750T Hardware Service
750T Hardware Service
Original Instructions
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Table of Contents
Chapter 1
Before You Begin Tests, General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Maintenance, or Repairs Qualified Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Personal Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Product Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Class 1 Light-emitting Diode Product . . . . . . . . . . . . . . . . . . . . . . 12
Remove Power from the Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Commonly Used Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Software Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Hardware Installation Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fastener Torque Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Chapter 2
Preventative Maintenance Recommended Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . 21
Predictive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Schedule Codes Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Shock Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Maintenance of Industrial Control Equipment . . . . . . . . . . . . . . . . . . 32
Solid-state Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 3
Component Inspection and Test Component Inspection and Maintenance . . . . . . . . . . . . . . . . . . . . . . . 35
Procedures Forward and Reverse Biased IGBT/Diode Tests . . . . . . . . . . . . . . . . . 37
AC Input Link Fuses Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
DC Link Fuse Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Component Fuse Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Chapter 4
Control Bay and Control Pod Control Bay and Control Pod Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Components IP/21IP54 Roof Vent Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . 46
Remove the IP21/IP54 Roof Vent Filter. . . . . . . . . . . . . . . . . . . . . 46
Install the IP21/IP54 Roof Vent Filter . . . . . . . . . . . . . . . . . . . . . . 47
IP54/IP21 Roof Vent Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . 47
Remove the IP21/IP54 Roof Vent Fan . . . . . . . . . . . . . . . . . . . . . . 47
Install the IP21/IP54 Roof Vent Fan . . . . . . . . . . . . . . . . . . . . . . . . 48
IP21/IP54 Door Vent Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . 49
Remove the IP21/IP54 Door Vent Filter . . . . . . . . . . . . . . . . . . . . 49
Install the IP21/IP54 Door Vent Filter . . . . . . . . . . . . . . . . . . . . . . 49
Control Pod Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Remove the Control Pod Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Install the Control Pod Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Fiber Transceiver Circuit Board Replacement . . . . . . . . . . . . . . . . . . . 52
Chapter 5
Input Bay Components Input Bay Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
IP21/IP54 Roof Vent Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . 83
IP54/IP21 Roof Vent Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . 83
IP54/IP21, 400/600 mm Wide Door Vent Filters Replacement. . . 83
Remove the IP54/IP21, 400/600 mm Wide Door Vent
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Install the IP54/IP21, 400/600 mm Wide Door Vent Filters . . 84
IP54, 800/1000 mm Wide Door Vent Filters Replacement . . . . . . . 84
Remove the IP54, 800/1000 mm Wide Door Vent Filters . . . . 84
Install the IP54, 800/1000 mm Wide Door Vent Filters . . . . . . 85
IP21, 800/1000 mm Wide Door Vent Filter Replacement . . . . . . . . 85
Remove the IP21, 800/1000 mm Wide Door Vent Filter . . . . . 85
Install the IP21, 800/1000 mm Wide Door Vent Filter . . . . . . . 86
IP54/IP21, 1000 mm Wide Door Vent Fan Replacement . . . . . . . . 86
Remove the IP54/IP21, 1000 mm Wide Door Vent Fan . . . . . . 86
Install the IP21/IP54, 1000 mm Wide Door Vent Fan. . . . . . . . 87
Guard Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Remove the Guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Install the Guards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
AC Precharge Control Circuit Board Replacement . . . . . . . . . . . . . . 90
Remove the AC Precharge Control Circuit Board . . . . . . . . . . . . 90
Install the AC Precharge Control Circuit Board . . . . . . . . . . . . . 93
AC Precharge Time Delay Relay Replacement . . . . . . . . . . . . . . . . . . . 93
Remove the AC Precharge Time Delay Relay . . . . . . . . . . . . . . . . 93
Install the AC Precharge Time Delay Relay . . . . . . . . . . . . . . . . . . 94
AC Precharge TVSS Module Replacement . . . . . . . . . . . . . . . . . . . . . . 94
Remove the AC Precharge TVSS Module . . . . . . . . . . . . . . . . . . . 94
Install the AC Precharge TVSS Module . . . . . . . . . . . . . . . . . . . . . 96
Chapter 6
Power Bay Components Power Bay Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
IP54 Exhaust Vent Filters Replacement . . . . . . . . . . . . . . . . . . . . . . . . 115
Remove the IP54 Exhaust Vent Filters . . . . . . . . . . . . . . . . . . . . . 115
Install the IP54 Exhaust Vent Filters . . . . . . . . . . . . . . . . . . . . . . . 115
IP54 Exhaust Fan Fuse Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Remove the IP54 Exhaust Fan Fuse . . . . . . . . . . . . . . . . . . . . . . . . 116
Install the IP54 Exhaust Fan Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . 117
IP54 Exhaust Fan Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Remove the IP54 Exhaust Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Install the IP54 Exhaust Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
IP54, 400/600 mm Wide Door Vent Filters Replacement . . . . . . . 124
Remove the IP54, 400/600 mm Wide Door Vent Filters. . . . . 124
Install the IP54, 400/600 mm Wide Door Vent Filters . . . . . . 124
IP21 400/600 mm Wide Door Vent Filter Replacement. . . . . . . . . 125
Remove the IP21, 400/600 mm Wide Door Vent Filter . . . . . 125
Install the IP21, 400/600 mm Wide Door Vent Filter . . . . . . . 126
IP54, 800 mm Wide Door Vent Filters Replacement . . . . . . . . . . . . 126
IP21, 800 mm Wide Door Vent Filter Replacement. . . . . . . . . . . . . 126
DC Precharge Module Disconnect Handle and Shaft
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Remove the DC Precharge Module Disconnect Handle
and Shaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Install the DC Precharge Module Disconnect Handle
and Shaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
DC Precharge Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Remove the DC Precharge Module from the Enclosure . . . . . . 128
Install the DC Precharge Module in the Enclosure . . . . . . . . . . 132
Chapter 7
Wire Entry/Exit Bay Components Wire Entry/Exit Bay Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
IP54/IP21, 400 mm Wide Door Vent Filters Replacement . . . . . . 189
IP54/IP21, 800 mm Wide Door Vent Filters Replacement . . . . . . 189
IP54/IP21, 400/800 mm Wide Door Vent Fan and Filter
Assembly Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Remove the IP54/IP21, 400/800 mm Wide Door Vent
Fan and Filter Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Install the IP54/IP21, 400/800 mm Wide Door Vent
Fan and Filter Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Thermal Switch Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Remove the Thermal Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Install the Thermal Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Chapter 8
Start Up After Repairs Before You Apply Power to the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . 195
No-load DC Bus Voltage and Output Current Measurements . . . 199
Appendix A
System Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Notes:
It is highly recommended that you obtain a copy of the PowerFlex Drives with
TotalFORCE Control Programming Manual, publication 750-PM100. The
Programming Manual contains fault, alarm, and programming information
that can help you troubleshoot drive errors and determine if repairs are
necessary.
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
AC Drives Common Bus Application Techniques, Provides basic information to properly wire and
publication 750-AT004 ground common bus PWM AC drives.
PowerFlex 750-Series Products with TotalFORCE Control Provides the basic steps to install PowerFlex 755TL
Installation Instructions, publication 750-IN100 drives, PowerFlex 755TR drives, and PowerFlex 755TM
bus supplies.
PowerFlex 755TM AC Precharge Modules Unpacking and These publications provide detailed information on:
Lifting Instructions, publication 750-IN102 • Component weights
• Precautions and recommendations
PowerFlex 755TM DC Precharge Modules Unpacking and • Hardware attachment points
Lifting Instructions, publication 750-IN103 • Lifting the component out of the packaging
PowerFlex 755TM Power and Filter Modules Unpacking
and Lifting Instructions, publication 750-IN104
PowerFlex 750-Series Service Cart and DCPC Module Lift Provides detailed set-up and operating instructions
Installation Instructions, publication 750-IN105 for the module service cart and lift extension option.
PowerFlex 755TM Power and Filter Module Storage Provides detailed installation and usage instructions
Hardware Installation Instructions, publication 750-IN106 for this hardware accessory.
PowerFlex 755T Module Service Ramp Instructions, Provides detailed usage instructions for the module
publication 750-IN108 service ramp.
PowerFlex Drives with TotalFORCE Control Programming Provides detailed information on:
Manual, publication 750-PM100 • I/O, control, and feedback options
• Parameters and programming
• Faults, alarms, and troubleshooting
PowerFlex 750-Series Products with TotalFORCE Control Provides detailed information on:
Technical Data, publication 750-TD100 • Drive and bus supply specifications
• Option specifications
• Fuse and circuit breaker ratings
Resource Description
PowerFlex 750-Series Safe Speed Monitor Option Module These publications provide detailed information on
Safety Reference Manual, publication 750-RM001 installation, set-up, and operation of the 750-Series
safety option modules.
PowerFlex 750-Series Safe Torque Off Option Module User
Manual, publication 750-UM002
PowerFlex 750-Series ATEX Option Module User Manual,
publication 750-UM003
Industry Installation Guidelines for Pulse Width Modulated Provides basic information on enclosure systems,
(PWM) AC Drives, publication DRIVES-AT003 considerations to help protect against environmental
contaminants, and power and grounding
considerations for installing Pulse Width Modulated
(PWM) AC drives.
Wiring and Grounding Guidelines for Pulse Width Provides basic information to properly wire and
Modulated (PWM) AC Drives, publication DRIVES-IN001 ground PWM AC drives.
Industrial Automation Wiring and Grounding Guidelines, Provides general guidelines for installing a Rockwell
publication 1770-4.1 Automation industrial system.
Safety Guidelines for the Application, Installation, and Provides general guidelines for the application,
Maintenance of Solid State Control, publication SGI-1.1 installation, and maintenance of solid-state control.
Topic Page
General Precautions 12
Remove Power from the Drive System 13
Commonly Used Tools 17
Hardware Installation Diagrams 18
Fastener Torque Sequences 18
Read the information in this chapter before you begin tests, maintenance, or
repairs on drive components.
General Precautions Read the following precautions before you begin to test components, perform
maintenance, or repair the drive.
Qualified Personnel
Personal Safety
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged before servicing. Measure the DC bus voltage
at the -DC and +DC TESTPOINT sockets on the front of the power module
(see Remove Power from the Drive System on page 13 for location).
ATTENTION: Potentially fatal voltages can result from improper usage of an
oscilloscope and other test equipment. The oscilloscope chassis can be at a
potentially fatal voltage if not properly grounded. If an oscilloscope is used to
measure high-voltage waveforms, use only a dual channel oscilloscope in
the differential mode with X 100 probes. It is recommended that the
oscilloscope is used in the A minus B Quasi-differential mode and the
oscilloscope chassis is grounded to an earth ground.
Product Safety
Remove Power from the The following procedures must be followed before attempting to service any
part of the drive system.
Drive System
WARNING: Remove power before you remove or make cable connections.
When you remove or insert a cable connector with power applied, an electric
arc can occur. An electric arc can cause personal injury or property damage in
theses ways:
• An electric arc can send an erroneous signal to system field devices, which
can cause unintended machine motion
• An electric arc can cause an explosion in a hazardous environment
Electric arcs cause excessive wear to contacts on both the module and its mating
connector. Worn contacts can create electrical resistance.
1. Turn off and lockout all input power, including any external power
sources (such as an Active Front End or other DC power source).
