SMART DIFFERENTIAL PRESSURE
TRANSMITTER APR-2000ALW
ü 4…20 mA output signal + HART protocol
(special version: 0…20 mA or 0…5 mA output signal + HART protocol)
ü Display with backlight
it
ü SIL 2 certificate
o 5 y ears r s s u re lim
ü Intrinsic safety certificate (ATEX, IECEx) up t rranty p
static to 700ba
r
ü Explosion proof certificate (ATEX, IECEx) wa up
ü PED Conformity (97/23/EC)
ü Programmable zero range, shift, characteristic and damping ratio with
local panel keys
ü Static pressure limit up to 700bar
ü Accuracy 0,075% (0,05%, 0,04% on request)
ü Marine certificate – DNV, BV
ü Gold plated diaphragms
ü Wetted parts material 316L/Hastelloy C276
133 18 132 18 Rating plate
APR-2000ALW/SS
APR-2000ALW
M20×1.5 packing gland
91,5
Ć6…12 cable
40
(80 in HS version)
Four holes Two holes (M6)
M10(standard)
or 7/16’’UNF
70
1/4NPT
41,3
60
Venting
and draining valves
54* 80
*Other distance on request
Transmitter APR-2000ALW – version with type C process connection
to be mounted together with a valve manifold
Version with process connection rotated 90 °
176
176
15
1/4NPT
SW27 2
M20×1.5
94.5
Transmitter APR-2000ALW
Transmitter APR-2000ALW Transmitter APR-2000ALW Version with direct or
Version with P type process connection. Version with PN type process connection. remote diaphragm seal.
II/ 2
Application and construction
The APR-2000ALW transmitter is applicable to the measurement of differential pressure of gases, vapours and liquids. The active element is a
piezoresistant silicon sensor separated from the medium by separating diaphragms and a specially selected type of manometric fluid. The
special design of the active sensing element ensures that it is able to withstand pressure surges and overloads of up to 250/320/413/700 bar.The
casing is made of aluminium alloy cast or 316SS stainles steel, degree of protection IP66/IP67. The design of the casing enables the use of a
local display, rotation of the display, rotation of the casing by 0–340° relative to the sensor, and a choice of cable direction.
Communication and configuration
The communication standard for data interchange with the The data interchange with the transmitter enables users to:
transmitter is the Hart protocol.
¨ identify the transmitter
Communication with the transmitter is carried out with: ¨ configure the output parameters:
– a KAP-03, KAP-03Ex communicator - measurement units and the values of the start points and end
– some other Hart type communicators(*) points at the measurement range
– a PC using an HART/USB converter and Raport 2 - damping time constant
configuration software. - conversion characteristic (inversion, user's non-linear
(*) .eddl files available on www.aplisens.com. characteristic)
¨ read the currently measured pressure value of the output current
and the percentage output control level
¨ force an output current with a set value
¨ calibrate the transmitter in relation to a model pressure
Installation
The transmitter with P or PN type process connection is not heavy, so can be installed without additional mounting bracket on application. For
fitting in any desired position we recommend an universal Aplisens mounting bracket for 2" pipe (AL mounting bracket, see page IV/ 5). The
version with C type process connections can be fitted directly to a 3- or 5- valve manifold. We recommend factory-mounted transmitters with VM
type valve manifold (page IV/ 2). A transmitter without a valve manifold can be fitted in any position on a 2" pipe or on a wall using the C-2"
mounting bracket (page IV/ 5). When the special process connections are required for the measurement of specific media levels in closed tanks
(e.g. in the sugar and chemical industries) the transmitter is fitted with an Aplisens diaphragm seal. Sets of differential pressure transmitters with
diaphragm seals are described in detail in the further part of the catalogue.
