2050 2350 2550 3270
NP 4033 Series
NP 403 3 series are three-phase output.
True on-line double conversion UPS system
designed with the most advanced electronic
technology equipped with microprocessor
control, digital communication for remote
supervision, and IGBT power technology.
Application
IT systems, process control systems
Telecommunications facilities
Instrumentation and control
Communication panel
Systems in power stations The standard communication panel offers all the
Industrial plants critical alarms and indications needed. The status of
the UPS is available at a glance thanks to the
Air traffic control systems integrated graphic and LC D panel alarm and
metering functions in clear tex t and different
languages.
T h e m aj or f eatures are:
Measurements of voltages, currents and
frequency
Startup, operation, alarms and history via LC D
display
Operation mode LED’s
Emergency power off ( EPO)
Alarm battery discharged
Automatic battery test and failure alarm
Battery boost charge ( option)
SNMP interface for remote monitoring and control
via PC
Options
M ultiple system s options
Units of any power rating can be connected in any
configuration
Parallel up to eight systems
H ot and C old standby unlimited systems
Advanced Power Management ( APM) - automated
autostart of systems with an increase in load
Any combination of parallel, hot or cold standby
connected as a single system ( APM)
C ustom er options
12 pulse rectification
Battery and distribution cubicles
Technical advancements C ubicle ratings to IP5 4
IGBT technology Galvanic isolation
Digital control Ex ternal bypass
True on-line double conversion Top cable entry
Progress Battery Management ( PBM) with Battery earth fault monitoring
temperature compensation
Input filters to G5 / 3
Individual phase control of inverter voltage and
current
H igh frequency PWM giving instant respond to
changes in load conditions
Integral static and manual bypass
Low noise and heat rej ection
Safety and protection to meet the highest
industrial demands
Microprocessor controlled LC D mimic and control
RS23 2 and RS485 communication ports
SNMP protocol
Volt free contacts
NP 4033 - Technical Data
UPS Power Rating 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
Rectifier Data
Nominal input voltage 3 Ph + N x 380 - 690 Vac
Tolerance + 15%, -10% for Vnom +/- 10%
Nominal input frequency 50 / 60Hz
Max. input power (kVA) 13.5 20 26.9 39.8 53.5 80 105 132 158 210 262 324 398 418 520
Inverter Data
Permissible input DC voltage range 285 - 420 Vdc
Nominal output voltage 380 / 400 / 415 - 690 Vac
Nominal output frequency 50 / 60Hz
Efficiency (%) 92 92 92 92 92 93 93 93 93 94 94 94 94 95 95
Load power factor range 0.5 lag to 0.5 cap
Phase displacement
Balance load 120 deg +/- 1% 120 deg +/- 1%
100% unbalance load 120 deg +/- 1% 120 deg +/- 4%
Voltage transient recovery < = 50msec to within +/- 2% of nominal voltage
Short circuit current (A) 150% 5sec, 200% 100msec 130% 1min
System Data
Output voltage distortion (THD)
Linear Load < 1% < 3%
Non-linear Load (CF = 3) < 4%
Output frequency regulation
Synchronisation with mains +/- 0.5 / 1 / 2 Hz (Selectable with software)
Free running +/- 0.01 %
Rated Output Power pf=0.8 (kVA) 10 15 20 30 40 60 80 100 120 160 200 250 300 350 400
System efficiency (%) 88 88 88 88 90 90 90 90 90 92 92 92 93 93 93
Losses at nominal load (KW) 0.8 1.2 1.6 2.4 3.2 4.8 6.4 8.0 9.6 9.0 11.2 15.1 16.8 19.6 22.4
Overload capacity
2000% 20 msec
Inverter < 110% continuous, 110 - 125% 10 min, 125 - 150% 1 min
180% 1 min
Static bypass switch (SBS) 2000% 20 msec, 200% 1 min, 150% 30 min, 130% continuous 140% continuous
Permissible inverter output variation
+/- 10%
for bypass switching
Insulation test for 60 sec 2.0 kV
Cabinet Protection IP 20 acc. To IEC 529 (other as option)
Ambient temperature
Operating temperature 0 to 55 deg C
Storage temperature 0 to 85 deg C (excluding battery)
Permissible relative humidity < 95 % UR (non condensing)
Max. altitude above sea level < 2000m. Higher altitudes require power derating or increase cooling
RFI Suppression EMC standard satisfied with EN 50091-2 (1995) Class A, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4
Audible noise level at 1 meter (dBA) 58 58 58 58 60 60 61 61 62 70 70 70 63 63 63
Colour RAL 7032 / 7035 (other as option)
W 550 550 550 550 550 1100 1100 1100 1100 2200 2200 2200 2200 2200 2200
Dimension (mm) D 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000
H 1600 1600 1600 1600 1600 1600 1900 1900 1900 1900 1900 1900 1900 1900 1900
Weight (Kgs) 310 310 345 385 440 510 669 712 745 1075 1175 2050 2350 2550 3270
Application, Standards and Quality
Adapted to your sector’s unique needs
NIKSA UPS systems are primarily designed to meet requirements for applications in the Petrochemical, Oil & Gas,
Power Generation industries and Railways.
Petrochemical Plants Oil and Gas Utilities Railway
Secured and reliable power The global oil and gas Business and public sector With the rigorous environment
continuity is crucial in today’s companies put their trust in us organization require secured within the railway industry, we
industrial and commercial through our successful electrical power, and are understand the demand and
businesses. With our high installation in their pipelines, always seeking to minimize stringent international
quality power supply it can drillings, production and the risk of power failure for standards. Our high quality
protect critical electrical system support operations. Given the business continuity and public power backup equipments are
in the Gas Processing, Liquid strict requirements within the safety. We have proven track capable to maintain the
Nitrogen and Petrochemical oil and gas industries, we are record of supplying to power functionality against wide
processing plants from the well-equipped to meet the generation, transmission, variation in temperature,
damaging effects of power most challenging and hostile distribution and also meeting heavy vibration, and electrical
failure and work disruptions. electrical environment. all the specification in the disruptions.
Utilities industry.
Worldwide recognized standards
Avatec supplies products that are designed and manufactured based on recognized worldwide technical and safety
standards, such as Bureau Veritas, bizSAFE, ABS, Lloyd's Register, Russian Maritime Register, TUV SUD, Under-
writer Laboratories and DNV.
ISO 9001 : 2008 ISO 14001 : 2004 bizSAFE ABS
Lloyd’s Register Russian Maritime TUV SUD Underwriters DNV
Register of Shipping Laboratories
Avatec Power Pte Ltd