Reference: F-31/IMS-PR-06
SHIBH AL JAZIRA CONTRACTING COMPANY
QHSE DEPARTMENT Rev. 0
Electrical Checklist Dated: July 15th, 2018
DATE OF INSPECTION……………………………..
CHECK POINTS Y/N COMMENT
CONFIRM THAT ALL GROUND WIRES ARE CONNECTED ON ALL CABLES /
1
EQUIPMENT ON SITE
CONFIRM THAT 30mA RCD'S HAVE BEEN PROVIDED FOR ALL MAIN
2 BOARDS FEEDING EXTENSION LEADS / HAND TOOLS / MACHINERY / WET
AREAS
CONFIRM THAT ALL ELECTRICAL BOARDS ARE LOCKED WITH A
3
PADLOCK/KEY AND HAVE ELECTRICIANS TAG
CONFIRM THAT ALL ELECTRICAL BOARDS HAVE DANGER LABELS AND
4
CONTACT DETAILS OF ELECTRICIAN
CONFIRM THAT ALL ELECTRICAL BOARDS HAVE AN INTERNAL COVER SO
THAT LIVE WIRES / TERMINALS CANNOT BE ACCESSED WHEN THE DOOR
5
IS OPENED, ALL EXTERNAL HOLES ARE SEALED TO PREVENT FROM
INSECTS
CONFIRM THAT ALL ELECTRICAL BOARD INCOMERS / FEEDERS ARE
6
IDENTIFIED ON A PAPER LABEL ATTACHED TO THE INSIDE OF THE DOOR.
CONFIRM THAT ALL ELECTRICAL BOARDS ARE NUMBERED AND
7 INSPECTED. CONFIRM THAT THE INSPECTION IS RECORDED ON THE
QUARTERLY INSPECTION LOG
CONFIRM THAT ALL ELECTRICAL BOARDS HAVE A GROUND TERMINAL
BAR AND ALL GROUND WIRES & THE BOARD ITSELF ARE CONNECTED TO
8 IT. WHERE THERE IS NO INCOMING GROUND THE GROUND TERMINAL BAR
SHOULD BE CONNECTED TO A 1 METER LONG COPPER GROUND ROD
DRIVEN INTO THE SAND.
CONFIRM THAT ALL ELECTRICAL BOARDS HAVE A NEUTRAL TERMINAL
9
BAR AND ALL NEUTRAL WIRES ARE CONNECTED TO IT.
CONFIRM THAT NEUTRAL & GROUND SYSTEMS ARE NOT
10
INTERCONNECTED
CONFIRM THAT ALL PORTABLE GENERATORS ARE GROUNDED WITH A 1
11
METER LONG COPPER GROUNDING ROD DRIVEN INTO THE SAND
CONFIRM THAT ALL HANDTOOLS/ELECTRICAL EQUIPMENT ARE
NUMBERED AND INSPECTED/MEGGER TESTED QUARTERLY. CONFIRM
12
THAT THE INSPECTIONS ARE RECORDED ON THE QUARTERLY
INSPECTION LOG
13 CONFIRM THAT ALL HANDTOOLS ARE DOUBLE INSULATED.
CONFIRM THAT THE CORRECT ELECTRICAL ADAPTORS / EXTENSION
14
LEADS ARE USED THAT ENABLE THE GROUND PIN TO BE CONNECTED
CONFIRM THAT THERE ARE NO CABLES RUNNING ALONG THE GROUND
15
AND ARE INSTEAD RUN ABOVE HEAD HEIGHT ( 2 METERS )
CONFIRM THAT ALL CABLES ARE HUNG ON WOODEN / INSULATED
16 HANGERS AND THERE ARE NO CABLES IN CONTACT WITH ANY
SCAFFOLDING.
CONFIRM THAT THE ELECTRICIANS OFFICE HAS AN UP TO DATE SINGLE
17
LINE DIAGRAM OF THE ELECTRICAL SYSTEM ON THE WALL
CONFIRM THAT CALCULATIONS HAVE BEEN DONE TO SIZE ALL
18 GENERATORS, CABLES AND MCB's. CHECK RECORD KEPT IN
ELECTRICIANS OFFICE
CONFIRM THAT ALL ELECTRICAL BOARD KEYS ARE LOCKED IN A
19
LOCKABLE KEY CABINET IN THE ELECTRICIANS OFFICE.
INSPECTED BY
ELECTRICAL COMPETENT PERSON ELECTRICIAN
Signature: Signature:
Name: Name:
SAFETY OFFICER
Signature:
Name: