Firenet Plus Wiring Instructions

This document provides wiring instructions for FireNET Plus fire alarm control panels. It describes the terminal connections and specifications for the power supply, battery, ground fault, signaling line, and notification appliance circuits. Various models of the FireNET Plus panel are supported, including options for 1 or 2 signaling loops and integrated digital alarm communicator transmitters. Wiring gauges between 18-14 AWG should be used for all field terminations except for the AC power wiring, which requires 14 AWG.

Uploaded by

Daniel Cox
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views8 pages

Firenet Plus Wiring Instructions

This document provides wiring instructions for FireNET Plus fire alarm control panels. It describes the terminal connections and specifications for the power supply, battery, ground fault, signaling line, and notification appliance circuits. Various models of the FireNET Plus panel are supported, including options for 1 or 2 signaling loops and integrated digital alarm communicator transmitters. Wiring gauges between 18-14 AWG should be used for all field terminations except for the AC power wiring, which requires 14 AWG.

Uploaded by

Daniel Cox
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

 

FireNET Plus Wiring Instructions

This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET
Plus panels, which supports our finest Hochiki’s DCP protocol.

Note: Refer to wiring diagrams for specific part numbers and descriptions of all fire control
panels covered in this manual. The operation of this product is intended for indoor use only.

Table of Contents
1. Front Panel View ...................................................................................................... 2
2. Wiring Gauge ............................................................................................................ 2
3. Reference Documents .............................................................................................. 2
4. Terminal Connection................................................................................................. 2
5. Model Description ..................................................................................................... 3
6. Power Supply Circuit ................................................................................................ 3
7. Battery Circuit ........................................................................................................... 4
8. Ground Fault ............................................................................................................. 5
9. Power Output Circuits ............................................................................................... 5
10. Limited Energy Circuit ........................................................................................... 5
11. Supervised Circuits ............................................................................................... 5
12. SLC Circuits .......................................................................................................... 5
13. NAC Circuits .......................................................................................................... 6
1. Maximum Current Ratings ..................................................................................... 6
2. Single and Dual Circuit Synchronization................................................................ 6
14. Communication Circuits......................................................................................... 7
15. Relay Circuits ........................................................................................................ 8
16. Auxiliary Voltage Circuits ....................................................................................... 8
 

Version 1.01
11 March 2015
PN# 1700-10842
 

FireNET Plus Wiring Instruction  1  V1.01 
 

1. Front Panel View


The figure below is the front panel view of the FireNET Plus Panel:

4 ? 2

Figure 1 

2. Wiring Gauge
Use 18 to 14AWG wiring for all field terminations except for AC terminal block. Use
14AWG only for line, neutral and ground of the AC terminations.

3. Reference Documents
For additional information on installing and operating the FireNET Plus Panel, refer to
the following documents:

 FireNET Plus Installation and Operating Manual, 1700-10840, Version 1.04


 Operating Instruction, 1700-10850, Version 0.3
 Inner Door Label, 1700-04520, Version 1.04

4. Terminal Connection
The figure below illustrates the terminal connections of the FireNET Plus Panel:

FireNET Plus Wiring Instruction  2  V1.01 
 

Earth Ground NAC 1 SLC 1 ZERO-OHM SLC 2 ZERO-OHM


10K EOL RESISTOR RESISTOR RESISTOR
S2030 S2026 S2026
TELCO 1

NAC 2 NETWORK
TELCO 2 10K EOL RESISTOR IN
S2030
24V OUT NETWORK COMMS
24VDC OUT RS485

AUX 24V
24VDC RELAYS

Figure 2 

5. Model Description
The following are the details of the various FireNET Plus Models:

 FNP-1127 – 1 SLC Loop, Not Expandable


 FNP-1127D – 1 SLC Loop with Integrated DACT, Not Expandable
 FNP-1127E – 1 SLC Loop Expandable to 2 SLC Loops and Networkable
 FNP-1127DE – 1 SLC Loop with Integrated DACT, Expandable to 2 SLC Loops
and Networkable

6. Power Supply Circuit


Following table is the electrical specification for the Power Supply Circuit:

Line Connection

Terminals Description Voltage Current

L AC Line 115 VAC @ 50/60 Hz 2.1 A max

230 VAC @ 50/60 Hz 1.1 A max

N AC Neutral

Earth Ground
G

FireNET Plus Wiring Instruction  3  V1.01 
 

Power Supply

Parameter Description

Rating 115 VAC @ 250 VA


230 VAC @ 250 VA

AC Input Fuse 3 A, 250 VAC, Slow-Blow, 5 x 20 mm

Input (Supervised) 115 VAC 50/60 Hz or


230 VAC 50/60 Hz

Transfer Voltage 115 VAC transfer @ 75 VAC


230 VAC transfer @ 160 VAC

7. Battery Circuit
Following table is the electrical specification for the Battery Circuit:

Parameter Description

Standby-Battery Type Two 12 VDC, 50 AH, Sealed Lead Acid (SLA), batteries

Standby-Battery Charging Two standby batteries wired in series

Charge Current Fast charge: 1.25 A


Trickle charge: 1.25 A (voltage limited)

