Substation QA
Substation QA
Answer: Hybrid substation is a combination of both conventional air insulated substation (AIS) and Gas Insulated Substation
(GIS). Some of the bays in the substation are gas insulated (enclosed in modules filled with SF6 gas) and some of the bays
are air insulated type (open to atmosphere). The design of hybrid substation is based on the convenience, local conditions,
availability of the area and cost
They are used for measuring purposes.They are used with ammeters, watt meters, KVA meters and kWh meters for
reducing line current to 1 ampere or 5 amperes
PROTECTIVE CURRENT TRANSFORMERS:
They are used with over-current protection, earth fault protection, differential protection, impedance protection
Which is the basic busbar scheme employed in 220kV and 400kV substations?
Answer: In case of 220kV and 400kV substations double main busbar scheme or one-and-half breaker schemes are
generally employed
maintenance and proper use of alloys provide necessary rigidity required for bus
material. Aluminum is used widely in EHV and HV stations
What is the first equipment of the substation connected to the incoming
transmission line?
Answer: Lightning arrestor is the first equipment of the substation connecting the
incoming transmission lines. It protects other substation equipment from lightning and
switching surges by suppressing them to ground. Lightning arrestors also placed in the
substation between both the ends of major equipment such as power transformers for
protection.
Reasons for using Stones/Gravel in Switch yard:
1. During Short circuit current Step and Touch potential increases.
Step potential : It is the potential developed between the two feet on the ground of a man or
animal when short circuit occurs. This results in flow of current in the body leads to electrical
shock
Touch potential: It is the potential that is developed between the ground and the body of the
equipment when a person touches the body during fault condition. When operating personnel
touch an electrical equipment during short circuit condition, fault current flows through the
human body. This is defined as touch potential.
Gravel/Stones in the substation is provided to reduce the step potential and touch
potential when operators work on switch yard.
2. Power Transformers installed in the substations will have oil as cooling and insulating
medium. Oil leakage takes place during operation or when changing the oil in the
transformer. This oil spillage which can catch fire is dangerous to the switchyard
operation. So Stones/Gravel is provided to protect from fire when oil spillage takes
place.
3. Stones eliminate the growth of small weeds and plants inside the switch yard
4. Improves yard working condition
5. Provides protection from wild life and snakes.
Step potential and Touch potentials during faults are more dangerous. Therefore it is important
to reduce the step potential and touch potential to be within limits during the substation design.
Temperature:
Above the freezing point of the water, temperature does not impact the soil resistivity
significantly but the temperature below the freezing point of the water soil resistivity rises and
will have significant impact
Salts in Soil:
The presence of soluble salts in the soil will significantly impact the resistivity of the soil. One of
the option to reduce the electrode resistivity is by chemical treatment of soil near the electrode.
Bentonite backfilles or salt treatment such as sodium chloride or calcium chloride can
significantly reduce the soil resistivity. The only disadvantage is some chemicals enhance the
metal corrosion rate which can damage the grounding rod to corrode.
If the grounding rod sustains significant current, the current flowing through the grounding rod
may dry out the surrounding soil and that can increase the resistance of the electrode. When
high currents flowing through the grounding rod or earthing electrode, this may be due to
lightning or from faults the soil surrounding the electrode breaks resulting in the increase in the
resistance
along the surface by tracking. Some of the typical creepage distance for insulators in
substation provided based on the level of pollution are tabulated below
S
Degree of
No. Pollution
Recommended Creepage
Distance for Insulators
Clean areas
16 mm/kV
Moderately
polluted areas
20 mm/kV
Industrial areas
22 mm/kV
Heavily polluted
areas
25 mm/kV
Shunt capacitors and series capacitors in the power system generate the reactive power
to improve the power factor and voltage, thereby enhancing the power system capacity and
reducing the losses. In series capacitors reactive power generation is proportional to the square
of the load current (I2Xc), whereas in shunt capacitors reactive power generation is proportional
to the square of the voltage (V2/Xc).
The cost of installation of series capacitors is higher than that of the shunt capacitors.
This is because the protective equipment for the series capacitors is often complicated. In
addition to that, series capacitors are generally designed for higher power to cope up with the
future increase in the load
For the same voltage improvement, the rating of the shunt capacitors will be higher than
that of series capacitors. Series capacitors compensation may create certain disturbances:
ferro-resonance in transformers, sub-synchronous resonance during motor starting, shunting of
motors during normal operation and difficulty in protection of capacitors from system faults.
Series capacitors are more effective on distribution circuits with higher X/R ratio and for
load variations involving a higher reactive content.
Series capacitors are generally employed to improve the stability of the system and
shunt capacitors are generally employed to improve the power factor of the system
Some of the factors which influence the choice between the shunt and series capacitors are
tabulated below:
Objective
Series
Capacitors
Shunt
Capacitors
Secondary
Primary
Secondary
Primary
Secondary
Primary
Reduce Voltage
Fluctuations
Primary
Not used
Minimum
Clearances (mm)
765
kV
400
kV
220
kV
132k
V
Phase to Phase
9400
320
Phase to earth
6400
320
Sectional
Clearance
3000
3700
33kV
Corona Ring:
This Metal Ring what we see in the substations and other transmission line network is "Corona Ring". At higher
voltages such as in EHV transmission networks corona discharge effect is prominent. Corona Ring distributes the
electrical potential gradient evenly and maintains the maximum value below the threshold limits of the corona effect.
Corona Rings are employed at high altitude electrical equipment where density of the air is less.
for conventional substations. Some of the advantages and disadvantages of Gas Insulated
Substations (GIS) are:
The main advantage of this Gas Insulated Substation is because of its compact size
due to high dielectric strength of the SF6 gas. And the availability and reliability of the
GIS
substations
are
more
compared
to
air
insulated
substations
(Faults occurring chances of Air insulated substation or conventional substations are
more. Hence GIS substations are provided where high reliability of electric power is
required such as nuclear plants and and other important facilities where un interruption
of power is more required.
Some of the places where Gas insulated substations are preferred are:
Large towns where space available is limited
Industrial complexes where un interruption of power is necessarily
Mountain regions and valleys
Underground substations
Off-shore (On sea or lake) substations
Pin insulators
Post insulators
Strain insulators
Suspension insulators
Hallow apparatus insulators
Dead-end insulators
Solid core insulators
What is creepage distance?
Answer: Creepage distance is the shortest distance between two conducting points along the
surface of the insulating material.
This type of substation arrangement is best suited for low voltage rating substations
(step down substations) and for those substations where there is ample amount of space
available for commissioning the equipment of the substation
The construction work required is comparatively less to indoor switch yard and the cost
of switchgear installation is also low
In future the extension of the substation installation is easier
The time required for the erection of air insulated substation is less compared to indoor
substation
All the equipment in AIS switch yard is within view and therefore the fault location is
easier and related repairing work is also easy
There is practically no danger of the fault which appears at one point being propagated
to another point for the substation installation because the equipment of the adjoining
connections can be spaced liberally without any appreciable increase in the cost
More space is required for outdoor substation when compared to indoor gas insulated
substation (GIS)
Outdoor switch yards are more vulnerable to faults as it is located in outside atmosphere
which has some influence from pollution, saline environment and other environmental factors.
