SMART CONNECT
USB-MAINTENANCE
CONCEPT
1. September 2014
MTU internal use only
© MTU Onsite Energy GmbH
Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
CONTENTS
1. Handling overview
2. Advantages and benefits
3. Requirements
4. Handling – Backup file
5. General details
Seite 2 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
1. HANDLING
MTU
Update
Backup
MTU –
Smart Connect central Database
Provider
ECU8
Smart Connect
USB Tool Smart Connect
Customer / OEM / MTU-Service S1600
Seite 3 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
2. ADVANTAGES AND BENEFITS
Benefits:
- Creating Backup- and Update file of ECU8
- Creating Backup-Update file with Lifedata (for exchanging defect ECU8 )
- Creating record file
- Firmware update of Smart Connect via USB possible
Advantages:
- No DIASYS necessary
- No MTU-Service on site necessary
- Easy handling of software tool
Seite 4 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
3. REQUIREMENTS
Backup and Backup and Firmware Creating
Update of Update update of Record file
ECU8 of ECU8 with Smart
Lifedata Connect
SC1-01
ECU8-06 X X
FSW1.2
SC1-02
ECU8-07 X X X
FSW1.3
SC2-01
ECU8-07A X X X X
FSW1.4
Seite 5 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
3. REQUIREMENTS
Characteristics of recording file:
- Creating record files with up to 99 PV‘s:
- maximum rate of 7 PV‘s / 5ms (depends on USB-drives)
- max. storage space of 2 GB/per record file (circular buffer)
e.g.: 40 PV‘s: 2 PV‘s/5ms => 40PV‘s/100ms=1280Byte => 46 MB/h
40 PV‘s: 7 PV‘s/5ms => 40PV‘s/30ms=1280Byte => 138,24 MB/h
- MTU has released USB-drives for fast recording:
MTU
Manufacturer Size Description
number
Mach Xtreme 8 GB
1 PDMT-015 X00E50210067
Pen Drive FAT32
Winkom 16 GB
2
WINKOM-Pendrive USB 3.0 - 16 GB X00E50210068
USB 3.0 FAT32
APRO Industrial USB Stick 2 GB
3
SMUFD002G-ADCSC-3 X00E50210069
HAMMER-D 3 SLC FAT32
Seite 6 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING OF FUNCTIONALITY
Procedure of handling Backup-File from ECU8
Procedure of handling Update-File to ECU8
Procedure of handling Backup/Update File with life data
Procedure of creating Record File
Procedure of handling firmware update Smart Connect
Skip procedures
Seite 7 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING – BACKUP
Smart Connect Provider
Creating an empty Backup-File:
1. „Overview“
2. „New Entry“
3. Enter engine serial number
4. „Check“
5. Select Filetype ( Backup)
6. „Assume“
Smart Connect
MTU Customer
ECU8
Seite 8 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
Smart Connect Provider
7. If necessary create an additional
Backup-File
8. „Finish“
9. Enter storage location for Zip-File
10. Send Zip-File via email to customer
Smart Connect
MTU Customer
ECU8
Seite 9 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
Once the email is received save
the file on the desktop
Smart Connect „USB-Tool“
10. Enter the „USB-Tool“
11. Insert USB flash drive in PC slot
12. If the USB flash drive has false format,
the tool will formating the stick with
FAT32 (Administration rights are
necessary)
13. „Save data to USB flash drive“
Smart Connect
MTU Customer
ECU8
Seite 10 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
Smart Connect „USB-Tool“
14. „Select ZIP file“ which needs to be
stored on the USB flash drive
15. „OK“
16. Data are saved to USB „OK“
Smart Connect
MTU Customer
ECU8
Seite 11 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
17. For using the recorded USB-flash drive, the ECU has to be turned off
(Smart Connect stay powered on).
18. Plug in USB-flash drive into the Smart Connect and switch on the ECU.
Smart Connect starts with creating a backup or updating the ECU.
19. Status of process is shown on the failure code display
Smart Connect
MTU Customer
ECU8
Seite 12 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
Smart Connect „USB-Tool“
20. Insert USB flash drive in PC slot
21. „Read data from USB stick“
22. Mark data which needs to be saved.
23. Save ZIP-file on desktop „Save as“
24. „OK“
25. „OK“
26. Send Zip-file to MTU via email.
Smart Connect
MTU Customer
ECU8
Seite 13 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
Once the email is received save the file on
the desktop
Smart Connect Provider
Save the returned file on Central Database.
27. „Import ZIP-File“
Smart Connect
MTU Customer
ECU8
Seite 14 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
Smart Connect Provider
28. Marking of returned file to CDB
29. „Backfile to CDB“
30. Backup will be stored as nominal-file
on Central Database.
