RT 1-10K User Manual

The document provides safety instructions for using an uninterruptible power supply (UPS). Key points include: do not operate the UPS before reading the manual, be aware that high voltages are present even when not connected to mains power, do not open the UPS case or touch battery terminals, and do not repair the UPS yourself. Installation instructions are also provided, such as unpacking and inspecting components, selecting an appropriate installation location with good ventilation, connecting loads and batteries properly, and fully charging batteries before use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
379 views25 pages

RT 1-10K User Manual

The document provides safety instructions for using an uninterruptible power supply (UPS). Key points include: do not operate the UPS before reading the manual, be aware that high voltages are present even when not connected to mains power, do not open the UPS case or touch battery terminals, and do not repair the UPS yourself. Installation instructions are also provided, such as unpacking and inspecting components, selecting an appropriate installation location with good ventilation, connecting loads and batteries properly, and fully charging batteries before use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 25

Thanks for using our products.

Please strictly obey all the instructions in this manual and pay attention to all the warning and operation
information. It is not advisable to install or operate the machine before reading this manual.

-1-
1. Safety instructions
?The power output voltage may still have 220V or 120V even not connect to the mains power.
?For the battery cable or power cord replacement, please contact our service station or dealer to purchase,
in order to avoid fire caused by inadequate capacity or heat ignition.
?Do not place the battery or battery pack in the fire, which will injure due to explosion.
?Please do not open the UPS case as you will, there is risk of electric shock
?Do not touch the battery connection terminals. Battery loop and input voltage loop is without isolation,
which may cause high voltage risk between the battery terminal and ground.
?Do not connect to the equipment like hair dryer or electric heater, to ensure the safety for the UPS
Attention:
UPS has high voltage inside, for personal safety, please do not repair by yourself. If any questions, please
contact local service center or dealer.

2. Installation Instructions

2.1. Unpacking Inspection

?Open the UPS package, please check the enclosed accessories including a user manual, communication
cable, support feet, CD-ROM. The long-back model also includes the cable for connection to battery
bank.
?Check the UPS if any damage in transport. If find it’
s damaged or parts missing, do not power on, please
turn to the carrier and dealer.
?To determine whether this UPS is the model you want to buy. Check the model name showed both on the
front panel and rear panel of UPS to confirm.

Model Type Model Type


1KVARTS 1KVA RT Standard model 1KVARTH 1KVA RT Long backup model
1.5KVARTS 1.5KVA RT Standard model 1.5KVARTH 1.5KVA RT Long backup model
2KVARTS 2KVA RT Standard model 2KVARTH 2KVA RT Long backup model
3KVARTS 3KVA RT Standard model 3KVARTH 3KVA RT Long backup model
6KVARTS 6KVA RT Standard model 6KVARTH 6KVA RT Long backup model
10KVARTS 10KVA RT Standard model 10KVARTH 10KVA RT Long backup model

-2-
Note:
Please save the packaging box and packaging materials for future transport use. As heavy product, please
transit the UPS with care.

2.2. Attention items of installation

?The UPS installation environment must be with good ventilation, away from water, flammable gases and
corrosive entities.
?Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air outtake
hole will be unobstructed.
?The peripheral environment temperature around the UPS should be within 0 ℃ ~ 40 ℃.
? If dismantling the machine at low temperatures, there may be condensation droplets, users can not install
or operate it before UPS completely got dry both inside and outside, otherwise there will be danger of
electric shock.
? Place the UPS near the mains socket to cut off AC mains without any delay at any emergent case.
Attention:
?Make sure the load behind the UPS is off when users connect the load to UPS, and then turn on the load
one by one later.
?Please connect the UPS with the socket which is over-current protected. Do not connect the UPS with the
socket which rated current is less than the Maximum input current of the UPS.
?All the power socket should be configured with earthling device for safety.
?UPS could be electrified or powered no matter the input power cable is tied or not, even when the UPS is
off. The only way to cut off the output is switching off the UPS, disable the EPO and disconnecting the
mains power supply.
?For all standard type UPS, it is advised to charge the battery over 8 hours before used. Once the AC
mains power energizes the UPS, it will automatically charge the battery. Without prior charging, UPS
output remains as usual but with shorter back-up time than normal.
?When connected to motor, display equipment, laser printer etc, UPS power selection should be based on
the startup power of the load which is usually twice as rated power.

2.3 UPS and Battery Pack rear panel view


Note: following diagrams take the type of 0.9PF for example, the type of 0.8PF is similar.

