White Rodgers-Gas Control
White Rodgers-Gas Control
Product Information
The 36C and 36D combination gas control valves and Cycle Pilot). Along with its compact size, all
are compact multifunction controls designed to control adjustments and features, as well as the
meet requirements for use with Standing Pilot system interface wiring panel, have been designed
systems and all types of intermittent ignition on the top surface of the control for simplified
systems (Direct Spark, Hot Surface, Proven Pilot, application and easy accessibility.
Information in this manual is provided to qualified HVAC Professionals Only for the installation and replacement of gas
valves. Homeowners must contact their local HVAC Contractor for gas valve replacement.
Any gas valve suspected of damage or if it has been flooded with water must be replaced immediately. There are no service-
able parts on a gas valve.
General Specifications
Standard Features
Optional Features
Regulator Information
ADJUSTMENT RANGE:
Natural Gas: 2.5” to 5” W.C. Maximum Pressure: 1⁄2 PSI
LP Gas: 4.2” to 11.0” W.C. Agency Approved: -AGA all models
7.5” to 12.0” W.C. -CGA all models
-UL as required
ECO
ADJUST ADJUST
MASTER SCREW VENT MASTER SCREW VENT
REGULATOR REGULATOR
OPEN BY PASS CLOSED BY PASS
ORIFICE ORIFICE
MANUAL VALVE
IN "ON" POSITION
RELAY RELAY
COIL COIL
VALVE
ECO TERMINALS LEVER
MANUAL
TO POWER HEAD COIL PILOT PILOT
VALVE CYCLING CYCLING
(OPTIONAL) FILTER CONTROL FILTER CONTROL
ORIFICE VALVE ORIFICE VALVE
MANUAL VALVE OPEN MANUAL VALVE OPEN
WINDOW OPEN WINDOW OPEN
TO DIAPHRAGM TO DIAPHRAGM
PILOT OUTLET PILOT OUTLET
5
OUTLET PRESSURE (IN. W.C.)
4.5
3.5
2.5
2
0 100 200 300 400 500
FLOW (1000 BTU/HR NAT. GAS)
7" MIN. INLET/2.5" W.C. OUTLET 14" MAX. INLET/2.5" W.C. OUTLET 21" W.C. INLET/2.5" W.C. OUTLET
7" MIN. INLET/5" W.C. OUTLET 14" MAX. INLET/5" W.C. OUTLET 21" W.C. INLET/5" W.C. OUTLET
RANGE OF REGULATION
0.5
0
0 100 200 300 400
FLOW (1000 BTU/HR NAT. GAS)
ON
3.5
P IL O T
3.0
It provides a fast rise of gas to the
2.5
manually adjusted outlet pressure
for a preferred flame setting in gas 2.0
This control has a step open feature 36C/36D STEP OPENING GAS VALVE
that regulates the outlet to an initial 4.0
0.5
a predetermined step pressure.
0.0
2. Fixed orifice step internally 0 2 4 6 8 10
orificed for a step pressure SECONDS
based upon inlet pressure NOTE: TYPICAL OPENING CURVE NATURAL GAS 200,000
BTU/HR. 7” W.C. INLET / 3.5” W.C. OUTLET/1” W.C. STEP.
and flow.
Convertible Regulator
ON
3.5
easy Natural to LP conversion (or vice
P IL O T
OFF
3.0
versa) by removing, inverting and re-
2.5
placing the regulator cap screw or by
2.0
LC
ON
P IL O T
OFF
easily lends itself to use in mobile 1.5
LIMIT
THERMOSTAT
redundant and main valves are opened. A flame must
be detected within a fixed time period or both valves MV
BLACK
close, the igniter is turned off and the HSI control locks REDUNDANT MAIN
WHITE
VALVE VALVE
out unless the system is equipped with retry. Retry MV
SPARK RETURN
The thermostat calls for heat and simultaneously
energizes the DSI control module and both
redundant and main gas valves. Sparks at the
ignition electrodes ignite the gas at the main burner.
