A B C A B C
9114.94 9114.94
788.36 8326.57 788.36 8326.57
FIRE EXIT
PANTRY
PD. R
3 3
OFFICE REF
ROOM 1 STORAGE ROOM
DN
1
GOING TO UNIT C12
12 2
11 3
10 COMMON OFFICE 4
9891.38
9891.38
9
AREA 5
8 6
7 7
COMMON OFFICE
6
AREA
5
UP
1 2 3 4
OPEN BELOW
RECEIVING AREA
2 2
1 ENTRY 1
UNIT C-14 UNIT C-14
A GROUND FLOOR PLAN B MEZZANINE FLOOR PLAN
A-3 SCALE 1 : 100 MTS. A-3 SCALE 1 : 100 MTS.
GENERAL NOTES LEGEND
1. ALL ELECTRICAL WORKS AND INSTALLATIONS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE 10. ALL PANELBOARDS SHALL BE EQUIPPED WITH GROUND KIT TERMINALS WITH NUMBER OF
TERMINALS EQUAL TO THE NUMBER OF BRANCH CIRCUITS. SYMBOL DESCRIPTION MOUNTING HEIGHT REMARKS
OF THE LATEST APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE WITH THE RULES AND
REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE ENFORCEMENT OF 11. ALL EXPOSED METAL CONDUIT SHALL BE TREATED WITH RED LEAD PRIMER THEN FINISHED WITH DUPLEX CONVENIENCE OUTLET, 10A, 250V, 2P, GROUNDING TYPE 300 MM ABOVE FLOOR BY CONTRACTOR
ELECTRICAL LAWS AND ORDINANCES AND WITH THE RULES AND REGULATIONS OF THE UTILITY LIGHT GRAY COLOR PAINT. WITH MOUNTING STRAP AND DEVICE PLATE COVER FINISH AT CENTER
COMPANIES CONCERNED.
DUPLEX CONVENIENCE OUTLET, 10A, 250V, 2P, GROUNDING TYPE 300 MM ABOVE FLOOR
2. POWER SERVICE TO THE BUILDING SHALL BE 230V, 3Ø, 3-WIRE SYSTEM. 12. ALL FEEDER RACEWAY SHALL BE INSTALLED INSIDE CEILING OR BY MEANS OF APPROVED HANGER/ WITH MOUNTING STRAP AND DEVICE PLATE COVER (WEATHER PROOF) FINISH AT CENTER - DO -
CONDUIT CLAMP.
3. WIRING METHOD SHALL BE AS SPECIFIED IN THE SPECIFICATION.
SINGLE CONVENIENCE OUTLET, 10A, 250V, 2P, GROUNDING TYPE WITH - DO -
13. PVC CONDUITS SHALL BE EMBEDDED IN CONCRETE SLAB OR WALLS. MOUNTING STRAP AND DEVICE PLATE COVER (FOR AIRCONDITION UNIT) FINISH AT CENTER
4. UNLESS OTHERWISE SPECIFIED IN THE PLAN, MINIMUM SIZE OF WIRES AND CONDUITS TO BE
USED SHALL BE NO. 3.5MM2 TW AND 15MM NOMINAL DIAMETER RESPECTIVELY. WIRES SHALL BE 14. SIZE OF ALL CONDUIT SHALL BE INSIDE DIAMETER.
INSULATED FOR RATING SUITED FOR THE EQUIPMENT SERVED. KEYLESS TYPE PORCELAIN LAMP RECEPTACLE WITH 100 WATTS - DO - BY CONTRACTOR
5. GENERAL USED RECEPTACLE SHALL BE RATED 10 AMPERES, 2 POLE, 250 VOLTS, GROUNDING 15. COORDINATE WITH THE CIVIL CONTRACTOR TO PROVIDE AN OPENING ON CEILING JUST BELOW THE
TYPE WITH PARALLEL SLOTS, SPECIAL PURPOSE OUTLET SHALL BE OF THE TYPE AND RATING LOCATION OF PULLBOXES FOR POWER AND AUXILIARY SYSTEM INSTALLED INSIDE CEILING FOR WALL BRACKET LAMP, 60 WATTS INCANDESCENT BULB
MAINTENANCE PURPOSES. IN DECORATIVE DIE-CAST ALUMINUM HOUSING - DO - BY CONTRACTOR
SUITED FOR THE EQUIPMENT SERVED.