2.3.1 The type of 120V (output could be 100V, 110V, 115V, 120V, 127V)

A、Standard model

2 3 4 2 11 7 8
5 6
R ESET

OUT

R ESET

R E S ET
EPO FUSE 250VAC3 5A
RESET

SLOT

TEL/MODEM/FAX
INTELLIGENT SLOT

ET
R ES
INTELLIGENT SLOT
RS232
EXT.BATTERY 

INPUT OUTPUT
RS232
24VDC 40A

EPO

USB
INTELLIGENT

FUSE 125VAC,15A
RESET  L N N L

EXT.BATTERY

USB
72VDC 40A

IN

IN OUT OUTPUT SOCKET


INPUT 
OUTPUT SOCKET 
TEL/MODEM/FAX

9 1 10 8 7 9 10 6 5 4

a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA&3KVA RT rear panel

B、Long-run model

-3-
9 2 3 4 7
2 3 4 5 6
ON
INTELLIGENT SLOT

R E S ET
EPO



ET
R ES

INTELLIGENT SLOT
RS232
EXT.BATTERY 

RS232
24VDC 40A

FUSE 125VAC,15A
RESET 

EPO

USB
USB INPUT OUTPUT OFF
L N L N

IN OUT
INPUT 
OUTPUT SOCKET 
TEL/MODEM/FAX

11 5 8 6
9 1 10 8 7

a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA RT rear panel

9 9
2 10 3 4 6
OUT

R ES
ET

DC OUTPUT DC OUTPUT


E S ET

RS232
TEL/MODEM/FAX

INPUT OUTPUT
FUSE 125VAC,35A
RESET  L N N L

USB
+ 72VDC - + 72VDC -
IN

EPO
INTELLIGENT
+ 72VDC 40A - OUTPUT SOCKET  SLOT
EXT.BATTERY 

9 11 8 5 7

c. 0.9PF 3KVA RT rear panel d. 0.9PF Battery Pack rear panel

2.3.2 The type of 220V (output could be 208V, 210V, 220V, 230V, 240V)

A、Standard model

2 4 5 6 8 3 7 1 2
INTELLIGENT SLOT

R ESE T RE SET
IN

EPO




R ESET R ES ET
RS232
EXT.BATTERY 

INTELLIGENT SLOT
24VDC 40A

TEL/MODEM/FAX

FUSE 250VAC,8A INPUT  FUSE 250VAC,20A


RESET  USB RESET 

RS232
OUTPUT SOCKET 
OUT

IN OUT

+ --

EPO

USB
INPUT  TEL/MODEM/FAX 48VDC 40A
EXT.BATTERY 

OUTPUT SOCKET 

9 1 10 3 8 7 6 5 4 10 9

a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA RT rear panel

9 2 3 4 7

8 3 7 1 2 ON
INTELLIGENT SLOT

INTELLIGENT SLOT


RE S T
IN

RS232

R ES ET
EPO
TEL/MODEM/FAX

USB
INPUT  FUSE 250VAC,20A
RESET  INPUT OUTPUT OFF
L N L N
RS232
OUT

EPO

USB

+ -
USB

72VDC 40A
EXT.BATTERY 

OUTPUT SOCKET 

6 5 4 10 9 11 5 8 6

c. 0.9PF 3KVA RT rear panel d. 0.9PF 6/10KVA RT rear panel

B、Long-run model

2 1 4 6
2 4 5 6

R ESE T
OUT

R ESET

EPO

RE T

R ESET SE
RS232

RS232
EXT.BATTERY 

TEL/MODEM/FAX
INTELLIGENT SLOT
24VDC 40A

FUSE 250VAC,15A INPUT 
FUSE 250VAC,8A RESET 
RESET  USB
USB

OUTPUT SOCKET 
IN

IN OUT EPO
INTELLIGENT
INPUT  TEL/MODEM/FAX + 48VDC 40A- SLOT
EXT.BATTERY 
OUTPUT SOCKET 

9 1 10 3 8 7 9 10 8 5 7

a. 0.9PF 1KVA RT rear panel b. 0.9PF 1.5K&2KVA RT rear panel

-4-
9 2 3 4 7

2 1 4 6
ON
INTELLIGENT SLOT

R ESET

OUT

RS232

R ESET

RS232
TEL/MODEM/FAX

USB
EPO
FUSE 250VAC,20A INPUT 
RESET  INPUT OUTPUT

USB
OFF
L N L N

EPO

IN
INTELLIGENT
+ 72VDC 40A- SLOT
EXT.BATTERY 
OUTPUT SOCKET 

9 10 8 3 5 7 11 5 8 6

c. 0.9PF 3KVA RT rear panel d. 0.9PF 6/10KVA RT rear panel


⑴Input Power Terminals;⑵Over Current Protector;⑶Fan;⑷USB;
⑸Emergency Power Off;⑹RS232 Communication Interface;⑺Intelligent Slot;
⑻Surge Protection for Network/Fax/Modem;⑼Battery Slot;⑽Output Socket;
⑾Terminal Block.

Note: Diagrams take the type of 0.9PF for example, the type of 0.8PF is similar. Due to the technology
upgrading and development, goods and diagrams might have some differences.

2.4 UPS output connection


Output connection of 1~10KVA type is configured with sockets or terminal blocks, users can plug the load
cable into the UPS socket to energize the load as below. Make sure the mains wire and breakers in the
building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire. 
Note: To the type of 6-10KVA, do not use the wall receptacle as the input power source for the UPS, which
rated current is less than the UPS’
s maximum input current. Otherwise the receptacle may be burned and
destroyed. 

Over Current Battery
Protector
OUT

ESE T

ON

T R

Over Current
ESE

FUSE 125VAC,20A
INPUT OUTPUT
   /MODEM/

RESET 

Protector
L N N L
IN

+ EXT.BATTERY 
48VDC 40A - OUTPUT SOCKET  INPUT OUTPUT
OFF
L N L N

Battery
Input output
LOAD
Input output

2.5 External battery connection procedure for long back up type


?For different UPS type, users are instructed to configure different battery voltage as below sheet. More or
less units are forbidden, or else something abnormal or faulty will appear.