5. For regenerative drives and bus supplies, measure the AC input and DC
bus voltage at the following test point sockets in the input bay to verify
that there is no voltage present:
• Using the circuit breaker output (CB1 SEC) test points R/L1, S/L2,
and T/L3, measure L to L and L to chassis GND.
• By using the fused disconnect output (FD1 SEC) test points R, S,
and T, measure L to L and L to chassis GND.
• By using the DC bus test points +DC and -DC, measure +DC to
-DC, +DC to chassis GND, and -DC to chassis GND.
Frame 9, IP21 UL Type 1 Input Bay Shown
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged completely before servicing. Verify that there
is no DC bus voltage present using the +DC to -DC testpoints on all power
modules by measuring +DC to -DC, +DC to GND, and -DC to GND.
6. For common bus inverters, by using the DC bus test points +DC and
-DC on the front of the power modules, measure the DC bus voltage of
all power modules and verify that there is no voltage present on the bus
capacitors. Measure +DC to -DC, +DC to chassis GND, and -DC to
chassis GND.
Commonly Used Tools Table 1 includes the tools that are needed for test measurements, basic
maintenance, and service repairs.
IMPORTANT Care must be taken to be sure that tools and/or hardware components do
not fall into open drive assemblies. Do not energize the drive unless all loose
tools and/or hardware components have been removed from the drive
assemblies and enclosure.
Software Tools
Connected Components Workbench™ software is an application that can be
used to upload and download parameter configuration and monitor system
parameters. Connected Components Workbench version 10.xx or later is
required for use with PowerFlex® 755T products.
Hardware Installation The disassembly illustrations throughout this manual contain diagrams (as
shown here) that identify the following: corresponding sequence number (if
Diagrams necessary), type of fastener, fastener size, tool type and size, and final assembly
torque.
M4 x 10 mm Fastener Size
1 T20 or F - 6.4 mm (0.25 in.) Tool Type and Size
4.8 N•m (42 lb•in) F Flat-nose screwdriver
Sequence Px Phillips screwdriver/bit and size
Number Final Assembly Torque PZx Pozidriv screwdriver/bit and size
Txx torx screwdriver/bit and size
Fastener Type xx mm Hexagonal socket wrench
Flat-head screw
Hexagonal bolt
Hexagonal screw
torx screw
Phillips screw
Pozidriv screw
The following illustrates initial and final tightening sequences for components
that are fastened to a heat sink by using two, four, and six screws. Initial torque
is 1/3 (33%) of final torque, except six-point mountings, which require
0.7 N•m (6 lb•in) initial torque. The numeric illustration labels are for your
assistance. Drive components do not contain these labels.
1 2
1 2
Initial Sequence
2 1
Final Sequence
1 3
4 2
1 2 3 4
Initial Sequence
4 3 2 1
Final Sequence
6 2 4
3 1 5
1 2 3 4 5 6
Initial Sequence
Do not exceed 0.7 N•m (6 lb•in) on initial torque of all six screws.
1 2 3 4 5 6
Final Sequence
Preventative Maintenance
Topic Page
Recommended Preventative Maintenance 21
Predictive Maintenance 22
Schedule Codes Explanation 22
Shock Events 31
Maintenance of Industrial Control Equipment 32
IMPORTANT Duty cycle and load profile can greatly affect the reliability of PowerFlex
750-Series Products with TotalFORCE Control.
Predictive Maintenance PowerFlex 750-Series Products with TotalFORCE Control contain algorithms
for predictive maintenance that are used to improve the “uptime” of machines,
processes, and facilities. These algorithms monitor the lifespan of certain
components and display the calculated value in specific parameters. These
algorithms can be used to alert personnel when the components are nearing the
end of their lifespan so the components can be replaced before they fail. The
shaded rows in Table 2…Table 4 on pages 23…29, respectively, identify the
components with predictive maintenance parameters. Use the predictive
maintenance parameters to determine a replacement schedule for the
applicable components. See Predictive Maintenance with Logix in the
PowerFlex Drives with TotalFORCE Control Programming Manual,
publication 750-PM100, for more information.
Schedule Codes Explanation The codes that are listed in this table are used to identify the task that is
associated with the components that are identified in the tables on pages
23…29.
23
Chapter 2
24
Table 2 - Recommended Maintenance Schedule for Normal Operation (Continued)
Years > 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Chapter 2
25
Chapter 2
26
Table 3 - Recommended Maintenance Schedule for High Temperature Operation
Chapter 2
Years > 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Module/Activity Component Predictive
Maintenance
Parameter (s)
Power Module Grease Power Stabs R R
Balance Resistors R R R
(cat. no. SK-RM-INVBRn-F8M)
Preventative Maintenance
27
Chapter 2
28
Table 3 - Recommended Maintenance Schedule for High Temperature Operation (Continued)
Years > 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Chapter 2
29
Chapter 2
30
Table 4 - Recommended Maintenance Schedule for Harsh Environment Operation (Continued)
Years > 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Chapter 2
Shock Events PowerFlex® 755T products can withstand a finite number of shock events. The maximum allowable number of shock
events increases as the peak amplitude decreases. Below 0.7 g peak, the maximum total shock events should not exceed
2000 cycles.
12
11
10
1
Preventative Maintenance
0
1.00 10.00 100.00 1000.00
Maximum number of shock events
31
Chapter 2
Chapter 2 Preventative Maintenance
Maintenance of Industrial
Control Equipment ATTENTION: Performing service on energized Industrial Control Equipment
can be hazardous. Severe injury or death can result from electrical shock,
bump, or unintended actuation of controlled equipment. Recommended
practice is to disconnect and lockout control equipment from power sources,
and release stored energy, if present. See National Fire Protection Association
Standard No. NFPA 70E, Part II and (as applicable) OSHA rules for Control of
Hazardous Energy Sources (lockout/tagout) and OSHA Electrical Safety
Related Work Practices for safety-related work practices. These publications
include procedural requirements for lockout/tagout, and appropriate work
practices, personnel qualifications, and required training where it is not
feasible to de-energize and lockout or tagout electric circuits and equipment
before working on or near exposed circuit parts.
Blowers and Fans - Inspect blowers and fans that are used for forced air
cooling. Replace any that have bent, chipped, or missing blades, or if the shaft
does not turn freely. Apply power momentarily to check operation. If the unit
does not operate, check and replace wiring, fuse, or blower or fan motor as
appropriate. Clean or change air filters as recommended in the product
manual. Also, clean the fins of heat exchangers so convection cooling is not
impaired.
Contacts - Check contacts for excessive wear and dirt accumulation. Wipe
contacts with a soft cloth, if necessary, to remove dirt. Discoloration and slight
pitting does not harm contacts. Do not file contacts - this action shortens the
life of the contact. Do not use contact spray cleaners because residue on magnet
pole faces or in operating mechanisms can cause sticking, and on contacts can
interfere with electrical continuity. Replace contacts only after the silver has
become badly worn. Always replace contacts in complete sets to avoid
misalignment and uneven contact pressure.
Terminals - Loose connections in power circuits can cause overheating that can
lead to equipment malfunction or failure. Loose connections in control circuits
can cause control malfunctions. Loose bond or ground connections can
increase hazards of electrical shock and contribute to electromagnetic
interference (EMI). Check the tightness of all terminals and bus bar
connections and torque any loose connections properly. Infrared technology
can be used to check for hot (high resistance/loose) connections during
periodic maintenance. Replace any parts or wiring that is damaged by
overheating, and any broken wires or bond straps.
Pilot Lights - Replace any burned out lamps or damaged lenses. Photoelectric
Switches-The lenses of photoelectric switches require periodic cleaning with a
soft dry cloth. Reflective devices that are used with photoelectric switches also
require periodic cleaning. Do not use solvents or detergents on the lenses or
reflectors. Replace any damaged lenses and reflectors.
Solid-state Devices
Locking and Interlocking Devices - Check these devices for proper working
condition and capability of performing their intended functions. Make any
necessary replacements only with Allen-Bradley renewal parts or kits. Adjust or
repair only in accordance with Allen-Bradley instructions.
Topic Page
Component Inspection and Maintenance 35
Forward and Reverse Biased IGBT/Diode Tests 37
AC Input Link Fuses Test 39
DC Link Fuse Test 39
Component Fuse Tests 40
This chapter provides details on how to inspect and test the major components of
the drive and includes recommendations for repairs. Review the Troubleshooting
chapter in the PowerFlex® Drives with TotalFORCE™ Control programming
manual, publication 750-PM100, for information on conditions that can cause a
fault or alarm and how to troubleshoot these conditions.
Component Inspection and Visually inspect the door filters and major components on the control pod, LCL
filter and power modules, DC precharge module, and AC precharge module and
Maintenance components for dirt and damage. Dirt build-up on some components can lead to
component damage or failure. Avoid damage to the product by replacing
components and/or circuit boards with burn marks, breakage, or foil
delamination. Follow these inspection and maintenance instructions along with
the Recommended Preventative Maintenance information on page 21.
Forward and Reverse Biased Follow these steps to perform forward and reverse biased IGBT/diode tests on
the power modules. A failed test indicates damage to the components in the
IGBT/Diode Tests power modules and requires replacement of the power module.
IMPORTANT The actual voltage readings can vary depending upon your equipment. If your
readings are not near the indicated values in Table 5 and Table 6, on page 38,
verify that the actual voltage that is measured is consistent for each phase of
the power module.
5 4 3
ID Connection ID Connection
1 +DC 3 R/L1, U/T1
2 -DC 4 S/L2, V/T2
5 T/L3, W/T3
V/T2 +DC
W/T3 +DC
(1) The actual voltage reading can vary depending upon your equipment.
AC Input Link Fuses Test The AC input link fuses contain fuse indicator switches that signal an open fuse
that will fault the drive system. Follow these steps to perform AC input link fuse
test.
DC Link Fuse Test The DC link fuses contain fuse indicator switches that signal an open fuse that
will fault the drive system. Follow these steps to perform DC link fuse test.
Notes:
This chapter provides detailed instructions for how to remove and replace
control bay and control pod components.
Control Bay and Control Pod Table 7 lists the replacement kits available for the control bay and control pod.
Kits A current list of spare parts for PowerFlex® 750-Series products with
TotalFORCE™ Control is available on the Allen-Bradley® website at:
http://www.ab.com/support/abdrives/powerflex70/PF7ReleasedParts.pdf
Table 7 - Control Bay/Control Pod Replacement Kits
Description Catalog Number Identification Identification No. Replacement Instructions
Ventilation Components
IP21/IP54 Roof Vent Filter SK-RM-IBFAN-54FLTR1 See Figure 5 on page 44 1 See page 46
IP21/IP54 Roof Vent Fan SK-RM-IBFAN1-F8 2 See page 47
IP21/IP54, 300 mm Wide Door Vent Filter SK-RM-CB3DR-FLTR1 3 See page 49
Control Pod Components
Fiber Transceiver Circuit Board 20-750-MFTB1-F8 See Figure 6 on page 45 4 See page 52
Regenerative/Low Harmonic/Inverter SK-RM-MCB1-PF755 5 See page 56
Main Control Circuit Board
Control Pod Backplane Circuit Board SK-RM-PODBP1 6 See page 59
Fiber-optic Interface Circuit Board, SK-RM-FIB1-F8, 7 See page 61
Regenerative and Low Harmonic
Fiber-optic Interface Circuit Board, Low SK-RM-FIB2-F8 7 See page 61
Harmonic
Control Pod Fan Assembly SK-RM-PODFAN1-F8 8 See page 68
Control Pod Assembly, Regenerative and 20-750-MCPOD1-F8M – See page 70
Low Harmonic
Control Pod Assembly, Low Harmonic 20-750-MCPOD2-F8M – See page 70
Control Power Components (1)
240V Power Distribution Fuse (FH2) SK-RM-IBFH2-FUSE2x-Fn See Figure 11 on page 82 13 See page 98
Roof Fan 240V Control Power Fuse (FH3) SK-RM-IBFH3-FUSE3x-Fn 14 See page 99
(1) These components are contained in the control bay for frame 8 and 9 drives and bus supplies. Removal procedures are included in Chapter 6 - Power Bay Components.
