Manual: Installation and Operating Instructions
Manual: Installation and Operating Instructions
O2
Module
Weishaupt Combustion Managers W-FM 100 and W-FM 200 83054802 - 1/2009
Contents
1 1. General instructions 6
2 2 Safety instructions 7
3 3 Technical description
3.1 Function
8
8
3.2 Display and operating unit ABE 10
4 4. Installation
4.1 Safety instructions for installation
11
11
4.2 Installation of components 12
4.3 Basic wiring diagram (does not replace burner wiring
diagram) 14
6 6 Commissioning - modulating
6.1 Set fuel and load points on W-FM
24
24
6.2 Commission burner 25
6.2.1 Set mixing pressure for ignition 25
6.2.2 Burner ignition 26
6.2.3 Set load point 1 27
6.2.4 Start full load 28
6.2.5 Optimise full load 29
6.2.6 Redefine intermediate load points 30
6.3 O2 functions - modulating 32
6.3.1 Set O2 guard 32
6.3.2 Set O2 trim 33
6.3.3 Set O2 regulating functions 34
6.3.4 Check and optimise O2 trim 35
6.3.5 Optimise O2 trim 36
6.4 Concluding work following commissioning 37
6.4.1 Set ratings range and flue gas temperature
limit values 37
6.4.2 Concluding work on the burner 37
7 7 Commissioning multi-stage
7.1 Set fuel and load required
38
38
7.2 Commission burner 39
7.2.1 Pre-set curve parameters 39
7.2.2 Burner ignition 40
7.2.3 Start full load 41
7.2.4 Set switch off point(s) 42
7.2.5 Check operating, switch on and off points 42
7.2.6 Check start behaviour 43
7.2.7 Define full load as required load 43
3
8 8 Load controller
8.1 Set operating mode
44
44
8.2 Configure sensors 45
8.3 Setpoint (external) 46
8.4 Setpoint (internal) 47
8.5 Modulating load control 48
8.5.1 Parameter internal load control 48
8.5.2 Optimise internal load control 49
8.6 Multi-stage load control 50
8.7 Cold start function 51
4
10 10 O2 sensor 106
11 11 Frequency converter
11.2 Parametering VLT 2800
108
108
11.3 Parametering FC 300 110
13 13 Service
13.1 Safety information for servicing
126
126
13.2 Service plan 126
14 14 Technical data
14.1 Combustion manager W-FM
127
127
14.2 Stepping motors SQM45.../48... 128
14.3 Flame monitoring 129
14.4 Display and operating unit (ABE) 130
A Appendix
Notes
131
131
5
1 General information
These installation and operating instructions Hand-over and operating instructions
• are an integral part of the equipment and must be The contractor is responsible for passing the operating
kept permanently on site. instructions to the plant operator prior to hand-over. He
should also inform the plant operator that these
• are to be used by qualified personnel only. instructions should be kept with the heating appliance. The
address and telephone number of the nearest service
• contain the relevant information for the safe assembly, centre should be entered on the reverse of the operating
commissioning and servicing of the equipment. instructions. The plant operator must note that an agent of
the contractor or other suitably qualified person must
• are for the attention of all personnel working with the inspect the plant at least once a year. To ensure regular
equipment. inspections, -weishaupt- recommends a service contract.
• in addition to this installation and operating manual, The contractor should instruct the plant operator in the use
the documentation for the relevant burner and the of the equipment prior to hand-over and inform him as and
type of frequency converter must be observed. when necessary of any further inspections that are required
before the plant can be used.
Abbreviations
Tab. Table
Ch. Chapter
6
2 Safety information 2
Dangers when using the equipment Electrical safety
Weishaupt products are manufactured in accordance with • Before starting work - isolate plant and protect against
the relevant existing standards and guidelines and the reactivation, check voltage is isolated, the unit is
recognised safety laws. However, improper use of the earthed, and protected from adjacent equipment that
equipment could endanger life of the user or a third party, might still be under voltage!
or result in damage to the plant. • Work on the electrical supply should be carried out by
a qualified electrician
To avoid unnecessary danger, the equipment is only to be • Electrical components should be checked during
used: servicing. Loose connections and heat damaged
• for its intended purpose cables should be dealt with immediately.
• under ideal safety conditions • The control panel should be locked at all times. Access
• with reference to all the information in the installation should be restricted to authorised button holder
and operating instructions personnel.
• in accordance with inspection and service work. • Should it be necessary to carry out work on live parts,
country specific safety regulations must be observed
Faults, which could affect the safe operation of the burner, and tools to EN 60900 must be used. A second
should be rectified immediately. person should be present to switch off the mains
supply in an emergency.
Personnel training
Only competent personnel may work on the appliance. Maintenance and fault rectification
Competent personnel according to this operating manual • Necessary installation, service and inspection work
are persons who are familiar with the installation, should be carried out at the specified time.
mounting, setting and commissioning of the product and • Inform the operator before beginning any service
have the necessary qualifications such as:- work.
• Training, instruction or authorisation to switch electrical • For all service, inspection and repair work, electrically
circuits and electrical devices on and off, to earth them isolate the equipment and ensure the mains switch
and to mark them in accordance with the safety cannot be accidentally switched back on. Cut off the
standards. fuel supply.
• Training, instruction or authorisation to carry out • Flame guarding devices, limit controls, correcting
installation, alteration and maintenance work on gas elements and all other safety devices must be
installations in buildings and on site. commissioned by, and may only be replaced by, the
manufacturer or an authorised agent.
• Following service work, all safety devices should be
Organisational measures tested to ensure they are functioning correctly.
• Everyone working on the plant should wear the
necessary protective clothing.
• All safety devices should be checked regularly. Alterations to the construction of the equipment
• No alterations to the equipment are to be made without
the approval of the manufacturer.
Informal safety measures All conversions require written confirmation from Max
• In addition to the installation and operating instructions, Weishaupt GmbH.
local codes of practice should also be adhered to. • Any parts not in perfect working order should be
Special attention should be paid to the relevant replaced immediately.
installation and safety guidelines given. • No additional components may be fitted, which have
• All safety and danger notices should be kept in a not been tested for use with the equipment.
legible condition. • Use only -weishaupt- replacement and connection
• Furthermore, all safety documentation and danger parts. Parts from other manufacturers are not
notes covering the frequency converter and burner guaranteed to be suitable to meet the necessary
must be observed. operational and safety requirements.
7
3 Technical description
The combustion manager W-FM contains all functions Functions
required for safe and efficient operation of multi-stage or • Burner control
modulating single fuel and dual fuel burners. • Electronic compound regulation for max. four or
The display and operating unit shows the conditions and six 1 stepping motors
allows programming via dial knob and function buttons. • Speed control 1
• O2 trim 1
• Valve proving
• True dual fuel operation
• Integral load controller 2
• Flame monitoring
• Separate ABE programmer
3.1 Function
Combustion manager Load controller 2
The combustion manager: The optional, integrated PID load controller can be used as
• controls the sequence of operation a temperature or pressure controller for multi-stage or
• monitors the flame modulating burners, depending on the connection and
• communicates with the stepping motors parametering. Furthermore the load controller contains a
• controls and monitors the frequency converter control reaction damper which protects the stepping
• carries out valve proving of the gas valves motors from unnecessary drive impulses, thus increasing
• has: – an integrated load controller 2 their life span.
– speed control 1 The load controller can be operated with one external
– O2 trim 1 setting value or setpoint input, or with two internal
setpoints.
The internal setpoints can be selected using an external,
Operating elements potential free contact.
The system can be controlled by several operating units: Switchover from external operation to the internal load
• A plug-in programmer ABE controller is via contact.
• PC module for onscreen control A separate start up programme is incorporated for boiler
• Remote main control system (Building Management cold start if required.
System)
Speed control 1
Flame sensor The frequency converter of the fan motor is started by a
Monitors the flame during all phases of operation. If the setpoint output (0/4 - 20 mA) and the speed is matched to
flame signal does not correspond to the sequence of the current burner rating required. The speed and the
operations, a safety lockout will occur. rotation are determined and monitored using an inductive
Flame sensors used: proximity switch in conjunction with an asymmetrical
• QRI and QRA 73 for continuous or intermittent transmitter disc. In compound with the stepping motors
operation for oil, gas and dual fuel burners. the required combustion air is automatically adjusted and
• Ionisation electrode only for gas, for continuous or the electrical consumption is reduced to a minimum.
intermittent operation. If the air supply fails or becomes insufficient, an air
• QRB photo resistor for intermittent operation for oil pressure switch initiates lockout.
burners.
O2 trim 1
Stepping motors The residual O2 content in the flue gas is determined by a
Stepping motors on: sensor, which compares it to the setpoints calculated
• Air damper during commissioning. Depending on the control
• Oil controller deviations the combustion manager controls the air
• Gas butterfly valve regulating devices and corrects the O2 content.
• Mixing head
Providing precise (0.1 degree acuracy) and direct control
of the correcting elements in compound. Low gas programme
The setting values are transmitted via CAN BUS from the If the control gas pressure falls below the setting of the low
combustion manager to the stepping motors, the stepping gas pressure switch during operation, the combustion
motors are electronically adjusted and the combustion manager starts a low gas programme.
manager constantly monitors their position return signals. If the gas pressure is below the setpoint prior to start, the
burner start is inhibited.
1
W-FM 200 only
2
optional on W-FM 100
8
3
Valve proving (only on gas operation) Sequence diagram valve proving
Following each controlled shutdown, the combustion
1st. Test phase 2nd. Test phase
manager carries out a valve proving test of the gas
solenoid valves.
Following lockout or power failure, the valve proving test is Valve 1
carried out prior to the next burner start. 33 secs.
sek. 10 sek.
10 secs. 33 secs.
sek. 10 sek.
10 secs.
Valve 2
Function
1st. Test phase:
During a controlled shutdown valve V1 closes P between
V1 and V2
immediately, and valve V2 has a slight delay in closing
which permits the volume between the valve seats to Gas press.
depressurise. The section between V1 and V2 must switch VP
remain depressurised once the second valve has
closed.
Setting pressure gas pressure switch
2nd. Test phase:
Valve V1 opens and immediately closes again, PR + PV
allowing gas pressure build-up between V1 and V2 = setting pressure
valve seats. During the test phase, the pressure 2
between the valve seats must not fall below the
pressure setting of the gas pressure switch. PR = Control pressure into V1 (reduce impact pressure)
PV = Maximum pressure during pre-purge downstream of V2
9
3
3.2 Display and operating unit ABE
Setting without tools Display and operating unit ABE
The advantage of electronic ratio control provided by the
W-FM lies in the simple setting via display menus. The
positioning for fuel, air, and auxiliary actuators is selected
digitally. With only a few input ratings-positions being
entered, the intermediate firing positions are automatically
interpolated.
Display
4 lines with scroll function
ESC button
Cancel or return
Info button
Return to operating display
Enter button
Execution
Scroll knob
Cursor control and value change
Contrast adjustment
To change the contrast of the display, press Enter button
and hold down whilst changing the contrast using the
scroll knob (+/–). (Only possible in menu Normal
operation, contrast adjustment with saving see Ch. 9.9.7).
10
4. Installation 4
4.1 Safety instructions for installation
Electrically isolate the plant
Prior to installation switch off the mains switch
and the safety switch.
Failure to comply could cause death or
serious injury by electric shock.
DANGER
11
4
4.2 Installation of components
The electrical connections should be carried out to the
wiring diagram supplied with the burner. All country and
local codes of practice (i.e. EN, DIN, VDE, BS, etc.) must
be observed.
Flame sensor
The 1.8 m senor line to the flame sensor can be extended
by up to 100m if installed separately (i.e. for W-FM in a
separate control panel).
Ignition line
The ignition cables should be installed as close as
possible to the ignition electrodes. Ignition cables must
have an adequate spacing away from any other wiring.
12
4
Installation example: W-FM in burner housing Installation example: W-FM in a control panel
O2-Modul Jumper with Bus (W-FM 200 only) O2 Module Jumper with Bus (W-FM 200 only)
connection connection
5 5
2 AT
con- con- con- nection nection nection
nection nection nection
ABE
5 5 5
5 5
AC1 12V 4 AT
AC2 12V 4 AT
AC2 12V
AC1 12V
CANH
CANL
GND
GND
5
AC2 12V 5
AC1 12V
AC2 12V
AC1 12V
CANH
CANH
CANL
CANL
GND
GND
4 AT
4 AT
ABE
3
6,3 AT
5
W-FM
AC2 12V
AC1 12V
CANH
CANH
CANL
CANL
GND
GND
Mains 4 AT
4 AT
5
Frequency W-FM
converter Supply transf. 1
Mains
Frequency
converter
13
14
Motor start
contactor
Burner lockout
Safety circuit
230V 1/N/PE 50-60Hz
External connections
Additional connections
Pre-sel. Gas
Pre-sel. Oil
Return signal motor
protection contact
Burner reset
Burner on
ext. control
contact
Start release oil
Residual oil immediate
start
Start release Gas
Gas operation
Oil operation
Legend:
T1 Ignition unit
FE Earth connection
Y7 Magnetic coupling
F10 Air pressure switch
T2 Control transformer
On multi-stage
light oil burners
size 30 - 50
On modulating
light oil burners
sizes 30 - 70
Legend: Legend:
15
16
4
+24V
Start frequency converter
Lockout frequency converter
Setpoint
Earth
Screen
Connection
frequency converter
brown
blue
black
Connection control panel
External signalling pressure switch (optional)
Legend:
17
18
O2 sensor
Mains voltage
4
O2 Module
Legend:
LOAD
3 Wire-PNP
X63
OUTPUT
0 4-20mA
PE X6-03 X6-02 X6-01 X7-03 X7-02 X7-01 PE
Reserve
P
FE
L
L
L
L
L
L
L
N
N
N
N
min
X70
N
PE
PE
PE
PE
PE
FE 0
X5-01
Start
Start
X8-03
Usensor 4-20mA
H0-Start
INPUT
2 Wire PE L
Pulse-IN 0-10V SET POINT
V2
V3
P
SV
M
3 Wire-PNP min
X62
PE
0
X5-02
OIL GAS OIL
X71
L N
FE FE
ON/OFF V1
X8-02
Usensor 0
2 Wire 3 L
Pulse-IN 4-20mA
X5-03
INPUT
3 Wire-PNP 2 OIL L
0 0-10V
TEMP./PRES.
