Substation Inspection List
Substation Inspection List
AREA Crusher
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                           CHECK POINTS
                                                                                                                               INSPECTED
           ROUTE                                         ROUTE Nº 191                                   IDEAL SETTING                           COMMENTS
       1
                                                                 IMPLEMENTATION PROCEDURE
                                         CHECK POINTS
                                                                                                                      INSPECTED
           ROUTE                                        ROUTE Nº 191                            IDEAL SETTING                         COMMENTS
       2
                                                                 IMPLEMENTATION PROCEDURE
                                            CHECK POINTS
                                                                                                                    INSPECTED
           ROUTE                                        ROUTE Nº 191                           IDEAL SETTING                        COMMENTS
       3
                                                                 IMPLEMENTATION PROCEDURE
                                            CHECK POINTS
                                                                                                                    INSPECTED
           ROUTE                                      ROUTE Nº 191                             IDEAL SETTING                    COMMENTS
       4
                                                                                                                    AREA               194 Substation - Mix Storage Area
N° OS DATE OF EXECUTION
                 5
IMPLE
MENTA
 TION
PROCE
DURE
CHECK                                                                                             INSPECT
POINT                                                                       IDEAL SETTING            ED              COMMENTS
   S
ROUTE                                                   ROUTE Nº 194
        6
IMPLE
MENTA
 TION
PROCE
DURE
CHECK                                                                                           INSPECT
POINT                                                                      IDEAL SETTING           ED             COMMENTS
   S
ROUTE                                                   ROUTE Nº 194
 19
        101CS100A01      I/O Cabinet
                         Door locks / locking mechanism                 In good working order     √
                         Check for tripped circuits - Alarms (ON/OFF)   Tripped c-breakers        √
 20
        101CS100A02      I/O Cabinet
        7
IMPLE
MENTA
 TION
PROCE
DURE
CHECK                                                                                         INSPECT
POINT                                                                    IDEAL SETTING           ED          COMMENTS
   S
ROUTE                                               ROUTE Nº 194
 22
        101UP210A04 UPS - Power Distribution Board
                       Door locks / locking mechanism                 In good working order     √
                       Check for tripped circuits - Alarms (ON/OFF)   Tripped c-breakers        √
 23                    GENERAL COMMENTS
        8
                                                                                                            AREA               291 Substation - Gypsum Crusher
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                                 INSPECTED
        ROUTE                                            ROUTE Nº 291                                   IDEAL SETTING                             COMMENTS
       9
                                                                IMPLEMENTATION PROCEDURE
                                           CHECK POINTS
                                                                                                                     INSPECTED
       ROUTE                                           ROUTE Nº 291                            IDEAL SETTING                         COMMENTS
       10
                                                               IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                  INSPECTED
       ROUTE                                          ROUTE Nº 291                           IDEAL SETTING                    COMMENTS
         201LV100 +
 13        NA08        Low Voltage Distribution Board
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits (ON/OFF)                                Tripped c-breakers      √
 14      201LV100 +
           NA09        Low Voltage Distribution Board
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits (ON/OFF)                                Tripped c-breakers      √
 15      201LV100 +
           NA10        Low Voltage Distribution Board
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits (ON/OFF)                                Tripped c-breakers      √
       LDB201LG100A
 16         1       Low Voltage Distribution Board
            201LV200   Metering Unit - 1 (Reading)                                        ……….……………kwh            √                119653
 17
            201UP100   110V DC Battery & Charger
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 18
       101CS200A01     I/O Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 19
       101CS200A02     I/O Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 24
       212AF060U01     Apron Feeder Frequency Drive Cabinet
                       Door locks / locking mechanism                                     In good working order   √
       11
                                                             IMPLEMENTATION PROCEDURE
                                        CHECK POINTS
                                                                                                                INSPECTED
       ROUTE                                      ROUTE Nº 291                             IDEAL SETTING                    COMMENTS
       12
                                                                                                            AREA                   391 Substation - Raw Mill
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                               INSPECTED
        ROUTE                                            ROUTE Nº 391                                   IDEAL SETTING                             COMMENTS
       13
                                                              IMPLEMENTATION PROCEDURE
                                         CHECK POINTS
                                                                                                                   INSPECTED
       ROUTE                                         ROUTE Nº 391                            IDEAL SETTING                         COMMENTS
       14
                                                           IMPLEMENTATION PROCEDURE
                                        CHECK POINTS
                                                                                                              INSPECTED
       ROUTE                                      ROUTE Nº 391                           IDEAL SETTING                    COMMENTS
        301LV100 +
 10       NA05       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
        301LV100 +
 11       NA06       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
                     Display Unit                                                     Working                 √
        301LV100 +
 12       NA07       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
                     Display Unit - 1                                                 Working
        301LV100 +
 13       NA08       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
 14     301LV100 +
          NA09       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
 15     301LV100 +
          NA10       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
        301LV100 +