Deposition of saline particles on insulators can cause insulator failures. They are also
vulnerable to direct lightning strikes and other external events such as heavy winds, rains and
cyclones. Therefore reliability wise air insulated substation or outdoor substations are relatively
low compared to indoor substation
Regular maintenance is required compared to indoor substations (Maintenance for Gas
Insulated Substation is very minimal and reliability is very high) as they are exposed to outside
environment
It is necessary to earth a power system at a suitable point by a suitable method as it offers many advantages as
1.
2.
3.
4.
5.
Solid Earthing
When the neutral of the power transformer and generator is directly connected to the earth, then the system is said to be
solidly earthed. The solidly earthing does not make a zero impedance circuit as generator or transformer would have its own
reactance in series with the neutral circuit. The direct earthing of a generator without external impedance causes earth fault
current from the generator to exceed the maximum 3-phase fault current if the impedance of the generator is too low. This
results in Stator winding damage as the short circuit current during fault will exceed the short circuit rating of the winding for
which it was designed. For this system of earthing, it is necessary that the earth fault current shall be in the range of 25% to
100% of the 3-phase fault current to prevent the development of high transit over voltages.
Resistance Earthing
In resistance earthing the neutral of the generator or transformer is connected to the earth trough a resistance in series.
Advantage Of Resistance Earthing are:
1.
It reduces the line voltage drop caused when earth fault occurs
2.
It reduces electric shock hazards to the persons, caused by stray earth fault currents in the return path
3.
4.
The magnitude of the resistance to be used should be such that it should limit the earth fault current to a value which will
reduce minimum damage at the point of the fault.
Reactance Earthing:
In reactance earthing a reactor is connected in between the neutral of the machine and earth. A low reactance is connected
in series with the neutral of the machine to limit the earth fault current through the generator. This current should not be
greater than the 3-phase fault current of the generator. The earth fault current of the earthed system should not be less than
25% of the 3-phase fault current in order to minimize the transient voltages
The Non linear lightning arrester basically consists of set of spark gaps in series with
the silicon carbide non linear resistor elements. Lightning arresters are connected
between the phase conductors and ground. During normal system operating voltage
conditions, the spark gaps are non conducting and isolate the high tension (HT)
conductors from the ground. However whenever an overvoltge of magnitude dangerous
to the insulation of the apparatus protected occurs ( these over voltages or over surges
may be caused due to lightning strikes on the conductors or due to Extra High Voltage
(EHV) switching) the spark gap breaks down and allows the high voltage surge current
to flow through the ground.
Working Principle of Silicon Carbide (SIC) Lightning Arresters:
The volt-ampere characteristics of the non linear resistor in the lignting arrester can be
approximately described by expression V = KI . Where K and are dependent on the
composition and manufacturing process of the Non linear Resistor (NLR). The value of
lies generally in the range of 0.3 and 0.45 for modern silicon carbide (SIC) lightning
arresters. If the voltage across the Non Linear Resistor (NLR) doubles, the current
would increase approximately by 10 times.
Therefore, with multiple spark gaps arresters can withstand high Rate of Recovery
Voltage (RRRV). The non-uniform voltage distribution between the gaps (which are in
series in lightning arresters) presents a problem. To overcome this, capacitors and nonlinear resistors are connected in parallel across each gap. In case of lightning arresters
employed for high voltage applications, capacitors and nonlinear resistors are
connected across the stock of gaps and NLRs. With the steep voltage wave surge the
voltage is mainly controlled by the capacitor and at the power frequency by the nonlinear resistors. It is obvious that when the over voltages cause the break down of the
series gaps, the current would be very high so as to make the voltage to subside very
fast. The highest voltage that appear across the lightning arrester would be either the
spark over voltage of the arrester or the voltage developed across the non-linear
resistor during the flow of surge current. The lowest spark over voltage of the arrester is
called the hundred percent impulse spark over voltage of the arrester. The voltage
developed across the non-linear resistor during the flow of surge current is called
residual voltage. The lower the value of the voltage developed the better the protection
of the lightning arrester.
Disadvantages of Silicon Carbide (SIC) Arresters:
A transformer that is designed to operate lower on the saturation curve draws less inrush
currents as there is more margin between the saturation point and the normal operating. The
extra flux during switching is less likely to push the core into saturation
Large transformers draw more inrush current. Large transformers will have smaller
saturation impedance
Higher source impedance relative to the transformer size limits the currents that the
transformer can pull from the system
the point where the circuit breaker close (position of flux wave in sine wave). The
worst case will be when the flux is at maximum (peak) and voltage is minimum (in
transformer the applied voltage lag behinds the flux by 90 deg).
Other factors have little significance. The load on the transformer does not significantly
change the inrush currents. While switching transients cause high inrush, other voltage
transients especially voltage transients with dc components can saturate the core of the
transformer and cause inrush currents
When the nearby fault was cleared and transformer voltage is recovering from
the voltage sag, the sudden rise in voltage can drive the transformer to saturation
Energizing a transformer can cause the nearby transformer to also draw inrush
currents. The inrush currents into the switched transformer has a significant dc
component that can cause the voltage drop. The dc component can push the other
transformer into saturation and draws inrush
A lightning flash near the transformer can drive the transformer core to saturation
THREE WINDING TRANSFORMER:
Generally in power system mostly two winding transformers are employed. But three winding
transformers are employed because of some advantages:
The most common reason for having a three winding transformer is to provide a delta
connection tertiary winding
To limit the fault level on the low voltage system of the transformer by dividing the LV
infeed (in order to provide double secondary windings)
Providing tertiary winding helps to interconnect different power system operating at
different voltages (Three winding transformer helps provide power supply at two different
secondary voltages, 220kV/11kV/6.6kV transformer can able to provide power at two different
voltage levels (11kV and 6.6kV)
To regulate the voltage and reactive power of the system by providing synchronous
capacitor connected to one of the terminals of the transformer
Noise In Transformer:
The basic cause for the noise in the transformer is due to magnetostriction of the
sheets in the magnetic circuit (core of the transformer). Variations in the magnetic
induction subjected to the sheets to periodic variations in the length, the amplitude
which is in the order of microns per meter length.
The fundamental frequency with which these vibrations occur is double that of
the system frequency, (for 60Hz frequency vibration frequency will be of the order of
120Hz) and also constitute numerous harmonics. Also various parts of the transformer,
starting with the magnetic circuit (core) are liable to vibrate due to magnetostricition
effect.
The noise generated due to magnetostricition effect transmitted from the
magnetic circuit to the tank of the transformer either through direct conduction to
supporting points or through the oil and insulating material used in transformer. The
transformer tank and the radiator radiate the acoustic noise or energy in to the ambient
atmosphere
Another source is due to the vibration of magnetic sheets perpendicular to the
surface either at the edge or at the core packets, or at the joints between the leg and
the yoke
The current carrying windings is also a source of noise, however the amplitude of
the noise is very less and is not detectable.