X72
X8-01
L GAS L
X61
FE
Start-OUT
min.
P
INT L
12-24VDC Alarm in
TEMP.
max.
P
GAS
0/4-20mA Setpoint OUT
Pt100
LT
X9-03
P
OIL
Pt/Ni1000
(CPI)
X60
X4-01
L
X73
FE PE
RESET
FREQUENCY CONVERTER
X9-02
PE IGNITION N
N V1 L
X4-02
L V2 L
FE
X9-01
P
PE PV L
12VAC2
N SV L
M
X4-03
TRAFO
L (START)
X52
12VAC1
X10-03
ION
FSV/QRI
PE
BUS
Anschlüsse
FLAME
L MOTOR
W-FM
L GND
X10-02
L ALARM
Power QRI CANL
Elektroanschluss
QRB CANH
L
L 12VAC2
FLANGE LINE
N 12VAC1
G0 Shield
X10-01
SAFETY 12VAC
G GND
L LOOP
CANL
PE
CANH
X3-04
L LINE
VOLTAGE 12VAC2
N
12VAC1
X50
Shield
BUS
19
5 Preparation for commissioning
5.1 Safety note
Check installation
All installation work must be completed and
checked prior to commissioning. The burner
must be mounted on the appliance, ready for
operation and all control and safety devices
DANGER must be connected correctly.
20
5
5.2 Preparation on the burner and the frequency converter
Burner
Check setting on burner, vent fuel lines and connect
measuring instruments.
If the burner is fitted with a moving mixing head, this should
be checked for freedom of movement.
21
5
5.3 Preparation on the combustion manager
1. Burner OFF Burner Off
To be able to carry out the following steps it is necessary
to set the burner to OFF in menu Manual Operation. Manual Operation ➩ Ch 9.4
Auto/Manual/Off
Auto/Manual/ Off
Curr: Automatic
New: Burner Off
1
W-FM 200 only when used with frequency converter
or O2 Module
22
5
5. Check O2 sensor temperature 1 Check O2 sensor temperature
The O2 sensor requires an internal operating temperature ➩ Kap 9.12.2
of 700° C ±(15°C). If the sensor has been connected Param + Display
incorrectly, this can lead to overheating and thus damage O2 module
of the sensor. If the sensor temperature exceeds 750° C, Displayed values
the sensor should be isolated and the electrical QGO SensorTemp
connection should be checked. If the operating QGO HeatingLoad
temperature is not achieved, the combustion manager
initiates a start prevention (Ch 9.7.1)
1
W-FM 200 only when used with frequency converter
or O2 Module
23
6 Commissioning - modulating
6.1 Set fuel and load limits on W-FM
Select fuel (only on dual fuel burners) Select fuel
Select the required fuel using the external fuel selection
switch. If an external fuel selection switch is not available, Operation ➩ Ch. 9.3
fuel selection is made using the ABE or BMS. Fuel
Fuel selection or:
Note The external fuel selection switch takes priority. That Fuel selection Fuel selection
means the commissioning can only be carried out Curr: Oil switch on Oil
with the fuel set at this switch. New: Gas
24
6
6.2 Commissioning the burner
6.2.1 Set mixing pressure for ignition
Set Program stop 36 Program stop 36: Ignition position without ignition
Prior to the first ignition trial, the program stop must be set
to 36 IntionPos. After burner start the burner runs to the RatioControl ➩ Ch. 9.6.1
ignition position without actual ignition occurring. ProgramStop
ProgramStop
Note In its delivered condition the program stop has Curr: 36 IgnitionPos
already been factory pre-set to 36. New: 36 IgnitionPos
Open manual fuel shut off devices and the burner is Burner On
ready to start
After the fuel shut off devices have been opened the RatioControl ➩ Ch. 9.4
burner should be started in manual operation. Auto/Manual/Off
Auto/Manual/Off
Note For burner start all safety devices, pressure and Curr: Burner Off
temperature controllers should be in operating New: Burner ON
position. Ensure sufficient heat requirement for the
duration of the commissioning procedures.
Set ignition positions Ignition positions (example gas operation 3LN multiflam®)
Set the ignition positions whilst observing the mixing
pressure. RatioControl ➩ Ch. 9.6.1
The speed during ignition should not be less than 80% for GasSettings
oil and 70% for gas (only when using a frequency SpecialPositions
converter / W-FM200). IgnitionPos
If the measured mixing pressure is too high, this can be IgnitionPosGas IgnitionPosGas
adjusted by reducing the air damper position. IgnitionPosAir Curr: 10.5°
IgnitionPosAux New: 15°
The relevant ignition pre-settings should be taken from the IgnitionPosFC
installation and operating instructions of the burner or its
test data sheet. IgnitionPosAir
Curr: 13°
Note The auxiliary motor position on 3LN burners New: 10°
(multiflam®) in ignition position and during burner
operation must be a minimum of 18°.
IgnitionPosAux
Curr: 18°
New: 19°
IgnitionPosFC
Curr: 100%
New: 70%
25
6
6.2.2 Burner ignition
Set program stop 52 Program stop 52: ignition after safety time
To ignite the burner the program stop should be set from
36 to 52. Fuel is released following pre-ignition. The SpecialPositions ➩ Ch. 9.6.1
motors remain in the ignition positions setting. ProgramStop
ProgramStop
Curr: 36 IgnitionPos
New: 52 Interv 2
26
6
6.2.3 Set load point 1
Deactivate program stop Deactivate program stop
To continue with commissioning the program stop has to
be deactivated. If the program stop is not deactivated, the RatioControl ➩ Ch. 9.6.1
burner remains in the position set and setting of additional ProgramStop
load points is not possible. ProgramStop
Curr: 52 Interv 2
New: deactivated
Set load point 1 Take over Ignition load point as load point 1
In Setting Oil, the first load point has been factory
pre-programme. Setting Gas ➩ Ch. 9.6.1
If the first load point has been deleted, the ignition load CurveParam
values will be taken over automatically as the first load Point Load :15.0
P Point Load :15.0
point just as with Setting Gas. Burn:15.0 : 1 Burn :15.0
In both cases the values should be matched and a ManualAir :10.0 O2 Air :10.0
combustion analysis should be carried out. Aux1 :19.0 4.9 Aux1 :19.0
FC :70.0 FC :70.0
At the first load point the fuel dependent minimum speed1 Change load point 1
should be aimed for whilst observing the combustion ➩ Ch. 9.6.1
quality and flame stability. Point Load: 10.5
Point I Point
Procedure: : 1 c
Change?
1. Drive up the air damper stepping motor until a residual Point Load:15.0 Point Load :15.0
O2 content in the flue gas of max. 8% has been 1 Burn:15.0 1 Burn:15.0
achieved (on 3LN burners multiflam® max. 7% residual O2 A
Air :10.0 O2 Air :223.6
O2 content in the flue gas). 4.9 Aux1 :19.0 4.9 Aux1 :19.0
FC :70.0 FC 50.2
:5
2. Reduce speed1 (not below minimum speed). To
achieve minimum speed it may be necessary to repeat
steps 1 and 2. esc
Point
save- >ENTER
3. Carry out combustion analysis and if necessary delete- >ESC
optimise combustion by adjusting the air damper
position.
Gas 50 % approx 25 Hz
1
W-FM 200 only when used with frequency converter
27
6
6.2.4 Start full load
Drive to full load via intermediate load points Increase load manually
Starting from the first load point, drive to full load via the
intermediate load points. Point Load:15.0 ➩ Ch. 9.6.1
Burn :15.0
Procedure: aanual Air :23.6
m
1. Set cursor to Manual and press <ENTER>. Aux1 :19.0
esc
Point
Save- >ENTER
enter->ESC
28
6
6.2.5 Optimising full load
Optimising full load
In the last load point (load = 100%) the exact fuel quantity
throughput for the required full load should be set.
Procedure:
1. Set fuel throughput
Optimising full load
Gas: At 65° to 70° gas butterfly setting, determine ➩ Ch. 9.6.1
gas throughput and adjust using the setting Point Load :100
screw on the pressure controller. 5 Burn 68.7
:6
O2 Air :67.8
Oil: Set pump pressure required, determine oil 4.5 Aux1 :78.5
throughput and adjust using stepping motor
setting of the oil controller (see burner test data
sheet: Indicator setting oil controller).
29
6
6.2.6 Re-define intermediate load points
Re-define load point 1 Drive to load point 1 and optimise combustion
To later allow O2 trim across the whole ratings range, point
1 must be a minimum 30% below the required partial load Point Load :100
(only when using an O2 module / W-FM 200). :5 Burn:68.7
O2 Air:76.2
Procedure: 3.8 Aux1 :78.2
1. Select point 1 with dial knob, press <ENTER>, confirm
Change point with <ENTER>, point 1 is started.
2. Check combustion quality, and optimise if necessary. Point Load :15.0 Point Point
Drive to combustion limit, note down and set excess air :1 Burn:15.0 : 1 c
vhange?
required for combustion limit. O2 Air :23.6 löschen?
Point Load:15.0
Excess air: • without O2 trim approx. 15% to 20% 6.4 Aux1 :19.0 11.9
: 1 Burn:1
• with O2 trim approx. 20% to 25% O2 Air :2 22.2
6.3 Aux: 18.6
Please observe the minimum speed and the mixing FC 50.0
:5
pressure required.
Procedure;
Select point 2 with dial knob, press <ENTER>, confirm
“Delete point” with <ENTER>, point 2 is deleted and Point Load:19.8 Point Point
the setting values for the next intermediate load point : 2 Burn :19.3 : 2 change?
below point 2 appear automatically. O2 Air :25.5 Manual d
lelete?
Repeat procedure, until full load settings appear under 5.9 Aux1 :23.2 Point Load :449.6
point 2. : 2 Burn: 35.9
Do not delete the full load point (Load: 100) and Manual Air: 47.3
point 1. 47.1 Aux1 :444.2
Check:
Select point 3 with dial knob. If all intermediate load
points have been deleted, no values are defined in
point 3 and the following display is shown.
Point Load: 100
:2 Burn: 68.7
Point Load :XXXX O2 Air :76.2
: 3 Burn: XXXX 3.8 Aux1 :78.2
Manual Air :XXXX
Aux1 :XXXX
30
6
Set new intermediate load points and carry out ratings Reduce rating and optimise combustion
distribution in percentages
For burner operation 5 load points are required, this means Point Load: 100 ➩ Ch. 9.6.1
at least 3 intermediate load points must be set. Burn :68.7
Depending on the installation, more intermediate load Hanual Air :76.2
M
points may be required (maximum 15 load points). Aux1 :78.2
P
Point Load :89.7
5. Leave point using <ESC> and save with <ENTER>.
Burn :62.0
ManualAir :68.8
6. Repeat procedure for all curve points.
Aux1 :70.7
FC :84.2
Gas:
305 m3/h
Rating [%] = • 100 = 89.7 %
340 m3/h
Oil:
260 kg/h
Rating [%] = • 100 = 89.7 %
290 kg/h
Point .
Load:90.0 Punkt Load 89.7
:8
: 3 Burn:62.0 : 3 Burn :62.0
O2 Air :68.8 O2 Air :68.8
4.0 Aux1 :70.7 4.0 Aux1 :70.7
31
6
6.3 O2 functions modulating
The settings for the O2 trim control must only be carried
out if a W-FM 200 with O2 trim control is to be used.
Determine O2 value of combustion limit and note it: Determine combustion limit
1. Select the point to be set using the dial knob and
confirm with <ENTER>. Point:1
: 13.9% ➩ Ch. 9.7.1
:9
Point:9 100%
2. Select P-Air manual using dial knob and confirm Point:9 100% Point:9 100%
with <ENTER>. 02-Setpoint: 3.8 02-Setpoint: 0.7
P-AirHand: 0.0. 10.4 .
P-AirMan:1
3. Turn dial knob to the right. The air rating is reduced on
the curve flow line in relation to the ratings setting of
P-Air manual. The fuel quantity throughput remains
unchanged.
Reduce air rating until the combustion limit (CO or O2 graph
soot) has been reached. 8
5
5. Enter O2 min value in the graph on the right.
4
3
2
1
0
0 10 20 30 40 50 60 70 80 90 100
32
6
6.3.2 Set O2 trim
For subsequent O2 trim settings, a standardisation has to O2 trim
be carried out at each point.
Param + Display ➩ Ch. 9.7.1
Procedure: O2Ctlr/Guard
1. Select point to be set using the dial knob and confirm Setting ...
with <ENTER>. O2 trim
min. 680°C 5
O2 S
4 etpo
int
3 O2 G
uard
2
1
T+273
QB · L · λ 0
0 10 20 30 40 50 60 70 80 90 100
273
v= Burner load [%]
d2 · 0.785 · 3600
33
6
6.3.3 Set O2 regulating functions
The O2 trim control function is set using OptgMode. O2 operating mode
O2 controller
The O2 controller and O2 guard are active.