 16       NA011      Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
        301LV100 +
 17       NA12       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
        301LV100 +
 18       NA13       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
        301LV100 +
 19       NA14       Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped c-breakers      √
 20
       301UP100A01   110V DC Battery & Charger
                     Door locks / locking mechanism                                   In good working order   √
       15
                                                              IMPLEMENTATION PROCEDURE
                                     CHECK POINTS
                                                                                                                 INSPECTED
        ROUTE                                      ROUTE Nº 391                             IDEAL SETTING                        COMMENTS
 24
       311AF160U02    Apron Feeder Frequency Drive Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                      Display Unit                                                       Working                 √
 25
       311SH162U01    Shredder Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 26
       321MD152U01    Apron Feeder Frequency Drive Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 27    LDB301LG100A
       01           Lighting Distribution Board
                      301LV100 - Meter                                                   ……….……………kwh            √                        443722
 28
       301UP110A01    UPS
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                      Display Unit                                                       Working                 √
 29
       301UP110A04    UPS - Power Distribution Board
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 30                   GENERAL COMMENTS
       16
                                     IMPLEMENTATION PROCEDURE
                  CHECK POINTS
                                                                                INSPECTED
       ROUTE                ROUTE Nº 391                        IDEAL SETTING               COMMENTS
       17
                                                                                                            AREA                     491 Substation - Kiln
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                               INSPECTED
        ROUTE                                           ROUTE Nº 491                                    IDEAL SETTING                             COMMENTS
       18
                                                            IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                                 INSPECTED
       ROUTE                                       ROUTE Nº 491                            IDEAL SETTING                         COMMENTS
       19
                                                          IMPLEMENTATION PROCEDURE
                                   CHECK POINTS
                                                                                                             INSPECTED
       ROUTE                                     ROUTE Nº 491                           IDEAL SETTING                        COMMENTS
 10    401LV100 +
       NA07         Low Voltage Distribution Board
                                                                                                                         one capacitor circuit
                    Door locks / locking mechanism                                   In good working order   √           is damage
       20
                                                           IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                              INSPECTED
       ROUTE                                      ROUTE Nº 491                           IDEAL SETTING                        COMMENTS
 21    401LV100 +
       NA18          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 22    401LV100 +
       NA19          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 23    401LV100 +
       NA20          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 24    401LV100 +
       NA21          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 25    401LV100 +
       NA22          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 26    401LV100 +
       NA23          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 27    401LV100 +
       NA24          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 28    401LV100 +
       NA25          Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √
                     Check for tripped circuits (ON/OFF)                              Tripped C-Breakers      √
 29
       331EP300A01   Low Voltage Distribution Board
                     Door locks / locking mechanism                                   In good working order   √           door lock is damage
 31
       331EP302A01   Low Voltage Distribution Board
       21
                                                                 IMPLEMENTATION PROCEDURE
                                      CHECK POINTS
                                                                                                                    INSPECTED
        ROUTE                                       ROUTE Nº 491                               IDEAL SETTING                        COMMENTS
       22
                                                              IMPLEMENTATION PROCEDURE
                                      CHECK POINTS
                                                                                                                 INSPECTED
        ROUTE                                      ROUTE Nº 491                             IDEAL SETTING                       COMMENTS
 48
       401UP110A01    UPS
                      Door locks / locking mechanism                                     In good working order   √           There is a warning
       23
                                                         IMPLEMENTATION PROCEDURE
                                   CHECK POINTS
                                                                                                             INSPECTED
       ROUTE                                    ROUTE Nº 491                            IDEAL SETTING                        COMMENTS
                  GENERAL COMMENTS
 52
       24
                                                                                                            AREA                     492 Substation - Cooler
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                               INSPECTED
        ROUTE                                            ROUTE Nº 492                                   IDEAL SETTING                              COMMENTS
       25
                                                            IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                                 INSPECTED
       ROUTE                                       ROUTE Nº 492                            IDEAL SETTING                         COMMENTS
       26
                                                          IMPLEMENTATION PROCEDURE
                                   CHECK POINTS
                                                                                                             INSPECTED
       ROUTE                                     ROUTE Nº 492                           IDEAL SETTING                    COMMENTS
       27
                                                               IMPLEMENTATION PROCEDURE
                                      CHECK POINTS
                                                                                                                  INSPECTED
        ROUTE                                       ROUTE Nº 492                             IDEAL SETTING                    COMMENTS
 25
       441FN300U01     Cooler Fan Frequency Drive Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                       Display Unit                                                       Working                 √
 26