4
5
IP/21IP54 Roof Vent Filter Replace an IP21/IP54 roof vent filter on a control or input bay with kit catalog
number SK-RM-IBFAN-54FLTR1.
Replacement
IMPORTANT Verify that the ‘X’ on the filter media is on the side that faces away from the
roof vent.
Install the IP21/IP54 roof vent filter in the reverse order of removal.
IP54/IP21 Roof Vent Fan Replace an IP21/IP54 roof vent fan on a control or input bay with kit catalog
number SK-RM-IBFAN1-F8.
Replacement
M4 x 10 mm
6 T20 or F - 6.4 mm (0.25 in.)
2.6 N•m (23 lb•in)
M4
7 7 mm
2.6 N•m (23 lb•in)
P2 P12
M8
5 13 mm
2.6 N•m (23 lb•in)
Install the IP21/IP54 roof vent fan in the reverse order of removal.
IP21/IP54 Door Vent Filter Replace an IP21/IP54 door vent filter with kit catalog number
SK-RM-CB3DR-FLTR1.
Replacement
IMPORTANT Verify that the Rittal logo on the fiber filter media points inward, toward the
interior of the enclosure.
Install the IP21/IP54 door vent filter in the reverse order of removal.
Control Pod Cover Removal You must remove the control pod cover to access other components inside the
pod.
M4 x 8 mm
4, 5 T20 or F - 6.4 mm (0.25 in.)
2.6 N•m (23 lb•in)
Fiber Transceiver Circuit Replace a fiber transceiver circuit board with kit catalog number
20-750-MFTB1-F8.
Board Replacement
TIP When all or many of the fiber-optic ports are used, it is easier to
remove the fiber transceiver circuit boards from the pod before
removing the fiber-optic cables. However, it is possible to remove
the fiber-optic cables without removing the boards. This procedure
assumes that all fiber-optic ports are used.
ACP0 L0 L1
ACP1 / TAM
M0
M1
L8 M2
L6 M4
L4 M6
L2 M8
L3 M9
L5 M7
L7 M5
L9 M3
6. Loosen the two captive thumb screws that secure the board and fiber-
optic cables to the chassis and remove the board and cables.
–
6 T15 or F - 5 mm (0.19 in.)
0.45 N•m (4 lb•in)
7. For each fiber-optic cable, remove the cable from the transceiver.
8. For each fiber transceiver board, remove the transceivers from the
connector on the board. Retain the transceivers for reuse.
Install the fiber transceiver circuit board in the reverse order of removal.
2. Insert the transceiver with fiber-optic cable into the port on the board,
until you hear an audible ‘click.’
Main Control Circuit Board Replace a main control circuit board with kit catalog number
SK-RM-MCB1-PF755.
Replacement
M3 x 6.4 mm
5 T15 or F - 5 mm (0.19 in.)
0.45 N•m (4 lb•in)
10. Loosen the three captive thumb screws that secure the main control
board to the pod chassis and remove the board.
10
–
10 T15 or F - 5 mm (0.19 in.)
0.45 N•m (4 lb•in)
Install the main control circuit board in the reverse order of removal.
Backplane Circuit Board Replace a control pod backplane circuit board with kit catalog number
SK-RM-PODBP1.
Replacement
M4 x 8 mm
7 T20 or F - 5 mm (0.19 in.)
2.6 N•m (23 lb•in)
Fiber-optic Interface Circuit Replace a fiber-optic interface board with kit catalog number
SK-RM-FIB1-F8 or SK-RM-FIB2-F8.
Board Replacement
J18
8. Remove the fiber-optic cables from the cable management devices in the
control pod.
9. Disconnect the AC precharge circuit board and torque accuracy module
fiber-optic cables from the ACP0 and ACPC1/TAM port on the fiber
transceiver board, respectively. Carefully coil the fiber-optic cable and
secure in a protected location. Follow the minimum bend radius
requirement.
10. For each line side inverter, disconnect the fiber-optic cable from the Ln
port on the fiber transceiver board. Carefully coil the fiber-optic cable
and secure in a protected location. Follow the minimum bend radius
requirement.
11. For each motor side converter, disconnect the fiber-optic cable from the
Mn port on the fiber transceiver board. Carefully coil the fiber-optic
cable and secure in a protected location. Follow the minimum bend
radius requirement.
ACP0 L0 L1
ACP1 / TAM
M0
M1
L8 M2
L6 M4
L4 M6
L2 M8
L3 M9
L5 M7
L7 M5
L9 M3
12. Loosen the screw that secures the HIM bezel to the pod chassis, and
rotate the bezel up to a 90° horizontal position.
13. Disconnect the HIM cable from the port on the main control board.
12
M3 x 6.4 mm
12 T15 or F - 5 mm (0.19 in.)
0.45 N•m (4 lb•in)
13
14. Disconnect the HIM plug-in terminal block for the mini-DIN
connector on the control board.
15. Disconnect any Ethernet cables from the ports on the bottom of the
main control board.
16. Disconnect the plug-in terminal block (TB1) on the bottom of the
main control board.
14
15
16
19. Loosen the three captive thumb screws that secure the main control
board to the pod chassis and remove the board.
19
–
19 T15 or F - 5 mm (0.19 in.)
0.45 N•m (4 lb•in)
20. Remove the four M4 x 8-mm screws that secure the control pod chassis
to the standoffs on the control panel, then remove control pod chassis.
IMPORTANT The four M4 x 8-mm screws that secure the control pod chassis to
the control panel are not retentive. Take steps to be sure that the
screws do not fall into the drive below.
M4 x 8 mm
20 T20 or F - 6.4 mm (0.25 in.)
2.6 N•m (23 lb•in)
21. Remove the three M4 x 8-mm long screws that secure the fiber-optic
interface board to the control pod.
22. Move the fiber-optic interface board slightly upward toward top of the
control pod, so that keyholes on board clear the mounting posts and lift
off the board.
23. Rotate the left side of fiber-optic interface board away from the control
pod so that the board clears the mounting tab on right sidewall of the
control pod. Remove the board from the control pod.
M4 x 8 mm
21 T20 or F - 6.4 mm (0.25 in.)
2.6 N•m (23 lb•in)
Install the fiber-optic interface circuit board in the reverse order of removal.
Control Pod Fan Assembly Replace the control pod fan assembly with kit catalog number
SK-RM-PODFAN1-F8.
Replacement
5. Disconnect the two fan power supply connectors from connectors J18
and J25 on the fiber-optic interface board.
6. Remove the harness from the cable supports on the side of the pod
chassis.
J25
J18
7. Loosen the two captive thumb screws on the fan assembly and pull the
assembly out and off the pod chassis.
–
7 T20 or F - 6.4 mm (0.25 in.)
2.6 N•m (23 lb•in)
Install the control pod fan assembly in the reverse order of removal.
Control Pod Replacement Replace the control pod assembly with kit catalog number
20-750-MCPOD1-F8M or 20-750-MCPOD2-F8M.
5. Remove the fiber-optic cables from the cable management devices in the
control pod.
6. Disconnect the AC precharge circuit board and torque accuracy module
fiber-optic cables from the ACP0 and ACPC1/TAM port on the fiber
transceiver board, respectively. Carefully coil the fiber-optic cable and
secure in a protected location. Follow the minimum bend radius
requirement.
7. For each line side inverter, disconnect the fiber-optic cable from the Ln
port on the fiber transceiver board. Carefully coil the fiber-optic cable
and secure in a protected location. Follow the minimum bend radius
requirement.
8. For each motor side converter, disconnect the fiber-optic cable from the
Mn port on the fiber transceiver board. Carefully coil the fiber-optic
cable and secure in a protected location. Follow the minimum bend
radius requirement.
ACP0 L0 L1
ACP1 / TAM
M0
M1
L8 M2
L6 M4
L4 M6
L2 M8
L3 M9
L5 M7
L7 M5
L9 M3
10
11
J18
16. Loosen the four M4 x 8 mm torx screws that secure the pod chassis to
the back panel.
17. Slide the pod up, so that the keyholes on the pod clear the mounting
screws, and remove the control pod.
M4 x 8 mm
16 T20 or F - 5 mm (0.19 in.)
2.6 N•m (23 lb•in)
Notes:
This chapter provides detailed instructions for how to remove and replace
input bay components.
Input Bay Kits Table 9 lists the replacement kits available for the input bay.
10
9 12
8 7
7
12
9
11
8
Figure 10 - Input Bay Frame 10…12 AC Precharge Module and Control Components Kits
Identification
Frame 12 Input Bay Shown
10
12
8
11
7
14
13
14 13
IP21/IP54 Roof Vent Filter Replace the IP21/IP54 roof vent filters with kit catalog number
SK-RM-IBFAN-54FLTR1. See IP/21IP54 Roof Vent Filter Replacement on
Replacement page 46.
IP54/IP21 Roof Vent Fan Replace the IP54/IP21 roof vent fan with kit catalog number
SK-RM-IBFAN1-F8. See IP54/IP21 Roof Vent Fan Replacement on page 47.
Replacement
IP54/IP21, 400/600 mm Wide Replace the IP54/IP21, 400/600 mm wide door vent filters with the
appropriate kit catalog number:
Door Vent Filters
• 400 mm, SK-RM-IB4DR-FLTR1
Replacement • 600 mm, SK-RM-IB6DR-FLTR1
Follow these steps to remove the IP54/IP21, 400/600 mm wide door vent
filters.
IMPORTANT Verify that the Rittal logo on the fiber filter media points inward, toward the
interior of the enclosure.
Install the IP54/IP21, 400/600 mm wide door vent filters in the reverse order
of removal.
IP54, 800/1000 mm Wide Replace the IP54 door vent filters for an 800 mm wide power bay or 1000 mm
wide input bay with kit catalog number SK-RM-PB8DR-54FLTR1.
Door Vent Filters
Replacement
Remove the IP54, 800/1000 mm Wide Door Vent Filters
Follow these steps to remove the IP54, 800/1000 mm wide door vent filters.
M4 x 10 mm
3 P2 or F - 6.4 mm (0.25 in.)
1.1 N•m (10 lb•in)
Follow theses steps to install the IP54, 800/1000 mm wide door vent filters.
IMPORTANT Verify that the weep holes on the metal mesh filter are at the bottom of the
filter when installed.
1. Insert the metal mesh filter into the filter cassette cover.
2. Place the slots on the cassette cover on the tabs on the door vent chassis.
IMPORTANT Verify that the airflow direction arrow on the fiber filter media points
inward, toward the interior of the enclosure.