Start-up only when the operating temperature of the
sensor has been reached.
If the O2 guard reacts, or if an error is detected during
measuring, lockout occurs, if there is no possibility of
repetition.
conAutoDeact
The O2 controller and O2 guard are active.
Start-up before operating temperature of the sensor has
been reached.
If the O2 guard reacts, or if an error is detected during
measuring the function auto deact is initiated.
34
6
6.3.4 Check and optimise O2 trim
Check O2 trim
Procedure:
1. Re-start burner in automatic operation. The start
behaviour can be checked again.
35
6
6.3.5 Optimise O2 trim
Depending on site specific requirements it may be O2 trim parameters
necessary to adjust the O2 trim parameters in the HE level.
Param + Display ➩ Ch. 9.7.1
O2Ctlr/Guard
Settings ...
ControlParams
Increase LoadCtrlSuspend
Reduce FilterTmeLoad
O2Offset increase
36
6
6.4 Concluding work following commissioning
6.4.1 Set ratings range and flue gas temperature limit values
Flue gas temperature limit value Set flue gas temperature limit values
If the limit value is exceeded the warning “Flue gas
temperature too high” is given. A prerequisite for this is a Param + Display ➩ Ch. 9.12.1
configured flue gas temperature sensor on the O2 module O2 Module
(only W-FM 200). Configuration
The limit value should be set approx. 20% above the flue MaxTempFlueGas
gas temperature at nominal load.
DANGER
37
7 Commissioning multi-stage
Prior to commissioning the preparations necessary for
commissioning (Ch. 5) must be completed.
38
7
7.2 Adjust burner
7.2.1 Preset curve parameter
For commissioning the fan speed1 and air damper setting Call up stepping motor positions
of each operating point as well as the On/Off switch points ➩ Ch. 9.6.1
must be checked and if necessary adjusted. Param + Display
Ratio
Procedure; Oil setting
1. Call up stepping motor positions. Curve parameter
Curve setting
2. Select option Without start Stepping motor
positions
3. Call up operating, the on and off stage switch points With start
one by one using the dial knob and compare air damper Without start
setting (air stepping motor) and fan speed1 (FC) with
table values. If they deviate, overwrite the parameter
by Activate option ‘without start’
• calling up operating, on and off switch points with
<ENTER>, ➩ Ch. 9.6.1
• selecting parameter using dial knob and confirming Stepping motor Point Air :40.0
with <ENTER>, positions ::BS1 FC :80.0
• inputting parameter value (dial knob +/-) and saving With start O2
with <ENTER>. W
Without start xxxx
• continue procedure until all parameters are the same
as the table values.
Call up operating, on and off switch points
1
Two Air damper [°<] Speed [%] ➩ Kap 9.6.1
operating stages Air PC Point Air :40.0 Point Air :40.0
::BS1 FC :80.0 ES2 FC
::E :90.0
Operating point BS1 40 80* O2 O2
Switch on point ES2 xxxx xxxx
Switch off point AS2 70 100
Operating point BS2
Overwrite parameters
* Valid only if the installation and operating manual of the Point Air :40.0
burner does not indicate a different value. :ES2 FFC :80.0 save values
O2
xxxx
4. Exit level with <ESC>.
Exit level
1
only W-FM 200 in connection with frequency
converter 39
7
7.2.2 Burner ignition
Set programme stop 36 Programme stop 36: Ignition position without ignition
Prior to first ignition the programme stop has to be set to
36 IgnitionPos. After burner start, the burner then SpecialPositions ➩ Ch. 9.6.1
drives to ignition position without igniting (with long pre- ProgramStop
ignition, ignition is carried out without fuel release). ProgramStop
Curr: 36 IgnPos
Note In its delivered condition the programme stop has New: 36 IgnPos
already been factory pre-set to 36.
Setting ignition position Set air damper fan speed and ignition position
The fan speed and the ignition position of the air damper
should be set whilst observing the mixing pressure. The Ratio ➩ Ch. 9.6.1
ignition speed1 should not be below 80%. Depending on Oil setting
the burner, the mixing pressure for ignition should be SpecialPositions
between 3 and 5 mbar. The mixing pressure can be IgnitionPos * The IgnitionPosOil does
adjusted with the air damper and diffuser positions. not need to be set for
IgnPosOil* multi-stage operation, as
It is recommended to note down the IgnPos values set. IgnPosAir no oil throughput
IgnPosAux regulator valve and thus
IgnPosFC no stepping motor is
fitted.
Set programme stop 44 Program stop 44: ignition position after safety time
To be able to ignite the burner the programme stop has to
be set from 36 to 44. Once the pre-ignition time has SpecialPositions ➩ Ch. 9.6.1
elapsed fuel is released. The stepping motors remain in the Curvenpater
ProgramStop
ignition position setting. Lostgrenzen
Igndpos rcksetz
ProgramStop
Curr: 36 IgnPos
New: 44 Interv 1
1
only W-FM200 in connection with frequency
40 converter
7
7.2.3 Start full load
Activate option “With start” Activate option “With start”
In stepping motor positions activate the option “With
start” by pressing <ENTER>. CurveParams ➩ Ch. 9.6.1
Lastgrenzen
Curve Settings
Stepping motor Point Air :40.0
Note Operation of the switch off points should be positions ::BS1 FC :80.0
avoided during commissioning, as this can lead to WMith start O2
excessive air deficiency. Without start xxxx
Pre-set operating point S1 Pre-set operating point and set switch on point
1. Select operating point BS1using the dial knob and
confirm with <ENTER>. Point Air :40.0 ➩ Ch. 9.6.1
2. Call up parameter values using the dial knob and ::BS1 FC :80.0
<ENTER> and adjust operating point BS1 whilst O2
observing the combustion quality. xxxx
1
only W-FM200 in connection with frequency converter
41
7
7.2.4 Set switch off point(s)
Change over to option “Without start” Activate option “Without start”
Exit option With start in stepping motor positions with
<ESC> and re-enter Curve setting to select option Curve Settings ➩ Ch. 9.6.1
Without start and activate with <ENTER>. Stepping motor Point Air :33.0
positions ::BS1 FC :63.0
With start O2
W
Without start xxxx
esc
42
7
7.2.6 Check start behaviour
Procedure: ProgramStop
1. Set ProgramStop to phase 44.
SpecialPositions ➩ Ch. 9.6.1
2. Re-start burner in manual operation. ProgramStop
ProgramStop
3. Check start behaviour and if necessary correct ignition Curr: deactivated
load setting. New: 44 Interv 1
Note If the ignition load setting has been altered, the start
behaviour has to be rechecked.
Restart burner
4. Deactivate programme stop.
Auto/Maual/Off ➩ Ch. 9.4
Auto/Manual/Off
Curr: Burner Off
New: Burner Off
Auto/Manual/Off
Curr: Burner On
New: Burner On
43
8 Load controller
The controller has to be configured relevant to the
installation to ensure safe and reliable load control. On the
W-FM100 the load controller is optional.
44
8
8.2 Configuring sensors
Sensors used Configuring sensors
Sensor selection has to be configured depending on
whether the actual value is determined by a temperature Param + Display ➩ Ch. 9.8.4
sensor (input X60) or a temperature or pressure sensor Load Controller
(input X61). Configuration
Sensor selection
PT 100 PT 100 sensor on terminal X60:1/2/4, Sensor selection
temperature limit function is active. Curr: PT 100
New: PT 100
PT 1000 PT 1000 sensor on terminal X60:3/4,
temperature limit function is active.
45
8
8.3 Setpoints (external)
External load / setpoint signal Define analogue signal at input X62
If a load controller is connected to input X62
(Ext LC X62), or if the setpoint signal for the internal load Param + Display ➩ Ch. 9.8.4
controller (Int LC X62) is given by this input, the type of LoadController
analogue signal must be defined. Configuration
Ext Inp X62 U/I
Ext LC X62 (load signal) : 4 to 20 mA or 2 to 10 V Ext Inp X62 U/I
Curr: 4 ... 20 mA
Int LC X62 (setpoint signal) : 4 to 20 mA or 0 to 10 V New: 0 ... 10V
Calculation:
80°C
• 100 ≈ 53.3%
150°C
46
8
8.4 Setpoints (internal)
Internal setpoints (W1 / W2) Internal setpoints (W1 / W2)
Two internal setpoints can be stipulated.
Switchover is with potential free contact on the terminals Param + Display ➩ Ch. 9.8.1
X62:1/2. LoadController
The setpoints cannot be set above the temperature limit ControlParam
value already entered. ContParamSelect
Setpoint W1
Setpoint W2
Setpoint W1
Curr: 80°C
New: 70°C
47
8
8.5 Modulating load control
8.5.1 Parametering internal load control
Adaption Filter time
During adaption, the internal load controller recognises the
control section and calculates the PID parameter. Param + Display ➩ Ch. 9.8.1
Adaption can be started in manual or automatic operation LoadController
independent of the operating phase (standby or ControlParam
operation). SW-FilterTmeCon
During adaption, the parameter SW-FilterTmeCon should SW-FilterTmeCon
be between 2 and 4 seconds. If the value selected is too Curr: 3 s
high, this can stop the adaption or lead to insufficient New: 3 s
control parameters.
• Start-up (Heating)
The direction of the actual value during the heat up
phase is determined.
Adaption complete
• Calculation of control parameter (Adaption ok)
Using the measured values of the stabilising phase, Adaption ok Adaption ok
the heat input and reaction times and the PID P-content (Xp) P-content (Tu)
parameter are calculated. 11.2% 53s
The values calculated can be called up using the dial continue with <> continue with <>
knob.
49
8
8.6 Multi-stage load control
Switching differentials Switching differentials
The switching differentials are formed in percentages
depending on the current setpoint. Param + Display ➩ Ch. 9.8.1
LoadController
SD_SStage1On: ControlParam
At this switching differential the control circuit is closed SD_Stage1On SD_Stage1On
and the burner is switched on. SD_Stage1Off Curr: 1.0%
SD_Stage2Off New: 1.0%
SD_SStage1Off: SD_Stage3Off
As this switching differential is exceeded the control circuit
is opened and the burner is switched off.
SD_SStage2Off:
As this switching differential is exceeded the system is
switched from stage 2 to stage 1.
SD_SStage3Off:
As this switching differential is exceeded the system is
switched from stage 3 to stage 2.
ThresholdStage3On:
Switch criteria for the release of third stage.
50
8
8.7 Cold start function
Activate cold start function Activate cold start function
In order to avoid the appliance operating at its maximum
loading before the required minimum appliance Param + Display ➩ Ch. 9.8.3
temperature has been reached, the cold start function has LoadControl
to be activated. Cold start On Cold start On
Curr: deactivated
New: activate
51
9 Parameters and functions
9.1 Menu structure (ABE)
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
OperationalStat NornalOperation
esc
Status/Reset
FaultHistory
LockoutHistory
Alarm Act/deact
LoadLimitAB ABmaxLoadMod
esc
ABmaxLoad St
Fuel CurrentFuel
esc
FuelSelect
SetClock Date
esc
TimeOfDay
Weekday
HoursRun GasFiring
esc
OilStage1/Mod
OiStage2
OilStage3
TotalHoursreset
TotalHours
SystemOnPower
StartCounter GasStartCount
esc
OilStartCount
TotalStartCountR
TotalstartCount
LockoutCounter
BurnerID
OptgModeSelect InterfacePC
esc
GatewayBASon
GatewayBASoff
Type of Gateway
O2 trim activate
only W-FM 200
End user: Access without password
Engineer: Access with HE password
52
9
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5
ManualOperation SetLoad
esc
Auto/Manual/Off
TimesStartup2 Interval1Gas
esc
Interval1Oil
Interval2Gas
Interval2Oil
TimesShutdown MaxTmeLowFire
esc
Postpurge
Postpurge1Gas
Postpurge1Oil
Postpurge3Gas
Postpurge3Oil
TimesGeneral AlarmDelay
esc
DelayStartPrev
Postpurge_lockout
ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers
SW Version
CurveParams
LoadLimits MinLLoad_Gas
esc
MaxLLoad_Gas
LoadLimits MinLoadOil
esc
MaxLoadOil
Auto/Manual/Off
Times OperatRampMod
esc
OperatRampStage
DriveRamp
ShutdownBehav
ProgramStop
O2CtrlThreshold
PLoadAdaptPtNo
Type of fuel
O2-Offset Gas
LoadContLock
FilterTimeLoad
OilSettings OptgMode
esc esc
O2 Control
O2 Guard
O2CtrlThreshold
PLoadAdaptPtNo
Type of fuel
O2-Offset Oil
LoadContLock
FilterTimeLoad
MinActuatorStep
SW_FilterTmeCon
SetpointW1
SetpointW2
SD_ModOn
SD_ModOff
SD_Stage1On
SD_Stage1Off
SD_Stage2Off
SD_Stage3Off
ThreshStage2On
ThreshStage3On
TempLimiter TL_ThreshOff
esc
TL_SD_On
ColdStart ColdStartOn
esc
ThresholdOn
StageLoad
StageSetp_Mod
StageSetp_Stage
MaxTmeMod
MaxTmeStage
ThresholdOff
AdditionalSens
TempAddSensor
Setp AddSensor
Release Stages
Configuration LC_OptgMode
esc
Sensor Select
MeasureRangePtNi
var.Meas.Ran.PtNI
Ext Inp X61 U/I
MRange TempSens
MRange PressSens
Ext Inp X62 U/I
Ext MinSetpoint
Ext MaxSetpoint
esc
AnalogueOutput Select output value
Current Mod 0/4ma
Scal 20mA Proc
Scal 20mA Temp
Scal 20mA Press
Scal 20mA Angle
Scaling 0/4mA
Adaption StartAdaption
esc
AdaptionLoad
SW Version
Language
DateFormat
PhysicalUnits UnitTemperature
esc
UnitPressure
eBus Address
esc
SendCycleBU
ModBus Address
esc
Baudrate
Parity
Timeout
Local/Remote
Remote Mode
W3
Display Contrast
ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers
SW Version
5 Auxiliary ASN
esc
Actuator 2 ProductionDate
(only on W-FM 200) SerialNumber
ParamSet Code
ParamSet Vers
6 Auxiliary ASN
esc
Actuator 3 ProductionDate
(only on W-FM 200) SerialNumber
ParamSet Code
ParamSet Vers
SW Version 1 AirActuator
esc
2 GasActuat(Oil)
3 OilActuator
4 AuxActuator
5 AuxActuator2
6 AuxActuator3
ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers
SW Version
O2 module SW Version
Konfiguration O2 Sensor
esc esc esc
(only W-FM 200) SupAirTempSens
FlueGasTempSens
MaxTempFlGasGas
MaxTempFlGasOil
ProductID ASN
esc
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers
SW Version
TempLimiter TL_Thresh_Off
esc
TL_SD_On
Sensor Select
MeasureRangePtNi
O2Ctrl/LimitrGas
O2Ctrl/LimitrOil
LR AnalogueOutput
Max.perm.Potidiff
HoursRun GasFiring
esc esc
OilStage1/Mod
OilStage2
OilStage3
TotalHoursReset
TotalHours
SystemOnPower
Reset GasFiring
esc
OilStage1/Mod
OilStage2
OilStage3
TotalHoursReset
StartCounter GasStartCount
esc
OilStartCount
TotalStartCountR
TotalStartCount
Reset GasStartCount
esc
OilStartCount
TotalStartCountR
Load_SW_from_PC
NormalOperation
Display of:
• Phases during start up
• Setpoints and actual values
• Current burner rating
• Flame signal
• By pressing ENTER the stepping motor positions,
speed and the O2 value can be displayed.