Measuring ranges
No. Nominal measuring range Minimum set range Rangeability Overpressure limit/ static pressure limit
(FSO)
1 0...70 bar (0...7 MPa) 7 bar (700 kPa) 10:1
2 0...16 bar * (0...1,6 MPa) 1,6 bar (160 kPa) 10:1
3 0...2,5 bar (0...250 kPa) 0,2 bar (20 kPa) 12,5:1
4 0...1 bar * (0...100 kPa) 50 mbar (5k Pa) 20:1 C-type: 250 / 320 / 413 bar
(250 bar for PED version)
5 0...0,25 bar * (0...25 kPa) 10 mbar (1k Pa) 25:1 P-type: 40 bar (for range no. 1: 70bar)
6 -0,5...0,5 bar * (-50...50 kPa) 0,1 bar (10 kPa) 10:1
7 -100…100 mbar * (-10…10 kPa) 10 mbar (1 kPa) 20:1
8 -5...70 mbar * (-0,5...7 kPa) 4 mbar (0,4 kPa) 18:1
9 -25…25 mbar * (-2,5…2,5 kPa) 2 mbar (0,2 kPa) 25:1 C-type: 200 bar (10 bar for PED version); P-type: 40 bar
10 -7…7 mbar ** (-700…700 Pa) 1 mbar (0,1 kPa) 14:1 20 bar
* available also in HS version
** available only in HS version
Technical data
Metrological parameters Electrical parameters
Accuracy Ł ±0,075% of the calibrated range Power supply:
(Ł ±0,1% for range no. 10) 10...55 VDC / Exia: 10,5…30 VDC / Exd: 10,5…45 VDC
Special version: Ł ±0,05% of the calibrated range SIL2: 15…45 VDC / SIL2 Exia: 16…28 VDC
(Ł ±0,04% on request)
Long term stability Ł accuracy for 3 years Output signal 4...20 mA + HART
(for the nominal measuring range) or Ł 2 x accuracy for 5 years
U sup[V] - 10V
HS version: Ł accuracy for 6 years Load resistance (for standard version) R[W] Ł
0,0225A
or Ł 2 x accuracy for 10 years
Resistance required for communication min. 240 W
Thermal error < ±0,05% (FSO) / 10°C for ranges no. 1 - 9
< ±0,08% (FSO) / 10°C for ranges no. 10
max. ±0,25% (FSO) in the whole compensation range Materials
spec. version for ranges no 1-9: Wetted parts SS316L, Hastelloy C276
Ł ±0,03% (FSO) / 10°C Diaphragms SS316L, Hastelloy C 276, Au
max. ±0,1% (FSO) in the whole compensation range Casing Aluminium
Thermal compensation range -25…80°C Option: SS316
Zero shift error for static pressure Material of window: polycarbonate glass, hardened glass
0,01% (FSO) / 10 bar for ranges no. 3, 4, 5, 6, 7, 9
0,03% (FSO) / 10 bar for range no. 8
0,06% (FSO) / 10 bar for ranges no. 1, 2
0,01% (FSO) / 10 bar for ranges no. 2, 8 in HS version
0,02% (FSO) / 10 bar for range no. 10
Zeroing the transmitter in conditions of static pressure can elimi-
nate this error.
Response time 16…480ms (programmable)
Exd version: 150ms
Additional electronic damping 0…60 s
Error due to supply voltage changes 0,002% (FSO) / V
II/ 3
Operating conditions
Operating temperature range (ambient temp.) -25...85°C
special version -40..85°C
Exia version -25…80°C
C-type process connection rotated 90°
Exd version -25…75°C
Medium temperature range -25...120°C
over 120°C – measurement with use an impulse line or dia-
phragm seals
up to 100°C - PED version
up to 100°C - version for 413bar static pressure
up to 80°C - version for 700bar static pressure
CAUTION: the medium must not be allowed to freeze in the im-
pulse line or close to the process connection of the transmitter
Accuracy depending on the set range
Accuracy r0 – error for range 30...100% FSO
r1 – error for range 10% FSO
r1 = 2 × r0
r1
Numerical error values are given in the technical data under metrological parameters
r0
Set range
10 30 100 [%]
II/ 4
Ordering procedure
Model Code Description
APR-2000 Smart differential pressure transmitter
/ALW……………........………………………………..… Aluminum housing, IP66 with display, output 4-20mA + Hart
Casing, output signal
/ALW/SS..................................................................... Stainless steel housing, IP66, with display, output 4-20mA + Hart
II 1/2G Ex ia IIC T4/T5 Ga/Gb
/Exia……………………………………………....
IECEx Ex ia IIC T4/T5 Ga/Gb
II 1/2G Ex ia IIC T4/T5 Ga/Gb
II 1D Ex ia IIIC T105°C Da
I M1 Ex ia I Ma (version with SS housing)
/Exia (Da)…………………………………...........
Ex ia IIC T4/T5 Ga/Gb
IECEx Ex ia IIIC T105°C Da
Ex ia I Ma (version with SS housing
II 1/2G Ex ia/db IIC T6/T5 Ga/Gb
II 1/2D Ex ia/tb IIIC T85°C/T100°C Da/Db
I M2 Exd ia I Mb (version with SS housing) Packing gland available on
/Exd………………………………………………..
Ex ia/db IIC T6/T5 Ga/Gb request
IECEx Ex ia/tb IIIC T85°C/T100°C Da/Db
II 1/2G Ex ia IIC T4/T5 Ex db ia I Mb (version with SS housing)
Ga/Gb II 2G Ex ia/db IIC T6/T5 Gb
II 2D Ex ia/tb IIIC T85°C/T100°C Db Packing gland available on
/Exd (2G)………………………………………….