Cooling fans and pumps employed for cooling the transformer is also acts as
source of noise
Methods to reduce Transformer noise:
The main source of noise in the transformer is due to magnetostriction effect of
the magnetic circuit or core. In order to reduce the noise cold rolled grain-oriented plant,
with low magnetostriction and improved flatness is employed
Ensuring uniform flux distribution and reduction in the cross flux also reduces the
noise
Elimination of the clamp bolt holes, use of resin impregnated glass-fibre bands
instead of core bolts, gluing of core packets can reduce the noise
These above specified remedial methods not only reduces the noise level by 5 to 10 dB,
but also reduces the losses and no-load current
Faults in Transformers:
Some of the faults in the transformers are likely to be over-voltages which
resulting from the atmospheric phenomenon (lightning) transmitted by overhead lines.
Switching in the power system (especially high voltage switching more than
400kV) can produce over-voltages of less steep but longer duration surges stressing
both liquid and solid dielectrics (insulation). These over-voltages should be restricted in
amplitude to a value below the transformer insulation breakdown withstanding level.
Short circuits in the power system subject the transformer to currents of 10 to 20
times the rated currents (short circuit current level will be severe when fault occur close
to transformer). Power transformer is generally designed to withstand tens of short
circuits, lasting not more than 2 sec duration in its life time. If there are more short
circuits than the designed limit special construction is required. Short circuits should
eliminated (by isolating faulty power system by opening circuit breakers) as quickly as
possible to limit the short circuit intensity on transformer.
The power transformer is on no-load (even an active load which can be less than one
tenth of the rated power can be sufficient to prevent the phenomenon of ferroresonance to occur
by absorbing the energy).
A large capacitance exists in line or the cable connected to at least one terminal of the
transformer while the other terminals remain at normal potential
An unbalanced situation is created by a single phase trip out, a break in the conductor or
blowing of one or two fuses
Earth the neutral point directly or through a resistor limiting the single phase fault current
Auto-transformer Advantages:
Auto-transformer Disadvantages:
An electrical connection between the primary and secondary is not always desirable,
particularly when the voltages levels on both the sides of transformer are quite different. If the
neutral point is not solidly earthed, the lower voltage side can be subjected to high potential in
the event of earth fault on high voltage side. In general practice, auto transformers are only
used on distribution systems where the neutral is connected to the earth
Auto-transformers are particularly sensitive to the atmospheric over-voltages. Therefore
the auto-transformer requires much highs standard of insulation compared to normal
transformer. Surge Arrester protection is required
As the short circuit impendace values of the auto-transformer are low, short circuit
currents can reach higher critical values.
Sources of Harmonics:
Several sources of harmonic currents that may be found on electrical power distribution
networks are listed below:
Disadvantages of Harmonics:
Harmonics degrades the performance of power system. Some of the disadvantages of harmonics in the
power distributed network are listed below:
The harmonics flowing in the distribution network downgrade the quality of the electrical
power supply. There can have several negative effects on the operation of the power system
Increased losses on the distribution system due to increase in the effective rms current
Over-load in neutral conductors due to cumulative increase in the third harmonics
created by the single phase loads
Overloads, vibration and premature ageing of the generators, transformers and motors
as well as increase in the noise level
Overloads and premature ageing of the power factor correction capacitors
Distortion of the supply voltage that can disturb the operation of the sensitive loads
Disturbances in the communication networks and telephone lines
Resonance between the supply inductance and capacitance of the power factor
correction capacitors
DRY TYPE TRANSFORMER:
Dry type transformers are most suitable in locations where conventional oil filled transformers present a safety
hazard. Some of the locations where dry type transformers are best suited are: Oil refineries, Chemical plants, Marine
applications, Metro railways where there is significant safety is required against fire.
Dry type transformers are lighter in weight compared to oil filled transformers
Answer: Isolation switches are provided for separating the disconnected element from
the live portion of the system for the purpose of safety.
Why asymmetrical breaking current is higher than the symmetrical breaking
current in a circuit breaker?
Answer: Asymmetrical breaking current is the rms value of the combined sum of the dc
and ac components of the short circuit current at the instant of separation of the breaker
contacts while symmetrical breaking current is the rms value of the ac component
alone. Thus asymmetrical breaking current is higher than the symmetrical breaking
current.
What is recovery voltage in circuit breaker?
Answer: Recovery voltage in circuit breakers is defined as the power frequency rms
voltage which appears across the breaker contacts after the transient oscillations die
out and the final extinction of the arc has resulted in all the poles of the circuit breaker.
It is the voltage developed after the arc extinction is competed
When does an arc extincts?
Answer: If the rate of rise of re-striking voltage (RRRV) is less than rate of rise of
dielectric strength between the breaker contacts arc will not sustain and extincts
What is re-striking voltage?
Answer: The Re-striking voltage may be defined as the resultant transient voltage which
appears across the breaker contacts at the instant of arc extinction
For an Resistive Load and Inductive load considered for switching operation of
circuit breaker, Switching of which load is difficult and Why?
Answer: In case of switching resistive load, current and voltage will be in phase i.e,when
during current zero voltage also will be zero in case of resistive load. Hence the voltage
at the breaker terminals during arc extinction is zero or minimal. On the other hand, for
switching inductive load during current zero voltage across the breaker will be
maximum. This results in re-striking of arc once again. Therefore switching inductive
load will be difficult
Why Earth Wire is provided in the overhead transmisssion lines?
Answer: Earth wire is provided above the overhead transmission lines for protection
against lightning strokes. The ground wire or earth wire protects the phase conductors
or line conductors by attracting itself the lightning strokes which in its absence would
strike the phase conductors. Also the ground wire reduces the voltage electrostatically
or electromagnetically induced in the conductors by the discharge of a neighboring
cloud. It also provides the additional protective effect by causing the attenuation of
traveling waves set in the lines by acting a short circuit secondary of the line current
What is meant by protective angle? Give its value for reliable operation?
Answer: Protective angle is the vertical angle through the ground wire axis and the line
passing from the ground wire axis to the outermost phase conductor. Its value for
reliable protection is taken equal to 20-30 degrees
What is the difference between the lightning arrester and surge absorber?
Answer: Lightning arrester limits the duration and amplitude of the follow current while a
surge absorber reduces the steepness of the wave front for a particular surge
What is meant by Lightning arrester or surge diverter?
Answer: A Surge Diverter is a device that is connected between line and earth, i.e, in
parallel with the equipment under protection at the substation. It limits the duration and
amplitude of the follow current.
What types of relays are suitable for the protection of radial feeders?
Answer: Induction type IDMT relays are more suitable for protection of the radial feeders
because the time current characteristics are similar in shape and in no case they cross each
other at any time
What is the purpose of Line trap and Coupling capacitors in carrier channels?
Answer: Line trap is an LC network inserted between the busbar and connection of
coupling capacitors to the line and tuned to resonance at the high frequency and are
used to confine the carrier currents to the protected section so as to avoid interference
with or from adjacent carrier current channel.
Coupling capacitors is used to connect the high frequency (carrier) equipment to one of
the line conductors and simultaneously serves to isolate the carrier equipment from high
power line voltage
What is Unit Protection?
Answer: Unit system of protection is one in which the protection responds to the faults in
the protected zone alone and it does not respond to through faults (faults beyond the
protected zone). None unit systems does not have zone boundry
What is the minimum time interval set for two adjacent circuit breakers to operate
in radial feeders?