Output Current 0 - 4 Amps

Standby-Operating Time 24 Hours

Battery Charge Voltage 27.6 VDC

Fire Control Panel Current Draw D.P. - TBD mA with buzzer sounding
From Battery While In Mains Fail,
Standby And Not in Alarm

Maximum Current Draw D.P. - TBD mA (Current does not include loads from NACs, Solenoid, Remote
of FACP, In Alarm Annunciators, Ancillary Boards and Auxiliary equipment)

Maximum Current Draw 4 Amps


From Batteries

FireNET Plus Wiring Instruction  4  V1.01 
 

8. Ground Fault
A ground fault indication occurs when 30K Ohms or less is detected between earth
ground and the following field terminals of the FireNET Plus Panel:

 24V OUT
 AUX 24V
 NAC1 and NAC 2
 SLC1 and SLC2
 NET IN and NET OUT
 COMMS

9. Power Output Circuits


Special Application outputs are provided on the NAC1 and NAC2 terminals of the
FireNET Plus Panel.

10. Limited Energy Circuit


All circuits are power limited except for AC input/output and the battery.

11. Supervised Circuits


All circuits of the FireNET Plus Panel are supervised except relay terminals for the
TROUBLE, FIRE, SUPERVISORY and the TELCO.

12. SLC Circuits


SLC circuits of the FireNET Plus Panel operates with Hochiki’s DCP-Protocol.

Terminals Description

SLC1 IN, SLC1 OUT Signaling Line Circuits are Class A, Style 7, Class A, Style 6 or Class B,
and SLC2 IN, SLC2 OUT Style 4.

FireNET Plus Wiring Instruction  5  V1.01 
 

13. NAC Circuits


Following table is the specification for the Notification Appliance Circuits (NAC1 and
NAC2):

Parameter Description

Fuse Self-resetting 1.6 A electronic

Regulated Continuous Current Continuous DC currents cannot exceed 1.6 A from NAC 1 and NAC with the
total DC current not to exceed 3.2 A.

Regulated Pulsed Current: Pulse DC currents cannot exceed 900 mA from NAC 1 and NAC with the total
DC current not to exceed 1.8 A.

Special Application 24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2
not to exceed 3.1 A.

Supervision EOL Device, 0400-01023

Synchronization Synchronize the regulated output of NAC 1 and NAC 2 with authorized and
compatible synchronization modules from Gentex, Amseco, System Sensor or
Wheelock. Connect End-Of-Line-Device S2030 to the output of each
Synchronization Module installed.
The FireNET Plus Panel provides internal device synchronization
between the outputs of NAC 1 and NAC 2 when operating NAC devices
from Gentex, Amseco, System Sensor or Wheelock.
External synchronization modules must not be used on the NAC outputs when
operating in the special application mode.

NFPA Operation Type Class B, Style Y

1. Maximum Current Ratings


The total sum of device loads in the NAC circuit must not exceed the maximum current
specified for the FireNET Plus Panel when operating in Continuous Regulated, Pulsed
Regulated, or Special Application mode.

Note: Reference NAC manufacturer datasheets for individual device loads and then
compare the total sum to the maximum current capability of the FireNET Plus Panel in
regulated or special application mode.

2. Single and Dual Circuit Synchronization


NAC channels 1 and 2 of the FireNET Plus Panel provides single and dual circuit
synchronization. Single circuit synchronization provides a synchronized output on one of
two NAC channels. Dual circuit synchronization provides a synchronized output on both
NAC channels.

FireNET Plus Wiring Instruction  6  V1.01 
 

14. Communication Circuits


Phone Line Terminal Connections:

Terminal Description

L1T TELCO Line 1 Tip

L1R TELCO Line 1 Ring

P1T TELCO Phone 1 Tip

P1R TELCO Phone 1 Ring

L2T TELCO Line 2 Tip

L2R TELCO Line 2 Ring

P2T TELCO Phone 2 Tip

P2R TELCO Phone 2 Ring

RS485 Serial Bus:

Terminal Rating

COMMS (+) (+) Data 3.3 VDC @ 30 mA max

COMMS (-) (-) Data

Network Terminals:

Terminal Rating

NET OUT (+) (+) Data 3.3 VDC @ 30 mA max

NET OUT (-) (-) Data

NET IN (+) (+) Data 3.3 VDC @ 30 mA max

NET IN (-) (-) Data

FireNET Plus Wiring Instruction  7  V1.01 
 

15. Relay Circuits


The following is the specification for the FireNET Plus Panel Relays:

Parameter Description

Operation Common: Operates for all of the signals relative to its type (such as alarm, trouble, supervisory).

Current 1A maximum, volt free change over contact

Voltage 30 VDC max

Power Factor 1.0 PF

16. Auxiliary Voltage Circuits


The following is the specification for the FireNET Plus Panel Auxiliary Voltage Circuits:

Terminal Description

24V OUT Regulated 24 VDC @ 360 mA max

AUX 24V Regulated 24 VDC @ 360 mA max

If you have any questions regarding this matter please contact Technical Support. 

Hochiki America Corporation 

Technical Support 

1‐800‐845‐6692 

Technicalsupport@hochiki.com 

FireNET Plus Wiring Instruction  8  V1.01 