3. Insert the fiber filter in the cassette chassis on the door and close and
secure the cassette cover to the door.
IP21, 800/1000 mm Wide Replace the IP21 door vent filters for an 800 mm wide power bay or 1000 mm
wide input bay with kit catalog number SK-RM-PB8DR-21FLTR1.
Door Vent Filter
Replacement
Remove the IP21, 800/1000 mm Wide Door Vent Filter
Follow these steps to remove the IP21, 800/1000 mm wide door vent filter.
3. Loosen the four slotted-Phillips head, captive screws that secure the
filter cassette cover and metal mesh filter to the cassette chassis on the
door and remove the cover and filter.
M4 x 10 mm
3 P2 or F - 6.4 mm (0.25 in.)
1.1 N•m (10 lb•in)
Follow theses steps to install the IP21, 800/1000 mm wide door vent filter.
IMPORTANT Verify that the weep holes on the metal mesh filter are at the bottom of the
filter when installed.
1. Place the slots on the cassette cover on the tabs on the door vent chassis.
2. Insert the filter in the cassette chassis on the door and close and secure
the cassette cover to the door.
IP54/IP21, 1000 mm Wide Replace the IP54/IP21, 1000 mm wide door vent fan for an input bay with kit
catalog number SK-RM-IBDR-FAN1.
Door Vent Fan Replacement
Remove the IP54/IP21, 1000 mm Wide Door Vent Fan
Follow these steps to remove the IP54/21, 1000 mm wide door vent fan.
M4 x 14 mm
5 T20
2.6 N•m (23 lb•in)
P12
P13
Follow theses steps to install the IP21/IP54, 1000 mm wide door vent fan.
IMPORTANT Verify that the airflow direction arrow on the fan points inward, toward the
interior of the enclosure.
Guard Removal You must remove the guards to access other components inside the input bay.
2. Remove system power. See Remove Power from the Drive System on
page 13.
3. Open the input bay enclosure door.
4. Loosen the M5.5 x 13 mm torx screws that secure the guard to the
enclosure and remove the guard.
• 400 mm wide input bay guards require removal of six screws.
• 600 mm wide input bay guards require removal of six screws.
• 1000 mm wide input bay guards require removal of 28 screws.
M5.5 x 13 mm
4 T25
2.6 N•m (23 lb•in)
Frame 8 Input Bay Frame 9 Input Bay
M5.5 x 13 mm
4 T25
2.6 N•m (23 lb•in)
AC Precharge Control Circuit Replace the AC precharge control circuit board with kit catalog numbers
20-750-MACPC1-CD and 20-750-MACPC1-EF.
Board Replacement
M5 x 12 mm
7 T25
2.6 N•m (23 lb•in)
5 and 6
• P4 from J4
• P5 from J5
• P6 from J6
• P7 from J7
• P11 from J11
• P12 from J12, if present
= ACP
3 3 1
1
J1 J12
+
+
+
+
8
6
J2
1
8 7 6 5 4 3 2 1
1 2
ON
J11
2
1
2
15 16
10
9
J3
6
1
12
10
8
6
5
4
3
2
1
J4
1
J8
3
J5 J7 J6
6 1 4 1 9 1
Install the AC precharge control circuit board in the reverse order of removal.
IMPORTANT Verify that the two pins on the back of the AC precharge module chassis are
properly inserted into the two holes on the circuit board panel before
tightening the panel mounting screws.
AC Precharge Time Delay Replace the AC precharge time delay relay with kit catalog number
20-750-MACPC-TDR.
Relay Replacement
Follow these steps to remove and replace the AC precharge time delay relay.
6. Pull up on the bottom of the relay chassis and lift it up and off the DIN
rail.
Install the AC precharge time delay relay in the reverse order of removal.
AC Precharge TVSS Module Replace the AC precharge TVSS module with kit catalog number
20-750-MACP-xx-TVSS.
Replacement
Remove the AC Precharge TVSS Module
Follow these steps to remove and replace the AC precharge TVSS module.
7. Loosen the terminal block screws that secure the wires to terminals R/
L1, S/L2, T/L3, and remove the wires.
= 7
6
M6 x 10 mm
6 T25
5.9 N•m (52 lb•in)
M6
6 10 mm 5
5.9 N•m (52 lb•in)
–
7 P2
4.0 N•m (35 lb•in)
M4 x 10 mm
7 T20 or F - 6.4 mm (0.25 in.)
2.6 N•m (23 lb•in)
AC Precharge Control Circuit Replace the AC precharge control circuit board fuses (labeled FH1) with the
appropriate kit catalog number that is identified in Table 10.
Board Fuses (FH1)
Replacement Table 10 - AC Precharge Control Circuit Board Fuse (FH1) Kit Ratings
Frame Size Voltage Class Fuse Kit Cat. No. Fuse Amp Quantity
Rating
8…12 400V/480V/600V SK-RM-IBCB-FUSE1A-F8 1 3
8…12 690V SK-RM-IBCB-FUSE1B-F9 1 3
For frames 8 and 9, the fuse holders (labeled FH1) are located in the AC
precharge module in the input bay. For frames 10…12, the fuse holders (labeled
FH1) are on the control panel in the input bay. Follow these steps to remove
and replace the AC precharge control circuit board fuses.
5. Pull out the tabs at the top of the fuse holders and remove the fuses.
Frame 8 AC Precharge Module Frame 10 Input Bay
Install the AC precharge control circuit board fuses in the reverse order of
removal.
240V Power Distribution Fuse Replace the 240V power distribution fuse (labeled FH2) with the appropriate
kit catalog number that is identified in Table 11.
(FH2) Replacement
Table 11 - 240V Power Distribution Fuse (FH2) Kit Ratings
Frame Size Voltage Class IP Rating Fuse Kit Cat. No. Fuse Amp Rating
8 400V/480V/600V IP21 SK-RM-IBFH2-FUSE2A-F8 15
690V SK-RM-IBFH2-FUSE2B-F8 16
400V/480V/600V IP54 SK-RM-IBFH2-FUSE2C-F8 20
690V SK-RM-IBFH2-FUSE2D-F8 20
9 400V/480V/600V IP21 SK-RM-IBFH2-FUSE2E-F9 25
690V SK-RM-IBFH2-FUSE2F-F9 25
400V/480V/600V IP54 SK-RM-IBFH2-FUSE2G-F9 35
690V SK-RM-IBFH2-FUSE2H-F9 40
10 400V/480V/600V IP21 SK-RM-IBFH2-FUSE2G-F9 35
690V SK-RM-IBFH2-FUSE2H-F9 40
400V/480V/600V IP54 SK-RM-IBFH2-FUSE2I-F10 60
690V SK-RM-IBFH2-FUSE2J-F10 63
11 400V/480V/600V IP21 SK-RM-IBFH2-FUSE2K-F11 45
690V SK-RM-IBFH2-FUSE2L-F11 50
400V/480V/600V IP54 SK-RM-IBFH2-FUSE2M-F11 70
690V SK-RM-IBFH2-FUSE2N-F11 80
12 400V/480V/600V IP21 SK-RM-IBFH2-FUSE2I-F10 60
690V SK-RM-IBFH2-FUSE2J-F10 63
400V/480V/600V IP54 SK-RM-IBFH2-FUSE2O-F12 70
690V SK-RM-IBFH2-FUSE2P-F12 80
Fuse holder (labeled FH2) is on the control panel in the input bay. Follow
these steps to remove and replace the 240V power distribution fuse.
5. Pull out on the tab at the top of the fuse holder and remove the fuse.
Frame 8 Input Bay Frame 10 Input Bay
Install the 240V power distribution fuse in the reverse order of removal.
Roof Fan 240V Control Power Replace the roof fan 240V control power fuse (labeled FH3) with the
appropriate kit catalog number that is identified in Table 12.
Fuse (FH3) Replacement
Table 12 - Roof Fan 240V Control Power Fuse (FH3) Kit Ratings
Frame Size Voltage Class IP Rating Fuse Kit Cat. No. Fuse Amp
Rating
8 and 9 400V/480V/600V IP21 / IP54 SK-RM-IBFH3-FUSE3B-F8 2
690V SK-RM-IBFH3-FUSE3A-F8 2
10…12 400V/480V/600V IP21 / IP54 SK-RM-IBFH3-FUSE3D-F10 4
690V SK-RM-IBFH3-FUSE3C-F10 4
Fuse holder (labeled FH3) is on the control panel in the input bay. Follow
these steps to remove and replace the roof fan 240V control power fuse.
2. Remove system power. See Remove Power from the Drive System on
page 13.
3. Open the input bay enclosure door.
4. Remove the guard from the enclosure. See Guard Removal on page 87.
5. Pull out on the tab on the fuse holder and remove the fuse.
Control Bay Frame 10 Input Bay
Control Transformer Fuses Replace the control transformer fuses (labeled FH4…FH7) with the
appropriate kit catalog number that is identified in Table 13.
(FH4…FH7) Replacement
IMPORTANT Control transformer fuse quantities vary based on the product voltage class
and IP rating. It is recommended that you replace all control transformer
fuses.
For frame 8, the fuse holders (labeled FH4) are located in the AC precharge
module in the input bay. For frames 9…12, the fuse holders (labeled
FH4…FH7) are on the control panel in the input bay. Follow these steps to
remove and replace the control transformer fuses.
5. Pull out on the tabs at the top of the fuse holder and remove the fuse.
Frame 8 AC Precharge Module Frame 10 Input Bay
AC Precharge Fused Replace the AC precharge fused disconnect (FD1) fuses with the appropriate
kit catalog number that is identified in Table 14.
Disconnect (FD1) Fuses
Replacement Table 14 - AC Precharge Fused Disconnect (FD1) Fuse Kit Ratings
Frame Size Voltage Class Kit Cat. No. Fuse Amp Rating Qty
8 400V/480V/600V SK-RM-IBD-FUSEA-F8 30 3
690V SK-RM-IBD-FUSEB-F8 32 3
9 400V/480V SK-RM-IBD-FUSEC-F9 70 3
600V SK-RM-IBD-FUSED-F9 60 3
690V SK-RM-IBD-FUSEE-F9 63 3
10 400V/480V SK-RM-IBD-FUSEF-F10 110 3
600V SK-RM-IBD-FUSEG-F10 80 3
690V SK-RM-IBD-FUSEH-F10 80 3
11 400V/480V SK-RM-IBD-FUSEI-F11 150 3
600V SK-RM-IBD-FUSEF-F10 110 3
690V SK-RM-IBD-FUSEJ-F12 125 3
12 400V/480V SK-RM-IBD-FUSEK-F12 200 3
600V SK-RM-IBD-FUSEI-F11 150 3
690V SK-RM-IBD-FUSEL-F12 160 3
For frames 8 and 9, the fused disconnect fuse holders (FD1) are located in the
AC precharge module in the input bay. For frames 10…12, the fused
disconnect fuse holders (FD1) are on the control panel in the input bay. Follow
these steps to remove and replace the AC precharge fused disconnect fuses.
5. Pull the front of the fuse assembly out and remove the fuses.
Frame 8 AC Precharge Module Frame 10 Input Bay
Install the AC precharge fused disconnect fuses in the reverse order of removal.
Control Transformers Control transformers are not available as a replacement kit. See the PowerFlex
755TM IP00 Open Type Kits, Technical Data, publication 750-TD101, for a
complete list of Rockwell Automation recommended control transformer
vendor catalog numbers.
This chapter provides detailed instructions for how to remove and replace
power bay components.
Power Bay Kits Table 15 lists the replacement kits available for the power bay.
4 5
7
6
8
Figure 14 - DC Link/Fuse Kits Identification
10
12
11
13
14
18
15
17 16
Figure 18 - LCL Filter and Power Module Fan Assembly and Fan Fuse Kits Identification
21
20
24
25
IP54 Exhaust Vent Filters Replace the IP54 exhaust vent filters on a power bay with kit catalog number
SK-RM-PBFAN-54FLTR1.
Replacement
Follow these steps to remove the IP54 exhaust vent filters on a power bay.
IMPORTANT Verify that the airflow direction arrow and “X” on the fiber filter media
points inward, toward the interior of the enclosure.
Install the IP54 exhaust vent filters on a power bay in the reverse order of
removal.
IP54 Exhaust Fan Fuse Replace the exhaust fan fuse on a power bay with kit catalog number
SK-RM-INVFAN1-FUSE (Time Delay, 250V, 3.5 A, Cartridge).
Replacement
Follow these steps to remove the IP54 exhaust fan fuse on a power bay.
4. Remove the four M8 x 12 mm torx screws that secure the screen to the
front of the fan housing and remove the screen.
5. Unscrew the fuse holder and fuse and remove the fuse.
M8 x 12 mm
4 T30
19.8 N•m (175 lb•in)
Install the IP54 exhaust fan fuse on a power bay in the reverse order of removal.
Tightening torque for the fuse holder is 3.4 N•m (30 lb•in).
IP54 Exhaust Fan Replace the exhaust fan on a power bay with kit catalog number
SK-RM-PBFAN1-F8.
Replacement
Follow these steps to remove and replace the IP54 exhaust fan on a power bay.
M8
4 13 mm
10.2 N•m (90 lb•in)
PE
P1
P12
6. Slide the front and rear vent covers up until the tabs on the vent cover
clear the slots on the vent housing, and remove the vent covers.
7. Remove the eight M8 x 12 mm torx screws that secure the metal screens
to the front and rear of the vent housing and remove the screens.
M8 x 12 mm
4 T25
19.8 N•m (175 lb•in)
8. Remove the four M5 x 12 mm torx screws that secure the vent assembly
cover to the fan assembly and remove the cover.
M5 x 12 mm
5 T25
6 N•m (53 lb•in)
9. Cut the cable ties that secure the wire harness to the fan housing.
10. Disconnect the two wires from the fuse holder on the front of the vent
housing.
11. Remove the two M3 x 20 mm Phillips head screws (white) that secure
the interconnection terminal block to the fan housing and remove the
terminal block.
12. Remove the two M4 x 11 mm torx screws that secure the fan power
connector to the fan and remove the connector and wires.
13. Remove the four M5 x 5 mm nuts that secure the fan assembly and
housing to fan base and carefully lift the fan assembly and housing from
off the base. As you lift the fan assembly and housing, pull the wire
harness carefully through the opening in the enclosure roof.
M3 x 20 mm
8 P1 10
8
0.6 N•m (5.3 lb•in) 9
M4 x 11 mm
9 T20 10
3 N•m (26.5 lb•in)
M5 x 5 mm
10 8 mm
6.5 N•m (58 lb•in)
10
10
14. Place the fan and housing assembly on a support block that is on a solid
work surface, with only the fan in contact with a support block. The
support under the fan allows you to lift the metal housing off the fan
unit after the screws have been removed.
15. Remove the four M6 x 16 mm torx screws that secure the fan to the roof
assembly housing and lift the fan housing off the fan.
M6 x 16 mm
12 T30
10 N•m (90 lb•in)
Install the IP54 exhaust fan on a power bay in the reverse order of removal.
IP54, 400/600 mm Wide Door Replace the IP54, 400/600 mm wide door vent filters with the appropriate kit
catalog number:
Vent Filters Replacement
• 400 mm, SK-RM-PB4DR-54FLTR1
• 600 mm, SK-RM-PB6DR-54FLTR1
Follow theses steps to install the IP54, 400/600 mm wide door vent filters.
IMPORTANT Verify that the weep holes on the metal mesh filter are at the bottom of the
filter when installed.
1. Insert the metal mesh filter into the filter cassette cover.
2. Place the slots on the cassette cover on the tabs on the door vent chassis.
IMPORTANT Verify that the airflow direction arrow on the fiber filter media points
inward, toward the interior of the enclosure.
3. Insert the fiber filter in the cassette chassis on the door and close and
secure the cassette cover to the door.
IP21 400/600 mm Wide Door Replace the IP21, 400/600 mm wide door vent filter with the appropriate kit
catalog number:
Vent Filter Replacement
• 400 mm, SK-RM-PB4DR-21FLTR1
• 600 mm, SK-RM-PB6DR-21FLTR1
Follow these steps to remove the IP21, 400/600 mm wide door vent filter.
Follow theses steps to install the IP21, 400/600 mm wide door vent filter.
IMPORTANT Verify that the weep holes on the metal mesh filter are at the bottom of the
filter when installed.
1. Place the slots on the cassette cover on the tabs on the door vent chassis.
2. Insert the filter in the cassette chassis on the door and close and secure
the cassette cover to the door.
IP54, 800 mm Wide Door Replace the IP54, 800 mm wide door vent filters with kit catalog number
SK-RM-PB8DR-54FLTR1. See IP54, 800/1000 mm Wide Door Vent Filters
Vent Filters Replacement Replacement on page 84.
IP21, 800 mm Wide Door Replace the IP21, 800 mm wide door vent filters with kit catalog number
SK-RM-PB8DR-21FLTR1. See IP21, 800/1000 mm Wide Door Vent Filter
Vent Filter Replacement Replacement on page 85.
DC Precharge Module Replace the DC precharge module disconnect handle and shaft with kit
catalog number SK-RM-DCPC-HNDL.
Disconnect Handle and Shaft
Replacement
Remove the DC Precharge Module Disconnect Handle and Shaft
Follow these steps to remove and replace the DC precharge module disconnect
handle and shaft.
M4 x 12 mm
4 T20
6.2 N•m (55 lb•in)
5. Remove the six M5 x 10 mm screws that secure the front cover to the
DC precharge unit and remove the cover.
6. Loosen the hexagonal screw that secures the disconnect handle shaft to
the disconnect switch and remove the handle.
M5 x 10 mm
5 T20
6.2 N•m (55 lb•in)
–
6 2.5 mm
0.6 N•m (5.4 lb•in)
Install the DC precharge module disconnect handle and shaft in the reverse
order of removal.
DC Precharge Module You must remove the DC precharge module from the enclosure to access
components inside the module. To remove the DC precharge module, you
must first remove the power module that is connected to the DC precharge
module. See Power Module Replacement on page 140.
Follow these steps to remove the DC precharge module from the enclosure.
4. Loosen the two M6 x 16 mm torx screws that secure the side guards to
the enclosure.
5. Loosen the two M6 x 16 mm torx screws that secure the bottom guard
to the enclosure.
M6 x 16 mm
4, 5 T30
4.8 N•m (42 lb•in)
8. Loosen the thumb screw that secures the connections cover to the front
of the power module.
9. Use the screw to lift the connections cover up and off the power module
chassis.
10. Disconnect connector P3 from J3 on the power module I/O control
panel.
11. Disconnect connector P4 from J4 on the power module I/O control
panel.
12. Without bending the cable to a radius less than 50 mm (2 in.), remove
the fiber-optic cable from the transceiver in the PDI port on the power
layer interface circuit board.
–
5 P2 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)
10
11
12
13. Remove the fiber-optic cable from the power module chassis.
14. Remove the power module from the enclosure. See Power Module
Replacement n page 140.
15. Remove the two M6 x 16 mm hex screws that secure the bottom of the
DC precharge module to the control bus support.
16. Remove the two M6 x 16 mm hex screws that secure the top of the DC
precharge module to the enclosure roof support bracket.
M6 x 16 mm
15, T30
16
10.2 N•m (90 lb•in)
17. To remove the module by using the service cart and DC precharge
module lift, follow the detailed instructions in the PowerFlex 750-Series
Service Cart and DCPC Module Lift Installation Instructions,
publication 750-IN105.
18. Remove the module out of the enclosure.
Install the DC precharge module into the enclosure in the reverse order of
removal.
1. Remove the transceiver from the fiber-optic port on the power layer
interface circuit board.
DC Precharge Circuit Board Replace the DC precharge module circuit board with the appropriate kit
catalog number:
Replacement
• SK-RM-DCPC1-CD (400V/480V)
• SK-RM-DCPC1-EF (600V/690V)
Follow these steps to remove and replace the DC precharge circuit board.
5. Remove the six M5 x 10 mm torx screws that secure the circuit board
cover to the DC precharge chassis.
M5 x 10 mm =
5 T25
2.8 N•m (25 lb•in)
= J2
J1
J3
J7
+
DCP
+
+
J9
+
+
+
1 J10
DC Precharge Fuses Replace the DC precharge fuses with the appropriate kit catalog number that is
identified in Table 16.
Replacement
IMPORTANT It is recommended that you replace both DC precharge fuses.
5. Remove the four M12 hex nuts that secure the fuses to the bus bars.
6. Pull the fuses out of the chassis and disconnect the signal cables from the
indicator switches.
Side and Back Panels Not Shown for Clarity Only.
M12
5 19 mm
45.0 N•m (398 lb•in)
Guard Removal When AC input bus bars and fuses or DC link and fuse assemblies are installed
in the power bay, you must remove the upper guard to access other
components.
M5.5 x 13 mm
4 T25
2.6 N•m (23 lb•in)
Power Module Replacement Replace the power module with the appropriate kit catalog number:
• 20-750-MI1-CnnnDnnn
• 20-750-MI1-EnnnFnnn
• 20-750-MI2-CnnnDnnn
• 20-750-MI2-EnnnFnnn
• 20-750-MI3-CnnnDnnn
• 20-750-MI3-EnnnFnnn
Equipment is available that is designed to help you safely handle the power
modules. The following equipment is recommended:
• PowerFlex 750-Series module service cart, catalog number 20-750-
MCART1, publication 750-IN105
• PowerFlex 750TM power and LCL filter module storage hardware,
catalog number 20-750-MINV-ATIP, publication 750-IN106
• PowerFlex 755T power module service ramp, catalog number 20-750-
MRAMP1, publication 750-IN108
IMPORTANT The service ramp is used only with power module when the cabinet is
mounted directly to the floor. Do not use the ramp to remove LCL filter
modules from the cabinet. Review service ramp instructions before using.
Follow these steps to remove the power module from the enclosure.
ATTENTION: IGBT power and LCL filter modules have a high center of gravity
and a tip-over hazard exists. To guard against death, serious personal injury,
or equipment damage, do not subject the module to high rates of
acceleration or deceleration while transporting. Do not push or pull above
the points that are indicated on the module.
M6 x 16 mm
5 T30
4.8 N•m (42 lb•in)
6. Loosen the thumb screw that secures the connections cover to the front
of the power module.