Answer: It will be usually around 0.4 sec
For what type of faults does differential protection is provided?
Answer: Differential protection responds to the phasor difference between two or more
electrical quantities. It operates for the internal faults occur in generators or
transformers. For external faults differential protection does not operate
What is the disadvantage of ordinary differential protection?
Answer: When differential relaying is used for protection, the CTs at both sides of the
generator winding must be of equal accuracy. Otherwise if the CT errors are excessive it
will cause the mal operation of the relay. To safeguard against such disadvantages
percentage differential protection is employed.
protection systems (operates faster) for any internal faults occurring within the
protection zone.
Under healthy conditions the currents at both ends of the windings will be equal. EMFs
induced in the secondaries of the CTs will be equal and so no current flows through the
operating coil of the relay. When an earth fault or phase to phase fault occurs the
condition no longer holds good and the differential current flows through the relay
operating coils makes the relay to operate. Relay operates for the faults occurring within
the zone of protection
Where does Negative phase sequence relay is employed?
Answer: Negative sequence relay is employed for the protection of generators and
motors against unbalanced loading that may arise due to phase to phase faults
What is the operation principle of differential relay?
Answer: A differential relay operates when the phasor difference of two or more similar
electrical quantities exceeds a pre-determined amount
Why distance protection is preferred as primary protection compared to over
current protection for transmission lines?
Answer: Distance relay is superior to over current protection for the protection of
transmission lines. Some the reasons are faster protection, simpler coordination,
simpler application, permanent settings without need for readjustment, less effect of the
amount of generation and fault levels, fault current magnitude, permits the high line
loading
Why biased differential protection is preferred over simple differential protection?
Answer: Biased differential relay is preferred because its operation is not affected by the
trouble arising out of the difference in the CTs ratios for high values of external short
circuit currents
Where Impedance relay, Reactance relay and Mho relays are employed?
Answer: The Impedance relay is suitable for the phase faults relaying for the lines of
moderate lengths Reactance type relays are employed for the ground faults while Mho
type of relays are best suited for the long transmission lines and particularly where
synchronizing power surge may occur
What is percentage differential relay?
Answer: It is a differential relay where the operating current required to trip can be
expressed as a percentage of load current
Star Connection:
In a star connection, phase voltage Vph = VL/ (3)1/2. Since the induced emf in the primary
winding of an alternator is directly proportional to the number of turns, a star connected
alternator will require less number of turns than a delta connected alternator for the same
voltage.
For the same line voltage, a star connected alternator requires less insulation than a
delta connected alternator. Due to the above reasons three phase alternators are generally star
connected.
In star connection, we get 3-phase and 4-wire system. This permits the use of two
voltages (phase voltages as well as line voltages). Single phase loads can be connected
between any one lie and neutral wire while the 3-phase loads can be put across the three lines.
Such a flexibility is not available in delta connection
In star connection, the neutral point can be earthed. Such a measure offers many
advantages. For example, in case of line to earth fault (L-G fault), the insulators have to bear
1/31/2 (57.7%) times the line voltage. Earthing of neutral also permits the use of protective
devices (relays) to protect the system in the case of ground faults
Delta Connection:
Sinusoidal voltages and currents produce less interference (noise) on telephone lines
The sine waveform produces the least disturbance in the electrical circuit and is
smoothest and efficient waveform
Due to above advantages, electrical supply is generate sinusoidal alternating voltage and
currents.
Hysteresis Loss:
When a magnetic material is subjected to a cycle of magnetization (magnetized first in
one direction and later magnetized in opposite direction in a cyclic manner), an energy
loss takes place. This energy loss is due to molecular friction in the material. That is, the
domains (or molecular magnets) of the material being turned first in one direction and
then the other. Energy is thus expended in the material in overcoming this opposition.
This loss is in the form of heat and is called hysteresis loss.
Hysteresis loss is present in all electrical machines whose iron parts are subjected to
cycle of magnetization like transformers, induction motors and other machines operated
on ac supply. When an alternating supply is provided to the electrical machines the flux
in the iron of these machines change in both direction and value alternatively. During
this process energy is lost and this loss constitutes the core loss of the machine. The
obvious effect of hysteresis loss is the rise of temperature of the machine
Transformers and most electric machines operate on alternating current. In such
devices, the flux in the iron changes continuously, both in magnitude and in direction.
Hence hysteresis loss occurs in these machines
Hysteresis loss also occurs when iron parts rotates in constant magnetic field egdc machines
Hysteresis Loop or B-H Loop area:
Hysteresis loop is obtained by plotting B-H (B: flux density, H:magnetizing force) of iron
for one cycle of magnetization.
When the core of the machine such as transformer, induction motors is magnetized
with the magnetizing force (H) by applying voltage, magnetic flux density (B) increases
as shown in the figure (dotted lines) and saturates (first quadrant). Saturation region in
one in which increase in the magnetization force (H) will not further appreciably increase
the magnetic flux density (B) in the material.
When the applied voltage reaches back to the zero position from the peak (first half
cycle), magnetizing force will also becomes zero. However the magnetic flux density in
the core will not reach zero but have some finite value. This property of magnetic
material to withhold some flux (B) when magnetizing strength becomes zero is
called Retentivity.
During the next half cycle all the domains in the magnetic core tries to align in opposite
direction as the applied voltage polarity changes and hence the magnetizing force
applied. With increase in the magnetizing force (H) a point is reached where the
magnetic flux density(B) becomes zero. This point is called coercivity. Beyond this point,
magnetic flux will be in opposite direction with increase in field strength and reaches
saturation as shown in figure (third quadrant).
Further applied magnetic field will starts decreasing from peak and reaches zero. This
decrease in the magnetic flux with decrease in field strength can be seen in figure (third
quadrant) and reaches back when the voltage polarity changes.
This forms the B-H loop of hysteresis loop of the magnetic material of the machines
for this reason silicon steel is widely used for manufacturing of transformer cores and
rotating machines which are subjected to rapid reversals of magnetism
The hysteresis loop for Hard Steel (large hysteresis loop area) indicates that the
material has high retentivity and coercivity. Therefore hard steel is quite useful in making
permanent magnets. But due to large area hysteresis loss is quite high. This is the
reason hard steel is not used for construction of electrical machines
Methods to reduce Hysteresis Loop or B-H Loop:
Hysteresis loop can by using soft magnetic materials (like CRGO core magnetic
material in transformers) having smaller loop to reduce the hysteresis loss.
DIFFERENCE BETWEEN LAN, WAN AND MAN NETWORKS:
A Computer network that spans relatively small area is called Local Area Network
(LAN). Most LANs are confined to small building or group of buildings. However one
LAN can be connected to other LANs over any distance via telephone lines and radio
waves. A system of LANs can be cconnected in this way is called Wide Area Network
(WAN)
Most LANs can connect workstations and personal computers. Each node (individual
computer) in a LAN has its own CPU with which it executes programs, but it is also can
able to access data and devices anywhere in the LAN. This means that many users can
able to share expensive devices, such as laser printers, as well as data. Users can also
use the LAN to communicate with each other, by sending e-mails or engaging in chat
sessions or can able to play games together
Metropolitan Area Network or MANs are large computer networks usually spanning a
campus or a city. They usually use wireless infrastructure or optical fiber
communications to their sites
For instance a university or college may have MAN that joins together many of the local
area networks (LANs) situated around site of a fraction of square kilometer. Then from
their MAN they could have several Wide Area Network (WAN) links to other universities
or the internet. Specially this type of MAN is known as campus area networks
1. What is the main reason for providing metallic sheath in underground cables?
Answer: The metallic sheath is provided around the insulation to protect it against the
ingress of moisture, gas and other damaging liquids (acid or alkalies) from the soil and
atmosphere
2. What are the main requirements of the insulation materials used for
underground cables?
