Electrical
Electrical
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. NOTE:
SERVICE LATERAL PROVIDED WITH 80mmØ
"TYPE F" CONDULETS FOR 230V, 3-WIRE, ALL SIZES OF SERVICE FEEDER (WIRES IN CONDUIT)
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE THREE-PHASE, 3-WIRE, 230V, 60 HERTZ, A.C REFER TO SCHEDULE OF LOADS AND COMPUTATIONS
60Hz, A.C. TO CONNECT TO AVAILABLE
POWER LINES.
3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE
DECKROOF
POWER COMPANY SERVICE POINT.
REINFORCED CONCRETE ELECTRIC
PEDESTAL 5.00m X 0.30m X 0.30m "DP2" "PP2"
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
300mm
3.5mm²,THHN AND 15mm NOMINAL DIAMETER, RESPECTIVELY. LIKEWISE ALL ELECTRICAL WIRES SHALL BE COLOR-CODED.
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE M "MDP" "DP1" "PP1"
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. HAND HOLE SIZE
"MDP"- 1
AS REQUIRED
1800mm
8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE. REM0VABLE
FIN. FLOOR LINE "MDP"- 3 CONC. COVER
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE
ELECTRICAL INSTALLATION SHALL BE USED. FIN. GRADE LINE
HH 10mmØ RSB
10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN SPCD. AS SHOWN
THE PLAN.
1-30mm² THHN IN 20mmØ C. -
a) WALL SWITCHES @ 1300mm 3- 150mm² THHN + 1-30mm²THHN(G) CLAMPED TO A 25mmØ X
b) WALL CONVENIENCE OUTLETS @ 300 mm IN 80mmØ RSC 3000mm COPPERCLAD
GROUNDING ELECTRODE
11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY REGISTERED
ELECTRICAL ENGINEER. ELECTRICAL RISER DIAGRAM
NOT TO SCALE
ELECTRICAL SYMBOLS:
PLAN
CEILING LIGHT OUTLET
REFER TO SCHEDULE OF
SCHEDULE OF LIGHTING FIXTURES AND LAMPS:
CEILING LIGHT OUTLET LIGHTING FIXTURES AND LAMPS
SYMBOL DESCRIPTION INSTALLATION / MOUNTING 12mmØ
LIFTING BAR REM0VABLE CONC.
CF1 CEILING FAN, 100 WATTS, 230V, 60Hz COVER
ONE (1) - 24 WATTS COMPACT FLUORESCENT LAMP WITH MEDIUM BASE KEYLESS
CF2
SURFACE CEILING MOUNTED
TYPE PORCELAIN RECEPTACLE
CEILING FAN, 100 WATTS, 230V, 60Hz
22mmØ PULLING -IN
IRON
SCF CEILING FAN CONTROL SWITCH TWO (2)- 28 WATTS, 230VOLTS, 60Hz., FLUORESCENT LIGHTING FIXTURE. 1200mm X
2 RECESSED CEILING MOUNTED 10mmØ HOR.
300mm MODULE/ HOUSING WITH LOW BRIGHTNESS ALUMINUM LOUVRE BAR @ 200mm. O.C
S SINGLE POLE WALL SWITCH IN ONE SWITCH PLATE
(10 AMP., 230 VOLTS)
S² 2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE 24 WATTS COMPACT FLUORESCENT LAMP IN 194mmØ RECESSED DOWN LIGHT AND
(10 AMP., 230 VOLTS) HIGH GLOSS MIRROR SIMILAR TO PHILIPS FUGATO CAT NO. FSB261 OR APPROVED RECESSED CEILING MOUNTED
S³ 3 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE EQUAL. SIZE AND NUMBER OF
(10 AMP., 230 VOLTS) CONDUIT AS PER PLAN
S3W THREE WAY WALL SWITCH (10 AMP., 230 VOLTS) TWO (2)- 18 WATTS, 230VOLTS, 60Hz., FLUORESCENT LIGHTING FIXTURE. 600mm X
3 RECESSED CEILING MOUNTED
300mm, BOX TYPE
DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
(15AMP., 250VOLTS)
SPECIAL PURPOSE OUTLET, GROUNDING TYPE ONE (1) - 26 WATTS, 230VOLTS, 60Hz., COMPACT FLUORESCENT LIGHTING FIXTURE 2"Ø PVC PIPE DRAIN
"SPO" (30AMP., 300VOLTS)
SIMILAR TO THORNLIGHTING FIXTURE "CITYSCAPE CONCEPT " CAT NO. CFPC 126
WITH OPAL POLYCARBONATE BOWL, DIE CAST ALUMINIUM, BLACK BODY AND 4 RING
WALL SURFACE MOUNTED AT SECTION
SINGLE CONVENIENCE OUTLET, GROUNDING TYPE LEAST 400mm ABOVE DOOR JAMB
EF "EF" DENOTES EXHAUST FAN (15 AMP., 230 VOLTS) QUARTER SPHERE GRILLE ATTACHMENT OR APPROVED EQUAL.