Smart Connect
MTU Customer
ECU8
Seite 15 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP
Back to handling overview
Seite 16 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING – UPDATE
Smart Connect Provider
Creating an Update-File:
1. „Overview“
2. „New Entry“
3. Enter engine serial number
4. „Check“
5. Select Filetype ( Update)
6. Select Calibration file
7. „Assume“
Smart Connect
MTU Customer
ECU8
Seite 17 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Smart Connect Provider
8. If necessary create an additional Up-
File with „new Entry“
9. „Finish“
10. Enter storage location for Zip-File
11. Send Zip-File via email to customer
Smart Connect
MTU Customer
ECU8
Seite 18 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Once the email is received save
the file on the desktop
Smart Connect „USB-Tool“
12. Enter the „USB-Tool“
13. Insert USB flash drive in PC slot
14. If the USB flash drive has false format,
the tool will formating the stick with
FAT32 (Administration rights are
necessary)
15. „Save data to USB flash drive“
Smart Connect
MTU Customer
ECU8
Seite 19 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Smart Connect „USB-Tool“
16. „Select ZIP file“ which needs to be
stored on the USB flash drive
17. „OK“
18. Data are saved to USB „OK“
Smart Connect
MTU Customer
ECU8
Seite 20 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
19. For using the recorded USB-flash drive, the ECU has to be turned off
(Smart Connect stay powered on).
20. Plug in USB-flash drive into the Smart Connect and switch on the ECU.
Smart Connect starts with updating the ECU.
21. After ECU is updated, a Backup-file will be also created.
22. Status of process is shown on the failure code display
Smart Connect
MTU Customer
ECU8
Seite 21 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Smart Connect „USB-Tool“
23. Insert USB flash drive in PC slot
24. „Read data from USB stick“
25. Mark data which needs to be saved.
26. Save ZIP-file on desktop „Save as“
27. „OK“
28. „OK“
29. Send Zip-file to MTU via email.
Smart Connect
MTU Customer
ECU8
Seite 22 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Once the email is received save the file on
the desktop
Smart Connect Provider
Save the returned file on Central Database.
30. „Import ZIP-File“
Smart Connect
MTU Customer
ECU8
Seite 23 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Smart Connect Provider
31. Marking of returned file to CDB
32. „Backfile to CDB“
33. Backup will be stored as nominal-file
on Central Database.
Smart Connect
MTU Customer
ECU8
Seite 24 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Back to handling overview
Seite 25 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING – BACKUP WITH LIFE DATA
Smart Connect Provider
Creating an Backup-File with Life data:
1. „Overview“
2. „New Entry“
3. Enter engine serial number
4. „Check“
5. Select Filetype ( Backup-File for
Life data)
6. „Assume“
Smart Connect
MTU Customer
ECU8
Seite 26 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP WITH LIFE DATA
Smart Connect Provider
7. If necessary create an additional
Backup-File with „new Entry“
8. „Finish“
9. Enter storage location for Zip-File
10. Send Zip-File via email to customer
Smart Connect
MTU Customer
ECU8
Seite 27 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP WITH LIFE DATA
Once the email is received save
the file on the desktop
Smart Connect „USB-Tool“
11. Enter the „USB-Tool“
12. Insert USB flash drive in PC slot
13. If the USB flash drive has false format,
the tool will formating the stick with
FAT32 (Administration rights are
necessary)
14. „Save data to USB flash drive“
Smart Connect
MTU Customer
ECU8
Seite 28 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - UPDATE
Smart Connect „USB-Tool“
15. „Select ZIP file“ which needs to be
stored on the USB flash drive
16. „OK“
17. Data are saved to USB „OK“
Smart Connect
MTU Customer
ECU8
Seite 29 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP WITH LIFE DATA
18. For using the recorded USB-flash drive, the ECU has to be turned off
(Smart Connect stay powered on).
19. Plug in USB-flash drive into the Smart Connect and switch on the ECU.
Smart Connect starts with creating Backup-File from ECU.
