Panelboard Diagram Fluorescent Light Fixture Mounting Detail

1. The document provides general notes for electrical works that must comply with Philippine electrical codes and regulations. 2. The electrical service will be 1-phase, 2-wire, 230V AC, 60Hz. Rigid steel or PVC conduit will be used for wiring. 3. All wires will be copper and thermoplastic insulated type THHN unless otherwise indicated. Outlet boxes will be galvanized 16 gauge. Materials must be new and approved for the location/usage.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
203 views1 page

Panelboard Diagram Fluorescent Light Fixture Mounting Detail

1. The document provides general notes for electrical works that must comply with Philippine electrical codes and regulations. 2. The electrical service will be 1-phase, 2-wire, 230V AC, 60Hz. Rigid steel or PVC conduit will be used for wiring. 3. All wires will be copper and thermoplastic insulated type THHN unless otherwise indicated. Outlet boxes will be galvanized 16 gauge. Materials must be new and approved for the location/usage.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES :

1. ALL ELECTRICAL WORKS SHALL COMPLY WITH THESE PLANS AND SPECIFICATIONS. THE APPLICABLE
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC), THE RULES AND
REGULATIONS OF THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL
POWER COMPANY.

2. THE ELECTRICAL SERVICE POWER SHALL BE 1-PHASE,2-WIRE,230V AC, 60Hz.

3. WIRING METHOD SHALL BE AS FOLLOWS:


RIGID STEEL CONDUIT OR POLYVINYL CHLORIDE CONDUIT SCHEDULE 40 SHALL BE USED AS
SPECIFIED IN THE PLAN.
1 2

450
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN" UNLESS OTHERWISE
3 4 INDICATED IN THE PLAN. THE MINIMUM SIZE WIRE FOR POWER AND LIGHTING CIRCUIT

GROUND TERMINAL BLOCK


TOTAL CONNECTED LOADS: 33616 VA

33616 5. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP TYPE.
I @ 75% D.F. = (.75) = 109.62 AMPERES
L 230 (150A/109.62A)
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED FOR THE PARTICULAR
LOCATION AND USAGE.

7. EQUIPMENT GROUNDING SYSTEM SHALL BE PROVIDED TO THE ELECTRICAL SYSTEM AS PER


PHILIPPINE ELECTRICAL CODE REQUIREMENT.

FLUORESCENT LIGHT 8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS:


a. LIGHT SWITCH - 1.20M ABOVE FINISH FLOOR
2 PANELBOARD DIAGRAM 4 FIXTURE MOUNTING DETAIL b. CONVENIENCE OUTLET - 0.3M ABOVE FINISH FLOOR

EE-1 NOT TO SCALE EE-1 NOT TO SCALE 9. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A
DULY REGISTERED ELECTRICAL ENGINEER.

LEGEND

TOTAL CONNECTED LOADS: 8002 VA - 1-18 WATTS COMPACT FLUORESCENT LAMP WITH MEDIUM BASE,
I @ 85% DF KEYLESS TYPE PORCELAIN RECEPTACLE
L
8002
I = (.85) = 29.57 AMPERES
L 230 (55A/29.57A) 1 - 1 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE

2
- 2 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE WITH
CANOPY BASE AND STEM 1.5 FT. (450mm) LENGTH SIMILAR TO AMCO
AP-1113-1.5 OR APPROVED EQUAL
2
- 2 x 36 WATTS FLUORESCENT LIGHTING FIXTURE, BOX TYPE
WF - WALL FAN OUTLET

- SINGLE POLE WALL SWITCH

- DUPLEX SWITCH, 2 SINGLE POLE SWITCHES ON ONE-GANG SWITCH


PLATE

- THREE WAY WALL SWITCH

- 2 THREE WAY WALL SWITCHES ON ONE-GANG SWITCH PLATE

- FAN CONTROL SWITCH


- RACEWAY CONDUIT CONCEALED IN CEILING

- RACEWAY CONDUIT CONCEALED UNDER FLOOR

- PANELBOARD, MARKED AS "LP"

- CKT. BREAKER, RATING AS INDICATED

- DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE 15 AMPS,


240 VOLT

WP - WEATHERPROOF DUPLEX CONVENIENCE OUTLET,


TOTAL CONNECTED LOADS: 8538 VA GROUNDING TYPE,15 AMPS, 240 VOLT
5000mm

I L@ 80% DF
- CIRCUIT HOMERUN
1800mm

8538
I L= (0.80) = 29.70 AMPERES (55A/29.70A)
230
- ENCLOSED AIR CIRCUIT BREAKER

FA - FIRE ALARM CONTROL PANEL

F - FIRE ALARM STATION OUTLET


1 LOAD SCHEDULE B - FIRE ALARM BELL
EE-1 NOT TO SCALE
- SERVICE METER
3 ELECTRICAL RISER DIAGRAM M

- SERVICE ENTRANCE
EE-1 NOT TO SCALE
MDP
- MAIN DISTRIBUTION PANELBOARD

VARIOUS DPWH LOAD SCHEDULE,


(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET) PROPOSED PROJECTS FLUORESCENT LIGHT FIXTURE BOD
MOUNTING DETAIL, 42
NOTE : ADOPTED FROM DEPED STANDARD PLANS STANDARD FOUR-STOREY ELECTRICAL RISER DIAGRAM, EE-1
GILBERTO S. REYES RAUL C. ASIS ROGELIO L. SINGSON 47
SCHOOL BUILDING PANEL BOARD DIAGRAM,
OIC, BUILDINGS DIVISION DIRECTOR IV, BOD UNDERSECRETARY SECRETARY GENERAL NOTES AND LEGEND
( 16-CLASSROOMS )