Battery Quantity Battery Voltage


Type
(unit) (volt)
1KVA 2/3 24/36
1.5KVA 4 48
2KVA 4/6 48/72
3KVA 6/8 72/96
6KVA 16 192
10KVA 16 192

?One end of battery cable is for UPS terminals while the other end with triple cables is for battery terminals.
-5-
Correct installation procedure is highly vital or else probable electric shock will arise. Users are strictly
required to follow the below procedure.
?Connect battery in correct way and make sure the total battery voltage is available for UPS.
?Correctly connect the long battery cable to battery terminals first, red wire is to positive plate while black is
to negative. If users connect the UPS first, electric shock or other danger could not be avoided.
?Before connecting load after UPS, users should supply main power to UPS and energize it.
?Connect long battery cable to UPS terminals with correct poles link (red is for “+”, black is for“-”), UPS will
start the charging work automatically.

+ -  + - 

RE S T
RED
O T

RE SET

FUSE 125VAC,20A
INPUT OUTPUT

RESET 
L N N L BLACK
-  + - 

+EXT.BATTERY 
48VDC 40A - OUTPUT 

+ -  + - 
Battery

2.6 Installation

?UPS installation work should comply with local electrical standard and only can be done by professional
technician. 1KVA~3KVA units could use wall socket as input power connection.
?For all type UPS, it is advised to charge the battery over 8 hours before the first use. Once the AC mains
power energizes the UPS, it will charge the battery automatically. Without prior charging, UPS output
remains as usual but with shorter back up time than normal.

Installation steps:
1) Please take out two groups of support feet from package, assemble by embedding them with each
other as shown below.

2) Place the two support feet in parallel on horizontal surface, and then put the machine into two support
feet carefully. Make sure the main power is off when you move it.

3) It also can be placed horizontally without support feet if you like, please remember not to put the
machine upside down. Please lie it down carefully and make sure the main power is off.
-6-
4) Machine and battery pack, can be put together, as two ways are showed in the pictures below, the
battery pack should be put under the machine. The battery pack is heavy, be careful when you move it.

3. Panel function and operation


The operation is simple, operators only need to read the manual and follow the operation instructions listed
in this manual without any special training.

3.1 Keys function


Inverter LED
Battery LED
Bypass LED
Warning LED

25% 50% 75% 100%

VAC
E
LIN

HZ
OUTPUT
25% 50% 75% 100%

ON/OFF ROTATE

TEST/MUTE

※ ON/OFF key ( + )
Press and hold this key for more than half a second to turn on/off the UPS.
※ TEST/MUTE key ( + )
Press and hold the key for more than 1 second in mains mode or economical mode: UPS runs the self-test
function.
-7-
Press and hold the key for more than 1 second in battery mode: UPS runs the mute function.
※ ROTATE key ( + )
Press and hold and for more than half a second (less than 2 seconds): Change the direction to
display items.

The direction has 75% 100% 50% 25%

25% 50% 75% 100%


been changed in

VAC
the picture.

HZ
OUTPUT
VAC
E

E
LIN

LIN
Press and hold
HZ
OUTPUT
keys for more than
25% 50% 75% 100%
half a second.
100% 75% 50% 25%

ON/OFF ROTATE ON/OFF ROTATE

TEST/MUTE TEST/MUTE

After finishing that, the machine can be placed flat, as shown in the picture below.
E
LIN

25% 50% 75% 100%

※ INQUIRING key ( , )
Non-function setting mode:
1) Press and hold or for more than half a second (less than 2 seconds): display the items orderly.
2) Press and hold for more than 2 seconds: Circularly and orderly display the items every 2 seconds,
when press and hold the key for some time again, it will turn to output status.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Select the set option.

※ FUNCTION SETTING key

Non-function setting mode:


Press and hold the key for more than 2 seconds: Function setting interface.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Enter the function setting option
Press and hold the key for more than 2 seconds, exit from this function setting interface.

3.2 LED Function

-8-
From left to right is inverter LED, battery LED, bypass LED and warning LED.
Warning red LED is on: UPS fault. For example: Overload beyond the allowed time, inverter fault, BUS fault,
over temperature fault etc.
Bypass yellow LED is on: UPS is alarming. For example: Bypass mode supply power and etc.
Battery yellow LED is on: UPS is alarming. For example: Battery mode supply power and etc.
Inverter green LED is on: UPS is normally powered by mains or ECO mode or battery mode.
PS: LED display detail in different mode is listed in 5 items.

3.3 LCD display function


LCD displays as following figure.
※ Icon display area:

i. The top diagram is for load, battery, fan, fault and buzzer icon. When UPS is over loaded, the load light
will blink as same as the battery light blinks when the capacity of battery gets low or battery is
disconnected. The left icon and right icon are for load and battery capacity indication, each grid of
which represents 25%.
ii. The fan icon is for fan working indication; when fan normally runs, the icon will display rotation; if the
fan is not connecting or faulty, the icon blinks;
iii. Press the mute button under the battery mode, buzzer icon will blink; it will disappear under other
cases.
iv. Fault icon will be on when UPS on fault mode, otherwise it will not.

