CENTRIFUGAL IN-LINE FANS
JETLINE Series
Range of in-line fans for circular
ducts, designed for high aerodynamic
performances with a very compact
profiles and very low sound levels.
The range comprises seven diameters
and covers a flow range from 260 to
1610 m3/h.
Low profile compact casing manufactured
from galvanised sheet steel. The terminal
box and the mounting bracket do not
increase the product’s profile.
Optimised design of the impeller, guide
vane and outlet diffuser, manufactured
from injection-moulded plastic, to
increase performance and lower the
sound level.
Airtight joint between the galvanised steel
casing and the plastic guide vane to avoid
air leaks. Rubber gaskets on the flanges
to improve airtightness with the ducts.
Silent-block between the motor and
the holder to reduce the motor’s
vibrations and lower the sound level of
the installation, even in terms of speed
regulation.
Motor
Fitted with an external rotor single-phase
AC motor:
- 220-240V 50/60Hz*, Class F, IP 44
- Speed controllable by voltage.
- Thermal protection with manual reset.
- Working temperature: -20/60 ºC
*JETLINE-315: 220-240V50Hz.
install-
friendly
DESIGNED FOR AN
EASY INSTALLATION
Terminal box Airtight joints High performance Impeller Mounting bracket
Built-in, IP65 terminal box that Rubber gaskets for a New impeller geometry for Strong mounting bracket
does not add to the overall more airtight joint with the reduced sound levels and to supplied with the fan.
height dimensions. installation’s ducts. offer high performance.
Two mounting positions for
support
The product can be mounted
in two different positions by
changing the position of the
support’s anchoring.
www.solerpalau.com In-Line duct fans JETLINE 1
CENTRIFUGAL IN-LINE FANS
JETLINE Series
TECHNICAL CHARACTERISTICS
Before installation check that the product electrical characteristics listed on the data plate label (voltage, power, frequency, etc.) match those of the
intended electrical supply.
Model type Speed Maximum Maximum Maximum Sound pressure level* Max. Air Weight Speed
(rpm) absorbed absorbed air (dB(A)) temp. (kg) controller
power current volume (ºC at 50Hz)
(W) (A-230V) (m3/h) Inlet Radiated Outlet REB RMB
JETLINE-100 2690 19 0,10 260 41 22 39 -20/+60 3 REB-1 N RMB-1,5
JETLINE-125 2640 40 0,20 420 47 25 47 -20/+60 3,4 REB-1 N RMB-1,5
JETLINE-150 2730 83 0,40 750 52 31 50 -20/+60 4,5 REB-1 N RMB-1,5
JETLINE-160 2730 84 0,40 760 52 31 51 -20/+60 4,5 REB-1 N RMB-1,5
JETLINE-200 2630 125 0,50 1080 58 42 55 -20/+60 5,6 REB-1 N RMB-1,5
JETLINE-250 2710 160 0,70 1280 59 45 58 -20/+60 6,5 REB-1 N RMB-1,5
JETLINE-315 2600 215 0,90 1610 61 49 60 -20/+60 8,4 REB-1 N RMB-1,5
* sound pressure level measured at 1,5 m in free field condition, at the duty point 2 of the performance curve.
DIMENSIONS (mm)
Model A B1 B2 C1 C2 ØD E F G H I ØJ K kg
JETLINE-100 276 15 15 181 190 95 256 306 70 98 - 15 6,5 3
JETLINE-125 279 15 15 206 214 120 265 315 70 111 - 15 6,5 3,4
JETLINE-150 323 20 20 243,5 252 145 298,5 348 70 130 - 15 6,5 4,5
JETLINE-160 323 20 20 243,5 252 155 298,5 348 70 130 - 15 6,5 4,5
JETLINE-200 322 30 30 273 281 195 320 369 100 144,5 - 15 6,5 5,6
JETLINE-250 329 20 30 293 301 245 326 375 120 154,3 50 15 6,5 6,5
JETLINE-315 369 20 33 322 331 310 357,5 407 120 170 50 15 6,5 8,9
2 In-Line duct fans JETLINE www.solerpalau.com
CENTRIFUGAL IN-LINE FANS
JETLINE Series
PERFORMANCE CURVES - ACOUSTIC CHARACTERISTICS
– qv: Airflow in m3/h.