Status/Reset
FaultHistory
LockoutHistroy
Alarm act/deact
62
9
9.3 Operation
Boiler Setpoint
Two setpoints (W1/W2) can be entered for the internal Setpoint switchover W1/W2
load controller. The setpoints cannot be set using the
current guarding temperature (optional on W-FM 100).
X62
potential free contact at input X62:1/2 Activation 2
2nd setpoint W2
1
LoadLimitAB
Fuel
Fuel determination with “CurrentFuel” (read only) External fuel selection switch
Date/TimeOfDay LockoutCounter
In this menu the date, time and weekday are shown and Total number of lockouts since commissioning (cannot be
can be adjusted if required. reset).
HoursRun is read only. Reset of the individual counters is Display of the current efficiency during burner operation
only possible in level Param & Display in menu (see Ch. 9.7.1).
HoursRun (see Ch. 9.15).
BurnerID
StartCounter Here, the burner specific serial number is saved at the
factory.
The burner starts are read only. Reset of the individual start Using the serial number it is possible to replace a failed
counters is only possible in level Param & Display in unit with one that has the same factory pre-settings.
menu StartCounter (see Ch. 9.16). BurnerID also acts as copy protection; this means burner
specific data in the memory of the ABE cannot be
transferred to another W-FM.
Fuel meter
63
9
OptgModeSelect
Interface PC
The ABE acts as PC interface. The W-FM is set using a
PC and software.
Gateway BMS on
Access by building management (BMS) to the W-FM
using the ABE. The ABE remains functioning.
GatewayBMS off
Operation without building management. Access to the
W-FM only with ABE.
Type of Gateway
Stipulated by the relevant bus protocol (eBus or Modbus).
0-100%
Load started in manual operation (burner On). If not
specified, partial load is started.
S1-S3
Highest stage which can be started in manual operation
(burner On).
Automatic
The burner is regulated by an external or the internal load
controller to setpoint. Regulation can be two stage, three
stage or modulating.
Manual On
The burner starts and is switched of by the external or
internal temperature guard. Prerequisite is a closed control
circuit or bridge at input X5-03 terminals 1 and 4.
Manual Off
Burner switches off. Even if the switch on hysteresis is not
reached, the burner remains off.
64
9
9.5 Burner control
Depending on the password entry the relevant parameter
for the operator or the engineer is displayed.
9.5.1 Times
Time start up 2
Time shutdown
MaxTime_LowFire
If the burner is shut down, or if fuel change over is initiated,
the shutdown program starts at the latest after completion
of this time. If low fire is reached prior to this time elapsing,
the shutdown program starts when low fire is reached.
Postpurge time 1
Duration of postpurge in phase 74. Once this time has
elapsed, the auxiliary actuator 3 (FGR) drives to postpurge
position and the air pressure switch of the flue gas
recirculation on termonal X4-01:3 is interrogated.
Postpurge time 3
Duration of postpurge.
65
9
9.5.2 Configuration
During normal start the fan is switched off and start-up PS-Relief_Inv
begins in phase 10. In phase 21 and Phase 79, the pressure switch relief
valve on output X4-03:2/3 is de-energised to test the air
During direct start the fan continues to run and start-up pressure switch.
jumps from phase 79 to phase 24.
This shortened start-up procedure is only possible with an
air pressure switch in conjunction with a pressure switch ConfigFlame Sensor
relief valve at output X4-03:2/3. Parameter Start/PS-
Valve in menu Config In-/Outp must be set to PS- Flame signal
RelVal Inv. Display of the current signal at the flame sensor.
66
9
9.5.3 Product ID and software version
Product ID
SW version
67
9
9.6 Ratio control
The setting parameters in menu “RatioControl” can only be
accessed with the password for the engineer.
Special positions
The special positions are fuel specific and can be entered Ignition positions
individually for oil and gas. This parameter is used to set the stepping motor positions
and speed for ignition. Ignition (phase 38) is only carried
Home positions out when all motors have reached their ignition positions.
This parameter is used to set the stepping motor positions
or speed control in Standby.
HomePosFC = 0 Frequency converter deactivated IIgnPosGas : Ignition must be carried out with excess
(frequency = 0Hz). air. The gas pressure has to be set to the
HomePosFC > 0 Start release frequency converter instructions given in the installation and
Fan motor starts with relevant operating instructions of the burner.
speed set (in %). Gas butterfly opening during ignition:
– with ignition pilot 10 to 20°<)
Pre-purge positions – without ignition pilot approx. 10°<)
This parameter is used to set the air determining stepping
motor positions or the motor speed for pre-purge. IgnPosOil : Position of the oil controller. The ignition
Pre-purge only starts once all motors have reached their position for oil can be found on the burner
pre-purge positions. test data sheet. The indicator position
given is the same as the data given for the
Post-purge positions degree of angle. If an oil controller is not
The parameter PostpurgePos allows separate setting of fitted (multi-stage) the ignition position of
the individual stepping motors. oil has no influence.
Pre-set values have been entered at the factory. Generally,
setting values are required, which ensure sufficient cooling IgnPosAir : When the fuel is ignited a pressure
of the mixing head whilst still maintaining adequate heat in increase occurs in the combustion
the heat exchanger. chamber. The burner must create a
resistance against this to avoid a back
Program stop flow of flue gases. Therefore ignition with
In menu, ProgramStop the start of the burner can be open air damper and matching of the
stopped at 7 defined positions and adjustments to the mixing pressure by speed only is not
burner settings can be made. possible. A setting of approx. 20°<) for the
air damper is recommended. The actual
24 PrePurgPos : Nominal load pre-purge position air damper opening will be determined
32 PreP FGR : Nominal load pre-purge for FGR later by the mixing pressure measurement.
36 IgnitPos : Ignition position without ignition
44 Interv 1 : End of first safety time IgnPosAux : The position of the adjustable mixing head
52 Interv 2 : End of second safety time can be found in the installation and
72 PostPPos : Air damper in post-purge position operating instructions of the burner. If an
(shutdown) adjustable mixing head is not fitted, the
76 PostPFGR : Air damper in post-purge position fixed sleeve or the adjustable flame head
for FGR must be pre-set to the operating points in
the capacity graph.
Reset ignition position
The values of ignition position for oil, air and auxiliary motor IgnPosAux2 : Auxiliary motors for special applications.
are deleted, existing programming points remain. IgnPosAux3 : For example: Second fuel Kerosene or
The burner without ignition position data can no longer Liquid Petroleum Gas, flue gas damper
start. etc. (only W-FM 200)
Note: In its delivered condition a provisional ignition IgnPosFC : The ignition speed depends on the fuel
position has been set, for fuel oil also the program and should not be below 70% for gas and
point P1 (these values are needed for burner 80% for oil. If the mixing pressure for
testing). ignition is outside of the limit, correction
To ensure that the burner does not start at the must be made using the air damper or
installation, a program has been set in phase 36. mixing head position (only in connection
with a frequency converter / W-FM 200).
68
9
Curve parameters (modulating)
Speed %
W-FM suggests the ignition position as load point 1. 80 90
10 10
Once the new load point has been saved, a new reference P1
line is created. The reference lines are drawn between the 0 0
previous and the new load point and are further extra- 0 10 20 30 40 50 60 70 80 90 100
polated. in manual load increase, the stepping motors are Rating %
now driven on the basis of the new reference lines.
This procedure is repeated until full load has been Curve lines after saving P2
reached.
90 100
Motor positions °<)
Speed %
80 90
80
70
4 70
60
60
50
50
40
40
30 3
30
20 2
20
1 P2
10 10
P1
0 0
0 10 20 30 40 50 60 70 80 90 100
Rating %
69
9
Optimising full load Drive to full load and optimise
The required nominal load in full load has to be set with the
90 100
fuel throughput.
Speed %
80 90
Gas: Due to the control characteristic of the gas butterfly
this should be set to 65° to 70°. The gas throughput 70
80
has to be determined and adjusted using the setting
4 70
screw on the pressure controller. 60
P5
60
Oil: Set required pump pressure in accordance with the 50
information given in the installation and operating P4 50
instructions or the burner test data sheet. Determine 40
oil throughput and adjust using the setting of the oil 40
controller’s stepping motor. 30 3
30
P3
2
Determine combustion limit at full load and set excess air. 20
20
1 P2
Excess air: approx. 15 to 20% 10 10
P1
0 0
For the air quantity setting this means, that the speed is set 0 10 20 30 40 50 60 70 80 90 100
to a minimum, depending on the load and the emissions, Rating %
however not below 40Hz (80%). If at all possible, the
position of the mixing head should be set for maximum
mixing energy and the air damper should be set to the
effective point. With additional O2 control, this will ensure
an effective involvement of the air damper.
Speed %
linear with the neighbouring points. 80 90
80
70
4 70
60
P4
P5 60
50
P3 50
40 P4
40
30
3 30
P2
2 P3
20
20
1 P2
10 10
P1
0 0
0 10 20 30 40 50 60 70 80 90 100
Rating %
70
9
Insert load points Enter intermediate load points
If a new load point is inserted, its number is always the
90 100
number of existing load points plus one. In setting
Speed %
“Manual” the load is set with the burner in operation to the 80 90
value at which the load point is required (recommendation:
all 10%). 70
80
Carry out combustion optimisation and once the fuel
70
throughput has been determined, carry out load 60
4
P7
apportionment. To achieve an even speed curve line, the P8 60
speed should not be adjusted during combustion 50
optimisation. 50
40
P8 40
When saving the intermediate load point, an automatic P7
“re-sorting” of the load points is carried out according to 30 P6
3 30
the load. P5
20
This means: The new point 8 now becomes point 7, 2
P4 20
P3
point 7 becomes point 8. 1
10 P2 10
P1
It is possible to optimise ratio control with up to 15 points. 0 0
0 10 20 30 40 50 60 70 80 90 100
Note: If O2 control is used, point P2 forms the minimum Rating %
O2 control load.
For loads below P2, the O2 control is deactivated 1 – Air damper
and the burner runs on the normal ratio control 2 – Fuel
curve. 3 – Mixing head
Point P1 is important for the air ratings reduction of 4 – Speed
the O2 control. This must have sufficient distance
to P2. – Manually started load points
– Saved load points
– Deleted load points
Load assignment
Once the curve points have been saved, they automatically
sort themselves according to the load assigned to them.
Current throughput
Load [%] = x 100 %
Full load throughput
Example;
Current throughput at point 7 (70%): 250m3/h
Throughput full load: 340 m3/h
250 m3/h
Load [%] = x 100 = 73.5 %
340 m3/h
71
9
Curve parameter (multi-stage)
The operating mode “multi-stage” is only possible in oil On and off switch point - 2 stage operation
operation. Depending on burner version two or three stage
operation is available. A three stage burner can also BS2
operate in two stage mode with low impact start.
With start-up
By pressing the ENTER button the point called up is
started and the motors follow the current settings made
with the dial knob.
The on and off switch points are also started, however the
valve does not yet switched at the on and off switch point.
This procedure is required to optimise the air quantity to
the fuel quantity.
Operating points
BS1: Stipulates the air quantity for fuel quantity for
stage 1 (excess air approx. 20 to 25%).