75% 100%
Icon display area

VAC
E
LIN

Battery capacity
Load capacity
display area display area
HZ

75% 100%

Working mode
display area
Digital display area

※ Digital display area:

A. Under none setting mode, it will display UPS output information when UPS normally runs in AC
mode; other information like input, battery, load and temperature will be showed after pressing the
inquiring key; Fault code will be told in fault mode.
-9-
B. Under setting mode, user could adjust different output voltage as well as activate ECO and BYPASS
mode by operating function setting key and inquiring keys.

※  Mode display area:

After over 20 seconds, this area will display the working mode of the machine. e.g. STDBY(Standby Mode),
BYPASS(Bypass Mode), LINE(AC mode), BAT(Battery mode), BATT(Battery Self Test Mode ),
ECO(Economic Mode), SHUTDN(Shutdown Mode).

3.4 Turn On/Off operation


3.4.1 Turn On operation
A. Turn on the UPS on Line mode
①Once mains power is plugged in, the UPS will charge the battery, at the moment, LCD shows that the
output voltage is 0, which means UPS has no output as default condition. If it is expected to have output
of bypass, you can set the bps “ON”by LCD setting menu.
②Press and hold the ON key for more than half a second to start the UPS, then it will start the inverter.
③Once started, the UPS will perform a self-test function, LED will light and go out circularly and orderly.
When self-test finishes, it will come to line mode, the corresponding LED lights, UPS is working on line
mode.
B. Turn on the UPS by DC without mains power
①When main power is disconnected, press and hold the ON key for more than half a second to start UPS.
②The operation of UPS in the process of start is almost the same as that when mains power is in. After
finishing the self-test, the corresponding LED lights and UPS is working on battery mode.

3.4.2 Turn Off operation


A. Turn off the UPS on line mode
①Press and hold the OFF key for more than half a second to turn off the UPS and inverter.
② After UPS shutting down, LED go out and there is no output. If output is needed, you can set bps “ON”
on LCD setting menu.
B. Turn off the UPS by DC without mains power
①Press and hold the OFF key for more than half a second to turn off the UPS.
②When turning off the UPS, it will do self-testing firstly. LED light and go out circularly and orderly until
there is no display on the panel.

3.5 UPS self-test/mute test operation

① When UPS is on line mode, press and hold the self-test/mute key for more than 1 second, LED light and
go out circularly and orderly. UPS comes to self-test mode and tests its status. It will exit automatically
after finishing testing, LED resume.
② When UPS is on battery mode, press and hold the self-test/mute key for more than 1 second, the
buzzer stops beeping. If you press and hold the self-test/mute key for one more second, it will restart to
beep again.

3.6 Panel function setting


- 10 -
UPS has setting function. It can run the setting on any mode. After setting, it will become effective at once
when meets some standards. The set information can be saved only when the battery connected and
normally turning off the UPS.
3.6.1 ECO mode setting

① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then
come to setting interface, the letters “ECO”will flash.
② Enter the ECO setting interface. Press and hold the function setting key for more than half a
second(less than 2 seconds), then come to setting interface of ECO, at this time, the letters “ECO”will
light for a long time. The “ON”(or OFF) will flash. Press and hold the inquiring key( , )for more
than half a second (less than 2 seconds) to determine whether the ECO function is used or not. If used,
the corresponding word is “ON”, if not, the word is “OFF”. It can be determined by yourself.
③ Confirm the ECO selecting interface. After selecting ON or OFF, press and hold the function setting
key for more than half a second (less than 2 seconds). Now, the ECO setting function is
completed and the “ON”or “OFF”will light without flash.
④ Exit from the setting interface. Press and hold function setting key for more than 2 seconds, exit
from the setting interface and turn to main interface.

25% 50% 75% 100% 25% 50% 75% 100%


E

E
LIN

LIN

25% 50% 75% 100% 25% 50% 75% 100%

3.6.2 Bypass mode setting

① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then
come to setting interface, Press and hold the function setting key for more than half a second(less
than 2 seconds), select the function setting, choose the bypass output interface, at the moment, the
letters “BPS”will flash.
② Enter the Bypass output selecting interface. Press and hold the function setting key for more than
half a second(less than 2 seconds), then come to setting interface of BPS, at this time, the letters “BPS”
will light for a long time. The “ON”letter will flash. Press and hold the inquiring key( , )for more
than half a second (less than 2 seconds) to determine whether the BPS function is used or not. If used,
the corresponding word is “ON”, if not, the word is “OFF”. It can be determined by yourself.
③ Confirm the Bypass output selecting interface. After selecting ON or OFF, press and hold the function
setting key for more than half a second (less than 2 seconds), Now, the BPS setting function is

- 11 -
completed and the “ON”or “OFF”will light without flash.
④ Press and hold function setting key for more than 2 seconds, exit from the setting interface and
return to main interface.
⑤ After setting BPS as ON, when mains power plugged in without turning on the UPS or no mains power
plugged in, there is bypass output but no power down backup function.