CONCEALED OR EMBEDDED CONDUIT RUN 5 HAND HOLE DETAIL
F.E. FIRE EXIT SIGN, GREEN LED, 5WATTS, 230VOLTS, SINGLE FACE WITH BATTERY SURFACE WALL MOUNTED E -1 NOT TO SCALE
UNDERGROUND OR UNDERFLOOR CONDUIT RUN EXIT
BACK UP (SUBMIT SAMPLE CATALOG FOR APPROVAL) (150mm ABOVE DOOR JAMB)
CIRCUIT HOMERUN
TWO(2) - 20WATTS, QUARTZ HALOGEN LAMPS SELF CONTAINED HIGH INTENSITY
SURFACE WALL MOUNTED
ENCLOSED CIRCUIT BREAKER EL FLOOD LIGHTING FIXTURES FOR NON-MAINTAINED EMERGENCY LIGHTING OF 3 HRS
TO BE INSTALLED AT LEAST 2250mm
RATING AS SHOWN ON THE PLAN DURATION SIMILAR TO THORN LIGHTING FIXTURE MODEL VOYAGER TORSK OR
ABOVE FLOOR LEVEL
APPROVED EQUAL.
ELECTRIC MOTOR
NOTE:
PB PULLBOX ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR WITH STARTER TYPE BALLAST
COMPLETE WITH ALL NECESSARY ACCESSORIES, WIRED AND READY FOR USE.
MAIN DISTRIBUTION PANELBOARD
DISTRIBUTION PANELBOARD
GROUNDING SYSTEM
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: GENERAL NOTES
ELECTRICAL SYMBOLS CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
ELECTRICAL RISER DIAGRAM
SCHEDULE OF LIGHTING FIXTURES AND
SHIELA C. BONDOC
ENGINEERING ASSISTANT
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-1
BUILDINGS DIVISION LAMPS JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER HAND HOLE DETAILS CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY
1 2 3 4 5 6 7 8 9
RISER UP-
G CONNECT
TO S3w y @
SECOND
2500
RISER UP- CONNECT b FLOOR u
TO S3w b @ SECOND S
FLOOR a f g h
F S²ab So
S3Wb EF2 o S³fgh
Su EL
EF3 2
PP1-05 2 t
z u AUXILLARY S²vw
CL-1 STAIR
5000
2 2 HALL 2 2 2 2
x x 2 2 2 2
6400
S3Wy v w v w
m n m n
2 2 2 2 2 2 2 2 2 2 2 2 EF1
w s
v a b c d e f g h i j
2 2
t p
S²vw EF1
r S
500 500
EL
800
D
S³abc
EF1 b a EF1 S³qrs
2 2 DP1-03 2
s q S S³opq o
2 2 EF1
EF1 S²rs
EL r
5000
a b
b 2 TO S²ab 2 2 2 2 2 2 2 2
@ "SB1" c d e f h i j
S g
EL
2 S³mno 2 EF1
EF1 2 3 3 2 S
r o o
c S
EF1
6400
C
EL
EL
OPEN
EF1
EL
c
EL
3000
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
s S²kl
EF1 m n m n c d e f TO S²gh h TO S²ij i j k l
g
c TO S²cd @"SB1" SB1 TO S²ef @ "SB1" @ "SB1" @ "SB1"
B
S²xy S3Wz
EL
a' b' c' d'
RISER UP-
EXIT
F.E.