       441FN305U01     Cooler Fan Frequency Drive Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                       Display Unit                                                       Working                 √
 27
       441FN310U01     Cooler Fan Frequency Drive Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                       Display Unit                                                       Working                 √
 28
       441FN315U01     Cooler Fan Frequency Drive Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                       Display Unit                                                       Working                 √
 29
       441FN320U01     Cooler Fan Frequency Drive Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                       Display Unit                                                       Working                 √
 30
       441FN325U01     Cooler Fan Frequency Drive Cabinet
                       Door locks / locking mechanism                                     In good working order   √
                       Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                       Display Unit                                                       Working                 √
       28
                                                             IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                                INSPECTED
       ROUTE                                      ROUTE Nº 492                              IDEAL SETTING                      COMMENTS
 31
       441FN330U01   Cooler Fan Frequency Drive Cabinet
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                     Display Unit                                                       Working                 √
 32
       441FN590U01   Cooler Fan Frequency Drive Cabinet
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                     Display Unit                                                       Working                 √
 33
       401UP200      110V DC Battery & Charger
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
                     Display Unit                                                       Working                 √
 34
       401CS200A01   I/O Cabinet
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 35
       401CS200A02   I/O Cabinet
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 36
       401CS200A03   I/O Cabinet
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 37
       401UP210A01   UPS
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √           The UPS is bypass
       29
                                                           IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                              INSPECTED
       ROUTE                                      ROUTE Nº 492                           IDEAL SETTING                    COMMENTS
       30
                                                                                                            AREA               497 Substation - Clinker Transport
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                                 INSPECTED
        ROUTE                                            ROUTE Nº 497                                   IDEAL SETTING                              COMMENTS
Main entrance Doors (locks) Working & not damaged √ The door is damage
       31
                                                             IMPLEMENTATION PROCEDURE
                                     CHECK POINTS
                                                                                                                  INSPECTED
       ROUTE                                        ROUTE Nº 497                            IDEAL SETTING                         COMMENTS
 11
       401UP710A04   UPS - Power Distribution Board
                     Door locks / locking mechanism                                     In good working order     √
       32
                                                          IMPLEMENTATION PROCEDURE
                                 CHECK POINTS
                                                                                                          INSPECTED
       ROUTE                                   ROUTE Nº 497                             IDEAL SETTING                 COMMENTS
       33
                                                                                                                                 591/592 Substation - Cement Mills
                                                                                                              AREA                            1&2
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                                   INSPECTED
        ROUTE                                          ROUTE Nº 591 - 592                                 IDEAL SETTING                              COMMENTS
       34
                                                            IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                                 INSPECTED
       ROUTE                                    ROUTE Nº 591 - 592                         IDEAL SETTING                         COMMENTS
       35
                                                          IMPLEMENTATION PROCEDURE
                                   CHECK POINTS
                                                                                                             INSPECTED
       ROUTE                                  ROUTE Nº 591 - 592                        IDEAL SETTING                    COMMENTS
       36
                                                             IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                                INSPECTED
       ROUTE                                   ROUTE Nº 591 - 592                          IDEAL SETTING                    COMMENTS
       37
                                                              IMPLEMENTATION PROCEDURE
                                     CHECK POINTS
                                                                                                                 INSPECTED
       ROUTE                                     ROUTE Nº 591 - 592                         IDEAL SETTING                        COMMENTS
 33
       532MD302U01    Frequency Drive Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 34
       531FN350U01    Frequency Drive Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 35
       532FN350U01    Frequency Drive Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 36
       501UP100A01    110V DC Battery & Charger
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 37
       501CS100A01    I/O Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 38
       501CS100A02    I/O Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 39
       501CS100A03    I/O Cabinet
                      Door locks / locking mechanism                                     In good working order   √           door lock is damage
 41
       502CS100A02    PLC & I/O Cabinet
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 42    LDB501LG100A
            01      Lighting Distribution Board
                      Meter 501LV100 - Reading                                           ……….……………kwh            √                       403623
 43
       501UP110A01    UPS
                      Door locks / locking mechanism                                     In good working order   √
                      Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
       38
                                                             IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                                INSPECTED
       ROUTE                                   ROUTE Nº 591 - 592                          IDEAL SETTING                        COMMENTS
 44
       501UP110A04   UPS - Power Distribution Board
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 45
       502UP110A01   UPS
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 46
       502UP110A04   UPS - Power Distribution Board
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 57
       502UP100A01   110V DC Battery & Charger
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √           Battery test is fault
58 GENERAL COMMENTS
       39
