TECHNICAL SPECIFICATION OF 2xRGY
2x1.5 rm 0.6/1.0 (1.2) kV Cable
TYPE & SIZE OF CABLE
2xRGY 2x1.5 rm (mm²)
VOLTAGE GRADE, U0/U (Um)
Permissible Service Voltage, U₀/U
0.6/1.0 (1.2) kV
0.72/1.2 kV
RELEVANT STANDARDS
IEC 60502-1, IEC 60228
TECHNICAL SPECIFICATION
Cross-sectional area of conductor, nominal 1.5 mm2
Number of core 2 core
Material Annealed Copper
Maximum conductor temperature in normal operation 90⁰ C
Conductor
Class of conductor Class 2
Shape of conductor Stranded Circular
Minimum number of wire 7/0.52 No./mm
Material XLPE
Thickness, nominal 0.7 mm
Insulation
Thickness, minimum 0.53 mm
Color of insulation Red & Black
Material PVC
Inner Covering Color Black
Minimum Thickness 1.0 mm
Armour Material Round Galvanized Steel Wire
Diameter of wire 0.8
Material PVC
Color Black
Sheath Thickness, nominal 1.8 mm
Thickness, minimum 1.24 mm
Overall diameter, approximate 13.3 ± 2 mm
Electrical Characteristics Other Characteristics
D.C resistance of conductor at 20 C, maximum
0
12.1 Ohm/Km Minimum bending radius 15 x Overall diameter
Insulation resistance constant ki at 200C, minimum 3670 M. ohm-km Operating temperature -15°C to 90°C
A.C. Voltage test for 05 minutes (2.5U₀+2 kV) 3.5 Kv
Current carrying capacity- Signature A K M Iftakher Ahmed
a. in ground at 30°C (Direct Laid) 34 A In Charge (QC & PD)
b. in free air at 35°C (Open) 27 A Date 22 November, 2020