25% 50% 75% 100%


25% 50% 75% 100%

VAC

E
LIN

E
LIN
HZ
INPUT 25% 50% 75% 100%
25% 50% 75% 100%

3.6.3 Output voltage setting

① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then
come to setting interface, Press and hold the inquiring key( , )for more than half a second(less
than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the
letters “OPU”will flash.
② Enter the output voltage selecting interface. Press and hold the function setting key for more than
half a second(less than 2 seconds), then come to setting interface of output voltage OPU, at this time,
the letters “OPU”will light for a long time. The numerical value below the OPU will flash. Press and hold
the inquiring key( , ) for more than half a second (less than 2 seconds), select the numerical
value in accordance with “OPU” function. The provided voltages are 100, 110V, 115V, 120V, 127V or
208V, 210V, 220V, 230V, 240V, you can choose anyone by yourself.
③ Confirm the output voltage selecting interface. After selecting numerical value, press and hold the
function setting , for more than half a second (less than 2 seconds). Now, the OPU setting function
is completed and the numerical value will light without flash.
④ Exit from the setting interface. Press and hold function setting key for more than half a second
(less than 2 seconds), exit from the setting interface and return to main interface.

- 12 -
25% 50% 75% 100% 25% 50% 75% 100%

E
E

LIN
LIN
25% 50% 75% 100% 25% 50% 75% 100%

3.6.4 Low voltage of battery setting

① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then
come to setting interface, Press and hold the inquiring key( , )for more than half a second(less
than 2 seconds), select the function setting, choose battery voltage setting interface, at the moment, the
letters “bat”will flash.
② Enter the battery voltage selecting interface. Press and hold the function setting key for more than
half a second(less than 2 seconds), then come to setting interface of battery voltage, at this time, the
letters “bat”will light for a long time. The numerical value below the “bat”will flash. Press and hold the
inquiring key( , ) for more than half a second (less than 2 seconds), select the numerical value
in accordance with “battery”function. The provided voltages are 10V, 10.2V, 10.5V, numbers stand for
the voltage of each battery, you can choose anyone by yourself (The default is 10V), anyone has been
chosen, the machine will shutdown when its battery voltage achieve the voltage which you chose.
③ Confirm the battery voltage selecting interface. After selecting numerical value, press and hold the
function setting , for more than half a second (less than 2 seconds). Now, the battery setting
function is completed and the numerical value will light without flash.
④ Exit from the setting interface. Press and hold function setting key for more than half a second
(less than 2 seconds), exit from the setting interface and return to main interface.

25% 50% 75% 100%


E
LIN

25% 50% 75% 100%

3.7 Parameters inquiring operation

Press and hold the inquiring key or for more than half a second(less than 2 seconds) to inquire

- 13 -
about items. The inquired items include input, battery, output, load, temperature. The displayed items on
LCD screen are showed as following:
Output:Display the output voltage and output frequency of the UPS. As the following picture shows, the
output voltage is 120V or 220V, the output frequency is 50Hz.

25% 50% 75% 100% 25% 50% 75% 100%

VAC VAC

E
LIN

LIN
HZ
HZ
OUTPUT
OUTPUT
25% 50% 75% 100% 75%
25% 50% 100%

Load: Display the numerical value of the active power (WATT) and apparent power (VA) of the load. For
example, as the following graphics shows: the WATT of the load is 800W or 900W, VA is 1000VA (when
disconnect load, it is a normal phenomenon to show a small numerical value of WATT and VA). or 900W

25% 50% 75% 100% 25% 50% 75% 100%

W W
E

E
LIN

LIN
KVA KVA

LOAD LOAD

25% 50% 75% 100% 25% 50% 75% 100%

Temperature: Display the maximum temperature of the components in the UPS. As the following picture
shows: the maximum temperature is 40℃.

25% 50% 75% 100%


E
LIN

TEMP

25% 50% 75% 100%

Input: Display the voltage and frequency of the input. As the following picture shows: the input voltage is
120V or 220V, input frequency is 50Hz.
- 14 -
25% 50% 75% 100% 25% 50% 75% 100%

VAC VAC

E
E

LIN
LIN
HZ HZ
INPUT INPUT
25% 50% 75% 100% 25% 50% 75% 100%

Battery: Display the voltage and capacity of the battery (determined by type). As the following picture
shows: the battery voltage is 24V or 36V, the capacity of battery is 100%(the capacity of battery is
approximately reckoned according to the battery voltage).

25% 50% 75% 100% 25% 50% 75% 100%

VDC VDC
E

E
LIN

LIN
% %

BATTERY BATTERY

25% 50% 75% 100% 25% 50% 75% 100%

Press and hold the inquiring key for more than 2 seconds, LCD begins to display the items circularly
and orderly which transfer to another every 2 seconds. Press and hold the key for some time again within
30s, it will return to output status.

4. Working mode introduction


4.1 Bypass mode
LED indications on front panel on bypass mode are as following:

Bypass yellow LED is on, the buzzer beeps once every 2 minutes. The warning red LED is on when
beeping, LCD displays are according to the exact load and battery capacity.
Turn to bypass mode under the following two conditions:
① Turn off the UPS on line mode while start the bypass output.
② Overload on line mode.
NOTE: When UPS is working on bypass mode, it has no back up function.

4.2 Line mode


LED indications on front panel on line mode are as following: The inverter green LED is on.

- 15 -
When input AC is in the range of working conditions, UPS will work on line mode.