Answer: Some the properties that insulation material require to possess are high
insulation resistivity, high dielectric strength, good mechanical properties, nonhygroscopic, non inflammable, immune to attacks by acids and alkalies
3. What are the advantages and disadvantages of oil filled cables?
Answer: Some of the advantages and disadvantages of oil filled cables are listed below:
Advantages:
Smaller overall size and smaller weight for given voltage and kVA rating due to
reduction in the thickness of the dielectric required
No ionization, oxidation and formation of voids
More perfect impregnation
Smaller thermal resistance due to decrease in the dielectric thickness, so higher
current rating
More maximum permissible stresses
Fault identification is easy
Disadvantages:
Greater cost
Complicated laying of cables and maintenance
4. Advantages of XLPE cables compared to PVC cables?
Answer:
XLPE cable can withstand higher temperature (90 0C) compared to PVC (700C)
XLPE cables can have higher over-load capacity
XLPE cables are lighter in weight and smaller bend radius hence lower
installation cost
XLPE cable has high short circuit rating
It has lower dielectric and constant power factor which can result in saving of
power
5. What are different insulation materials used in cables for high voltage and
medium voltage?
Answer:
Medium Voltage:
Polyethylene (PE)
Cross linked polyethylene (XLPE)
Tree retardant cross linked polyethylene (TR-XLPE)
Ethylene-Propylene Elastomers (EPR)
PILC
High Voltage:
Cross linked polyethylene (XLPE)
Paper/Oil
Paper/Polypropylene
SF6 gas
NEUTRAL GROUNDING:
Answer: Switch is just a device when can be able to open and close the circuit during
normal operation. Whereas on the other hand circuit breaker has the ability to open and
close the contacts during abnormal or fault conditions. Thus circuit breaker has the
potential to break and make heavy short circuit currents. Auto-reclosures in the circuit
beaker has the ability to re-close after certain designed duration to verify whether the
short circuit was cleared
What is meant by making capacity of the circuit breaker?
Answer: The making capacity of the circuit breaker when closed on a short circuit is the
peak value of the maximum current wave (including dc component) in the first cycle of
the current after the circuit is closed by the circuit breaker
Why current chopping is not common in oil circuit breakers?
Answer: Current chopping is not common in oil circuit breakers because in most of the
oil circuit breakers the arc extinguishing power is proportional to the magnitude of
current to be interrupted
Name the materials used for the contacts of vacuum circuit breakers?
Answer: Copper-Bismuth, Copper-lead, Copper-tellurium, Silver-bismuth, Silver-lead
and Silver-tellurium are some of the alloys employed as contact materials in the vacuum
circuit breakers
Why current chopping considered as serious drawback in a circuit breaker?
Answer: The current chopping is considered as serious drawback because it sets up
high voltage transient across the breaker contacts.
For EHV applications which type of circuit breaker is mostly preferred?
Answer: For Exta High Voltage (EHV) applications SF6 gas insulated switchgear is
preferred
system restores to normal operation. It is not advised to open the breaker contacts and isolate the line for such
small transients. Therefore auto re-closers are employed which when relay senses the fault trips the circuit
breaker contacts. After some time breaker contacts again try to close, if there is no fault in that instant power
system restores to normal operation. However if fault further exists circuit breaker contacts open up
permanently until it is reset. The cycles of closing and opening is designed for the circuit breaker depends on
the application.
Therefore circuit breaker should close under short circuit condition. The MAKING CAPACITY of the circuit
breaker depends on the ability to withstand the effects of electromagnetic forces which which are proportional
to the square of the peak value of the making current. Making current of circuit breaker when closed on short
circuit is the peak value of maximum current wave (including dc component) in the first cycle of the current after
the circuit is closed by the breaker
For determing the making current of the circuit breaker we must multiply symmetrical breaking current by
(2)1/2 to convert to peak value from rms value. and then by 1.8 to take into account the doubling effect of
maximum asymmetry.
Rated Making Current = 1.8 x (2)1/2 rated short circuit breaking current
= 2.55 x rates short circuit breaking current
= 2.55 x symmetrical breaking capacity
Protective reactors are used to reduce the flow of short circuit so as to protect the apparatus from
excessive mechanical stresses and from the overheating and thus protect the system as whole
Protective reactors are used to reduce the magnitude of the voltage disturbances caused by the short
circuits
Reactors also localize the fault by limiting the current that flows into the fault from other healthy
feeders or parts of the system, thereby avoiding the fault from spreading. This increases the chances of
continuity of the supply
Reactors reduce the duty imposed on the switching equipment during the short circuits to be within
economical ratings. So they are used (1) In the systems where extensions have been made and the circuit
breaker rupturing capacities have become inadequate (2) In large systems, so as to limit the short circuit MVA
to mach with the rupturing capacity of the circuit breakers
In general reactors should be placed at the points in the network where they can be most effective. Very few
occasions arise where it is necessary or desirable to introduce reactance in the generator circuits as modern
alternators have sufficient inherent reactance to enable them to withstand the forces of the short circuit.
However when older machines operate in parallel with the older machines, a case may arise where the added
reactance in the circuits of the older machines will provide protection and give them a roughly the same
characteristics as the new machines
Reactors installed in the individual feeder circuits are not an economical proposition as often a considerable
number of feeders are involved. Generally reactors are employed so that a group of feeders where the insertion
of additional reactance is necessary to protect the group of circuit breakers of rupturing capacity. Similarly
interconnection between the new and the old sections of the installation may profitably include a reactor and
thus eliminate the need of replacing old circuit breakers
BATTERY:
Valve Regulated Lead Acid (VRLA) Batteries are popularly termed as maintenance free lead
acid batteries. Each cell in VRLA battery will have a value (automating operating) to allow the
gas to escape if developed by the over charging the cells and to hinder the entrance of oxygen
from the air into the cell
These VRLA batteries are also called sealed lead acid batteries and also recombinant batteries.
Oxygen which evolve during discharging at the positive plate of the battery recombine with the
hydrogen which evolve at the negative plate of the cell to from water. This results in prevention
of the water loss and unlike flooded batteries water is not needed to be added periodically. The
valve present in VRLA cell acts as a safety valve which opens when the concentration of
hydrogen gas inside the battery increases dangerously high. Some of the advantages of VRLA
cell is listed below:
Advantages:
VRLA battery is maintenance free and no periodic water refilling is not required
VRLA batteries will have longer life. Life span of this batteries will be around 10 years
Feasibility for float charge operation with the same voltage of the cells, to continue in
using existing charging equipment
VRLA batteries are economical
What factors that decide the VRLA battery to completely charged from fully discharged condition?