Switch on point
Only once the switch on point has been exceeded will the
solenoid valve for the next stage open. This means the
solenoid valve of the next stage remains closed at the
direct start of the point. This allows the flame stability can
be checked prior to switching to the next stage.
72
9
Load limits Load limits
Using the parameter min and max load, the burner can be
1 P15
limited fuel specific in its load range within the
programmed curve lines.
MinLoad_Gas/Oil P1
Limits the load range downwards (low fire).
The min load cannot be set below point 1 and if used with 0 100
MinLoad Gas
MaxLoad Gas
O2 control not below point 2.
MaxLoad_Gas/Oil
Limits the load range upwards (full load).
73
9
9.6.2 Times
The duration of the slowest motor across a setting section
of 90° is important for parametering the drive times.
OptgRampMod
OptgRampStage
DriveRamp
SM stopped
Post purge
HomePos
74
9
9.7 O2 control and guarding
Here, the relevant parameters for the operator or the
engineer are displayed depending on the password
entered (only W-FM 200).
Operating mode
auto deact
Is activated automatically, if the O2 control is switched off
in operating mode “RegAuto deact”.
O2 controller and guard are deactivated and ratio control
drives on the curve lines programmed. At the same time a
warning message appears in the display. Manual activation
of operating mode is not recommended.
man deact
O2 controller and guard are deactivated. The systems
drives on the parametered ration control curve lines. The
burner starts with cold sensor (only for commissioning, not
recommended for normal operation).
O2 guard
Only the O2 guard is active.
If the O2 sensor has not reached operating temperature,
start is prevented.
If the O2 guard reacts, or if a fault occurs in connection
with the O2 measurement, the O2 module or the O2 sensor,
a safety shutdown is initiated. If repetition is not possible
lockout occurs.
O2 controller
The O2 controller and guard are active. The same data
applies as for O2 guard.
ConAutodeact
The O2 controller and guard are active. Start-up is carried
out prior to the operating temperature of the O2 sensor
being reached (700°C ±15°C). Activation of the O2
control in operation is only carried out once the operating
temperature has been reached and the sensor test has
been successful.
75
9
O2 trim
Using this parameter an O2 setpoint standardisation has to
be carried out at each point.
The air determining stepping motors are driven down on
the programmed ration control curve lines in line with the
standard values given. The air load this reduced, but the
fuel quantity remains unchanged.
O2 guard
Using this parameter, an O2 limit value has to be set for O2 min limit
each point (CO/soot).
If during operation, the O2 min limit is not reached for 3,0
3 secs. this leads to either a safety shutdown or an
automatic deactivation of the O2 control / guarding 2,5
function, depending on the operating mode selected.
2,0
O2 content [%]
76
9
Control parameter
The O2 control is supported by the pre-control function. O2 control behaviour
If equal ambient conditions are present, the pre-control
calculates the air load reduction for the total load range. If O2 Currual value
O2 content [%]
the load signal changes, a setting size alteration (air) of the O2 setpoint
ratio control is carried out by the pre-control. This means,
the O2 control only has to adjust deviations in ambient
conditions (temperature, air pressure, ...).
Load [%]
exceeded, the O2 control becomes active again once the 2 3
delay time full load has elapsed.
1 Parameter LoadContLock
Using the control parameter the behaviour of the O2 2 Locked range
control can be influenced. 3 Delay time full load ( 2 x Dew full load)
4 Burner load
5 Following actual load
P Low/high fire
Proportional part of O2 control.
I Low/high fire
Integral part of O2 control.
LoadContLock
Limit value of the load difference from which the O2 control
is locked. The smaller the value, the more often the 02
control will be locked and driven to the value 02 Offset
set.
FilterTimeLoad
Lock time after which a load change in the size of the
LoadContLock can be made.
77
9
O2 control limit
For burner ratings below the set value, the O2 control is
deactivated and the system drives on the programmed
curve lines of the ratio control. If the burner rating
increases to 5% points above the control limit, the O2
control is reactivated.
PartLoadAdaptPtNo
The parameter Partial Load Adaption Point Number
determines the intermediate load point at which the Dew
Partial Load (flue gas reaction time) is calculated.
Example.:
If the O2ContLimit is between point 4 and point 5,
PartLoadAdaptPtNo should be set to 4.
Type of Fuel
To calculate the combustion efficiency the fuel currently The values
used must be set. V_Lnmin = Air volume under normal conditions at λ 1
V_afNmin = Flue gas volume wet under normal cond. λ 1
If the fuel is not available, its fuel values can be entered V_atrNmin = Flue gas volume dry under normal cond. λ 1
under FuelUseDef. are required for converting O2 wet to O2 dry
In parameter FuelUseDef the calculation values for the
combustion efficiency will be displayed. A2 = Adjustable constancies for ηF
B/1000 = Adjustable constancies for ηF
are constancies depending on the fuel.
As P Air:
A change in air density (temperature pressure) will affect
the fuel throughput.
Recommended setting for fuel Gas.
In theory:
A change in air density (temperature pressure) will not
affect the fuel throughput.
Recommended setting for fuel Oil.
78
9
LoadContLock
Limit value of the load difference from which the O2 control
is locked.
FilterTimeLoad
Lock time after which a load change in the size of the
LoadContLock can be made.
O2 Offset Gas/Oil
O2 Offset Gas / Oil
Increase of O2 content in percent points, if the O2 control
is locked during load increase via parameter
LoadContLock.
The O2 Offset ensures that the O2-MinValue is
maintained during LoadContLock .
9.7.2 Prozessdaten
The menu process data is read only:
– about the current combustion efficiency
– about the setting size of the O2 controller
– release of O2 controller (activated/deactivated)
– current load of the air determining motors
– diagnostic codes if the controller is locked
79
9
9.8 LoadController
Here, the relevant parameters for the operator or the
engineer are displayed depending on the password
entered.
On W-FM 100 the load controller is optional.
9.8.1 ControlParam
ControlParamSelect
Under (StandardParam) 5 standard parameter sets and Adapt control parameters
the adaption PID values can be accessed. Each one of
these parameter sets can be copied direct into the PID Xp too small Xp too large
memory, the existing values will be overwritten.
MinActuatorStep
The smallest possible correcting element step is used for
setting value damping.
If the difference between the new calculated setting size
and the current setting size is smaller than
MinActuatorStep, the current setting size is maintained.
SW FilterTmeCon
Using the filter time actual value fault signals, which
predominantly affect the D content, can be weakened.
However, if the filter time is too long this influences the
actual value determination and has a negative effect on the
control accuracy.
80
9
Setpoints W1/W2
Two setpoints (W1/W2) can be set for the internal load Setpoint switchover W1/W2
controller. The setpoints can not be set above the current
limit temperature.
X62
contact at input X62:1/2 Activation 2
2. setpoint 1
SD ModOn/Off
Switch difference in percent for modulating operation.
With positive SD ModOn the switch difference is above the
setpoint, with negative below.
SD Stage On/Off
Switch difference in percent for multi-stage stage
operation.
With positive SD Stage1On the switch difference is above
the setpoint, with negative below.
ThresholdStage... On
If control deviations occur an integral is created over the Switch ThresholdStage... On
time.
If the integral drops below the ThresholdStage...On Actual
the next stage is switched. This can influence the value
Setpoint
switching frequency of the individual stages.
SD_Stage
1 On
Stage 2
Q2 Q2
Stage 3
Q3
81
9
9.8.3 Cold start
Threshold On Threshold
Off
Switch on threshold in percent relating to the setpoint StepSetpoint
(W1/W2) or Setpoint AddSens. Threshold
The cold start function is started if the boiler temperature is On
below this switch on threshold at heat demand.
Actual
value
Step Load (modulating) appliance
The cold start load increases by this value, when the boiler
Cold start load modulating
temperature has reached the next setpoint step. If the
setpoint step is not reached, the cold start load is
increased after completion of the parametered
MaxTmeMod.
MaxTime MaxTmeMod
ThresholdOff Stage 1
Additional sensor
TempAddSensor
Setpoint AddSens
82
9
Release Stages
Not released:
Cold start only in the first burner stage. Stage 2 and stage
3 are locked during the cold start.
Released:
Cold start is carried out in the first burner stage. Once the
boiler temperature reaches the current cold start setpoint,
the next stage is released.
83
9
9.8.4 Configuration load controller
LC operating mode
The load controller setting (internal/external) in
SystemConfig has priority. This means that if an external
load controller has been activated in SystemConfig,
operating mode selection is not possible.
X5-03
°C
3 Stage 2 Open
4
L
int LC X62
The building management system stipulates an analogue eBus
signal as setpoint for the internal load controller. The setting Interface
range automatically matches itself to the parametered W-FM 200
measuring range of the sensor (MeasureRange PtNI).
Additionally, it is possible to limit the setpoint range both up
and down (Ext SetPoint ...).
0
2
4…20 mA
1
4 mA ➙ 0% load
20 mA ➙ 100% load
84
9
ext LC X62 External load input
The building management system stipulates an analogue Modulating Multi-stage
load signal (tab. External load input). The W-FM Analog.
converts the signal and starts the relevant motors or the signal Low fire High fire Stage 1 Stage 2 Stage 3
frequency converter.
I (mA) 4 20 5 10 15
eBus
Interface
W-FM 200
Senor selection
PT100 Sensor connection
PT 100 sensor on terminal X60:1/2/4 (three core switching)
➔ temperature limiting function is active.
Pt 100 Pt/Ni 1000
4
PT1000
X60
3
PT 1000 sensor on terminal X60:3/4
2
➔ temperature limiting function is active.
1
Ni 1000
Ni 1000 sensor on terminal X60:3/4
➔ temperature switch function is active.
PT100 PT1000
PT 100 sensor on terminal X60:1/2/4 (three core switching)
for temperature switch function.
PT1000 sensor on terminal X60:3/4 for temperature
limitng function.
PT100 Ni 1000
PT 100 sensor on terminal X60:1/2/4 (three core switching)
for temperature switch function.
Ni 1000 sensor on terminal X60:3/4 for temperature
limiting function.
4…20 mA
3
Pressure sensor at input X61 0…10 V
2
➔ no limiting function. 20V DC
1
none
No sensor connected to W-FM (i.e. external ratings input
without temperature guarding function).
85
9
Measuring range PtNi
The start of the measuring range is fixed at 0° C or 32° F
and cannot be altered.
var.Meas.R. PtNi
The start of the measuring range is fixed at 0° C or 32° F
and cannot be altered.
The end of the measuring range can be configured via this
parameter (max. 850°C / 1562°F).
86
9
Ext Input X62 U/I
If an external load or setpoint signal is switched at terminal
X62, the analogue signal has to be defined.
Upper setpoint limit required = 80° C Lower setpoint limit required = 50° C
Calculation: Calculation:
80°C 50°C
• 100 ≈ 53.3% • 100 = 12.5%
150°C 400°C
16 mA 10 V
• 80°C + 4mAOffset ≈ 12.53 mA • 50°C = 1.25 V
150°C 400°C
87
9
9.8.5 Analogue output
Load Flame
Load signal of internal load controller Flame signal
Speed FC
Setpoint speed
Scaling 0/4mA
Defines the internal value at which 0/4 mA is given at
output X63:1/2. The relative designation relates to the
values set under Current Mod 0/4mA.
88
9
9.8.6 Adaption
Start adaption
The adaption allows the load controller to automatically
identify the control section and to create the PID
parameter from the data determined. Adaption is available
for both temperature and pressure control. The adaption
can be started in manual or automatic operation. The
installation can be in operation or standby.
Adaption is not possible in multi-stage operation.
Adaption Load
With this parameter, the adaption load can be reduced by
up to 40%. This could be necessary, if the heat demand
during adaption for full load (100%) is insufficient and the
installation switches off during the adaption process.
If the adaption load is selected so low that the set
temperature is not reached this leads to interruption of the
adaption.
9.8.7 SW Version
The “SW Version” supplies details about the software
version of the load controller.
89
9
9.9 AZL (ABE)
9.9.1 Times
Manual or automatic changeover from Summer to Winter European or American Summer / Winter times can be
time can be selected. selected.
9.9.2 Language
Six languages are available for selection. Note An exception is the ABE in version Eastern
If the required language is not available the language Europe 2, whre the language group function is
group can be overwritten with PC software. A total of 4 not supported.
language groups, each with 6 languages, are available in
the software.
9.9.5 eBus
Here the eBus address of the W-FM is set, which the Here the cycle time for sending operating data of the
building management uses to communicate with the combustion manager to the BMS is set.
combustion manager.
9.9.6 Modbus
Here the Modbus address of the W-FM is set, which the In Local setting the internal load controller of the
building management uses to communicate with the combustion manager becomes active.
combustion manager. In remote setting, the building management system is
active.
Baud rate
Remote Modus
The baud rate stipulates the transfer speed.
The baud rate of the combustion manager and the BMS The parameter is read only, input is by BMS.
must be identical.
Remote Auto : Setpoint input W3 by BMS
Parity Remote on : Set degree input by BSM
Remote off : The internal load controller is active
Parity is a safety feature for data words during transfer.
The parity of the combustion manager and the BMS must W3
be identical.
Setpoint input press or temperature by BMS.
Timeout
90
9
9.9.7 Display contact
With this selection the dial knob is active and the required
contrast can be set and saved.
Product ID SW Version
The “Product ID” gives information about: The “SW Version” gives information about the software
• Type description (ABE) version of the display and operating unit (ABE).