7. Use the screw to lift the connections cover up and off the power module
chassis.
–
6 P2 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)
P1
P3 P4
13. Loosen the two M10 x 10 mm hex nuts and bolts that secure the power
input/output terminals to the DC precharge module or DC link fuse
terminals.
14. Remove the two M10 x 20 mm torx screws that secure the power
module chassis to the control bus frame.
15. Leave the two M10 x 20 mm screws that secure the power module
chassis to the floor mounting bracket while preparing the PowerFlex
750-Series service cart or service ramp.
14
13 14
M10 x 10 mm
13 17 mm
38 N•m (336 lb•in)
M10 x 20 mm
14, T45
17 42.4 N•m (375 lb•in)
16. To remove the module by using the service cart, follow the detailed
instructions in the PowerFlex 750-Series Service Cart and DCPC
Module Lift Installation Instructions, publication 750-IN105.
To remove the module using PowerFlex 755TM service ramp, follow the
procedures that are detailed in the PowerFlex 755T Module Service
Ramp Instructions, publication 750-IN108.
17. To release the LCL filter module, remove the two remaining M10
screws.
18. Remove the power modules from the enclosure.
Install the power module into the enclosure in the reverse order of removal.
1. Remove the transceiver from the fiber-optic port on the power layer
interface circuit board.
DC Link Fuses Replacement Replace the DC link fuses with the appropriate kit catalog number that is
identified in Table 17.
IMPORTANT It is recommended that you replace both DC link fuses for each power
module installed.
–
5 P2 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)
8. Remove the four M12 x 13 mm hex nuts that secure the fuses to the DC
link bus bars and remove the fuses.
M12 x 13 mm
8 19 mm
45 N•m (398 lb•in)
Power Module PE-B1 Power Replace the power module PE-B1 power jumper with kit catalog number
SK-RM-INV-JMPR-F8.
Jumper Replacement
Follow these steps to remove and replace the power module PE-B1 power
jumper.
4. If present, remove the guards from the enclosure. See Guard Removal on
page 139.
5. Loosen the torx thumb screw that secures the connections cover to the
front of the power module. 1.8 N•m (16 lb•in)
6. By using the thumb screw, lift the connections cover up and off the
power module chassis.
7. Remove the jumper from connector P5/P6 on the power layer interface
circuit board.
–
5 P2 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)
Install the power module PE-B1 power jumper in the reverse order of removal.
Circuit Board Tray Removal You must remove the circuit board tray from the power module to access the
power layer interface and power interface circuit boards.
2. Remove system power. See Remove Power from the Drive System on
page 13.
3. Open the corresponding power bay enclosure door.
4. Remove the power module from the enclosure. See Power Module
Replacement on page 140.
5. Remove the three M6 x 16 mm torx screws that secure the left-side cover
to the power module chassis and remove the cover.
M6 x 16 mm
5 T30
5.2 N•m (46 lb•in)
4
2
J13 +
=
3
+
PDI CTL
P4 P5
+ P6
P12
+
+
+
+
+
P10
+ P11
+
+
+ +
+
+
+
+
+
P3
P7 P8 P9 E2
9. Remove all cables from the cable mounts on the front of the circuit
board tray.
10. Remove the three M5 x 12 mm slotted-torx screws that secure the circuit
board tray to the power module chassis and, remove the tray by rotating
the left side away from the chassis and by sliding the tabs on the right
side of the tray out of the mounting slots.
M5 x 12 mm
10 T25
6 N•m (53 lb•in)
1. Remove the transceiver from the fiber-optic port on the circuit board.
Power Layer Interface Circuit Replace the power module power layer interface circuit board with kit catalog
number SK-RM-PLI1-F8.
Board Replacement
Two versions of the circuit board tray are released. Each version of the tray uses
different screw sizes to secure the power layer interface circuit board to the tray.
Circuit board trays and screw combinations for the power layer interface board
include:
• Part number PN-371633 contains five M3 x 20 mm slotted-torx screws
• Part number PN-417691 contains five M4 x 18 mm slotted-torx screws
Follow these steps to remove and replace the power layer interface circuit
board.
IMPORTANT The power layer interface circuit board replacement kit excludes screws.
Therefore, all existing screws for this board must be reused. Verify the screw
size that is supplied with your circuit board tray and apply the recommended
torque during reinstallation.
8. Slide the board to the right to disconnect the two 64-pin edge
connectors and remove the circuit board.
M3 x 3 mm
7 T20
0.6 N•m (5.0 lb•in)
OR
M4 x 18 mm
7 T20
2.6 N•m (23.0 lb•in)
Install the power layer interface circuit board in the reverse order of removal.
Power Interface Circuit Board Replace the power module power interface circuit board with the appropriate
kit catalog number:
Replacement
• SK-RM-PIB1-CnnnDnnn
• SK-RM-PIB1-EnnnFnnn
• SK-RM-PIB2-CnnnDnnn
• SK-RM-PIB2-EnnnFnnn
• SK-RM-PIB3-CnnnDnnn
• SK-RM-PIB3-EnnnFnnn
Two versions of the circuit board tray are released. Each version of the tray uses
different screw sizes to secure the power interface circuit board to the tray.
Circuit board trays and screw combinations for the power interface board
include:
• Part number PN-371633 contains five M4 x 10 mm slotted-torx screws
• Part number PN-417691 contains five M4 x 18 mm slotted-torx screws
Follow these steps to remove and replace the power interface circuit board.
IMPORTANT The power interface circuit board replacement kit excludes screws.
Therefore, all existing screws for this board must be reused. Verify the screw
size that is supplied with your circuit board tray and apply the recommended
torque during reinstallation.
M4 x 10 mm
7 T20
2.6 N•m (23.0 lb•in)
OR
M4 x 18 mm
7 T20
2.6 N•m (23.0 lb•in)
Install the power interface circuit board in the reverse order of removal.
Balance Resistors Replace the power module balance resistors with the appropriate kit catalog
number:
Replacement
• SK-RM-INVBR1-F8M (400/480V)
• SK-RM-INVBR2-F8M (600/690V)
M4 =
7, 8 7 mm
2.6 N•m (23 lb•in)
Current Sensors Replace the power module current sensors with the appropriate kit catalog
number:
Replacement
• SK-RM-INVCS1-F8M (622 A)
• SK-RM-INVCS2-F8M (1000 A)
4. Remove the power module from the enclosure. See Power Module
Replacement on page 140.
5. Remove the circuit board tray from the power module. See Circuit
Board Tray Removal on page 148.
6. Remove the six M8 x 20 mm torx screws that secure the three flexible
bus cables to the IGBT power terminals and pull the flexible bus cables
through the opening in the current sensors.
7. Remove the six M4 x 10 mm torx screws that secure the three current
sensors to the power module chassis and remove the current sensors.
M8 x 20 mm
6 T40
15 N•m (133 lb•in)
M4 x 10 mm
7 T25
2.6 N•m (23 lb•in)
LCL Filter Module Replace the LCL filter module with the appropriate kit catalog number:
Replacement • 20-750-ML1-CnnnDnnn
• 20-750-ML1-EnnnFnnn
Equipment is available that is designed to help you safely handle the LCL filter
modules. The following equipment is recommended:
• PowerFlex 750-Series module service cart, catalog number 20-750-
MCART1, publication 750-IN105
• PowerFlex 750TM power and LCL filter module storage hardware,
catalog number 20-750-MINV-ATIP, publication 750-IN106
Follow these steps to remove the LCL filter module from the enclosure.
ATTENTION: IGBT power and LCL filter modules have a high center of gravity
and a tip-over hazard exists. To guard against death, serious personal injury,
or equipment damage, do not subject the module to high rates of
acceleration or deceleration while transporting. Do not push or pull above the
points that are indicated on the module.
5. Loosen the screw that secures the connections cover to the front of the
adjoining power modules.
6. Use the screw to lift the connections cover up and off the power module
chassis.
–
5 P2 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)
=
LCL filter with one line side converter. LCL filter with two line side converters.
P3
9 10
11. Remove the three M12 x 13 mm hex nuts that secure the flexible bus
cables to the AC input fuse terminals and remove the flexible bus cables.
12. Remove the two M10 x 20 mm torx screws that secure the LCL filter
module chassis to the control bus frame.
13. Leave the two M10 x 20 mm screws that secure the LCL filter module
chassis to the floor mounting bracket while preparing the PowerFlex
750-Series service cart.
M12 x 13 mm
11 19 mm
45 N•m (398 lb•in)
11
12
M10 x 20 mm
12, T40
15 42.4 N•m (375 lb•in)
15
14. Secure the service cart to the floor mounting bracket in the enclosure.
See the PowerFlex 750-Series Service Cart and DCPC Module Lift
Installation Instructions, publication 750-IN105, for information on by
using the service cart.
15. To release the LCL filter module, remove the two remaining M10
screws.
16. Remove the LCL1 filter module from the enclosure.
Install the LCL filter module into the enclosure in the reverse order of removal.
1. Remove the transceiver from the fiber-optic port on the power layer
interface circuit board on the adjoining power module.
AC Input Link Fuses Replace the AC input link fuses with the appropriate kit catalog number that is
identified in Table 18:
Replacement
IMPORTANT It is recommended that you replace all three AC line fuses.
Table 18 - AC Input Link Bus Bar and Fuse Assembly Kit Fuses
AC Input Link Bus Bar Frame LCL Filter Voltage Fuse Kit Cat. No. Bussman Fuse Fuse Rating Fuse
and Fuse Kit Cat. No. Rating Number Qty.
20-750-MACL1-F8M 8 One 20-750-ML1-C540D505 400/480V SK-RM-ACFUSE1-F8 170M6463 690/700V (IEC/U.L.), 900 A (1) 3
20-750-MACL3-F8M One 20-750-ML1-E395F370 600/690V SK-RM-ACFUSE5-F8 170M6461 690/700V (IEC/U.L.), 700 A (1) 3
20-750-MACL2-F8M One 20-750-ML1-C770D740 400/480V SK-RM-ACFUSE2-F8 170M6466 690/700V (IEC/U.L.), 1250 A (1) 3
20-750-MACL1-F8M One 20-750-ML1-E395F370 600/690V SK-RM-ACFUSE1-F8 170M6463 690/700V (IEC/U.L.), 900 A (1) 3
20-750-MACL1-F9M 9 One 20-750-ML1-C1K1D1K0 400/480V SK-RM-ACFUSE3-F9 170M6470 690/700V (IEC), 1800 A (2) 3
20-750-MACL2-F8M One 20-750-ML1-E760F735 600/690V SK-RM-ACFUSE2-F8 170M6466 690/700V (IEC/U.L.), 1250 A (1) 3
20-750-MACL2-F9M One 20-750-ML1-C1K4D1K3 400/480V SK-RM-ACFUSE4-F9 170M6471 690/700V (IEC), 2000 A (3) 3
20-750-MACL3-F9M One 20-750-ML1-E980F920 600/690V SK-RM-ACFUSE6-F9 170M6469 690/700V (IEC/U.L.), 1600 A (1) 3
20-750-MACL2-F8M 10 One 20-750-ML1-C770D740 and 400/480V SK-RM-ACFUSE2-F8 170M6466 690/700V (IEC/U.L.), 1250 A (1) 3
one 20-750-ML1-C1K4D1K3
20-750-MACL2-F9M SK-RM-ACFUSE4-F9 170M6471 690/700V (IEC), 2000 A (3) 3
20-750-MACL1-F8M One 20-750-ML1-E545F505 and 600/690V SK-RM-ACFUSE1-F8 170M6463 690/700V (IEC/U.L.), 900 A (1) 3
one 20-750-ML1-E980F920
20-750-MACL3-F9M SK-RM-ACFUSE6-F9 170M6469 690/700V (IEC/U.L.), 1600 A (1) 3
20-750-MACL2-F9M 11 Two 20-750-ML1-C1K4D1K3 400/480V SK-RM-ACFUSE4-F9 170M6471 690/700V (IEC/U.L.), 1600 A (3) 3
20-750-MACL3-F9M Two 20-750-ML1-E980F920 600/690V SK-RM-ACFUSE6-F9 170M6469 690/700V (IEC/U.L.), 1600 A (1) 3
Table 18 - AC Input Link Bus Bar and Fuse Assembly Kit Fuses
AC Input Link Bus Bar Frame LCL Filter Voltage Fuse Kit Cat. No. Bussman Fuse Fuse Rating Fuse
and Fuse Kit Cat. No. Rating Number Qty.