MAIN CONNECT
3600
PYLON
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: GROUND FLOOR LIGHTING LAYOUT
CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
ALEXIS Z. EBACUADO
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-2
BUILDINGS DIVISION JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY
1 2 3 4 5 6 7 8 9
500
RISER DOWN-
G CONNECT TO
S3w y @ GROUND
b c FLOOR
2500
S3Wb Sc
900
2 2
e f o o
F S²ef
S3Wy EL
2 s
2 2 2 S³mno
p q r
2
EXIT
F.E.
y
5000 2 2 2 2 2 2 2
2 2 2 2 t
w x
m n m n
n m n m
DP2-05 S²uv
2 2 2 DP2-03 S²wx
S³mno 2 s
EL
p q S³pqr r 2 u 2 v PIPE CHASE
EL
E S²st
EF1
z EF1
EL EL
y z
2 DP2-01 2 v
v DP2-02
DP2-04
5000
2 2 2 2 2 2 2 2 2 2 2 2 EF1
EF1 z
y
a b c d e f g h i j k l
2 2 w
w
S EF1 S
D y
EL
EL
SS
PIPE CHASE
2 2 v
x EF1 v x
EF1
5000
2 2 2 2 2 2 2 2 2 2 2 2
EL
EL
EF1 a b c d e f g h i j k l
EF1 x EF1 x EF1
d
d
2 2 u 2 u 2
c
c
C S²cd S³uvw S³xyz S³xyz S³uvw S²cd
S²mn S²op
TO S²ab TO S²cd TO S²ij TO S²kl
3000
EL
3600
EXIT
F.E.
S²ef S²gh q q r r s s t z
S²ij S²kl open
EL St S3Wz
A
RISER DOWN-
CONNECT TO
S3w z @ GROUND
FLOOR
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: SECOND FLOOR LIGHTING LAYOUT
CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
ALEXIS Z. EBACUADO
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-3
BUILDINGS DIVISION JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY
1 2 3 4 5 6 7 8 9
3500
LINE OF SEC. FLR. ( BALCONY) 6000 1700
LINE OF SEC. FLR.
1300
RAMP FL - 3
UP
G
3497
LANDING
896
1000
SUPPLY DELIVERY LOADING BAY RAMP AREA
STORAGE UP (FOR DELIVERY)
2199
2500
UP
1300
1200
UP
F
SERVICE 6 PAX SPO SPO
UP PUMP
1800
STAIRS
DP1-11 DP1-12 ROOM
AUXILLARY REAR LAUNDRY
COOKING SPO DP1-13 STORAGE STAIR LOBBY AREA
5000 DINING CASE
FOOD AREA
AREA UP
W-3 PREPARATION
W-2 FEMALE
TOILET
W-2
D-6
UTILITY RM.
SLEEPING AREA
FL - 1
2649
TOILET DP1-09
5000
LOBBY
PWD
MALE MALE FL - 1
TOILET
TOILET
LOBBY PWD
FIRST
DP1-08 FEMALE
AID
C STATION
5001
3000
ADMIN
B
1300
DP1-15 UP MAIN
ENTRANCE LOBBY STAIR
2800
3600
LANDING RECEPTION/
AREA CONTROL CASE
SLOPE 1: 12
1300
HH1
UP UP
3 - 150mm² THHN + 1 - 30mm² THHN (G) in 80mm Ø RSC. 2435 2370 2435
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: GROUND FLOOR POWER LAYOUT
CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
ALEXIS Z. EBACUADO
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-4
BUILDINGS DIVISION JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY
1 2 3 4 5 6 7 8 9
500
G
SERVICE DN SPO
TO WATER LINE OF ROOF EAVES/PARAPET RC ROOF TO WATER DP2-11
STAIRS
2500
TANK ABOVE SLAB TANK ABOVE
FOOD
F COUNTER
MDFPABX AMP SPO
UP
FE DP2-09
DP2-12
5000
BALCONY AREA DP2-10
ROOM ROOM DN
6 PAX SPO
1000
5000
700 1000
D PIPE CHASE SS
PIPE CHASE
SS PIPE CHASE
MALE
SLEEPING AREA
TOILET
FEMALE
2350
TOILET
5000
2150
PWD PWD
MALE FEMALE
DP2-06
3000
TOILET TOILET FE
LOBBY LOBBY
MAIN STAIRCASE
3600
LOBBY
DN
4800
2200
A
1500
PYLON
CAGE LADDER ACCESS
1000 1000 GOING TO ROOF
2000 (SEE DETAIL)
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: SECOND FLOOR POWER LAYOUT
CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
ALEXIS Z. EBACUADO
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-5