4.3 Battery mode


LED indications on front panel on battery mode are as following: both the inverter green LED and battery
yellow LED are on, the buzzer beeps once every 4 seconds. The warning red LED is on when beeping.

When the AC power is low or unstable, UPS will turn to battery mode at once.

4.4 ECO mode


LED indications on front panel on ECO mode are as following: both the inverter green LED and bypass
yellow LED are on.

When the input mains meets the input range of the ECO mode and start the ECO function, the UPS will
works on ECO mode. If input AC exceeds the range of ECO several times in a row in a minute but stays in
inverter input range, UPS will work on AC inverting mode automatically.

4.5 Fault mode


LED indications on front panel on Fault mode are as following: warning red LED is on and LCD display fault
code and related icon.

Fault mode (LCD interface on which the fault code display)


When UPS has faulted. The warning LED is on and the buzzer beeps. UPS will turn to fault mode. UPS
cuts off the output and LCD display fault codes.
LT
FAU

At the moment, you can press the mute key to make the buzzer stop beeping temporarily to wait for
maintenance. You can also press the OFF key to shut down the UPS when confirm that there is no serious
fault.

5. The warning list of the LED light and display panel


- 16 -
Appendix 1: The table of the fault code

Fault reason Fault code

BUS voltage fault 00-14

Power soft start fault 15-24

Inverter voltage fault 25-39


Overheat 40-44

Output short circuit 45-49

Overload 50-54

Input NTC fault 55-59

Power fault 60-64


Input FUSE fault 65-69

Other 88

Appendix 2: Table for working status

LED on Front panel


Alarm
S/N Working status Bypas Note
Normal Battery Fault beep
s

1 Inverter mode (mains power)


Mains power
?       N
voltage
Mains power
 
high/low voltage One beep /
? ?   ★  
protection, switch to 4 sec
battery mode

2 Battery mode
Battery voltage - One beep /
? ?   ★  
normal 4 sec
  Warning for
One beep /
abnormal voltage of ? ★ ★  
sec
battery  
3 Bypass mode

Mains power –
One beep /
normal(under     ? ★
2 mins
Bypass)
 
Mains power – high
One beep /
voltage warning     ? ★  
4 sec
(under Bypass)

- 17 -
Mains power – low
One beep /
voltage warning     ? ★  
4 sec
(under Bypass)

4 Warning for battery disconnected


One beep /
Bypass mode     ? ★
4 sec
One beep /
  Inverter mode ?     ★
4 sec
Power on / Switch
6 beeps
on
5 Output overload protection

Warning for mains 2 beeps /


?     ★
power overload sec
Protect operation
for mains power     ? ? Long beep
mode overload
 
Warning for battery 2 beeps /
? ?   ★
overload sec
Protect operation
for battery mode ? ?   ? Long beep
overload
Warning for bypass One beep /
6     ? ★
mode overload 2 sec
One beep /
7 Fans fault(fan icon) ? ? ? ★
2 sec

8 Faults mode ? Long beep

? LED Indicator lights long time


★ LED Indicator flicker
? LED indicator status depends on other conditions
Note: Users need to provide below information when require to maintain the UPS.
Ø UPS Model No. & Serial No.
Ø Date of fault occurrence.
Ø Fault detail (LED status, noise, AC power situation, load capacity, for long back up type, battery
capacity configuration is also necessary.)

6. Trouble shooting
When the system runs in failure mode, the LCD will show as below:

- 18 -
Fault icon

LT
FAU
Fault code

Explicit Troubleshoot Introduction Sheet


Trouble indication Failure point Solution

Fault LED on, audible buzzer Please test the bus bar voltage or contact
Persistently alarm, the fault code Bus bar voltage fault the supplier.
is 00-14
Fault LED on, audible buzzer Please check the soft start up circuit,
persistently alarm, the fault code Soft start fault especially the soft start resistance or
is15-24 contact the supplier directly.

Fault LED on, audible buzzer Please contact the supplier.


persistently alarm, the fault code is Inverter voltage fault
25-39
Please make sure the UPS didn’ t get
overload, and the fan vent was not
Fault LED on, audible buzzer obstructed, as well as the indoor
Over temperature
persistently alarm, the fault code is temperature is not high.
inside
40-44 Leave alone the UPS 10 minutes for
cooling, and restart it. If failure remains,
please contact the supplier.
Turn off the UPS and disconnect all the
Fault LED on, audible buzzer load, make sure there no any fault or
Persistently alarm, the fault code Output short-circuit internal short circuit of the load.
is 45-49 And then restart the UPS, if failure still,
please contact the supplier.

