Outdoor power cabinet

The Type 2 cabinet platform is designed for a


variety of applications and can be tailored to fit
your specific needs. The cabinet is well suited for
power, batteries and telecom/industrial equipment,
all integrated into a robust package.

TYPE 2
OUTDOOR CABINET
Doc 234747.DS3 – rev6

RELIABILITY APPLICATIONS KEY FEATURES


Reliability within the outdoor plant depends The Type 2 cabinet is well suited for a wide  19” EQUIPMENT SPACE
upon a cool, dry and secure environment for range of Telecom and Industrial applications  OPTIONAL THERMAL INSULATION
the electronics such as the DC power, such as:  DC POWER, TELECOM/INDUSTRIAL
EQUIPMENT AND BATTERY BACKUP
Telecom and Industrial equipment. The Type  Radio Access Networks
2 Outdoor Power Cabinet more than (2G, 3G, 4G / LTE / WiMax)  ALUMINUM CONSTRUCTION
accomplishes this with a variety of Thermal  Optical Networks  DOOR MOUNTED THERMAL
MANAGEMENT OPTIONS:
Management solutions that will keep sensitive  Cable TV
O FAN / FILTER
electronics functioning in the most extreme  DSL
O AIR-CONDITIONER
environments.  SCADA
 FLOOR, WALL OR POLE MOUNT
 Rail and Metro
 3U SECTION FOR A DIN RAIL AC
 Power distribution
DISTRIBUTION
 UL 50
The cabinet works very well as a stand-alone
 IP55, NEMA 3R
power / battery backup solution and provides
 CLOGGED FILTER DETECTION
additional space for telecom / Industrial
 EASY INSTALLATION
equipment. In addition the outdoor enclosure
 EASY FILTER CHANGE
is suited for Industrial environments.
 EASY MAINTENANCE

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2013 – www.eltek.com
TYPE 2
OUTDOOR CABINET

Model 15U F/F 15U Air-con 22U F/F 22U Air-con


Part number 237143 250661 263236 263237

PHYSICAL SPECIFICATIONS
Exterior Height (mm) 743 (29.3”) 743 (29.3”) 1047,5 (41,2”) 1047,5 (41,2”)
Exterior Width (mm) 586 (23,1”) 586 (23,1”) 586 (23,1”) 586 (23,1”)
Exterior Depth (mm) 580 (22,8”) 790 (31,1”) 580 (22,8”) 790 (31,1”)
Net weight (Kg) 28,4kg (62,6lbs) 48,4kg (106,7lbs) 32,4kg (71,5lbs) 52,4kg (115,5lbs)
All Models
CONSTRUCTION SPECIFICATIONS
Skin material 1.5mm (0.06”) thick aluminum (lightweight, corrosion-resistant)
Frame Material Galvanized Steel
Powder-Coat Paint Outdoor Polyester light gray RAL 7035 coating
Insulation Closed Cell Insulation (optional)
Rail mounting Pattern EIA Standard with holes for Cage nuts
Orientation 19” mount
Usable Mounting Height 12U (533mm / 21.0”) or 19U (844mm / 33”)
DOOR SPECIFICATIONS
Latches Two point latch, with optional euro lock cylinder
Gasket UL rated for outdoor use
Door Stop / Door Stay Wind latch to hold door during maintenance (120o)
Fan and Filter Solution Filter class F5 (EN 779),
Air Conditioning Unit 570W at 50Hz and 35C/35C
MISC. SPECIFICATIONS AND OPTIONS
Cable Glands Bottom Cable Access Different options available
19” tray(s)
Space: 448,5mm W x 398mm D
Battery trays Each Tray weighs 2.1kg (4.6lbs)
(17,6” W x 15,6” D)
Max. 150kg (330 lbs) weight load
Ground Bar 4xM6 inserts on 19” rails, left/right
Heater Optional 400W Kit weighs 1.3kg (2.9lbs)
Optional 152mm (6”) high plinth.
Plinth Foot Print: 579mm W x 502mm D Weighs 7.6kg (16.7lbs)
(22,8” W x 19,8” D)
Stainless Steel wall or pole
Mounting Brackets Pole diameter Ø 60-115mm Weighs 11kg (24.2lbs)
Max 200Kg (441lbs) weight load
4 Detachable sheet metal ears
Lifting Ears
connected with 4 x M8 bolts
Shipments made in an upright
Packaging Information Weighs 7kg (15.4lbs)
position on a wood pallet
DESIGN STANDARDS
IEC 60950, UL 60950*, CAN CSA-C22.2 No. 60950-1-03
Electrical
(Depending on Equipment Installed)
EMC ETSI EN 300 386 V.1.3.1, EN 61000-6-3, EN 61000-6-2
Environment ETS 300 019, Ingress Protection: EN 60529 IP55

Doc 234747.DS3 – rev6 Specifications are subject to change without notice

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2013 – www.eltek.com