– psf: Static pressure in Pa.
– P: Input power in W.
– SFP: Specific fan power in W/m3/s (blue curves).
– Performance data in accordance with ISO 5801.
JETLINE-100 JETLINE-125
Sound power spectrum (dB(A)) Sound power spectrum (dB(A))
Working point 63 125 250 500 1000 2000 4000 8000 LwA Working point 63 125 250 500 1000 2000 4000 8000 LwA
INLET 30 33 44 50 54 51 51 36 58 INLET 41 38 52 63 55 56 52 43 65
1 OUTLET 27 32 45 49 50 49 46 34 55 1 OUTLET 29 45 52 61 56 56 54 41 64
BREAK-OUT 19 15 23 27 35 34 34 19 40 BREAK-OUT 31 25 27 37 34 35 33 25 42
INLET 27 31 42 47 51 48 48 34 55 INLET 40 37 50 58 52 54 51 41 61
2 OUTLET 27 32 44 47 48 46 46 34 53 2 OUTLET 28 47 48 58 54 54 54 39 62
BREAK-OUT 16 13 21 24 32 31 31 17 37 BREAK-OUT 30 24 25 32 31 33 32 23 39
INLET 29 39 51 52 56 51 50 36 60 INLET 43 46 59 63 57 56 53 42 66
3 OUTLET 29 41 53 51 53 49 47 35 58 3 OUTLET 31 52 53 61 58 56 57 40 65
BREAK-OUT 18 21 30 29 37 34 33 19 41 BREAK-OUT 33 33 34 37 36 35 34 24 43
INLET 27 30 41 47 51 48 48 33 55 INLET 39 36 50 61 53 54 50 41 62
4 OUTLET 24 29 42 46 47 46 43 31 53 4 OUTLET 27 43 50 59 54 54 52 39 62
BREAK-OUT 16 12 20 24 32 31 31 16 37 BREAK-OUT 29 23 25 35 32 33 31 23 39
INLET 24 28 39 44 48 45 45 31 52 INLET 37 34 47 55 49 51 48 38 58
5 OUTLET 24 29 41 44 45 43 43 31 50 5 OUTLET 25 44 45 55 51 51 51 36 59
BREAK-OUT 13 10 18 21 29 28 28 14 33 BREAK-OUT 27 21 22 29 28 30 29 20 36
INLET 27 37 49 50 54 49 48 34 57 INLET 41 44 57 61 55 54 51 40 64
6 OUTLET 27 39 51 49 51 47 45 33 56 6 OUTLET 29 50 51 59 56 54 55 38 63
BREAK-OUT 16 19 28 27 35 32 31 17 38 BREAK-OUT 31 31 32 35 34 33 32 22 41
INLET 23 26 37 43 47 44 44 29 51 INLET 34 31 45 56 48 49 45 36 58
7 OUTLET 20 25 38 42 43 42 39 27 48 7 OUTLET 22 38 45 54 49 49 47 34 57
BREAK-OUT 12 8 16 20 28 27 27 12 32 BREAK-OUT 24 18 20 30 27 28 26 18 35
INLET 18 22 33 38 42 39 39 25 47 INLET 32 29 42 50 44 46 43 33 53
8 OUTLET 18 23 35 38 39 37 37 25 45 8 OUTLET 20 39 40 50 46 46 46 31 54
BREAK-OUT 7 4 12 15 23 22 22 8 28 BREAK-OUT 22 16 17 24 23 25 24 15 31
INLET 23 33 45 46 50 45 44 30 53 INLET 37 40 53 57 51 50 47 36 60
9 OUTLET 23 35 47 45 47 43 41 29 52 9 OUTLET 25 46 47 55 52 50 51 34 59
BREAK-OUT 12 15 24 23 31 28 27 13 34 BREAK-OUT 27 27 28 31 30 29 28 18 37
www.solerpalau.com In-Line duct fans JETLINE 3
CENTRIFUGAL IN-LINE FANS
JETLINE Series
PERFORMANCE CURVES - ACOUSTIC CHARACTERISTICS
– qv: Airflow in m3/h.