6. ALL ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE 16. PIPING SYSTEM OF SANITARY PIPES AND THE LIKES SHALL BE INSTALLED AT LEAST 0.30 M. BELOW Sa SINGLE POLE SWITCH 15A, 300V, WITH MOUNTING STRAP 1400 MM ABOVE FLOOR
BY CONTRACTOR
INSTALLATIONS SHALL BE OF THE APPROVED TYPE FOR BOTH LOCATION AND PURPOSE INTENDED. AND DEVICE PLATE COVER FINISH AT CENTER
ELECTRICAL CONDUITS, AND IN CASE WATER OR LIQUID CARRIER PIPE AND ELECTRICAL CONDUITS
7. ALL ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE ARE AT THE SAME LEVEL, PIPES AND CONDUITS SHALL BE INSTALLED OF AT LEAST 1.0M APART. 2Sab TWO (2) SINGLE POLE SWITCH 15A, 300V, WITH COMMON - DO - - DO -
REQUIREMENT OF THE PHILIPPINE ELECTRICAL CODE. MOUNTING STRAP AND DEVICE PLATE COVER
17. ALL JUNCTION BOXES THAT ARE EXPOSED TO WEATHER SHALL BE WEATHERPROOF ENCLOSURE OR
8. ALL MATERIALS TO BE USED SHALL BE NEW AND OF THE APPROVED TYPE FOR BOTH LOCATION CAST STEEL BOX. 3Sabc THREE (3) SINGLE POLE SWITCH 15A, 300V, WITH COMMON - DO - - DO -
AND PURPOSE INTENDED. MOUNTING STRAP AND DEVICE PLATE COVER
9. OUTLET BOXES SHALL BE FABRICATED FROM 1.5MM THICK GALVANIZED IRON SHEET, DIP IN RED 18. A REMOVABLE CIRCUIT DIRECTORY SHALL BE PROVIDED FOR EACH PANELBOARD FOR FIELD
MARKING OF FUNCTION AND NUMBER OF EACH BRANCH CIRCUIT. ALL DIRECTORIES SHALL BE OF NOTE : PREFIX NO. DENOTES NUMBER OF GANG AND
LEAD PRIMER AND AS FOLLOWS : INCORRODIBLE MATERIAL WITH MATCHING CLEAR PLASTIC HOLDER OR JACKET. SUBSCRIPT LETTER INDICATES LIGHT BEING CONTROLLED
A. CEILING LIGHT OUTLETS ------- 40MM DEEP, 100MM OCTAGONAL BOX FOR 1 OR 2 1400 MM ABOVE FLOOR
RACEWAY ENTRIES, 55MM DEEP, 100MM OCTAGONAL 19. ALL ELECTRICAL CIRCUITS SHALL BE WIRED ACCORDING TO THE PANELBOARD LOAD SCHEDULE. ELECTRICAL PANELBOARD FINISH AT CENTER - DO -
BOX FOR 3 OR MORE RACEWAY ENTRIES.
20. COLOR CODING OF WIRE SHALL BE AS FOLLOWS : CONDUIT RACEWAY RUNNING EXPOSED / OVERHEAD CONCEALED
B. LIGHT CONTROL SWITCH ----- 40MM DEEP, 50MM x 100MM DEEP UTILITY BOX FOR 1 BLACK --------230V INSIDE CEILING, CONCRETE SLAB AND WOODEN PARTITION
2 RACEWAY ENTRIES IN ONE STRAP, 55MM DEEP, 50MM GREEN --------GROUND WIRE
x 100MM UTILITY BOX FOR 3 SWITCHES IN ONE STRAP YELLOW -------CONTROL WIRE CONDUIT RACEWAY RUNNING EMBEDDED IN CONCRETE SLAB
AND PARTITIONS AND UNDERGROUND
C. CONVENIENCE OUTLETS ------ 55 MM DEEP UTILITY BOX BLUE --------POWER LINES (CONVENIENCE OUTLET)
AIRCON OUTLETS PB1 CIRCUIT HOMERUN, LETTER DENOTES PANEL DESIGNATION
21. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY 1 AND NUMBER INDICATE BRANCH CIRCUIT NUMBER
D. TELEPHONE/TV OUTLET -------- 55MM DEEP UTILITY BOX REGISTERED ELECTRICAL ENGINEER.
E. OTHERS -----------------------------
AS REQUIRED BY EQUIPMENT SERVED
PROJECT OWNER SHEET CONTENTS REVISION DRAWN/CAD BY: SHEET NO.
GROUND FLOOR POWER LAYOUT
PRC
PROFESSIONAL ELECTRICAL ENGINEER
VALID
OFFICE RENOVATION MIRIAM YANGA MEZZANINE FLOOR POWER LAYOUT
GENERAL NOTES
LEGEND CHECK BY
E-01
LOCATION RODERICK YANGA
IAPOA
PTR
TIN
ISSUED
AT
UNIT C-14, THE GRAND TOWERS MANILA,
P. OCAMPO ST., MALATE, MANILA ANTONIO CAMACHO 3 6