Answer: Some of the important factors that determine the duration of the discharged battery to charge are:
Duration of the discharge occurred
Temperature
Current Transformers (CT) and Potential Transformers (PT) are used to measure the current and voltage in a
circuit of the order of hundreds of amperes and volts respectively.
A CT has large number of turns on its secondary winding, but very few turns on its primary winding. The
primary winding is connected in series with the load so that it carries full load current. A low voltage range
ammeter (0-5A) is connected across the secondary winding terminals. Secondary of the CT is practically short
circuited since the ammeter resistance is very low. It should be remembered that secondary of the CT should
not be made open as it draws heavy current and damages the primary winding of the CT
A PT has large number of turns in the primary and fewer turns in the secondary and hence it steps down the
voltage. The primary winding is connected across the supply voltage and low range voltmeter (0-110V) is
connected across the secondary winding terminals
Some of the main difference between current transformers (CT) and potential transformers (PT) are given
below:
The secondary of the CT is almost short circuit, whereas the secondary of the PT is practically a open
circuit
The primary winding of the CT is connected in series with the load so that it carries the full line current,
but there is only a small voltage across it. However the primary winding of the PT has the full supply voltage
applied across it
In CT the excitation current I 0 and flux density vary over a wide range whereas in PT, they vary over a
limited range only,
Three phase system is widely used in generation, transmission and distribution. Single phase system is only
used to operate small electrical appliances at consumer ends where the power rating is very less. Some of the
advantages of three phase system or poly phase systems compared to single phase system is explained below
Advantages of three phase system:
The output of 3 phase machine is always greater than single phase machine of same size. The output
will be approximately 1.5 times than single phase machine. So for given size and voltage 3 phase alternator or
electrical machines occupy less space and less cost compared to single phase machine having same rating
For transmission of electrical power three phase supply requires less copper or less conducting
material than that of single phase system for given volt-amperes and voltage ratings. Hence 3 phase system is
more economical compared to single phase system
Single phase machines are not self starting machines. On the other hand three phase machines are
self starting due to rotating magnetic field. Therefore in order to start a single phase machine an auxiliary
device is required which not in the case of 3 phase machine.
Power factor of single phase machines is poor compared to three phase machines.
In single phase system the instantaneous power is function of time. Hence fluctuates with respect to
time. The fluctuating power will cause significant vibrations in the single phase machines. Hence performance
of single phase machines is poor. While instantaneous symmetrical three phase system is always constant
Single phase system can be obtained from three phase supply system, vice-versa is not possible
For converting systems like rectifiers, the dc voltage waveform becomes more smoother with the
increase in the number of phases of the system. Hence three phase system is advantageous compared to
single phase system
3 phase motors will have uniform torque whereas single phase motors will have pulsating torque
Parallel operation of three phase generators will be simple compared to single phase generators
because of pulsating reaction in single phase generator
Class Y:
Maximum hot spot temperature for this type of insulator is 90 oC
Some of the materials used are cotton, silk, paper, wood without impregnated
Class A:
Maximum hot spot temperature for this type of insulator is 105 oC
Cotton, Silk, and Paper when suitably impregnated are the type of materials used
Class E:
Hot spot temperature is 120oC
Materials possessing degree of thermal stability allowing them to be operated at
a temperature 15oC above higher than Class A. Ex: wire, enamel etc
Class B:
Maximum hotspot temperature is 130oC
Mica, Glass fibre, asbestos, etc with suitable impregnation or coating substance
Class F:
Hot spot temperature is 155oC
Mica, glass, asbestos etc with suitable binding impregnation or coating
substances capable of withstanding 25oC higher than Class B
Class H:
Maximum hotspot temperature of 180oC
Combination of materials such as mica, glass fibre, asbestos suitably bonded
Class C:
Hotspot temperature above 180oC
Mica, porcelain, glass, quartz and asbestos with and without inorganic binder
Two alternators or synchronous generators which are to be operated in parallel should have same
output voltage rating
The rated speed of the machines which are operating in parallel should be such as to give the same
frequency (f is equal to (PxN)/120)
The alternators should be of the same type so as to generate voltages of the same waveform.
Generators operating can have different power rating (KVA rating)
The prime movers of the alternators should have same speed load characteristics, the nature of
characteristics should be drooping so that load on the generator is proportional to output rating of the
alternators
Without reactancce the alternators will not develop generating power and parallel operation would not
be possible. Hence the alternators should have reactances in armature circuits, otherwise they will not operate
in parallel
Reactive Power if possible should be generated close the load centers or close to the point of its consumption.
Some of the reasons why reactive power cannot be transmitted to long distances are:
It is inefficient during the high real power transfer and also requires higher voltage magnitude
gradients.
It causes high real and reactive power losses if reactive power is transmitted through long distances.
Real power losses should be kept minimum for economic point of view and reactive power should be reduced
to minimize the investment in reactive power devices such as shunt capacitors.
It can lead to damaging temporary over voltages following load rejections. When the receiving end
circuit breaker opens with transmission line still energized from sending end, then over voltages occurs as the
voltage magnitude depends upon the reactive power in the system. Over voltage will damage the insulation of
the conductor and wingdings.
If reactive power is to be transmitted through long distances in the power system It requires larger size
of the equipment (transformers and cables) in the power system.
In Stability analysis investigations the synchronizing force between the machines is affected by the
positive sequence components.
Heating effect due to unbalanced currents depend on the negative sequence components. (when
heating is observed due to unbalanced currents that determines presence of negative sequence component
currents flowing the system. By reducing the unbalanced currents heating effect and negative sequence
components can be reduced.
When earth fault occurs zero sequence currents flows through the system. Hence all ground or earth
fault relay operates on determining the zero sequence components.
Transformer makes "hum" noise because of Magnetostriction effect. Magnetostriction effect is the property of
ferromagnetic magnetic such that change in the dimension of material when the varying magnetic field is
applied.
In electrical transformer alternating voltage is applied to the core. This results in the varying magnetic filed
direction in the core. Grain directions will be varied in every half cycle. Due to this varying magnetic field,
dimensions of the material will be changed causing the vibrations.
Some of the methods employed to reduce the noise are:
Preventing vibration of core-plate, which use the lower flux density
Tightly bolting and clamping the laminations and structural parts of the transformer
Sound insulating the transformer from the tank by cushions, padding and oil barriers
Preventing transformer tank wall vibration by suitable design of tank and stiffeners
compared to the normal transformer oil and moves up in to the conservator. This heat will be dissipated in to
the atmosphere from hot transformer oil.
When load on transformer increases, transformer breather breathes air in. Air contains moisture when come in
contact with the oil will affect the purity of the transformer oil. Moisture and impurity level in the transformer oil
increases results in the damage of insulation property of the transformer oil.
To avoid entry of moisture air in to the transformer silica gel crystals are used. Silica gel will absorb the
moisture in the air and allows dry air in to the transformer. Silica gel will be blue when they are installed or dry.
When the crystals absorb the moisture they turn to pink color.
Thus silica gel protects the insulation strength of the transformer oil by absorbing the moist air entering in to the
transformer.