Ex ia/db IIC T6/T5 Gb request
IECEx
Ex ia/tb IIIC T85°C/T100°C Db
/SA………………………………………………… Surge arrester for Exia version
/Safety.…………....…….............………………. SIL2 - Functional Safety certificate according to PN-EN 61508-1:2010;
PN-EN 61508-2:2010; PN-EN 61508-3:2010; PN-EN 61511-1:2007; PN-EN 62061:2008+A1
/PED………….....….......................................... European Pressure Equipment Directive N° 97/23/EC, category IV
/HS…..……….....…........................................... Ultra stable version (only ranges no. 2, 4÷10)
/0,05%............................................................... Accuracy Ł ±0,05%
/0,04%............................................................... Accuracy Ł ±0,04%
/MR...…………....……...............……………….. Marine certificate – DNV, BV
/Tlen…………..............…….....………......……. For oxygen service (sensor filled with Fluorolube fluid)
/320 bar............…............................................. Static pressure 320 bar, only for C process connection, not available in PED version
/413 bar............…............................................. Static pressure 413 bar, only for C process connection, not available in PED version
more than one option /700 bar............…............................................. Static pressure 700 bar, only for C process connection, not available in PED version
is available Execution on request – please consult availability with manufacturer
/IP67………………………………………………. Protection class IP67
/NACE…………………………………………….. NACE MR-01-75 certificate (process connections: C)
Range Min. set range
/0÷70 bar..........................................….. 0÷70 bar (0÷7000 kPa) 7 bar (700 kPa)
/0÷16 bar…............................................ 0÷16 bar (0÷1600 kPa) 1,6 bar (160 kPa)
/0÷2,5 bar...................................…..….. 0÷2,5 bar (0÷250 kP) 0,2 bar (20 kPa)
/0÷1 bar….............................................. 0÷1 bar (0÷100 kPa) 50 mbar (5 kPa)
Nominal measuring ranges /0÷0,25 bar…................................……. 0÷0,25 bar (0÷25 kPa) 10 mbar (1 kPa)
/-0,5÷0,5 bar…............................……… -0,5÷0,5 bar (50÷50 kPa) 0,1 bar (10 kPa)
/-0,1÷0,1 bar…............................……… -0,1÷0,1 bar (-10÷10 kPa) 10 mbar (1 kPa)
/-5÷70 mbar…………………………….. -5÷70 mbar (0,5÷7 kPa) 4 mbar (0,4 kPa)
/-25÷25 mbar......................................... -25÷25 mbar (-2,5÷2,5 kPa) 2 mbar (0,2 kPa)
/-7÷7 mbar……...................................... -7÷7 mbar (-0,7÷0,7 kPa) 1 mbar (0,1 kPa)
Measuring set range /…÷… [required units] Calibrated range in relation to 4mA and 20mA output
/C…....................................... Thread 1/4NPT F on the cover flanges cover flanges material SS316. Allows mount-
ing with a valve manifold. Process connection of cover flange: M10 (option /C(7/16) -
Process connections 7/16”UNF acc. to IEC 61518)
/CR……………………………. C-type process connection rotated 90°
/P........................................... Thread M20x1,5 (male)
/PN......................................... Thread 1/4”NPT (female)
/code of diaphragm seal……. Diaphragm seal (see chapter of diaphragm seals) mounted on Hi side of transmitter,
Lo side 1/4NPT Female
(without marking)............... Diaphragms material SS316L
Material of diaphragms /(H)..................................... Diaphragms material Hastelloy C276
(refers only to C, CR, P, PN process connection) (all wetted parts in Hastelloy C276 on request)
/(Au)................................... Gold plated diaphragms (not available for transmitters in HS version)
(without marking)........... FPM Viton
Gasket (refers only to C, CR process connection)
/NBR.............................. NBR
/PTFE…………………… PTFE
(without marking) Packing gland M20x1,5
Electrical connection
/US............................. Thread 1/2”NPT Female
/C-2”.................. Mounting bracket for 2” pipe (to C process conn.), mat. zinced steel
/C-2”(SS).......... Mounting bracket for 2” pipe (to C process conn.), mat. Stainless Steel
/C-2”B............... Mounting bracket for 2” pipe (to C(7/16) process conn.), mat. zinced steel
/C-2”B(SS)........ Mounting bracket for 2” pipe (to C(7/16) process conn.), mat. Stainless Steel
/FI25………...… Mounting bracket for 1” pipe (to P process conn.), mat. Stainless Steel
/RedSpaw P….. Connector to weld impulse pipes dia. 12 and 14 mm, material 15HM(SO) or
Accessories SS316(S). Only process connection P type
/RedSpaw C….. Connector to weld impulse pipes dia. 12 and 14 mm, material 15HM. Only process
connection C type.
Adapter for differential pressure transmitters with C type process connection, output
/Red d/P 1/2’’…
thread 1/2NPT F. Material SS316L
/ST.................... Stainless Steel plate fixed to the housing
/MT................... Stainless Steel Tag plate mounted on wire
Other specification /............... Description of required parameters (e.g. IP66/67)
II/ 5