• Production date
• Serial number
• Parameter set code
• Parameter set version
91
9
9.10 Stepping motors (Actuators)
9.10.1 Addressing
If only one stepping motor is changed the addressing and Addressing stepping motor
the rotational direction will remain the same. If more than
one stepping motor is changed, a new address has to be
entered for each new motor.
Bus connection
If the stepping motor is the last unit in the bus line,
a bus connection has to be made using a jumper. The bus
connection on all other units must be deactivated (the ABE
has a fixed bus connection).
Delete address
If a wrong address has been entered, this can be deleted
by pressing the push button on the stepping motor for 10
seconds, if necessary disconnect the mains voltage whilst
holding down the button. The LED will return to continuous without bus with bus
illumination. connection connection
Delete Curves
Deletes curve lines of all stepping motors, only required to
change the rotation direction in menu level OEM.
Product ID SW Version
The “Product ID” gives information about: The “SW Version” gives information about the software
• Type description (stepping motor) version of the stepping motor.
• Production date
• Serial number
• Parameter set code
• Parameter set version
92
9
9.11 FC-Modul
Depending on the password entered this displays the
parameters for the operator or the engineer
(only W-FM200).
9.11.1 Configuration
Release cont. FC
The release contact for the frequency converter (X73:1/2)
closes automatically, if the setpoint speed is higher than 0%.
Speed
Number of impulses per rotation Speed determination
Speed determination is carried out with an asymmetrical
transmitter (3 impulses per rotation) at input X70. The 180°
asymmetrical transmitter construction (60°, 120°, 180°) is 10 V DC 60°
1
2 wire
used for recognising the rotation direction, motor start with 2 Pulse
3 wirePNP
X70
the wrong direction is therefore not possible. 3 GND
120°
4 Reserve
Standardisation Screen Pulse sequence: 60°, 120°, 180°
5
During standardisation a setpoint signal of 95% is given
at open air or auxiliary stepping motor. This means that
there is a shortfall of 5% of the max. frequency set at the
transformer (52.5 Hz x 0.95 = 50 Hz). The speed reached Connection frequency converter
at the standardised 50 Hz is saved in parameter
Standardised Speed as 100% value for the speed control. 1 24 V FU
If more than 50 Hz is shown during standardisation, the 2 Start FU
motor slip adjustment (=0) on the frequency converter has 12…24 V DC in (Alarm)
X73
3
to be checked. 4 0/4…20 mA out (setpoint)
If the standardised speed is not reached during operation 5 GND
at 100%, a reserve of 5% is available to the system. 6 Screen
Standardised speed
The speed determined during standardisation is saved in
this parameter and can be altered if necessary (not
recommended).
Absolute speed
Displays the current speed determined.
Setpoint output
The output signal (0/4…20 mA) on terminal X73 of the
W-FM and the input signal of the frequency converter
must be matched to one another.
The setting 4…20 mA should be selected on the W-FM
and frequency converter to monitor the signal line.
93
9
Fuel meter
Fuel meters with Namur or Reed output and Open Fuel meter
Collector (pnp) can be used.
The system continually calculates the current fuel Gas 10 V DC Fuel meter
1
throughput for the fuel selected. Calculation time 2 wire Gas
Pulse
X71
2
is dynamic and is between 1 and 10 seconds. GND
3 wire PNP
3
If the meter does not supply an impulse for 10 seconds, Screen
4
throughput “Zero” is displayed. This means that the
transmitter should have a minimum impulse frequency of
0.1 Hz at minimum throughput.
At maximum throughput the maximum frequency is 300 Hz. Oil 1 10 V DC Fuel meter
2 wire Oil
Pulse
X72
2
3 wire PNP
3 GND
Example: Screen
4
Data on gas meter: 250 impulses per m3
Throughput full load: 20 m3/h ^
= 5000 Imp./h ^
= 1.388Hz
Throughput partial load: 4 m3/h ^
= 1000 Imp./h ^
= 0.277Hz
MaxStatDeviation NoDeviation>...
The “maximum static deviation” shows the largest speed Shows the frequency of static deviations at the end of a
deviation at the end of value input alteration. value input alteration, which were > 0.3% or > 0.5%.
Werkskennung SW Version
The “Product ID” gives information about: The “SW Version” gives information about the software
• Type description (FC module) version of the FC module.
• Production data
• Serial number
• Parameter set code
• Parameter set version
94
9
9.12 O2 Module
Depending on the password entered this displays
the parameters for the operator or the engineer (only
W-FM200).
9.12.1 Configuration
Heating Load:
Flue gas temperature Start heat load up to 100° C ______________approx. 13%
Flue gas temperature measured by the Pt/Ni sensor. Used Heat up process approx. 60%
to determine combustion efficiency. Operating temperature ______________approx. 15 to 25%
QGO Resistance
The internal resistance is a measure for the function ability
QGO SensorTemp of the sensor. It changes during the operating time.
Current operating temperature of the O2 sensor. If the internal resistance is < 5 Ω or > 150 Ω the sensor is
ageing.
Product ID SW Version
The “Product ID” gives information about: The “SW Version” gives details about the software version
• Type description (O2 module) of the O2 module.
• Production date
• Serial number
• Parameter set code
• Parameter set version
95
9
9.13 Flue gas recirculation
Depending on the password entered, the relevant
parameters for the operator or for the heating engineer are
displayed (W-FM 200 only).
Deactivated
No flue gas recirculation.
Time
Flue gas recirculation without O2 module.
Temperature
Flue gas recirculation with O2 module.
FGR sensor
CurrTmpFGR sensor
96
9
9.14 SystemConfig
LC operating mode LC analogue output
The configuration of the load controller operating mode is Stipulates which value is given as current signal at
identical to that in menu LoadController (Ch. 9.8.4). output X63:1/2.
However, the setting in SystemConfig has priority.
This means that if an external load controller is selected in Load
menu SystemConfig you cannot change over to internal Load signal of internal load controller
operating mode in menu LoadController.
O2
Ext Input X62 U / I Residual oxygen content in the flue gas
TempLimit Speed FC
Setpoint speed
The configuration of the TL ThresholdOff and
TL SD Off is identical to that in menu LoadController Flame
(Ch. 9.8.2). Flame signal
The configuration for SensSelect and for MeasureRange Temp Pt... / Temp Ni1000
is identical to that in menu LoadController (Ch. 9.8.4). Temperature sensor input X60
97
9
9.16 Start counter
Start counter Gas TotalStartCounterR
Burner starts with fuel gas since last reset. Total burner starts with fuel oil and gas since last reset.
Reset
Here all parameters, which can be reset, can be set to
“Zero”.
Displays the current throughput for gas in m3/h or oil in l/h. Fuel throughput for gas in m3 since last reset. Reset by
pressing the ENTER button.
Volume Gas
Reset date Gas
Total gas throughput in m3.
This value cannot be reset. Date of last reset for fuel gas.
Volume Gas R
Fuel throughput for oil in litres since last reset. Reset by
pressing ENTER button.
98
9
9.18 Updating
9.18.1 Parameter backup
9.19 Password
PW login Deactivate PW (PW Logout)
After entering the engineer’s password additional access Using this parameter the password protected level can be
to the engineer’s level is available. The password is protected at an earlier stage.
deactivated 120 minutes after the last input.
STL Test
99
Start up Operation Shutdown Valve proving
100
tv TSA1 TSA2
9
ON
Safety
Standby
Fuel valve
Home run
Pre-purge
Fan = ON
Press test
Safety fuel
Post purge
relay = ON
Direct start
valve = ON
Pre-ignition
Ignition OFF
Safety phase
Fill valve train
Test no press
Interval time 2
Lockout phase
ignition position
Ignition position
Low fire position
Flame signal ON
After burner time
Empty valve train
Stepping motor in
pre-purge position
Flame stabilisation
Operating phase 1
Operating phase 2
post purge position
tn3 5
6
V1 = Closed, V2 = Closed
V1 = Closed, V2 = Closed
Operating phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79 80 81 82 83
Timer-Event- Link and and or and
Timer 1 t0 t10 t21 t22 t30 t34 t38 t42 t44 t52 t62 t70 t74 t78 t80 t81 t82 t83
Timer 2 9 tv TSA
Times
Timer 3 = Phase max. time t01 tmx1 tmx1 tmx2 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx2
Fuel switch GAS X4-01: 1 C B B B B B B B B B F F F F G B
Safety circuit X3-04: 1 C B B B B B B B B B D D D D D D D D E B w D D D D
Sequence diagram gas with direct ignition
Gas + Oil
BrnFan motor aux-contact X4-01: 3 e A/c A/c 9 C A A A A A A A A A A A A A A A A A A A A A A
Inputs
FGR-LP alt. to GSK X4-01: 3 A/c A/c c C A A A A A A A A A A A A A A A c A A A A
CPI alt. to valve proving DK
X9-03: 2 C A A A A A A A A A a a A A A A A
Low gas press.switcg X9-03: 4 3t G B B B B B B B D D D D D D D D H w D D D D
Release Gas X7-03: 1 3w G B B B B B B B D D D D D D D D H w D D D D
Gas
Lockout HGPS. X9-03: 3 3 A A A A A A A A
Gas pressure switch GPSVP X9-03: 2 A a
Burner motor / Fan X3-01: 1 9/0 9 9 9 9 N N N N N N N N N N N N N N N N N N N N N N N N N
Ignition X4-02 N N
Start signal / DW valve X4-03 u 49 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 N 4 4 4 4
Alarm X3-01: 2 i N 8
Gas + Oil
Safety relay internal X3-04: 1/2 N N N N N N N N N N N N N N N N N N N N N N N N N N N
Safety relay Gas X9-01: 1 N N N N N N N N N N N N N N N N N N N N N
Outputs
Valve pilot ignition Gas X9-01: 2
Gas
Fuel valve 1 Gas X9-01: 4 N N N N N N N N N
Fuel valve 2 Gas X9-01: 3 N N N N N N N N N
Fuel
Partial load
Ignition position
Standby position
Actuators
90° (Full load)
Pre-purge position
Post-purge position
Air
Partial load
Ignition position
Standby position
Start up Operation Shutdown Valve proving
tv TSA1 TSA2
ON
Safety
Standby
Fuel valve
Home run
Pre-purge
Fan = ON
Press test
Safety fuel
Post purge
relay = ON
Direct start
valve = ON
Pre-ignition
Ignition OFF
Safety phase
Fill valve train
Test no press
Lockout phase
ignition position
Ignition position
Low fire position
Flame signal ON
After burner time
Empty valve train
pre-purge position
Flame stabilisation
Operating phase 1
Operating phase 2
Stepping motors in
post purge position
Air stepping motor in
tn3 5
6
V1 = Closed, V2 = Closed
V1 = Closed, V2 = Closed
Operating phase 00 01 10 12 20 21 22 24 30 32 34 36 38 40 42 44 50 52 54 60 62 70 72 74 76 78 79 80 81 82 83
Timer-Event- Link and and or and
Timer 1 t0 t10 t21 t22 t30 t34 t38 t42 t44 t52 t62 t70 t74 t78 t80 t81 t82 t83
Timer 2 9 tv TSA
Times
Timer 3 = Phase max. time t01 tmx1 tmx1 tmx2 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx1 tmx2
Fuel switch GAS X4-01: 1 C B B B B B B B B B F F F F G B
Sequence diagram gas with pilot ignition
Gas + Oil
BrnFan motor aux-contact X4-01: 3 e A/c A/c 9 C A A A A A A A A A A A A A A A A A A A A A A
Inputs
FGR-LP alt. to GSK X4-01: 3 A/c A/c c C A A A A A A A A A A A A A A A c A A A A
CPI alt. to valve proving DK X9-03: 2 C A A A A A A A A A a a A A A A A
Low gas press. sw. LGPS X9-03: 4 3t H B B B B B B B D D D D D D D D H w D D D D
Release Gas X7-03: 1 3w H B B B B B B B D D D D D D D D H w D D D D
Gas
Lockout HGPS. X9-03: 3 3 A A A A A A A A
Gas press. switch GPSVP X9-03: 2 A a
Burner fan / motor X3-01: 1 9/0 9 9 9 9 N N N N N N N N N N N N N N N N N N N N N N N N N
Ignition X4-02 N N
Start signal / DW valve X4-03 u 49 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 N 4 4 4 4
Alarm X3-01: 2 i N 8
Gas + Oil
Safety relay internal X3-04: 1/2 N N N N N N N N N N N N N N N N N N N N N N N N N N N
Safety relay Gas X9-01: 1 N N N N N N N N N N N N N N N N N N N N N
Outputs
Valve pilot ignition Gas X9-01: 2 N N N N
Gas
Fuel valve 1 Gas X9-01: 4 N N N N N N N N N
Fuel valve 2 Gas X9-01: 3 N N N N N N
Fuel
Partial load
Ignition position
Standby position
Actuators
90° (Full load)
Pre-purge position
Post-purge position
Air
Partial load
Ignition position
Standby position
9
101
Start up Operation Shutdown
102
tv TSA1 TSA2
9
ON
Safety
Standby
Fuel valve
Home run