20. Status of process is shown on the failure code display
Smart Connect
MTU Customer
ECU8
Seite 30 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP WITH LIFE DATA
Smart Connect „USB-Tool“
21. Insert USB flash drive in PC slot
22. „Read data from USB stick“
23. Mark data which needs to be saved.
24. Save ZIP-file on desktop „Save as“
25. „OK“
26. „OK“
27. Send Zip-file to MTU via email.
Smart Connect
MTU Customer
ECU8
Seite 31 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP WITH LIFE DATA
Once the email is received save the file on the
desktop
Smart Connect Provider
Create Update-File with Life Data for new ECU
28. „Import ZIP-File“
Smart Connect
MTU Customer
ECU8
Seite 32 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP WITH LIFE DATA
Smart Connect Provider
29. Marking of „Backup-File for Life Data“
30. „Create new Update-File of Life Data“
31. Enter storage location for Zip-File
32. Send Zip-File via email to customer
Smart Connect
MTU Customer
ECU8
Seite 33 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - BACKUP WITH LIFE DATA
Once the email is received save
the file on the desktop
Please follow up procedure for updating ECU8 with Update-File
Smart Connect
MTU Customer
ECU8
Back to handling overview
Seite 34 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING – CREATING RECORD FILE
Smart Connect Provider
Creating a Record File:
1. „Overview“
2. „New Entry“
3. Enter engine serial number
4. „Check“
5. Select Filetype ( Data Record File)
6. „Assume“
Smart Connect
MTU Customer
ECU8
Seite 35 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Smart Connect Provider
7. Select Engine Controller
8. Select Functional Software (for having correct recording parameter)
9. „Import“
Smart Connect
MTU Customer
ECU8
Seite 36 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Smart Connect Provider
10. Select recording parameters
11. Adjust if desired:
„Number of PV`s per 5ms“
„Min cycle time“
„File size in MB“
12. Take a look to
„max. Recording time“
13. „Complete“
Max. 99 PV‘s selectable
Seite 37 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Smart Connect Provider
14. If necessary create an additional File
15. „Finish“
16. Enter storage location for Zip-File
17. Send Zip-File via email to customer
Smart Connect
MTU Customer
ECU8
Seite 38 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Once the email is received save
the file on the desktop
Smart Connect „USB-Tool“
18. Enter the „USB-Tool“
19. Insert USB flash drive in PC slot
20. If the USB flash drive has false format,
the tool will formating the stick with
FAT32 (Administration rights are
necessary)
21. „Save data to USB flash drive“
Smart Connect
MTU Customer
ECU8
Seite 39 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Smart Connect „USB-Tool“
22. „Select ZIP file“ which needs to be
stored on the USB flash drive
23. „OK“
24. Data are saved to USB „OK“
Smart Connect
MTU Customer
ECU8
Seite 40 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
25. For using USB-flash drive for recording parameters on Smart Connect no
power reset is necessary.
26. Plug in USB-flash drive into the Smart Connect. Smart Connect starts
immediately with creating a Record-File till USB-Flash drive is disconnected.
If the maximum file size is reached, the recording starts from begin (circular
buffer).
27. Status of process is shown on the failure code display “rec…”
Smart Connect
MTU Customer
ECU8
Seite 41 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Smart Connect „USB-Tool“
28. Insert USB flash drive in PC slot
29. „Read data from USB stick“
30. Mark data which needs to be saved.
31. Save ZIP-file on desktop „Save as“
32. „OK“
33. „OK“
34. Send Zip-file to MTU via email.
Smart Connect
MTU Customer
ECU8
Seite 42 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Once the email is received, save the file on
the desktop
Smart Connect Provider
Import Record File for analyzing data.
35. „Import ZIP-File“
Smart Connect
MTU Customer
ECU8
Seite 43 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
Smart Connect Provider
36. Marking Data Record File
37. „Evaluation of Data Record File“
38. MS-Excel will be open and the
recorded data can be analyzed.
Smart Connect
MTU Customer
ECU8
Seite 44 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING - CREATING RECORD FILE
MS-Excel
36. For better overview please cancel
column „Status“ and
„Motorbetriebsstunden[s]“
37. Mark all relevant data and create a
new „PivotTable“
38. MS-Excel will open and recorded data
can be analyzed.
Smart Connect
MTU Customer
ECU8
Back to handling overview
Seite 45 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
4. HANDLING – FIRMWARE UPDATE
1. Save Firmware file on USB-flash drive
2. For using the recorded USB-flash drive, the ECU has to be turned off
(Smart Connect stay powered on).
3. Plug in USB-flash drive into the Smart Connect and switch on the ECU.
Smart Connect starts with updating its Firmware
4. Status of process is shown on the failure code display
Smart Connect
MTU Customer
ECU8
Back to handling overview
Seite 46 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten
SMART CONNECT - USB-MAINTENANCE CONCEPT
5. GENERAL DETAILS
1. Installation of MTU-Software (Smart Connect Provider and USB-Tool) via Netinstaller
2. The USB-flash drive must not have other Data.
3. To format the USB-flash drive, admin rights are necessary
4. Engine number on engine controller needs to be the same as engine number on the
memory stick.
5. It is possible to store more than one Backup-/Update file (different engine serial
numbers) on one USB-flash drive.
6. Status of files in Central Database does not change automatically from „modernized„ to
„nominal“
Seite 47 Smart Connect | OASO, M. Dorner | 31.08.2015 MTU internal use only
© MTU Onsite Energy GmbH / Alle Rechte vorbehalten