– psf: Static pressure in Pa.
– P: Input power in W.
– SFP: Specific fan power in W/m3/s (blue curves).
– Performance data in accordance with ISO 5801.
JETLINE-150 JETLINE-160
Sound power spectrum (dB(A)) Sound power spectrum (dB(A))
Working point 63 125 250 500 1000 2000 4000 8000 LwA Working point 63 125 250 500 1000 2000 4000 8000 LwA
INLET 29 40 58 62 59 61 59 50 67 INLET 38 49 54 63 60 62 64 52 69
1 OUTLET 40 43 57 62 59 59 57 46 66 1 OUTLET 39 42 56 63 59 59 60 51 67
BREAK-OUT 14 27 34 39 39 41 42 33 47 BREAK-OUT 24 14 23 35 38 40 47 38 49
INLET 28 39 58 62 58 60 57 49 66 INLET 36 47 54 62 58 60 60 49 67
2 OUTLET 28 43 56 61 57 58 55 44 65 2 OUTLET 44 42 55 62 58 58 57 47 66
BREAK-OUT 13 26 34 39 38 40 40 32 46 BREAK-OUT 22 12 23 34 36 38 43 35 46
INLET 34 43 53 61 57 60 55 47 65 INLET 38 45 54 61 56 60 57 47 65
3 OUTLET 31 46 55 61 57 58 53 42 65 3 OUTLET 45 46 55 61 57 58 55 45 65
BREAK-OUT 19 30 29 38 37 40 38 30 45 BREAK-OUT 24 10 23 33 34 38 40 33 44
INLET 27 38 56 60 57 59 57 48 65 INLET 36 47 52 61 58 60 62 50 67
4 OUTLET 38 41 55 60 57 57 55 44 65 4 OUTLET 37 40 54 61 57 57 58 49 65
BREAK-OUT 12 25 32 37 37 39 40 31 45 BREAK-OUT 22 12 21 33 36 38 45 36 47
INLET 26 37 56 60 56 58 55 47 65 INLET 34 45 52 60 56 58 58 47 64
5 OUTLET 26 41 54 59 55 56 53 42 63 5 OUTLET 42 40 53 60 56 56 55 45 64
BREAK-OUT 11 24 32 37 36 38 38 30 44 BREAK-OUT 20 10 21 32 34 36 41 33 43
INLET 32 41 51 59 55 58 53 45 64 INLET 36 43 52 59 54 58 55 45 63
6 OUTLET 29 44 53 59 55 56 51 40 63 6 OUTLET 43 44 53 59 55 56 53 43 63
BREAK-OUT 17 28 27 36 35 38 36 28 43 BREAK-OUT 22 8 21 31 32 36 38 31 42
INLET 24 35 53 57 54 56 54 45 62 INLET 34 45 50 59 56 58 60 48 64
7 OUTLET 35 38 52 57 54 54 52 41 61 7 OUTLET 35 38 52 59 55 55 56 47 63
BREAK-OUT 9 22 29 34 34 36 37 28 42 BREAK-OUT 20 10 19 31 34 36 43 34 44
INLET 22 33 52 56 52 54 51 43 61 INLET 30 41 48 56 52 54 54 43 61
8 OUTLET 22 37 50 55 51 52 49 38 59 8 OUTLET 38 36 49 56 52 52 51 41 60
BREAK-OUT 7 20 28 33 32 34 34 26 40 BREAK-OUT 16 6 17 28 30 32 37 29 40
INLET 29 38 48 56 52 55 50 42 61 INLET 32 39 48 55 50 54 51 41 60
9 OUTLET 26 41 50 56 52 53 48 37 60 9 OUTLET 39 40 49 55 51 52 49 39 59
BREAK-OUT 14 25 24 33 32 35 33 25 40 BREAK-OUT 18 4 17 27 28 32 34 27 38
4 In-Line duct fans JETLINE www.solerpalau.com
CENTRIFUGAL IN-LINE FANS
JETLINE Series
PERFORMANCE CURVES - ACOUSTIC CHARACTERISTICS
– qv: Airflow in m3/h.