20-750-MACL2-F8M 12 One 20-750-ML1-C770D740 400/480V SK-RM-ACFUSE2-F8 170M6466 690/700V (IEC/U.L.), 1250 A (1) 3
and two 20-750-ML1-C1K4D1K3
20-750-MACL2-F9M SK-RM-ACFUSE1-F8 170M6463 690/700V (IEC), 2000 A (3) 3
(1)
20-750-MACL1-F8M One 20-750-ML1-E545F505 and 600/690V SK-RM-ACFUSE1-F8 170M6463 690/700V (IEC/U.L.), 900 A 3
two 20-750-ML1-E980F920 (1)
20-750-MACL3-F9M SK-RM-ACFUSE6-F9 170M6469 690/700V (IEC/U.L.), 1600 A 3
(1) Bussman Square Body - Flush End Contact -BKN/- Type K Indicator.
(2) Bussman Square Body - Flush End Contact -BKN/- Type K Indicator. Rated Voltage IEC 600V (Consult Bussmann for U.L. Recognition/ CSA Component Acceptance status.)
(3) Bussman Square Body - Flush End Contact -BKN/- Type K Indicator. Rated Voltage IEC 550V (Consult Bussmann for U.L. Recognition/ CSA Component Acceptance status.)
7. Remove the three M12 x 13 mm hex nuts that secure the flexible bus
cables to the AC input fuse terminals and remove the flexible bus cables.
8. Remove the three M12 x 13 mm hex nuts that secure the fuse to the AC
input bus bars and remove the fuses.
M12 x 13 mm
7 19 mm
Frame 9…12 Power Bay Shown 45 N•m (398 lb•in)
P5
P1
8
M12 x 13 mm
8 19 mm
45 N•m (398 lb•in)
LCL Filter Capacitor Assembly Replace the LCL filter module capacitor assembly with the appropriate kit
catalog number:
Replacement
• SK-RM-LCLCP1-F8M (30 μF)
• SK-RM-LCLCP2-F8M (41 μF)
• SK-RM-LCLCP3-F8M (62 μF)
• SK-RM-LCLCP4-F8M (80 μF)
5. Remove the wire access cover to more easily feed the wiring through the
back of the chassis when a capacitor assembly is removed. Remove the
eight M4 x 10 mm torx screws that secure the capacitor wire access cover
to the chassis and remove the cover.
M4 x 10 mm
5 T25
3 N•m (26 lb•in)
IMPORTANT The interconnection wires cannot be removed from the terminal block on
the top of the capacitor until the capacitor assembly has been removed from
the chassis.
6a
6b
Install the LCL filter capacitor assembly in the reverse order of removal.
EMC Filter Circuit Board Replace the LCL filter module EMC filter circuit board with kit catalog
number SK-RM-EMCFB1.
Replacement
Follow these steps to remove and replace the EMC filter circuit board.
5 =
6. Remove the four cables from the connectors at the top and side of the
EMC filter circuit board.
6
=
7. Remove the two M6 x 16 mm screws that secure the EMC filter circuit
board to the support bracket and remove the circuit board.
M6 x 16 mm
7 T30
12.5 N•m (110.6 lb•in)
7
=
Install the EMC filter circuit board in the reverse order of removal.
Current Sense Circuit Board Replace the LCL filter module current sense circuit board with the appropriate
kit catalog number:
Replacement
• SK-RM-CSB1-700 (700 A)
• SK-RM-CSB1-525 (525 A)
• SK-RM-CSB1-350 (350 A)
• SK-RM-CSB1-263 (263 A)
Follow these steps to remove and replace the current sense circuit board.
8. If the top-most receptacle on the back of the LCL filter module contains
a DC capacitor, remove the capacitor. See Remove the LCL Filter
Capacitor Assembly on page 167. If the top-most receptacle on the back
of the LCL filter module does not contain a DC capacitor, complete
steps a and b.
a. Remove the lower two M6 x 16 mm torx screws that secure the cover
to the chassis.
b. Loosen the upper two M6 x 16 mm torx screws that secure the cover
to the chassis and remove the cover.
M6 x 16 mm
8 T30
12.5 N•m (110.6 lb•in)
9. Remove the two M5 x 10 mm torx screws that secure the current sense
circuit board tray to the side of the chassis.
10. While supporting the circuit board tray, loosen, but do not remove, the
two M5 x 12 mm torx screws that secure the current sense circuit board
tray to the back of the chassis and lift the tray off the screws.
M5 x 10 mm M5 x 12 mm
9 T25 10 T25
4 N•m (35.4 lb•in) 4 N•m (35.4 lb•in)
9 10
11. Cut the cable ties that secure the wires to the circuit board tray.
12. Disconnect these connectors from the current sense circuit board:
• P8 from J8
• P5 from J5
• P6 from J6
• P13 from J13
• P4 from J4
• P1 from J1
• P14 from J14 (must be reused to maintain the rating of the module)
13. Remove the circuit board tray from the module chassis.
14. Remove the five M4 x 8 mm torx screws that secure the current sense
circuit board to the circuit board tray and remove the circuit board.
M4 x 8 mm
14 T25
1.8 N•m (15.5 lb•in)
Install the current sense circuit board in the reverse order of removal.
1. Secure the wires to the circuit board tray by using cable ties in the same
locations as previously secured.
2. When installing the fiber-optic cables:
IMPORTANT
Minimum inside bend radius for fiber-optic cable is 50
mm (2 in.). Any bends with a shorter inside radius can
permanently damage the fiber-optic cable. Signal 50 mm
(2 in.)
attenuation increases as inside bend radius is decreased.
Power/LCL Filter Module Fan Replace the power or LCL filter module fan fuse with kit catalog number
SK-RM-INVFAN1-FUSE (Time Delay, 250V, 3.5 A, Cartridge).
Fuse Replacement
Follow these steps to remove and replace the power /LCL filter module fan
fuse.
5. Unscrew the fuse holder cover and fuse and remove the fuse.
Fan Shown Removed from Module for Clarity Only
Install the power /LCL filter module fan fuse in the reverse order of removal.
Fan Assembly Replacement Replace the power or LCL filter module fan assembly with kit catalog number
SK-RM-INVFAN1-F8.
Follow these steps to remove and replace the power or LCL filter module fan
assembly.
M6
6 T30
2.6 N•m (23 lb•in)
Install the power or LCL filter module fan assembly in the reverse order of
removal.
Torque Accuracy Module Replace the torque accuracy module with the appropriate kit catalog number:
Replacement • 20-750-MTAM1-CD (400/480V)
• 20-750-MTAM1-EF (600/690V)
Follow these steps to remove and replace the torque accuracy module.
4. Remove the right-most power module from the enclosure. See Power
Module Replacement from the Enclosure on page 140.
M4
9, 7 mm
10
2.6 N•m (23 lb•in)
9
5
10
DC Bus Conditioner Replace the DC bus conditioner with kit catalog number
20-750-MDCBUS-COND.
Replacement
5. Loosen the thumb screw that secures the connections cover to the front
of the power module.
6. By using the screw, lift the connections cover up and off the power
module chassis.
7. Disconnect the DC bus conditioner cable connector P2 from J2 on the
I/O panel in the power module.
–
5 P2 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)
7
6
9. Remove the two M6 x 12 mm torx screws that secure the +DC and -DC
cables to the +DC and -DC terminals on the DC bus conditioner,
respectively, and remove the cables.
10. Remove the M6 x 12 mm torx screw that secures the ground cable to the
GND (PE) terminal on the DC bus conditioner and remove the cable.
M6 x 12 mm
9, T30
10
5 N•m (44 lb•in)
11. Remove the two M5 hexagonal nuts and washers that secure the DC bus
conditioner to the sheet metal mounting panel and remove the DC bus
conditioner.
M5
11 8 mm
4.8 N•m (42 lb•in)
Notes:
This chapter provides detailed instructions for how to remove and replace wire
entry/exit bay components.
Wire Entry/Exit Bay Kits Table 19 lists the replacement kits available for the wire entry/exit bay.
2 3
IP54/IP21, 400 mm Wide Replace the IP54/IP21, 400 mm wide door vent filters with kit catalog number
SK-RM-IB4DR-FLTR1.
Door Vent Filters
Replacement See IP54/IP21, 400/600 mm Wide Door Vent Filters Replacement on page
83.
IP54/IP21, 800 mm Wide Replace the IP54/IP21, 800 mm wide door vent filters with kit catalog number
SK-RM-IB4DR-FLTR1.
Door Vent Filters
Replacement See IP54/IP21, 400/600 mm Wide Door Vent Filters Replacement on page
83.
IP54/IP21, 400/800 mm Wide Replace the IP54/IP21, 400 mm or 800 mm wide door vent fan and filter
assembly with the appropriate kit catalog numbers:
Door Vent Fan and Filter
• 400 mm, SK-RM-WBDR-FANFLR1
Assembly Replacement • 800 mm, SK-RM-WBDR-FANFLR2
Remove the IP54/IP21, 400/800 mm Wide Door Vent Fan and Filter
Assembly
Follow these steps to remove the IP54/IP21, 400/800 mm wide door vent fan,
and filter assembly.
4. On the inside of the enclosure door, remove the M8 hex nut and washer
that secures the two ground wire lugs to the door, and remove the wires.
5. Disconnect the fan power wires from connector P1 on the fan assembly.
6. Press the tabs on the vent cover inward and pull the vent off the front of
the enclosure door.
M8
4 13 mm
10.2 N•m (90 lb•in)
Install the IP54/IP21, 400/800 mm Wide Door Vent Fan and Filter
Assembly
Install the IP54/IP21, 400/800 mm wide door vent fan, and filter assembly in
the reverse order of removal.
Thermal Switch Replacement Replace the thermal switch with kit catalog number SK-RM-THRMSW-WB.
4. Loosen the 12 screws that secure the guards to the enclosure and remove
the guards.
M5.5 x 13 mm
4 T25
2.6 N•m (23 lb•in)
5. Remove the two M6 x 25 mm torx screws that secure the thermal switch
assembly to the mounting bracket on the bus bar and remove the
assembly. Retain the screws, guard, and clamp for reuse.