BUILDINGS DIVISION JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY
LEGEND :
AUTOMATIC CIRCUIT BREAKER
A
50AF, 2P, 240VOLTS, 30AT
9
1
IN NEMA 1 ENCLOSURE
G
SUPPLY DELIVERY LOADING BAY
2500
STORAGE
F
CF1 WP2
PP1-06 A
A WP1
AUXILLARY PP1-07 A
STAIR
REAR LAUNDRY
CF1 CASE
STORAGE LOBBY AREA
5000
49.7sqm
B
DINING
PP1-02
AREA
CF1
EE/MAINTENANCE
C
ROOM
E
SB4
FOOD
PP1-01 PP1-03
COUNTER
CF1 CF2 CF2 CF2 CF2 CF2
5000
D
K N
FEMALE
F H Q
TOILET
CF1 41sqm
UTILITY
E
D
SS
SLEEPING AREA
CF2 CF2 CF2 CF2 CF2
G I L O R
5000
TOILET
LOBBY
PWD PWD
MALE MALE FEMALE
TOILET PP1-09
FIRST TOILET
CF2 CF2 CF2 CF2 LOBBY
C
B ACCU-B
A
ADMIN
FCU-2.0
SB3
(WM)
B
B PP1-11
ACCU-A
MAIN
3600
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: GROUND FLOOR AIRCONDITIOING AND
VENTILATION POWER LAYOUT CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
SHIELA C. BONDOC
ENGINEERING ASSISTANT
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-6
BUILDINGS DIVISION JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY
LEGEND :
9
1
AUTOMATIC CIRCUIT BREAKER
A
50AF, 2P, 240VOLTS, 30AT
IN NEMA 1 ENCLOSURE
AUTOMATIC CIRCUIT BREAKER 5000 5000 5000 5000 5000 5000 5000 5000
B
50AF, 2P, 240VOLTS, 50AT
IN NEMA 1 ENCLOSURE
G
SERVICE TO WATER RC ROOF TO WATER
STAIRS TANK ABOVE TANK ABOVE
2500
SLAB
ACCU-C WT-1.0
FOOD B ACCU-D A A
COUNTER
F
ACU
FE PP2-05
CF1 CF1 CF1
LAUNDRY
MULTI-PURPOSE CONTROL REAR STAIRCASE
C D E AREA
5000
C ROOM D ROOM LOBBY
BALCONY
CF1 CF1
PP2-03 PP2-10 FCU-1.5
PP2-07
A B DINING FCU-3TR (WM)
ROOM (CS)
EE ROOM
SB9
CAGE
E
LADDER
PP2-02 PP2-01
CF2 CF2 CF2 PP2-04
CF2 CF2 CF2
CF2
F I L O R U X
UTILITY UTILITY
D
SS
5000
G J M P S V Y
BALCONY
PWD
FEMALE
LADDER
H K N Q T W Z
FE
3000
TOILET TOILET
LOBBY LOBBY
SB6 SB7 SB8
B
CAGE
MAIN STAIRCASE LADDER
LOBBY
3600
TO ROOF
A
SWITCH BANK 6 ("SB6") SWITCH BANK 7 ("SB7") SWITCH BANK 8 ("SB8") SWITCH BANK 9 ("SB9")
SCFF SCFG SCFL SCFM SCFU SCFV SCFA SCFB
SCFH SCFI SCFN SCFO SCFW SCFX SCFC SCFD
SCFJ SCFK SCFP SCFQ SCFY SCFZ SCFE
SCFR SCFS
SCFT
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: SECOND FLOOR AIRCONDITIONING AND
VENTILATION POWER LAYOUT CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
SHIELA C. BONDOC
ENGINEERING ASSISTANT
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-7
BUILDINGS DIVISION JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY
SCHEDULE OF LOADS AND COMPUTATIONS:
3 LIGHT OUTLETS 1000 1000 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 3 CEILING FAN 600 600 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in 15mmØ C. I = 3 ( VA ) = 3 ( 35135 )
4 LIGHT OUTLETS 1185 1185 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 4 373 WATTS EXHAUST FAN 500 500 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in 15mmØ C. 230 230
5 LIGHT OUTLETS 1400 1400 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 5 373 WATTS EXHAUST FAN 500 500 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in 15mmØ C. I = 264.59 AMPS
6 CONVENIENCE OUTLETS 1620 1620 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 6 2HP, 1Ø, 250V, WATER PUMP MOTOR 2760 2760 230 50 2 30 2 -5.5 mm² THHN + 1- 3.5mm² THHN(G) in 15mmØ C.