LEAD
H.V.
gas. Once the flame is detected, the sparks stop. After sufficient heat MAIN COIL 2
COLD
is sensed by the Mercury Flame Sensor, the main valve is energized 3
PILOT 4
and the system is in operating mode. (Fig. 1) REDUNDANT
COIL
PRESSURE
SWITCH
6 3 2 5 4
BLUE
ORG
RED
coil and locks out the system should a flame not be detected within a
TAN
YEL
fixed period of time. 5 4 2 3 1
WARP
Accessories: Mercury Flame Sensor, Pilot Burner/Electrode SWITCH SAFETY
TIMER
Assembly, Pilot Relight Control, Safety Timer (for all gas systems). 5022
24 VAC
T2 T1
LIMIT
THERMOSTAT
5059 TO ELECTRODE LINE
6 5 4 3 2 1
5 4 3 2 1
THRU MOUNTING
ALL GASES
HOLES Figure 2
24 VAC
40VA
TRANSFORMER LIMIT
THERMOSTAT
6 5 4 3 2 1
LINE
NATURAL GAS
Figure 1
TH TH-TR TR Options:
* - 1⁄4” dual male terminals MAIN VALVE RELAY
- 1⁄4” single male terminals
- 1⁄4” combination tab/screw
- Conduit connector with (2) flying leads
TH TR
Note: Redundant/Pilot valve leads
terminated on panel if applicable.
REDUNDANT PILOT/VALVE
3 Terminal Panel
TH TH-TR TR Options:
* - 1⁄4” dual male terminals MAIN VALVE RELAY
- 1⁄4” single male terminals
- 1⁄4” combination tab/screw terminals
- Conduit connector with (3) flying leads
TH TH - TR TR
Note: Redundant/Pilot valve leads
terminated on panel if applicable.
REDUNDANT PILOT/VALVE
4 Terminal Panel
REDUNDANT PILOT/VALVE
Cycle Pilot With 4 Terminal Panel
Options: 1 RELAY 2
1 2
* - 1⁄4” dual male terminals with
3
⁄16” pin terminal on #2
PILOT ADJ.
3 4
TAN 3 TAN
PILOT Options:
ADJ. REDUNDANT
- Edge connector
COM.
COIL 4 2
- Wiring harness with connector
- Flying leads MAIN
RELAY BLACK PRESSURE
* - 1⁄4” male “Com, L, S” terminals COIL
L
SWITCH
WHITE
- Plug in receptacle on top
or outlet side
S
L
TAN
COMMON
TAN
Bi-metal 2 Stage
C-2
PILOT
ADJ.
W-2
Relay 2 Stage
GREEN
1 2 Options:
RED
* - 1⁄4” dual male terminals 4
3
2
- Edge connector TAN PRESSURE
SWITCH
- Flying leads REDUNDANT TAN
3 VALVE
3 4 TAN
2ND STAGE
Note: Second stage relay leads RELAY
36D13
and redundant valve leads
PILOT ADJ. terminated on panel. MAIN VALVE
2 6 5 4 3 2 1
RELAY COIL
2 1 4
( WITH PRESSURE SWITCH
AND EDGE CONNECTOR )
TH TH-PG PG
* Indicates optional terminals shown
Regulated Step
LINE
*
MODEL NO. TYPE GAS REGULATOR INTERRUPTER STEP OPERATOR SPECIAL FEATURES
36C01 NAT YES NO NO RELAY NO LINE INTERRUPTER, RELAY OPERATOR, REGULATOR
36C02 NAT/LP YES YES NO RELAY NAT/LP FLIP-FLOP SELECTOR
36C03 NAT YES YES NO RELAY STANDARD STANDING PILOT
