TECHNICAL SPECIFICATION OF 2xCY

4x10 rm+10C 0.6/1.0 (1.2) kV Cable


TYPE & SIZE OF CABLE

2xCY 4x10 rm+10C (mm²)


VOLTAGE GRADE, U0/U (Um)
Permissible Service Voltage, U₀/U

0.6/1.0 (1.2) kV
0.72/1.2 kV
RELEVANT STANDARDS

VDE 0276-627,IEC 60502-1, IEC 60228


TECHNICAL SPECIFICATION
Cross-sectional area of conductor, nominal 10 mm2
Number of core 4 core
Material Annealed Copper
Maximum conductor temperature in normal operation 90⁰ C
Conductor
Class of conductor Class 2
Shape of conductor Stranded Circular
Minimum number of wire & diameter (manufacturing) 7/1.35 No./mm
Material XLPE
Thickness, nominal 0.7 mm
Insulation
Thickness, minimum 0.53 mm
Color of insulation Red , Yellow, Blue & Black
Material PVC
Inner Covering Color Black
Thickness, nominal 1.0 mm
Screen Material Solid Copper wire concentric
Number & Diameter of concentric wire 7/1.35 No./mm
Binder(Optional) Material Helically Copper Tape
Material PVC
Color Black
Sheath Thickness, nominal 1.8 mm
Thickness, minimum 1.24 mm
Overall diameter, approximate 21.6 ± 2 mm
Electrical Characteristics Other Characteristics
D.C resistance of conductor at 200C, maximum 1.83 Ohm/Km Minimum bending radius 15 x Overall diameter
0
Insulation resistance constant ki at 20 C, minimum 3670 M. ohm-km Operating temperature -15°C to 90°C
A.C. Voltage test for 05 minutes (2.5U₀+2 kV) 3.5 Kv
Current carrying capacity- Signature A K M Iftakher Ahmed
a. in ground at 30°C (Direct Laid) 83 A In Charge (QC & PD)

b. in free air at 35°C (Open) 75 A Date 14 October, 2020