                                                                                                            AREA               691 Substation - Packing Plant
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                               INSPECTED
        ROUTE                                            ROUTE Nº 691                                   IDEAL SETTING                            COMMENTS
       40
                                                             IMPLEMENTATION PROCEDURE
                                     CHECK POINTS
                                                                                                                  INSPECTED
       ROUTE                                        ROUTE Nº 691                            IDEAL SETTING                         COMMENTS
                     Door locks / locking mechanism                                     In good working order     √            some earthing wire
                                                                                                                               disconnect & some
                                                                                                                                cables disconnect
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers        √               w/o isolation
                     Door locks / locking mechanism                                     In good working order     √            some earthing wire
                                                                                                                               disconnect & some
                                                                                                                                cables disconnect
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers        √               w/o isolation
       41
                                                          IMPLEMENTATION PROCEDURE
                                 CHECK POINTS
                                                                                                             INSPECTED
       ROUTE                                   ROUTE Nº 691                             IDEAL SETTING                    COMMENTS
       42
                                                                                                                               791 Substation - Compressor Room
                                                                                                             AREA                               1
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                                 INSPECTED
        ROUTE                                            ROUTE Nº 791                                   IDEAL SETTING                             COMMENTS
       43
                                                             IMPLEMENTATION PROCEDURE
                                     CHECK POINTS
                                                                                                                INSPECTED
       ROUTE                                        ROUTE Nº 791                            IDEAL SETTING                       COMMENTS
 3
       701LV100-1    Low Voltage Distribution Board
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits (ON/OFF)                                Tripped C-Breakers      √
 4
       701LV100-2    Low Voltage Distribution Board
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits (ON/OFF)                                Tripped C-Breakers      √
 5
       401CS110A01   I/O Cabinet
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 6
       701LG100A01   Lighting Distribution Board
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 7
       701UP110A01   UPS
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 8
       701UP110A04   UPS - Power Distribution Board
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 9
       401CS120A01   Profibus Box
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 10
       401CS120A02   Profibus Box
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 11                  GENERAL COMMENTS
       44
                                                                                                                               792 Substation - Compressor Room
                                                                                                             AREA                               2
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                                 INSPECTED
        ROUTE                                            ROUTE Nº 792                                   IDEAL SETTING                             COMMENTS
       45
                                                              IMPLEMENTATION PROCEDURE
                                      CHECK POINTS
                                                                                                                 INSPECTED
        ROUTE                                        ROUTE Nº 792                            IDEAL SETTING                      COMMENTS
 12
       701UP210A01    UPS
                      Door locks / locking mechanism                                     In good working order   √           not energized
       46
                                                             IMPLEMENTATION PROCEDURE
                                    CHECK POINTS
                                                                                                                INSPECTED
       ROUTE                                      ROUTE Nº 792                             IDEAL SETTING                       COMMENTS
 14
       701CS120A02   Profibus Box
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 15
       701CS120A03   Profibus Box
                     Door locks / locking mechanism                                     In good working order   √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers      √
 16                  GENERAL COMMENTS
       47
                                                                                                            AREA                     891 Substation - Main
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
                                          CHECK POINTS
                                                                                                                               INSPECTED
        ROUTE                                            ROUTE Nº 891                                   IDEAL SETTING                             COMMENTS
Main entrance Doors (locks) Working & not damaged √ The door is damage
       48
                                                             IMPLEMENTATION PROCEDURE
                                     CHECK POINTS
                                                                                                                  INSPECTED
       ROUTE                                        ROUTE Nº 891                            IDEAL SETTING                         COMMENTS
 5
       801UP100A01   110V DC Battery & Charger
                     Door locks / locking mechanism                                     In good working order     √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers        √
 6
       701CS100A01   I/O Cabinet
                                                                                                                                 the door lock is
                     Door locks / locking mechanism                                     In good working order     √                  damage
 10
       801UP120A01   UPS
                     Door locks / locking mechanism                                     In good working order     √
                     Check for tripped circuits - Alarms (ON/OFF)                       Tripped C-Breakers        √
 11
       801UP120A04   UPS - Power Distribution Board
       49
                                                          IMPLEMENTATION PROCEDURE
                                 CHECK POINTS
                                                                                                             INSPECTED
       ROUTE                                   ROUTE Nº 891                             IDEAL SETTING                    COMMENTS
50