– psf: Static pressure in Pa.
– P: Input power in W.
– SFP: Specific fan power in W/m3/s (blue curves).
– Performance data in accordance with ISO 5801.
JETLINE-200 JETLINE-250
Sound power spectrum (dB(A)) Sound power spectrum (dB(A))
Working point 63 125 250 500 1000 2000 4000 8000 LwA Working point 63 125 250 500 1000 2000 4000 8000 LwA
INLET 29 44 60 65 65 64 65 60 72 INLET 34 47 64 65 67 68 65 66 74
1 OUTLET 28 45 61 65 64 63 62 56 71 1 OUTLET 34 46 66 65 68 70 65 60 75
BREAK-OUT 18 36 48 50 50 46 49 42 56 BREAK-OUT 20 36 43 48 54 56 49 42 59
INLET 30 40 56 66 68 64 62 57 72 INLET 41 43 60 67 70 66 61 60 73
2 OUTLET 28 44 57 64 65 62 58 53 69 2 OUTLET 34 46 62 66 68 68 58 55 73
BREAK-OUT 19 33 44 51 53 46 45 39 56 BREAK-OUT 28 32 39 51 57 54 45 36 59
INLET 41 51 63 68 70 68 61 54 74 INLET 45 52 65 66 68 67 61 54 73
3 OUTLET 39 55 63 66 67 67 59 51 72 3 OUTLET 44 54 64 65 68 70 59 52 73
BREAK-OUT 30 44 52 53 54 49 44 36 59 BREAK-OUT 32 41 44 49 55 55 45 31 59
INLET 26 41 57 62 63 62 62 57 69 INLET 32 46 63 64 66 66 63 64 72
4 OUTLET 25 42 58 62 62 60 59 53 68 4 OUTLET 33 45 64 64 67 69 64 59 73
BREAK-OUT 15 33 45 47 47 43 46 40 53 BREAK-OUT 19 35 42 47 53 55 48 41 58
INLET 25 36 52 62 64 60 58 52 68 INLET 39 41 58 65 68 64 59 58 71
5 OUTLET 23 40 52 60 61 58 54 48 65 5 OUTLET 32 44 60 64 66 66 56 53 71
BREAK-OUT 15 28 40 47 49 42 41 35 52 BREAK-OUT 25 30 37 49 54 52 43 34 57
INLET 37 47 60 64 66 64 57 50 70 INLET 43 49 62 63 66 65 59 52 71
6 OUTLET 35 51 59 62 63 63 55 47 68 6 OUTLET 41 52 62 63 66 67 57 50 71
BREAK-OUT 26 40 48 49 50 45 40 32 55 BREAK-OUT 29 38 42 47 53 53 43 28 57
INLET 22 36 53 58 58 57 58 53 64 INLET 31 44 61 62 64 65 61 62 71
7 OUTLET 21 37 54 58 57 56 55 48 63 7 OUTLET 31 43 63 62 65 67 62 57 71
BREAK-OUT 11 29 41 43 43 39 41 35 49 BREAK-OUT 17 33 40 45 51 53 46 39 56
INLET 20 30 46 56 58 54 52 47 62 INLET 36 38 55 62 65 61 56 54 68
8 OUTLET 17 34 47 54 55 52 48 43 59 8 OUTLET 29 41 57 61 63 63 53 50 68
BREAK-OUT 9 23 34 41 43 36 35 29 46 BREAK-OUT 22 27 34 46 51 49 40 31 54
INLET 31 42 54 58 60 58 51 44 64 INLET 39 46 59 60 63 62 55 49 67
9 OUTLET 29 45 53 57 57 57 50 41 63 9 OUTLET 38 48 59 59 62 64 53 47 68
BREAK-OUT 20 34 42 43 45 40 35 26 49 BREAK-OUT 26 35 38 44 50 50 39 25 54
www.solerpalau.com In-Line duct fans JETLINE 5
CENTRIFUGAL IN-LINE FANS
JETLINE Series
PERFORMANCE CURVES - ACOUSTIC CHARACTERISTICS
– qv: Airflow in m3/h.
