Caterpillar EMCP4
Installation Guide
1. Unpack the monitor, antenna and the data / power cable.
   The 25 pin connector plugs onto the front of the
   OMNIMETRIX Monitor. This cable includes wires to power
   the monitor as well as wires for alarm inputs, relay outputs
   and analog inputs. Take a moment to inspect all components
   to verify there is no shipping damage.
2. Place the antenna on the roof of the generator and route the
   antenna cable through the louvers down into the area of the
   generator control. The antenna used for transmitting must be
   installed to provide a separation distance of at least 20 cm
   from all persons and must not transmit simultaneously with
   any other antenna transmitters. BE SURE to provide a drip
   loop lower than the monitor to keep water from running down          Data / Power Cable
   the antenna cable into the monitor connection. If the roof is
   aluminum (non-magnetic), simply mount the antenna near the
   roof line on the steel side walls.
3. Attach the monitor via its magnetic feet, on top of the engine
   controller or other appropriate location. Horizontal surfaces
   are best, but the unit may be mounted vertically or even
   upside down if necessary.
4. Route the data / power cable to the terminal strip to pick up
   generator battery power and RS485 data.
5. The monitor connects to the Caterpillar EMCP 4 through a
   simple 4-wire connection. Connect the red wire to generator
   Battery B+, the black wire to generator Battery B- (GND), the
   white wire to Modbus Data+ and the green wire to Modbus
   Data-. For remote start capability, connect the white/yellow
   wire and the white/brown wire to the Genset 2-wire Start
                                                                       CAT EMCP 4 Controller
   Terminal.
6. Attach the antenna cable to the front of the monitor, and
   tighten thumb tight.
7. Set up Modbus via the front panel control, using the steps
   provided on the following page. Be sure to utilize a baud rate
   of 9600, 8 bits, no parity, 1 stop bit.
8. Turn on the monitor and confirm that the LEDs light up and
   blink. If not, check for power on the terminal strip. If, after 5
   minutes, the only LED lit is the Power LED, check the
   antenna mount and cable connection.
9. Allow 15 minutes for the monitor to log into the network and
   then call OMNIMETRIX at 770-209-0012 to confirm
   installation. Access to machine data is through the
   OmniView™ web interface at www.omnimetrix.net. Contact
                                                                        CAT EMCP 4 Wiring
   OMNIMETRIX for login instructions and web training.
Enabling Modbus Communication (Step 7 continued)
Definitions:
               Front Panel Escape Key                          Front Panel Enter Key
Steps:
   1. Escape to MAIN MENU.
   2. Down Arrow to CONFIGURE, then ENTER key.
   3. Down Arrow to SETPOINTS, then ENTER key.
   4. Down Arrow to NETWORK, then ENTER key.
   5. At Data Link = SCADA, ENTER key.
   6. Down Arrow to BAUD RATE, then ENTER key.
   7. Up / Down Arrow to set Baud Rate to 9600, the ENTER key.
   8. Down Arrow to PARITY, the ENTER key.
   9. Up / Down Arrow to set Parity to NONE, the ENTER key.
   10. Down Arrow to SLAVE ADDRESS, the ENTER key.
   11. Up / Down Arrow to set Slave Address to 1, then ENTER key. (Note: if multiple engines are
       involved, then each must have a different slave address.)
   12. Down Arrow to ENABLE STATUS, then ENTER key.
   13. Up / Down Arrow to set ENABLED, the ENTER key.
   14. ESCAPE key multiple times to return to main menu.
The EMCP3 has a timeout option in which it can go into low power mode. In this case, Modbus support
ceases. Be sure the EMCP is set up with the low power setting (sleep mode) OFF. This is done under
CONFIGURE / SETPOINTS / OTHER…Reduced Power mode DISABLE.
If you have any questions, please call OMNIMETRIX Tech Support at 770-209-0012 or email at