Please check the load level and


disconnect the noncritical devices, recount
Fault LED on, audible buzzer
the total capacity of your load and reduce
persistently alarm, the fault code is Over load
the load to the UPS.
50-54
Please check whether the load device has
fault or not?
Fault LED on, audible buzzer Please contact the supplier.
persistently alarm, the fault code is Input NTC fault
55-59
Fault LED on, audible buzzer Power fault Please Check whether the input & output

- 19 -
persistently alarm, the fault code is power normal or not, contact the supplier if
60-64 it is abnormal.
Please check if the input fuse is burnt.
Fault LED on, audible buzzer
Replace the old fuse and restart the UPS.
persistently alarm, the fault code is Input fuse fault
If failure remains, please contact the
65-69
supplier.
Please check whether the fans connect
Fault LED on, audible buzzer
well, is the fan plugged and is the fan
Persistently alarm, fan icon in the Fan fault
broken? If all above condition is OK,
LCD flickers
please contact the supplier.
Please press the power key more than 2
Pressing time too short
seconds to start the UPS.
The input connection is Please connect the input well, if the battery
UPS fail to start when operate not ready or voltage is too low, please disconnect the
“On”key UPS internal battery input and start the UPS with no-load.
disconnect
UPS internal system Please contact the supplier.
fault
Please keep the UPS battery recharging
Battery undercharge
more than 3 hours.
Please check the load level and
UPS overload
Back up time become short disconnect the noncritical devices,
Please change new battery, contact your
Battery maturing,
supplier to get the new battery and spare
capacity descend
parts.
UPS doesn’ t have any power go UPS input breaker Please reset the circuit breaker by manual.
through even main power on disconnects
Attention: When the output is short-circuited, the action of the protection of the UPS will show up.
Before turning off the UPS, please make sure to disconnect the entire load and cut off the AC mains power
supply, otherwise will make the AC input short-circuit.

7. Attention of battery disposal


◇Please take off your ring, watch and other metals before operate the batteries.
◇If you want to change the battery cable, please purchase the material from our local service center or
distributors, to avoid heating or spark due to the inadequate power capacity, and even causing fire.
◇Don’
t dispose of the battery or battery pack near or into fire, otherwise it will explode and injure person.
◇Don’
t damage or open the battery case, the battery electrolyte overflow is with highly toxic which is
harmful to human.
◇Please avoid short circuit between positive and negative terminal, otherwise may cause fire or electric
shock.
◇Please check the battery voltage before touching. If the loop of battery and loop of input voltage is
non-isolated, that will cause high voltage risk between battery terminals and ground.

8. Network communication
- 20 -
This series UPS offer intelligent network interface with a dedicated Ethernet card (optional accessory),
realizing network communication and management. For more information about this function, please turn
to our local distributor or service center.

9. Communication interface introduction


The UPS communicates with PC via analog relay joint and serial interface (RS232). The former transmits
the input power and UPS status to PC by choosing “on” or “off” states of transistor. The latter offers
communication interface serials with PC to monitor input power and UPS status information, and control
the UPS also.
Note: The communication function is only realizable with the specific communion cable from the supplier.
Rs232 interface is set as below:
◇Bit rate: 2400bps
◇Byte: 8bit
◇Completion code: 1bit
◇Bit Pattern: None

Appendix 1: EMC Level


The series product is designed to meet the below standard.
EMS
IEC61000-4-2(ESD) Level 4
IEC61000-4-3(RS) Level 3
IEC61000-4-4(EFT) Level 4
IEC61000-4-5(Suege) Level 4
EMI
GB9254-1998/IEC 62040-2 Class B

Appendix 2: Symbol instructions:

Symbols and significations


Symbol Significations Symbol Significations

Caution Protect grounding

Danger! High Voltage! Alarm cancel

Turn on Overload

Turn off Battery inspection

Standby or Shutdown Repeat

- 21 -
AC Display screen repeat key

DC Battery

Appendix 3: Specification Sheet


Rated Capacity 1KVA 1.5KVA 2KVA 3KVA
Input
Rated input voltage 220V or 120V
Rated input frequency 50Hz/60Hz auto-adaptive
Input voltage range (115~295)±5VAC (half load)
(the type of 220V) (145~295)±5VAC(full load)
Input voltage range (55~145) ±5VAC(60% LOAD); (65~145) ±5VAC(70% LOAD)
(the type of 120V) (75~145) ±5VAC(80% LOAD); (85~145) ±5VAC(100% LOAD)
45-55Hz+/-0.5% 50Hz type
Input frequency range
55-65Hz+/-0.5% 60Hz type
220V 8A max 12A max 15A max 23A max
Input current
120V 14A max 21A max 27A max 40A max
PFC =0.98
THDI ﹤6%
Bypass voltage 220V Rated output voltage -34V ~ Rated output voltage +32V
range 120V (95~135) ±5VAC
Output
220V 208VAC /210VAC/220VAC/230VAC/240VAC Setting available
Output voltage
120V 100/110/115/120/127VAC Setting available
Output PF 0.8/0.9 0.8/0.9 0.8/0.9 0.8/0.9
Output power(Watt) 800/900 1200/1350 1600/1800 2400/2700
105%~150%: transfer to bypass mode after 30s giving alarm;
Inverter overload capability
>150% : transfer to bypass mode after 300ms giving alarm;
Voltage accuracy ±0.2
Load crest 3:1
From AC mode to BAT mode 0ms(transfer time)
From BAT mode to AC mode 0ms(transfer time)
LINE mode ≧90 % (full load)
Efficiency BAT mode 87%
ECO mode 98%
Output frequency
Under Mains mode Same as input frequency
Under battery mode (50/60±0.2)Hz
Phase-locked rate =1Hz/s
Total voltage harmonic
Full linear load< 3%;Full nonlinear load< 5%
distortion
Battery
Battery type Sealed lead acid maintenance free battery
Quantity 2 3 4 4 6 6 8
- 22 -
DC voltage 24V 36V 48V 48V 72V 72V 96V
Inbuilt battery 9AH/12V 7AH/12V 9AH/12V 9AH/12V 7AH/12V 9AH/12V 7AH/12V
Output voltage 27.1±0.4V 40.6±0.5V 54.2±0.6V 54.2±0.6V 81.3±0.9V 81.3±0.9V 108.4±1V
Back up time Based on battery capacity
Charge method Three-stage charging
Standard model :1A
Charge current
Long time model: 6A
System Control and Communication
Function Silence; cold start; AC restart; Auto restart.
Over-temp protection; Fan testing protection;
Protection AC L and N reversely connecting protection;
Output short circuit protection
Communication port RS232; SNMP card; USB
Graphics analyze; Switch on/off UPS system; Monitor UPS working status; History
Software function
record and event log
Display LCD/LED