– psf: Static pressure in Pa.
– P: Input power in W.
– SFP: Specific fan power in W/m3/s (blue curves).
– Performance data in accordance with ISO 5801.
JETLINE-315
Sound power spectrum (dB(A))
Working point 63 125 250 500 1000 2000 4000 8000 LwA
INLET 44 54 66 66 68 69 69 67 75
1 OUTLET 39 51 67 70 74 73 70 63 79
BREAK-OUT 29 48 60 55 61 58 53 44 66
INLET 33 49 62 67 68 66 61 62 73
2 OUTLET 36 50 62 67 70 70 60 57 75
BREAK-OUT 18 43 56 56 61 55 46 39 64
INLET 44 56 67 66 68 67 61 55 74
3 OUTLET 46 57 66 68 73 73 61 53 77
BREAK-OUT 29 51 62 55 61 56 45 32 65
INLET 42 52 65 64 66 67 67 65 74
4 OUTLET 37 49 65 68 72 72 69 61 77
BREAK-OUT 27 47 59 53 59 56 51 42 64
INLET 29 45 58 63 64 62 58 58 69
5 OUTLET 32 46 58 63 66 66 56 53 71
BREAK-OUT 14 40 52 52 57 51 42 35 60
INLET 40 52 63 62 64 63 57 51 69
6 OUTLET 42 53 62 64 69 69 57 49 73
BREAK-OUT 24 47 57 51 57 52 41 28 61
INLET 39 49 62 61 63 64 64 62 71
7 OUTLET 34 46 62 65 69 69 66 58 74
BREAK-OUT 24 44 56 50 56 53 48 39 61
INLET 24 40 53 58 59 57 52 53 64
8 OUTLET 27 41 53 58 61 61 51 48 66
BREAK-OUT 9 34 47 47 52 46 37 30 55
INLET 34 47 58 56 58 58 51 46 64
9 OUTLET 36 47 56 58 64 63 51 44 68
BREAK-OUT 19 41 52 45 51 47 36 23 56
6 In-Line duct fans JETLINE www.solerpalau.com
CENTRIFUGAL IN-LINE FANS
JETLINE Series
MOUNTING ACCESSORIES
MBE MBW SIL
Electric heater. Hot water coil. Circular sound
attenuators.
MFL-G4 MFL-F CAR
Filtration box of G4 Box in galvanized Backdraught
grade filtration. steel for inserting shutters.
the MFR F5, F6
and F7 filters.
GSA M0 GSI M0 CX
Aluminium flexible Insulated aluminium Worm drive duct
ducting. ducting. connectors.
BOC BOR GCI
Metal inlet valves. Plastic inlet valves. Circular inlet grilles.
VR GRI RP
GCI mounting frame. Interior square GRI mounting frame.
grilles.
ACOP-VENT DEF-VENT
Flexible connectors. Protection grille.
ELECTRICAL ACCESSORIES
REB RMB
Electronic single Autotransformer
phase speed single phase speed
controllers. controllers.
www.solerpalau.com In-Line duct fans JETLINE 7