Pre-purge
Fan = ON
Safety fuel
Post purge
relay = ON
Direct start
valve = ON
Pre-ignition
Ignition OFF
Safety phase
Interval time 2
Lockout phase
ignition position
Ignition position
Low fire position
Flame signal ON
After burner time
pre-purge position
Flame stabilisation
Operating phase 1
Operating phase 2
Stepping motors in
post purge position
Air stepping motor in
Times
Timer 3 = Phase max time t01 tmx1 tmx1 tmx2 tmx1 tmx1 tmx1 tmx3 tmx1 tmx1 tmx1 tmx1 tmx1 tmx2
Fuel switch OIL X4-01: 2 C B B B B B B B B B D D D D G B
Safety circuit X3-04: 1 C B B B B B B B B B D D D D D D D D E B
Temperature limit internal C B B B B B B B B B D D D D D D D D E B
Controller ON C B B B B B B B B B D D D D G m 5
Sequence diagram light oil with direct ignition
Gas + Oil
BrnFan motor aux-contact X4-01: 3 e A/c A/c 9 C A A A A A A A A A A A A A A A A A A
Inputs
FGR-LP alt. to GSK X4-01: 3 A/c A/c c C A A A A A A A A A A A A A A A c
CPI alt. to valve proving DK X9-03: 2 C A A A A A A A A A A A A A A A A A A A A A A A
Low oil press. sw. LOPS X5-02: 1 3 r C A A A A A A A A
High oil press. sw. HOPS X5-02: 2 3
Oil
C A A A A A A A A A A A A A A A
Start release Oil X6-01: 1 3 H B B B B B B B D D D D D D D D H
Burner fan /motor X3-01: 1 9/0 9 9 9 9 N N N N N N N N N N N N N N N N N N N N N
Ignition X4-02 2 2 2 2 2 2 N N
Start signal / DW valve X4-03 49 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 N
Alarm X3-01.2 u N 8
Gas + Oil
Safety relay internal X3-01: 1/2 i N N N N N N N 2
N N N N N N N N N N N N N N N N
Safety relay Oil X6-03: 3 N N N N N N N N N N N N N N N N N N
Output
Fuel valve 1 Oil X8-02/-03 N N N N N N N N
Oil
Fuel valve 2 Oil X7-01 N
Fuel valve 3 Oil X7-02 N
Magnetic clutch/sep. pump X6-02: 3 z 2 2 2 2 2 2 N N N N N N N N N
Fuel
Partial load
Ignition position
Standby position
Actuators
90° (Full load)
Pre-purge position
Post-purge position
Air
Partial load
Ignition position
Standby position
Start up Operation Shutdown
tv TSA1 TSA2
ON
Safety
Standby
Fuel valve
Home run
Pre-purge
Fan = ON
Safety fuel
Post purge
relay = ON
Direct start
valve = ON
Pre-ignition
Ignition OFF
Safety phase
Interval time 2
Lockout phase
ignition position
Ignition position
Low fire position
Flame signal ON
After burner time
pre-purge position
Flame stabilisation
Operating phase 1
Stepping motors in
Operating phase 2
post purge position
Medium/heavy oil
Air stepping motor in
Operating phase 00 01 10 12 20 21 22 24 36 38 40 42 44 30 32 34 50 52 54 60 62 70 72 74 76 78 79
Timer-event-connection and and and and or and
Timer 1 t10 t21 t22 t30 t34 t36 t38 t42 t44 t52 t62 t70 t74 t78 tmx1
Time
Timer 2 9 tv TSA1
Timer 3 = Phase max time t01 tmx1 tmx1 tmx2 tmx1 tmx1 tmx1 tmx3 tmx1 tmx1 tmx1 tmx1 tmx1 tmx2
Fuel switch OIL X4-01: 2 C B B B B B D D D D G B
Safety circuit X3-04: 1 C B B B B B B B B B D D D D D D D D E B
Temperature limit internal C B B B B B B B B B D D D D D D D D E B
Controller ON C B B B B B B B B B D D D D G m 5
Flame signal X10-02: 6 q c k i i i i L L L L L L k k k k k
Air press. switch APS X3-02: 1 1 A/c A/c c C A A A A A A A A A A A A A A A A A A c
Gas + Oil
BrnFan motor aux-contact X4-01: 3 e A/c A/c 9 C A A A A A A A A A A A A A A A A A A
Input
FGR-LP alt. to GSK X4-01: 3 A/c A/c c C A A A A A A A A A A A A A A A c
CPI alt. to valve proving DK X9-03: 2 C A A A A A A A A A A A A A A A A A A A A A A A
Sequence diagram medium/heavy oil with direct ignition
Oil
C A A A A A A A A A A A A A A A
Start release Oil X6-01: 1 3 H B B B B B B B D D D D D D D D H
H
Burner motor / fan X3-01: 1 9/0 9 9 9 9 N N N N N N N N N N N N N N N N N N N N N
Ignition X4-02 2 2 2 2 2 2 N N
Start signal / DW valve X4-03 u 49 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 N
Alarm X3-01.2 i N 8
Gas + Oil
Safety relay internal X3-01: 1/2 N N N N N N N N N N N N N N N N N N N N N N N
Safety relay Oil X6-03: 3 N N N N N N N N N N N N N N N N N N
Output
Fuel valve 1 Oil X8-03 N N N N N N N N N
Oil
Fuel valve 2 Oil X7-01 N N N N N N N N
Fuel valve 3 Oil X7-02 z N
Magnetic clutch/sep. Pump X6-02: 3 2 2 2 2 2 N N N N N N N N N N
90° (Full load)
Pre-purge position
Post-purge position
Fuel
Partial load
Ignition position
Standby position
Actuator
90° (Full load)
Pre-purge position
Post-purge position
Air
Partial load
Ignition position
Standby position
9
103
9
Legend for sequence diagrams
Signal “ON” Signal “OFF” Reaction if relevant signal to sequence diagram is not given
6 Follow on phase 24
e With normal venting: Check for ON in phase 10, stop until completion of phase max. time, then jump to phase 01
With continuous running fan: Check for ON in phase 10 and 12, stop until completion of phase max. time, then jump to
phase 01
r If the min. oil pressure switch input has been parametered to “Act from ts” no check is carried out prior to completion of
TSA 1 time
t If the low gas pressure switch input has been parametered to “deactOgp” no check is carried out with oil with gas pilot
ignition
z If the output is parametered to “DirectCoupl”, the safety valve Oil has to be connected. The output is driven together
with the fan and stops 15 s after the fan in time delay.
u If the output is parametered to “PS relief”, this (output PS relief valve) is inverted logically
i The alarm output can be temporarily deactivated for the current fault
104
9
Assignment times:
Time Description
Actuators
In Standby:
The SA can be moved within the permitted
position range, will however, always be driven
to the standby position, and must be in
standby for phase change.
Abbreviations
FGR Flue gas recirculation
CPI Closed position indicator
PS Pressure switch
VP Valve proving
BrnFan Auxiliary contact burner fan contactor
PL or LF Low fire position
AD Air damper
APS Air pressure switch
PP Post-purge position / post-purge
S Standby
SR Safety relay
STB Safety temperature limiter
TL Temperature guard
PV Pre-purge position / pre-purge
Z Ignition position
105
10 O2 sensor
Installing the O2 sensor
• The O2 sensor must only be fitted with the relevant Sensor position
flanges and to the enclosed drawing.
180 mm
115 mm
53,5 mm up to 45°
Installation instruction
mm
64
90
do not insulate
106
10
Electrical connection
Connection to O2 module
O2 Module
L
X89-01
Mains
N
PE 1
L (Q4)
X89-02
N (Q5)
PE 1
Q5
Q4
GND
U3 U3
G2 G2
M
M B2
X81
B2 M
B1
M
B1 1
L, N, PE: Supply voltage sensor heating 230V pulsed Nernst voltage at 700° C sensor temperature
(N switching)
700°C
U3 : Temperature compensation 1 µA/K relating to 120
absolute zero, i.e. 273 µA corresponds to a
sensor temperature of 0° C 100
Nernst voltage [mV]
0
0,05 0,1 0,2 0,5 1 2 5 10 20
O2 content [%]
107
11 Frequency converter
If the W-FM 200 is used in connection with a frequency
converter VLT 2800 or FC 300 (Danfoss), the
parametering of the frequency converter has to be
checked and if necessary adjusted.
123 Frequency stop function 2 Hz activation motor free run if not reached
108
11
No. Description Value Unit Meaning
207 Ramp time Open 1 81/152/283 sec. acceleration time from 0 Hz to nominal frequency
208 Ramp time From 1 81/152/283 sec. delay time from nominal frequency to 0 Hz
211 Ramp time Jog 81/152/283 sec. acceleration/delay time fixed speed
212 Ramp time From Quick Stop 81/152/283 sec. delay time quick stop
1 up to size 50
2 for sizes 60 to 70
3 WK burners
109
11
11.3 Parameter setting FC 300
The burner delivery includes a parameter list with specific
setting values (MCT 10 Set-up Software). In connection
with the W-FM 200 certain parameters on the frequency
converter have to be checked and set if necessary.
0-03 Country settings [0] International Sets the unit for parameters 1-20 to kW
0-04 Mains-On-Mode (manual) [2] LCP Stop, setp.= 0 With Mains-On the frequency converter is at stop
0-40 [Manual-On]-LCP button [1] Activated Function of Manual-On button on operating panel
0-41 [Off]-LCP button [1] Activated Function of Off button on operating panel
0-42 [Auto-On]-LCP button [1] Activated Function of Auto-On button on operating panel
0-43 [Reset]-LCP button [1] Activated Function of Reset button on operating panel
0-60 Main menu Password [100] Password for the main menu (Main-Menu button)
0-61 Main menu Access w/o PW [1] No access Access via operating panel only with password
1-00 Control behaviour [1] Without return signal Speed control with automatic slip adjustment
(without actual value signal from motor)
1-03 Torque behaviour of load [1] Constant Matches the U/f ratio to a constant load 1
torque
1-05 Manual/Local operation [1] as par. 1-00 Defines the control behaviour in manual operation
configuration (Manual-On button) 1
1-10 Motor, type [0] Asynchronous Selection of motor type or MCT 10 Set-up list 1
1-20 Motor, nominal rating [0.09 - 1200 kW] see name plate of motor or MCT 10 Set-up list 1
1-22 Motor, voltage [10 - 1000 V] see name plate of motor or MCT 10 Set-up list 1
1-23 Motor, nominal frequency [20 - 1000 Hz] / [55 Hz2] see name plate of motor or MCT 10 Set-up list 1
1-24 Motor, nominal current [... A] see name plate of motor or MCT 10 Set-up list 1
1-25 Motor, nominal speed [10 - 60000 Hz] see name plate of motor or MCT 10 Set-up list 1
1-52 Min. speed norm. [0.5] Frequency limit for normal magnetisation current
magnetis. [Hz]
110
11
Parameter Setting Meaning
1-60 Load adjust. low [0] Load compensation in lower speed range
1-61 Load adjust. high [0] Load compensation in upper speed range
1-80 Function at Stop [0] motor override Function after stop signal
1-90 Thermal motor protection [4] ETR Alarm 1 Switches off motor if overloaded
2-00 DC hold current [10] Hold current in % relating to motor nominal current.
Only active if 1-80 is set to [1]
2-01 DC brake current [50] Brake current in % relating to motor nominal current
2-04 DC brake ON [Hz] [2] DC brake current is active from this frequency
2-10 Brake function [2] Brake resistance Configuration frequency converter with brake resistance
2-12 Brake resistance rating see list Monitoring limit in kW for brake power
MCT 10 Set-up
2-13 Brake resistance [2] Alarm If the monitoring limit is exceeded, the frequency
load monitoring converter switches off and signals an alarm
2-15 Brake resistance test [2] Alarm Test with shutdown and alarm signal if fault occurs
3-00 Setpoint range [2] Min. to Max Only positive setpoint and actual values are permitted.
3-01 Setpoint/Act. value unit [2] Hz Unit for PID process control
3-03 Maximum setpoint value [52] / [572] Hz Maximum permissible setpoint default
3-04 Setpoint function [0] adding A total is created for several setpoints
3-40 Ramp type 1 [0] linear Ramp type for acceleration and deceleration
3-41 Ramp time Up 1 [83] / [154] / [285] Acceleration time from 0 Hz to nominal speed
3-42 Ramp time Down 1 [83] / [154] / [285] Deceleration time from nominal speed to 0 Hz
3-81 Ramp time quick stop [83] / [154] / [285] Deceleration time quick stop
111
11
Parameter Setting Meaning
4-10 Motor rotation direction [0] Clockwise only Rotation direction required1
4-14 Max. frequency [Hz] [52] / [57 Hz2] Maximum frequency incl. control correction
4-16 Torque limit motorised [160.0] Torque limit for motorised operation
4-18 Current limit [160.0] Limits the maximum current of the frequency converter,
If 160 is not possible set value in % relating to motor nominal current
maximum value
4-19 Maximum output frequency [52] / [572] Absolute limit of output frequency1
4-53 Warning speed high [3120] / [34202] Warning if speed set is exceeded.
5-00 Switch logic [0] PNP Configuration of digital inputs and outputs to positive
switch logic
5-10 Terminal 18 digital input [8] Start On frequency converter terminal 18 start signal from
W-FM 200
5-15 Terminal 33 digital input [1] Reset Resets the frequency converter following alarm shutdown
via terminal 33
5-30 Terminal 27 digital output [0] Alarm Alarm signal is given via the output on terminal 27.
Only visible if 5-01 = [1] output
6-14 Terminal 53 scal. [0] Hz The min. value on analogue input 53 is assigned with
min. setpoint/actual value 0Hz.
6-15 Terminal 53 scal. [52] / [572] Hz The min. value on analogue input 53 is assigned with
max. setpoint/actual value the stipulated frequency.