Appendix 4: Specification Sheet (6-10KVA)


Rated Capacity 6KVA 10KVA
Input
Rated input voltage 220V
Rated input frequency 50Hz/60Hz auto-adaptive
Input voltage range (115~295)±5VAC (half load); (145~295)±5VAC(full load)
45-55Hz+/-0.5% 50Hz type
Input frequency range
55-65Hz+/-0.5% 60Hz type
Input current 46A max 76A max
PFC =0.99
THDI ﹤5%
Bypass voltage range Rated output voltage -34V ~ Rated output voltage +32V
Output
Output voltage 208VAC /210VAC/220VAC/230VAC/240VAC Setting available
Output PF 0.8 0.9 0.8 0.9
Output power(Watt) 4800 5400 8000 9000
105%~125%: 10 mins; 105%~125%: 3 mins; 105%~125%: 10 mins; 105%~125%: 3 mins;
Inverter overload capability 125%~150%: 30 secs; 125%~150%: 30 secs; 125%~150%: 30 secs; 125%~150%: 30 secs;
>150%: 100ms; >150%: 100ms; >150%: 100ms; >150%: 100ms;
Voltage accuracy ±0.2
Load crest 3:1
From AC mode to BAT mode 0ms(transfer time)
From BAT mode to AC mode 0ms(transfer time)
LINE mode ≧92% (full load)
Efficiency BAT mode 90%
ECO mode 98%
Output frequency
Under Mains mode Same as input frequency
- 23 -
Under battery mode (50/60±0.2)Hz
Phase-locked rate =1Hz/s
Total voltage harmonic
Full linear load< 3%;Full nonlinear load< 5%
distortion
Battery
Battery type Sealed lead acid maintenance free battery
Quantity 16
DC voltage 192V
Output voltage 216.8±1V
Inbuilt battery 16*9AH/12V
Charge method Three-stage charging
Back up time Based on battery capacity
Standard model:1A
Charge current
Long time model: 1A /3A /5A /8A
System Control and Communication
Function Silence; cold start; AC restart; Auto restart.
Over-temp protection;
Over-temp protection; Fan testing protection;
Protection
AC L and N reversely connecting protection;
Output short circuit protection
Communication port RS232; SNMP card; USB
Graphics analyze; Switch on/off UPS system; Monitor UPS working status; History
Software function
record and event log
Display LCD/LED

Appendix 5: Physical (The type of 220V)


Rated Capacity 1KVA 1.5KVA 2KVA 3KVA
Long 440×468×88
Dimension UPS 440×468×88 440×468×88 (Without Internal battery)
Standard
(W*D*H) (With Internal battery) 440×640×88 (With Internal battery)
Battery pack 440×468×88
Quantity of Battery 2 3 4 4 6 6 8
Long 6 12 12 13

WOIB / 12 12 13
Weight (Kg) Standard
WIB 12 14.5 28 28 33 33 /

Battery pack / 17 17 23 23 28
*WOIB: Without Internal battery 
*WIB: With Internal battery

Rated Capacity 6KVA 10KVA


Dimension UPS 440×565×132
(W*D*H) Battery pack 440×565×132

Long 19 19

Weight (Kg) Standard 19 19

Battery pack 52 52
- 24 -
Appendix 6: Physical (The type of 120V)
Rated Capacity 1KVA 1.5KVA 2KVA 3KVA

Long 440×468×88

Dimension 440×468×88 440×468×88 (Without Internal battery)


Standard
(W*D*H) (With Internal battery) 440×690×88 (With Internal battery)

Battery pack 440×468×88


Long 6 12 12 13
WOIB / 12 12 13
Weight (Kg) Standard
WIB 12 28.5 28.5 33.5
Battery pack / 17 17 23
*WOIB: Without Internal battery 
*WIB: With Internal battery

Appendix 7: Communication port


l Communication port for PC
At the rear panel of this model, there is one DB9 port, which provides several signals as follows:

Foot Explanation Foot Explanation


1 empty 6 empty
2 Send 7 empty
3 receive 8 empty
4 empty 9 awaken
5 GND

Communication port for PC

l TCP/IP
This model UPS can supply one Intelligent Slot at the rear panel, which was compatible with most of the
software and hardware all of the world, such as running HP open view,IBM net view,SUN net manager
and other operation system. UPS is with function login on internet supplying information of UPS status and
input power, and even capable of controlling UPS via net management system.
For more information, please turn to local supplier or distributor.