Consider two conductors carrying current in the same direction "+" sign represents
current flowing into the plane and "." sign represents current flowing out of the plane
When current flowing in the same direction in the two adjacent conductors magnetic
filed will be produced in such a manner that they attract each other
On the other hand, when current flowing in opposite direction in two adjacent
conductors magnetic field will establish in such a manner such that both the conductors
repel each other
However large transformer impedance cause large drop in the power system during the normal operation. This
will cause a significant impact on the starting of the large motors (when large motors are started during low
voltage condition other loads connected to the bus will trip due to huge drop in voltage at the bus) and voltage
regulation of the power system
Hence transformer impedance is designed for a optimum value considering the above conditions.
Stranded Conductors:
Stranded wire consists of sub conductors touch each other. It is costlier to manufacture compared to solid wire.
For the given current carrying capacity the size of the stranded conductor is large compared to solid wire.
Different elements of strands can be wound together to get the transmission line of desired property (eg: ACSR
conductor contains Aluminum and Steel stands wound together). Proximity and skin effect is reduced using
stranded conductors.
Bundled Conductors:
Bundled conductors are employed in Extra High Voltage (EHV) transmission as at higher voltages corona effect
is significant. In bundled conductors sub conductors are placed as certain distance throughout the transmission
lines. This reduces the corona discharge loss and interference with the communication lines nearby.
Bundled conductors per phase reduces the voltage gradient in the vicinity of the line. Thus reduces the
possibility of the corona discharge. (Corona effect will be observed when the air medium present between the
phases charged up and start to ionize and acts as a conducting medium. This is avoided by employing bundled
conductors)
Improvement in the transmission efficiency as loss due to corona effect is countered.
Bundled conductor lines will have higher capacitance to neutral in comparison with single lines. Thus
they will have higher charging currents which helps in improving the power factor.
Bundled conductor lines will have higher capacitance and lower inductance than ordinary lines they will
have higher Surge Impedance Loading (Z=(L/C)1/2). Higher Surge Impedance Loading (SIL) will have higher
maximum power transfer ability.
With increase in self GMD or GMR inductance per phase will be reduced compared to single
conductor line. This results in lesser reactance per phase compared to ordinary single line. Hence lesser loss
due to reactance drop.
Mobility in service
Increase in Reliability
Mobile Substations are employed to provide emergency power supply during natural
disasters and during wars
It also used to supply power when ordinary conventional substation is under
maintenance or fault
It also employed for providing temporary load supply to industrial plants, remote
locations.
Electrical Questions:
1. What are the different conditions for parallel operation of Transformers?
2. What are V and inverted V curves in Synchronous motor and their significance?
3. Explain electrical corona? and methods to reduce the electrical corona?
4. Explain about P, PI and PID controller? Their advantages and disadvantages?
5. What are the different braking methods used in dc motors
6. What is water hammering phenomenon?
7. Advantages of DC motors over AC motors?
8. What is Load factor, Demand factor, Installed capacity, spinning reserve?
9. Which power plants can be used as a peak load plants. Reason?
What is a Signal
Anything which carries information is a signal. A signal is a real (or complex) valued function of one or more
real variable(s).When the function depends on a single variable, the signal is said to be one dimensional. A
speech signal, daily maximum temperature, annual rainfall at a place, is all examples of a one dimensional
signal. When the function depends on two or more variables, the signal is said to be multidimensional. An
image is representing the two dimensional signal, vertical and horizontal coordinates representing the two
dimensions A signal is a description of how one parameter is related to another parameter.
Types of Signal
For example, the most common type of signal in analog electronics is avoltage that
varies with time. Since both parameters can assume a continuous range of values, we
will call this a continuous signal. If this signal is passed through an analog-to-digital
converter force each of the two parameters to be quantized. Signals formed from
parameters that are quantized in this manner are said to be discrete signals. Discrete
signals are quantized in one dimension ( as discrete signal is obtained by sampling of a
continuous signal the signal obtained will be discrete with respect to time axis and
amplitude of the signal is continuous . Digital signals are those which obtained by
taking finite number of distinct values. Digital signals are discrete with respect to both
time and amplitude. Digital signals are quantized in both dimension ( X-axis and Y-axis
particular value exist; signal represented as just like a set of points in the plot depends
on the sampling rate)
Manufacturers of Transformers and alternators does not know at what power factor the consumer uses the
machine and the nature of the load (capacitive, resistive and inductive) connected to the machine. Hence they
rate the transformer depends on the maximum current carry and the voltage to be applied. This rating of the
transformer corresponds to apparent power of the machine (VA). Also iron losses in transformer depends on
the the voltage applied and copper losses depends on the current flowing through the winding. These losses
are independent of the power factor at which the transformer operates.
On the other hand induction motors are rated with real power (Watts) as the machine operating at defined
power factor at full load is pre determined.
Eg: Consider a transformer can carry maximum current of 50A and max voltage applied is 200V. Then
Power rating of the at full load (Unity power factor) = 50x200
= 10kW
Power rating of the at full load (0.5 power factor) = 50x200x0.5 = 5kW (This means load having 0.5 power
factor can connect maximum of 5kW to the transformer. 5kW is the full load of the transformer)
Reactive Power:
Reactive power is the power which will not do any useful work in the power system but helps the active power
to flow. Without Reactive Power active power will not able to flow in the system.
Hence it is understood that for the flow of reactive power from one point to other in power system difference in
the voltage should exist. Active power will flow in power system from leading power angle to lagging power
angle even the voltage at receiving end is higher compared to sending end (still active power flows).
1.
2.
3.
4.
5.
1.
SCADA systems improves the performance of the operation of the plant
2.
SCADA systems provides better protection to the equipment of the plant
3.
SCADA systems improves productivity of the personnel
4.
Information receives very fast, process the information and display it to opertor in graphs and
plots. Hence helps the operator to take the decisions fast.
5.
Provides better energy savings and saves economy.
To reduce this effect to minimum the conductors are transposed. Transposition can be made either to the
power conductors or telephone (communication ) lines.In a transposed line each of the three conductors
occupies all the three positions relative to the other conductors for one third of the total length of the
transmission line. The purpose of transposition is due to balance the capacitance of the line so that electrostatically induced voltages balances out in the transposed lines.
Under balanced condition the conductors magnetic field linking an telephone line is shifted by 120 o out of
phase. As the power lines are transposed, over the length of one complete transposition cycle ( three different
positions of the power conductor) of power line, the net voltage induced in the telephone line is zero. This is
because the sum of three induced voltages which are displaced by 120 o in phase combines zero.
Routine tests:
These are carried out on every transformers before dispatch to ensure that it is in accordance
with the specifications.Some of the tests come under routine test include:
Type Tests:
Type tests are performed on the first transformer of one type and are intended to check the
design characteristics. It is presumed that every transformer would also comply with the type
test, since its design is identical.
Special Test:
Special tests are conducted in the presence of the purchaser or his representatives as specified
in the tender
Vibration test
When dc supply is given to transformer what happens? and which winding will
burn (primary or secondary)?
Electric Grid:
Electrical Grid is an interconnection of power system constitutes generating plants, transmission
network and distribution system ( to consumer ends). In normal grid, energy losses takes place
due to the poor transmission and distribution networks including power thefts which results in
loss in economy.No communication exist between the consumers and grid authorities. Power
consumed is charged at same rate during all the day. So many flaws in today power grid makes
it weak to sustain small disturbances.