7 CONVENIENCE OUTLETS 1620 1620 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 7 2HP, 1Ø, 250V, WATER PUMP MOTOR 2760 2760 230 50 2 30 2 -5.5 mm² THHN + 1- 3.5mm² THHN(G) in 15mmØ C.
KVA = 3 E I ( D.F ) @ DIVERSITY FACTOR = 1.10
8 CONVENIENCE OUTLETS 900 900 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 8 SPARE 1500 1500 230 50 2 20 1000 ( DIV.F. ) DEMAND FACTOR = 85%
9 CONVENIENCE OUTLETS 1080 1080 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 9 2 HP, 1Ø, SPLIT TYPE ACU 1750 1750 230 50 2 30 2 -5.5 mm² THHN + 1- 3.5mm² THHN(G) in 15mmØ C.
10 CONVENIENCE OUTLETS 1260 1260 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 10 SPARE 2500 2500 230 50 2 20 KVA = 3 ( 230 ) ( 264.59 ) ( 0.85 )
2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 3.0 TR, 1Ø, SPLIT TYPE ACU 2 -8.0 mm² THHN + 1- 5.5mm² THHN(G) in 20mmØ C.
1000 ( 1.10 )
11 SPECIAL PURPOSE OUTLET 1500 1500 230 50 2 30 11 4850 4850 230 50 2 50
= 81.45 kVA
12 SPECIAL PURPOSE OUTLET 1500 1500 230 50 2 30 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 12 SPARE 1500 1500 230 50 2 20
13 SPECIAL PURPOSE OUTLET 4000 4000 230 50 2 30 2 -5.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. TOTAL CONNECTED LOADS 20520 6560 6610 7350 MAIN LUGS ONLY: 100 AMPS, 3P, 240V, 10kAIC USE: ONE(1)- 100 kVA, 34.5KV/230V, 3Ø, 60HZ., A.C.
14 SPECIAL PURPOSE OUTLET 4000 4000 230 50 2 30 2 -5.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 7350 OISC, POLE MOUNTED DISTRIBUTION TRANSFORMERS
I L @ 90% D.F. = 1.732 230 ( 0.90) + (0.25) (21.09) = 55.09 AMPS. USE : 3 - 30mm² THHN + 1 - 8mm² THHN (G) in 40mm Ø RSC.
15 SPARE 4000 4000 230 50 2 30 (55.09A / 115A )
16 FACP 1500 1500 230 50 2 30 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C.
2 LIGHT OUTLETS 1080 1080 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C.
9 SPARE 4850 4850 230 50 2 20 PAD MOUNTED DIESEL ENGINE GENERATING SET
10 3.0 TR, 1Ø, SPLIT TYPE ACU 4850 4850 230 50 2 50 2 -8.0 mm² THHN + 1- 5.5mm² THHN(G) in 20mmØ C.