6-50 Terminal 42 analogue output Motor current [A] Output signal 0...20 mA
6-51 Term. 42, output [0] At minimum value the minimum current (mA) set
min. scaling under 6-50 is applied
6-52 Term. 42, output [100] At maximum value (100%) 20mA is applied
max. scaling
112
11
Parameter Setting Meaning
14-03 Over modulation [1] On Output voltage can exceed mains voltage by 15%
14-10 Mains failure function [1] Ramp stop Frequency converter carries out a controlled Ramp down
at mains failure.
14-21 Autom. recording time [10] secs. Waiting time between automatic recording functions
113
12 Cause and rectification of faults (fault list)
Faults are displayed alternating as codes and clear text Display - Fault history / Lockout history
information. The following fault possibilities are listed in
order of fault code and diagnostic code. Operating mode
Fault history
Fault rectification: Lockout history Stepping motor
• Call up fault history - analyse last fault 1 18.06.99 10:35 fault from ECR
• Determine cause, determine reason C:15 D:1 P:81
• Rectify fault Start No: 123456
• If necessary, record fault Load:25.0 Gas
C: = Fault code
D: = Diagnostic code
P: = Phase
Fault list
01 01 ROM Fault • 1)
02 01…07 RAM Fault • 1)
03 01…44 Fault at internal data comparison • 1)
04 – Synchronisation fault • 1)
05 01,02 Fault flame signal booster test • 1)
• Replace flame sensor
06 01…04 Fault internal hardware test • 1)
10 01…1B Fault inputs / outputs The number of the diagnostic codes shows
which input is faulty.
01 Load controller on/off • Neutral conductor may be missing, (or not zero V)
02 Fan contact
03 Oil operation selection • The fault could be caused by capacitance loads,
04 Gas operation selection causing longer than 10 ms to reduce the voltage
05 Reset to 0 Volts before the relay switches off.
06 Pressure switch Oil maximum
07 Pressure switch Oil minimum
08 Pressure switch valve proving • Check control wiring
09 Safety valve Oil return signal
0A Fuel valve 1 Oil return signal • 1)
0B Fuel valve 2 Oil return signal
0C Fuel valve 3 Oil return signal
0D Safety valve Gas return signal
0E Fuel valve 1 Gas return signal
0F Fuel valve 2 Gas return signal
10 Fuel valve 3 Gas return signal
11 Safety circuit burner flange
12 Safety relay return signal
13 Pressure switch Gas minimum
14 Pressure switch Gas maximum
15 Ignition transformer return signal
16 Fan pressure switch
17 Start release Oil
18 Residual oil immediate start
19 Load controller open
1A Load controller closed
1B Start release Gas
114
12
Fault Fault Cause Recommended measures
list code
115
12
Fault Diagnostic Cause Recommended measures
code code
1C 01…3F The relevant ignition positions The diagnostic value is made up of the faults listed
have not been parametered. or their combination. The individual diagnostic
codes are added hexadecimal.
01 Ignition pos. air stepping motor not param. Set ignition position
02 Ignition pos. of active fuel stepping motor
not parametered
04 Ign. pos. auxiliary stepping motor 1 not param.
08 Ign. pos. auxiliary stepping motor 2 not param.
10 Ignition pos. FC not parametered
20 Ign. pos. auxiliary stepping motor 3 not param.
1D 01…3F Run time fault stepping motors / The diagnostic value is made up of the faults listed
frequency converter or their combination. The individual diagnostic
codes are added hexadecimal.
01 Run time fault air stepping motor • Check motor for mechanical overload.
02 Run time fault current fuel stepping motor • Check supply voltage and fuses.
04 Run time fault auxiliary stepping motor 1 • Drive ramp of the stepping motor must be ≤
08 Run time fault auxiliary stepping motor 2 parametered ramp.
10 Run time fault frequency converter • Ramp of the frequency converter must be smaller than the
20 Run time fault auxiliary stepping motor 3 ramp parameter in the WM-F. Recommendation 20%.
116
12
Fault Diagnostic Cause Recommended measures
code code
1E 01…3F The base unit has detected, that one The diagnostic value is made up of the faults listed
or more stepping motors (incl. FC) have or their combination. The individual diagnostic
not reached the special position codes are added hexadecimal.
required for the phase.
01 Special pos. air stepping motor not reached • Check motor for mechanical overload.
02 Special pos. current fuel stepping motor • Check supply voltage and fuses.
not reached
04 Spec. pos. auxiliary stepping motor 1 not reached
08 Spec. pos. auxiliary stepping motor 2 not reached
10 Spec. pos. FC (speed) not reached
20 Spec. pos. auxiliary stepping motor 3 not reached
1F 01…06 Fault detected with FC module With sporadic occurrences:
Check CAN Bus wiring or improve EMC measures.
With permanent occurrence, replace W-FM
01 Fault internal test in FC module
02 Wrong rotation direction of fan • Check rotational direction of motor and transmitter disc.
• Check rotational direction on FC, correct if necessary
03 Impulse sequence and length at speed • Check installation of transmitter disc and transmitter.
input different than expected • Check distance and connection inductive transmitter.
04 Nominal speed not reached stable • Check motor is running
• Check distance and connection inductive transmitter.
05 Air stepping motor(s) did not reach open • Check motor(s) for mechanical overload.
position for standardisation • Check voltage supply to stepping motors
06 Fault internal speed test FC module
21 – Safety circuit opened
22 – Temperature guard value exceeded
23 – Extraneous light during start up
24 – Extraneous light during shutdown
25 – No flame end of safety time ts1
26 – Flame failure during operation
27 – Impermissible air pressure signal “On”
28 – Impermissible air pressure signal “Off”
29 – Impermissible message “On”
from fan relay contact
2A – Impermissible message “Off”
from fan relay contact
2B – Impermissible air pressure signal “On”
flue gas recirculation
2C – Impermissible air pressure signal “Off”
flue gas recirculation
2D 00, 01 Impermissible message “On”
from valve closing contact
2E 00, 01 Impermissible message “Off”
from valve closing contact
2F – Low gas pressure switch has reacted Check gas supply pressure
30 – High gas pressure switch has reacted Check setting gas pressure switch
31 – Gas pressure switch VP has reacted V1 leaking
32 – Gas pressure switch VP not reacted V2 leaking
33 – Unexpected oil pressure present
34 – Low oil pressure switch has reacted Min. permissible oil pressure not reached
35 – High oil pressure switch has reacted Max. permissible oil pressure exceeded
117
12
Fault Diagnostic Cause Recommended measures
code code
118
12
Fault Diagnostic Cause Recommended measures
code code
119
12
Fault Diagnostic Cause Recommended measures
code code
120
12
Fault Diagnostic Cause Recommended measures
code code
A0 01…1F Auxiliary stepping motor3 has signalled fault With sporadic occurrences,
A1 01…1F Air stepping motor has signalled fault improve EMC measures.
A2 01…1F Gas stepping motor has signalled fault With permanent occurrence,
A3 01…1F Oil stepping motor has signalled fault replace the relevant motor.
A4 01…1F Auxiliary stepping motor1 has signalled fault
A5 01…1F Auxiliary stepping motor2 has signalled fault
01 CRC fault at ROM test
02 CRC fault at RAM test
04 Fault in button value test
05 Time block overrun
07 Sync fault or CRC fault
08 Revolution counter
09 Fault at stack test
0C Temperature warning and shutdown Check housing temperature (max. 60° C)
0D Wrong rotation direction
0E Ramp time for stretch too small • Match ramp time to slowest motor
• Reduce spanning between special positions
10 Timeout at AD change
11 Fault at ADC test
12 Fault at AD change
13 Stepping motor is outside of the valid Check setting range (0-90°), reset mechanically
degree of angle (0-90°)
15 CAN fault Check CAN wiring
16 CRC fault of one parameter section
17 Section was opened too long Reset unit
18 Section is damaged If this fault occurred during parametering:
19 Invalid access to parameter check parameter last changed for plausibility.
1B Fault at copying parameter section If reset does not achieve faultless condition:
Restore parameters from ABE
Otherwise, replace defective base unit.
1E Invalid setting in drive order Check special positions are within valid range
1F Plausibility fault internal Improve EMCmeasures
121
12
Fault Diagnostic Cause Recommended measures
code code
A6 10…FF Internal LC has signalled fault Type of fault: see diagnostic code
10 No actual value increase 1)
12 Invalid XP identified
13 Invalid TN identified
14 TV larger than identification time
15 Invalid TV identified
16 Timeout during observation time
17 Cold start thermal shock protection is active
18 Timeout during adaption load
22 Temp controller setpoint larger limit value
30…32 Internal fault load controller
33 Invalid CRC when reading a section Reset unit, poss. repeat Backup Restore
34…3B Internal fault load controller 1)
40 Section open too long Reset unit. If this fault occurred during parametering:
check parameter last changed for plausibility.
If reset does not achieve faultless condition:
Restore parameters from ABE.
Otherwise, replace defective base unit.
41…43 Internal fault load controller 1)
44 Section was set to ABORT Reset unit
45 Section was set to RESTO If this fault occurred during parametering: check para-
46 Section has invalid status meter last changed for plausibility. If reset does not
achieve faultless condition: Restore parameters from ABE
Otherwise, replace defective base unit.
4A…4E CAN fault 1)
50 PT 100 sensor short circuit Check wiring and sensor
on input X60:1/4
51 PT 100 sensor break
on input X60:1/4
52 Break in compensation line
on input X60:2/4
53 PT 1000 sensor short circuit
on input X60:3/4
54 PT 1000 sensor break
on input X60:3/4
55 Ni 1000 sensor short circuit
on input X60:3/4
56 Ni 1000 sensor break
on input X60:3/4
57 Over voltage on input X61
58 Break or short circuit
on input X61
59 Over voltage on input3, terminal X62
5A Break or short circuit at
input X62
5B Analogue output value (X63:1/2) not Check setting Analogue output and Sensor
available in current configuration. selection
122
12
Fault Diagnostic Cause Recommended measures
code code
123
12
Fault Diagnotic Cause Recommended measures
code code
124
12
Fault Diagnotic Cause Recommended measures
code code
125
13 1Service
3
13.1 Safety information for servicing
Failure to carry out maintenance and service Endangering operational safety
work properly can have severe conse- Maintenance work on the following parts may only be
quences, including the loss of life. Pay close carried out by the manufacturer or their appointed agent
attention to the following safety notes. on the individual components.
DANGER • Combustion manager
• Stepping motors
Detailed information and instructions for maintenance can • Flame sensor
be found in the installation and operating instructions of • Gas pressure switch
the burner. • Air pressure switch
• Oil pressure switch
Qualified personnel • Solenoid valves
Only qualified and experienced personnel must carry out
maintenance and service work.
126
14 Technical data 14
14.1 Combustion manager W-FM
Mains voltage AC 230 V –15 % / + 10 % Low-voltage transformer
When the W-FM is fitted into a control panel, the burner
Transformer AGG5,220 – primary AC 230 V must also be fitted with a low-volt transformer for the
– secondary 3 x AC 12 V control voltage to the stepping motors.
UeMaxUmains + 10%
UeMinUmains - 15%
leMax 1.5 mA peak
leMin 0.7 mA peak
The cable diameters of the mains supply (L, N, PE) and the
safety circuit (STB, low water, etc.) must be selected for
the nominal currents relative to the selected external pre-
fusing.
The cable diameters of the remaining conductors should
be dimensioned in relative to the internal unit fusing (max.
6.3 AT).
127
14
14.2 Stepping motors SQM45.../48...
Supply voltage AC 2 x 12 V Cable connection
The connection of the screened Bus cable is via plug
Protection class Install low voltage cables with safe screw terminal Rast 3.5. The two connection sockets
separation from mains voltages (x1, X2) on the stepping motor have the same value.
Dimensions
90
,4
15 116 76 ø5
2
12
ø1
0 +0
,0 6
0 5
41
+0,1
3N9
33
2,5 0
ø10 h8
ø16
SQM 45
Groove for
25
Woodruff key
3 x 3.7 DIN 6888
122
137
87
50
Prepared for
self tapping screws
+0,1
6 0 M5, 10mm deep,
to DIN 7500
7814m01
25,5
47 2 x M16x1,5
+0,1
0
P9
5
1,9
key 5 x 28
36
SQM 48 39
2 28
ø14 h8
128
14
14.3 Flame monitoring
QRI QRI flame sensor
The infrared flame sensor QRI... has the following
characteristics:
• Infrared flame sensor with IR sensitive sensor for gas
and oil flames
• Integrated flame signal amplifier
• Self checking of flame signal for continuous run
• For front or side (90°) viewing
• Fitted to burner body with flange and clamp
Ionisation electrode
Flame supervision with ionisation electrode for gas
operation is suitable for continuous run.
129
14
14.4 Display and operating unit (ABE)
Supply voltage via Bus cable AC 12 V Dimensions
Installation optional
130
Appendix A
Notes
131
Max Weishaupt GmbH
D-88475 Schwendi
WK Modular powerhouses: Up to
industrial burners Adaptable, robust, powerful. 22,000 kW
Oil, gas and dual fuel burners for industrial plant.
Thermo Unit The Thermo Unit heating systems from cast iron or Up to 55 kW
steel: Modern, economic, reliable.
For environmentally friendly heating.
Fuel: Gas or oil as desired.
Thermo Condens The innovative condensing boilers with the SCOT system: Up to
Efficient, low in emissions, versatile. Ideal for domestic 1,200 kW
heating. Floor standing gas condensing boiler with up to
1200 kW (cascade), for higher heat demand.
Heat pumps The heat pump programme offers solutions for utilisation Up to 130 kW
of heat from air, soil and ground water. The
systems are suitable for refurbishment or new builds.