Smart Grid:
Smart Grid is an an intelligent, future electricity system that connects all the generating systems
(supply), grid and distribution systems ( consumer terminals) through an intelligent
communication system.Smart Grid is a family of network control systems and asset
management tools, empowered by sensors, communication pathways and information tools.
Simply smart grid is an secure integration of electrical and information infrastructures.
Smart Grid at Consumer's side:
Major focus on the smart grid is on the distribution level or consumers. Demand is what drives
the supply, so better management at consumer level helps the overall system. Important
component of smart grid is 'smart metering'. Older meters connected to consumers just
indicated the units consumed by the consumer. Smart meters evolved in to advanced metering
system where the meter not only stores but also communicates loads and other power statistics
in real time and even advice the consumers for better and optimal load control for reduction in
prices. Smart grid explains and gives choice to the consumers to decide the timing and amount
of power consumption based on the price per unit at that instant. Thus smart grid provides many
wide features to the consumers for reducing the electricity bills and participating the consumers
in improving the performance of the grid.
Smart Grid at Transmission side:
Smart grid helps the Generation and Transmission companies in dealing effectively with the
power thefts and system losses through smart metering and advanced communication features.
This also reduce in the reduction in the CO2 emissions in to atmosphere.
Thus smart grid helps in reducing the losses, electricity bills and global warming and makes the
electrical grid stronger to disturbances.
Please find some more sources related to this and i hope this can become a good seminar topic
as it is the emerging technology and everybody talking about. Add some surveys, reports and
case studies while presenting the seminar topic which makes the subject more informative and
useful.
SCADA systems
SCADA systems:
SCADA systems consists of SCADA Master which is generally referred as SCADA Master Station which
includes SCADA hardware system and SCADA software system and Remote Terminal Unit (RTU). SCADA
master station job is to communicates with Remote Terminal Unit (RTU) for carrying out monitoring, control,
data storage and Human Machine Interface (HMI) operations. SCADA hardware consists of hardware
components such as very reliable PC ( work station ) and its peripherals present in the master station and able
to control the RTUs or PLCs (programmable Logic Controllers) through SCADA software. SCADA software
system was developed to communicate with the PLCs or RTUs for data acquisition and control operations.
Display the real time data received from PLCs, RTUs, and IEDs
Human machine Interface: Includes input and output devices for interaction between the operator and software,
the way the data is displayed in graphs and the commands given to the system
Low voltage generation for particular power level (say 500MW) requires large
size of the stator conductors as huge currents flow through the stator because of low
voltage. ( Any current carrying conductor size is decided by the amount of current
flowing through the conductors). With larger the stator current flowing through the higher
the copper loss and the heat dissipated. Therefore requires better and larger heat
removing medium. Thereby increase in the cost and size of the machine. Low voltage
power generation also results in increase in the size of the generator and occupies
larger space.
On the other hand, increase of the machine voltage significantly beyond the
minimum necessary value results in requirement of more insulation for the generator
stator windings, thus increasing its size and cost. This increase in voltage for power
generation also increases the size of the machine.
Therefore an optimum value of Voltage and Current values are attained for designing
the generator considering the cost and size factors of the generator.
Example:
660 MW electrical generation plant usually operate at 23.5 kV with line currents of about
19,000 A at 0.85power factor.
Electrical Objective Questions With Answers:
1) In a transmission line the distributed constants are:
a) Resistance and Capacitance
b) Capacitance and Inductance
c) Resistance, Inductance, and Capacitance only
d) Resistance, Inductance, Capacitance and Shunt Capacitance
2) If the frequency of the transmission line increases then:
a) Line resistance increases
b) Line resistance decreases
c) Shunt rectance increases
d) Shunt reactance decreases
3) The phenomenon in which the conductor surface carries more current compared to
core when alternative voltage is applied is
a) Corona
b) Skin Effect
c) Ferranti Effect
d) Lenz's Law
4) On what factors does Skin Effect depends:
a) Cross section of the conductors
b) Supply Frequency
c) Permeability of the conductor material
d) all the above
5) The Skin Effect of a conductor reduces with increase in the:
a) Cross section of the conductor
b) Supply frequency
c) permeability of the conductor
d) Resistivity of the conductor material
6) Skin effect of the conductor results in the:
a) decrease in the dc resistance
b) Increase in the dc resistance
c) decrease in the ac resistance
d) Increase in the ac resistance
1.The nature of the current flowing in the armature of the DC machine is:
a) ac
b) dc
c) pulsating
d) dc superimposed on ac
6.A Conductor is rotating within a magnetic field. At which position do the peak voltage occur:
a) At the right angles to the axis of magnetic field
b) Along the axis of the magnetic field
c) At 45 degree angles to the axis of magnetic field
d) Anywhere
8.EMF induced in a coil rotating in a uniform magnetic field will be maximum when the:
a) flux linking with the coil is maximum
b) rate of change of flux linkage is minimum
c) rate of change of flux linkage is maximum
d) rate of cutting flux by the coil sides is minimum
Answers:
(1) a (2) c (3) b (4) a
(5) d (6) b (7) b (8) c
Explanations for the Objective Questions:
1. Answer (a).In the armature of the DC machine the current flow direction will be alternating
manner. This alternating current is made to uni directional with the help of Commutator. This is
the
main
use
of
the
commutator
in
the
DC
machine.
2. Answer (c). Commutator is used to convert the ac current or voltage to dc and dc variables in
to ac. This is interesting, in DC generator the current flow direction in armature winding is ac in
nature, so commutator helps in rectifying ac to dc. In DC motor the current we supply to the
motor is dc, however for armature of dc motor ac current is required to be supplied to produce
alternative flux for generating rotating torque. Hence commutator in DC motor converts dc to ac.
3. Answer (b). The emf produced in the dc generator is dynamically induced emf. This can be
explained
with
the
help
of
faradays
law
electro
magnetic
induction.
4. Answer (a). DC generator works on the principle of faraday's law of electro magnetic
induction
7. Answer (b). Fleming's left hand rule is applicable for DC Motors.
By increasing the spacing between the transmission line conductors. However the
spacing between the lines cannot be increased very much as this effects the size of the tower,
weight of the supporting structures and the land occupied by the tower.Hence the distance
between the conductors should be chosen optimum so that the critical breakdown voltage
increases.
Other factor on which the critical breakdown voltage is diameter of the conductor. By
increasing the diameter of the conductor breakdown voltage of the corona can be increased.
The increase in the conductor diameter results in reduction of the electric field intensity which
reduces the corona. Hence hollow conductors are employed for reducing the corona in EHV
lines.
Conductor:
For dirty surfaced conductor the break down voltage required for corona formation is
less than clean surfaced conductor.
Spacing between Conductors:
With increase in the spacing between the conductors the electrostatic stresses reduces
results in reduced corona effect
Line Voltage:
At low line voltage there will be no corona. When the voltage applied increases
breakdown voltages then corona formation takes place
disadvantage of all the equipment ( bus bars, insulators ) expose to the external atmosphere susceptible to
fault and life of equipment decreases.