3 LIGHT OUTLETS 1370 1370 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C.
11 SPARE 1500 1500 230 50 2 20
4 LIGHT OUTLETS 1080 1080 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C.
12 SPARE 1500 1500 230 50 2 20
5 LIGHT OUTLETS 1560 1560 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C.
TOTAL CONNECTED LOADS 24775 8100 8350 8325 MAIN ACB: 100AF, 3P, 240 V, 100AT, 10kAIC
6 CONVENIENCE OUTLETS 1440 1440 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C.
7 CONVENIENCE OUTLETS 1800 1800 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 8350
I L @ 90% D.F. = 1.732 230 ( 0.90) + (0.25) (21.09) = 61.87 AMPS. USE : 3 - 30mm² THHN + 1 - 8.0mm² THHN (G) in 40mm Ø RSC.
8 CONVENIENCE OUTLETS 1620 1620 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. (61.87A / 115A )
9 SPECIAL PURPOSE OUTLET 1500 1500 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C.
10 SPECIAL PURPOSE OUTLET 1500 1500 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. MAIN DISTRIBUTION PANEL "MDP"
2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. BRANCH BREAKER
11 SPECIAL PURPOSE OUTLET 1500 1500 230 50 2 20 VA PER VA PER PHASE SIZES OF HOMERUN
CKT. LOAD DESCRIPTION VOLTS
RATING
12 M AIN DISTRIBUTION FRAME 1500 1500 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. NO. CKT AB BC CA AF P AT (WIRES AND CONDUIT)
13 PUBLIC ADDRESS SYSTEM 1500 1500 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 1 DP1 32365 10965 10700 10700 230 225 3 125 3 - 30mm² THHN + 1 - 8.0 mm² THHN(G) in 40mm Ø RSC.
14 NETWORK VIDEO RECORDER 1500 1500 230 50 2 20 2 -3.5 mm² THHN + 1- 3.5mm² THHN(G) in15mmØ C. 2 DP2 26360 8790 8810 8760 230 225 3 100 3 - 30mm² THHN + 1 - 8.0 mm² THHN(G) in 40mm Ø RSC.
15 SPARE 1500 1500 230 50 2 20 3 PP1 20520 6560 6610 7350 230 225 3 100 3 - 30mm² THHN + 1 - 8.0 mm² THHN(G) in 40mm Ø RSC.
16 SPARE 1500 1500 230 50 2 20 4 PP2 24775 8100 8350 8325 230 225 3 100 3 - 30mm² THHN + 1 - 8.0 mm² THHN(G) in 40mm Ø RSC.
17 SPARE 1500 1500 230 50 2 20 TOTAL CONNECTED LOADS 104020 34415 34470 35135 MAIN ACB: 400AF, 3P, 240V, 300AT, 25kAIC
18 SPARE 1500 1500 230 50 2 20
35135
I L @ 100% D.F. = 1.732 230 (1.0) + (0.25) (21.09) = 269.86 AMPS. USE : 3 - 150mm² THHN + 1 - 30mm² THHN (G) in 80mm Ø RSC.]
TOTAL CONNECTED LOADS 26360 8790 8810 8760 MAIN ACB: 100AF, 3P, 240V, 100 AT, 10kAIC ( 269.86A / 295A )
8810
I L @ 85% D.F. = 1.732 (0.85 D.F) = 56.39 AMPS. USE : 3 - 30mm² THHN + 1 - 8.0mm² THHN (G) in 40mmØ RSC.
230
(56.39 A / 115 A )
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED BY: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: SCHEDULE OF LOADS AND COMPUTATIONS
CADD:
BUREAU OF DESIGN TWO (2) STOREY
STANDARD PAGCOR MULTI-PURPOSE
SHIELA C. BONDOC
ENGINEERING ASSISTANT
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
EMIL K. SADAIN, CESO I
SEE COVER SHEET FOR SIGNATURE AND APPROVAL BOD
E-8
BUILDINGS DIVISION JOSEPHINE P. ISTURIS ARISTARCO M. DOROY JAMES PATRICK R. BONDOC 8 83
EVACUATION CENTER CHECKED: B
ERIBERTO B. SIOSON OFFICER-IN-CHARGE UNDERSECRETARY FOR TECHNICAL SERVICES VICE PRESIDENT
PORT AREA, MANILA CHIEF, BUILDINGS DIVISION
BONIFACIO DRIVE ENGINEER IV BUREAU OF DESIGN AND UPMO OPERATIONS CORPORATE SOCIAL RESPONSIBILITY