36C04 NAT YES YES REGULATED RELAY REGULATED STEP OPENING
36C05 NAT YES YES REGULATED RELAY MANUAL HI-LO (TWO STAGE), NATURAL GAS
36C10 ALL NO YES NO RELAY 36C03 WITH OUT REGULATOR
36C12 NAT/LP YES YES REGULATED RELAY NAT/LP SELECTOR, REGULATED STEP OPENING W/NAT/LP SELECTOR
36C13 LP YES YES NO RELAY 36C03 ONLY LP GAS
36C14 LP YES YES REGULATED RELAY 36C04 ONLY LP GAS
36C15 LP YES YES REGULATED RELAY MANUAL HI-LO (TWO STAGE), LP GAS
36C21 ALL NO NO NO RELAY NO MANUAL VALVE, NO PILOT
36C27 NAT YES NO REGULATED RELAY 36CO4 WITH OUT LINE INTERRUPTER
36C36 NAT/LP YES NO NO RELAY PLUG-IN-PILOT
36C38 NAT YES NO NO RELAY BI-METAL 2 STAGE
36C40 NAT YES YES NO RELAY BI-METAL 2 STAGE
36C41 LP YES YES NO RELAY BI-METAL 2 STAGE
36C53 NAT.LP YES YES NO RELAY SLOW OPENING
36C67 NAT/LP YES YES FIXED RELAY NAT/LP SELECTOR (”FLIP-FLOP“), STEP OPENING
36C68 NAT/LP YES SOLENOID NO RELAY 36C03/C13 WITH REDUNDANT
36C74 NAT/LP YES SOLENOID REGULATED RELAY 36C04/C14 WITH REDUNDANT
36C76 NAT/LP YES SOLENOID NO RELAY BI-METAL 2 STAGE
36C77 NAT/LP YES SOLENOID FIXED RELAY NAT/LP SELECTOR (”FLIP-FLOP“), STEP OPENING
36C78 NAT/LP YES SOLENOID NO RELAY 36C77 WITH OUT STEP OPENING
36C81 NAT/LP YES SOLENOID NO RELAY 36C53 WITH REDUNDANT, SLOW OPENING
36C84 NAT/LP YES SOLENOID NO RELAY PRESSURE SWITCH, PLUG IN PILOT
36C87 NAT/LP YES SOLENOID REGULATED RELAY PRESSURE SWITCH
36C90 NAT/LP YES SOLENOID NO RELAY 36C68 LESS MANUAL VALVE
36C92 NAT/LP YES SOLENOID NO RELAY 36C76 WITH PRESSURE SWITCH
36C94 NAT/LP YES SOLENOID SLOW RELAY SLOW OPEN, PRESSURE SWITCH WITH PLUG IN PILOT
36D01 NAT/LP YES NO FIXED RELAY 36C67 WITH OUT LINE INTERRUPTER
36D11 ALL NO SOLENOID NO RELAY 36C90 WITH OUT REGULATOR
36D13 NAT/LP YES SOLENOID NO RELAY RELAY OPERATED 2 STAGE
36D14 NAT/LP YES SOLENOID NO RELAY 36D13 WITH PRESSURE SWITCH
36D22 NAT YES YES NO RELAY 36C03 WITH BRITISH THREADS
36D23 NAT/LP YES SOLENOID NO RELAY 36D13 WITH OUT MANUAL VALVE
36D24 NAT/LP YES SOLENOID NO RELAY NEGATIVE REGULATOR WITH DELAYED OPENING
36D27 NAT/LP YES SOLENOID NO RELAY NEGATIVE REGULATOR
36D29 NAT/LP YES SOLENOID NO RELAY 36C76 WITH OUT MANUAL VALVE
36D32 NAT/LP YES YES NO RELAY MANUAL HI-LO ADJUSTMENT
*Models numbers may not be current production. Please consult White-Rodgers distributor or visit www.white-rodgers.com.
White-Rodgers is a division
of Emerson Electric Co.
R-3769C www.white-rodgers.com
1006 www.emersonclimate.com