6. Disconnect the wires from the two terminals on the thermal switch.
M6 x 25 mm
5 T30
4.8 N•m (42 lb•in)
Notes:
Topic Page
Before You Apply Power to the Drive 195
No-load DC Bus Voltage and Output Current Measurements 199
Before You Apply Power to ATTENTION: To avoid an electric shock hazard, verify that there is no AC
the Drive input and DC bus voltage before servicing by taking these measurements:
• Verify that there is no AC input voltage present using the R/L1, S/L2, and
T/L3 test point sockets in the input bay.
• Verify that there is no AC input voltage present using the R, S, and T test
point sockets in the input bay by measuring L to L and L to GND.
• Verify that there is no DC bus voltage present using the +DC to -DC test
points in the input bay by measuring +DC to -DC, +DC to GND, and -DC to
GND.
1. For regenerative drives and bus supplies, measure the AC input and DC
bus voltage at the following test point sockets in the power bay to verify
that there is no voltage present:
• Using the circuit breaker output (CB1 SEC) test points R/L1, S/L2,
and T/L3, measure L to L and L to chassis GND.
• Using the fused disconnect output (FD1 SEC) test points R, S, and
T, measure L to L and L to chassis GND.
• Using the DC bus test points +DC and -DC, measure +DC to -DC,
+DC to chassis GND, and -DC to chassis GND.
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged completely before servicing. Verify that there
is no DC bus voltage present using the +DC to -DC test points on all power
modules by measuring +DC to -DC, +DC to GND, and -DC to GND.
2. For common bus inverters, using the DC bus test points +DC and -DC
on the front of the power modules, measure the DC bus voltage of all
power modules and verify that there is no voltage present on the bus
capacitors. Measure +DC to -DC, +DC to chassis GND, and -DC to
chassis GND.
4. For all products, perform phase to ground resistance tests to verify that
there are no shorts on the following test points.:
In an input bay:
• Using the circuit breaker output (CB1 SEC) test points R/L1, S/L2,
and T/L3, measure L to chassis GND.
• Using the fused disconnect output (FD1 SEC) test points R, S, and
T, measure L to chassis GND.
• Using the DC bus test points +DC and -DC, measure +DC to
chassis GND, and -DC to chassis GND.
In a power bay:
• Using the DC bus test points +DC and -DC on the front of the
power modules, measure +DC to chassis GND, and -DC to chassis
GND.
5. If the measured value of any resistance test is less than 1 kΩ,
troubleshoot to find the short, correct the problem, and repeat step 4.
6. For any module or component that has been removed and re-installed,
complete the following:
• Verify that all hardware connections have been replaced and are
properly torqued.
No-load DC Bus Voltage and Follow theses steps to measure the DC bus voltage and output current and
diagnose problems without connecting the motor to its mechanical load.
Output Current
Measurements 1. Verify that the input power and ground wires are connected.
2. Verify that the AC line power at the disconnect device is within the
rated value for the drive or bus supply.
3. Verify that the control power voltage is correct.
4. Verify that the motor cables are connected.
5. Verify that the motor load is disconnected.
6. Energize the system. See Remove Power from the Drive System on page
13.
7. Measure the DC bus voltage and verify that the measured value is
displayed in port 0, parameter 3 [DC Bus Volts].
8. Start the system and increase the speed from zero to base speed.
9. Measure the system output current and verify that the measured value is
displayed in port 10, parameter 3 [Output Current].
10. Stop the system.
11. Reconnect the load to the motor before proceeding with drive startup.
Notes:
System Schematics
Topic Page
PowerFlex 755TM LCL Filter Module 203
PowerFlex 755TM Power Module 204
PowerFlex 755TM DC Precharge Module 205
PowerFlex 755TM DC Bus Conditioner 206
PowerFlex 755TM Frame 8 AC Input Bay 207
PowerFlex 755TM Frame 9 AC Input Bay 208
PowerFlex 755TM Frame 10 AC Input Bay 209
PowerFlex 755TM Frame 11 AC Input Bay 210
PowerFlex 755TM Frame 12 AC Input Bay 211
PowerFlex 755TM Frame 8 Regenerative Drive with DC Bus Conditioner 212
PowerFlex 755TM Frame 8 Regenerative Drive with no DC Bus Conditioner 213
PowerFlex 755TM Frame 9 Regenerative Drive 214
PowerFlex 755TM Frame 10 Regenerative Drive (Page 1 of 2) 215
PowerFlex 755TM Frame 10 Regenerative Drive (Page 2 of 2) 216
PowerFlex 755TM Frame 11 Regenerative Drive (Page 1 of 2) 217
PowerFlex 755TM Frame 11 Regenerative Drive (Page 2 of 2) 218
PowerFlex 755TM Frame 12 Regenerative Drive (Page 1 of 2) 219
PowerFlex 755TM Frame 12 Regenerative Drive (Page 2 of 2) 220
PowerFlex 755TM Frame 8 Regenerative Bus Supply with DC Bus Conditioner 221
PowerFlex 755TM Frame 8 Regenerative Bus Supply with no DC Bus Conditioner 222
PowerFlex 755TM Frame 9 Regenerative Bus Supply 223
PowerFlex 755TM Frame 10 Regenerative Bus Supply 224
PowerFlex 755TM Frame 11 Regenerative Bus Supply 225
PowerFlex 755TM Frame 12 Regenerative Bus Supply 226
PowerFlex 755TM Common Bus Inverter Control Bay 227
PowerFlex 755TM Frame 8 Common Bus Inverter with DC Link Fuses 228
PowerFlex 755TM Frame 9 Common Bus Inverter with DC Link Fuses 229
PowerFlex 755TM Frame 10 Common Bus Inverter with DC Link Fuses 230
PowerFlex 755TM Frame 11 Common Bus Inverter with DC Link Fuses 231
PowerFlex 755TM Frame 12 Common Bus Inverter with DC Link Fuses 232
PowerFlex 755TM Frame 8 Common Bus Inverter with DC Precharge Module 233
PowerFlex 755TM Frame 9 Common Bus Inverter with DC Precharge Module 234
Topic Page
PowerFlex 755TM Frame 10 Common Bus Inverter with DC Precharge Module 235
PowerFlex 755TM Frame 11 Common Bus Inverter with DC Precharge Module 236
PowerFlex 755TM Frame 12 Common Bus Inverter with DC Precharge Module 237
Entry Wire Bay 238
Exit Wire Bay 239
This chapter provides schematics for PowerFlex® 755T modules and products.
MID
VRFY
VRFY
VRFY
TO
+24V
+24V
+24V
-24V
-24V
-24V
M
M
M
+ + + + +
ONLY FOR FR-8C
J12-PCBA1
2 1
-DC 4 3 2 1 4 3 2 1 4 3 2 1
C2 C4 C6 C8 C10
NTC
NTC
NTC
- - - - - R5
CHASSIS
R6
OPTIONAL
NEG BUS BAR GATE BOARD
-NEG
-NEG
J1
(ONLY FOR 20-750-MI3-xxxxxxx)
Ver
TP2 40 PINS
P1 (PCBA3)
-DC
TP3
10001416614
Of
2 /DC FUSE GOOD
1
1 2
J1
2 1 DC FUSE COM
On Panel, IGBT PS
/BUS_COND_GOOD
1 1
1 2 3
2 BUS_COND_COM
J2
2
3 /BUS_COND_PRESENT
4 3
40 PIN RIBBON CABLE
On Panel, IGBT PS
3
2
1 3
/BUS_COND_PRESENT
4
5
/BUS_COND_GOOD
2 1 +24 OUT
5 1
BUS_COND_COM
2 COM OUT
BLOWER_CONTROL
/DC FUSE GOOD
1
DC FUSE COM
AC FUSE COM
INTAKE_TEMP_A
INTAKE_TEMP_B
6 2
BLOWER_FDBK
4 AC FUSE COM
BLOWER_COM
P5/P6 must be connected to J5(PE-B1 IN) For
J3
1 CONV_A_TEST
+POS
Sheet
COM OUT
-NEG
MID
+24 OUT
2 CONV_VARY_A 7 3
R4-1 R2-1 R1-1 connected to J6(PE-B1 OUT)
Size
R3-1 3 CONV_VARY_B
P5/P6 4 CONV_B_TEST 8 4
P4 On Panel, IGBT PS
1 2 34
ONLY FOR FR-8C
1 2 3 4 5 On Panel, IGBT PS
ONLY FOR FR-8C
1 2 3 4 5 1234 1234
J4 J5 J6 P13 1. CONV_A_TEST 2 240VAC_H
4 3 240VAC_N
3
4 3
1
11 4 4 11
10 3 3 10
12 5 5 12
13 6 6 13
14 7 7 14
PE-B1 IN PE-B1 OUT 3. CONV_VARY_A 1
8 1 1 8
9 2 2 9
J13
J4
64 PINS
R4 R2 R3 R1 2 1 2 1 2. CONV_VARY_B CUST_+24V
J18
1
P10 1
4
2
2 4. CONV_B_TEST CUST_COM
2
3 On Panel, IGBT PS
4
PLI BOARD
J10
(PCBA2)
R4-2 R2-2 R3-2 R1-2 CUST_+24V
1
Fiberlink
Fiberlink
1 2
1 2
J11
FIBER LINK to DCP / LCL
64 PINS
CTL
PDI
P3
J19
40 PINS 2
J3 P11 CUST_COM
On Panel, IGBT PS FIBER LINK to Mx-POD1
1 PIB BOARD
1 2 3
1 2 3
J12
2
J7 (PCBA1) J8 J9
1. Thermal switch_1 3 4 3 4 3 4
P12
2. Thermal switch_2 1 2 1 2 1 2
1 2 1 2 1 2
1. CS1_+24V 1. CS2_+24v 1. CS3_+24V
3 4 3 4 3 4 2. CS3_-24V
2. CS1_-24V 2. CS2_-24V
3. CS3_M
1 2 3 P12
3. CS1_M 3. CS2_M
3 2 3 2 4. CS3_VERY
1 4 4. CS1_VERY 1 3 24 4. CS2_VERY 1 4
Label for Test Points on Front
TP1= +DC
TP2= -DC
System Schematics
204
System Schematics Appendix A
Figure 39 - PowerFlex 755TM Frame 8 Regenerative Bus Supply with DC Bus Conditioner
Figure 40 - PowerFlex 755TM Frame 8 Regenerative Bus Supply with no DC Bus Conditioner
Figure 46 - PowerFlex 755TM Frame 8 Common Bus Inverter with DC Link Fuses
Figure 47 - PowerFlex 755TM Frame 9 Common Bus Inverter with DC Link Fuses
Figure 48 - PowerFlex 755TM Frame 10 Common Bus Inverter with DC Link Fuses
Figure 49 - PowerFlex 755TM Frame 11 Common Bus Inverter with DC Link Fuses
Figure 50 - PowerFlex 755TM Frame 12 Common Bus Inverter with DC Link Fuses
Figure 51 - PowerFlex 755TM Frame 8 Common Bus Inverter with DC Precharge Module
Figure 52 - PowerFlex 755TM Frame 9 Common Bus Inverter with DC Precharge Module
Figure 53 - PowerFlex 755TM Frame 10 Common Bus Inverter with DC Precharge Module
Figure 54 - PowerFlex 755TM Frame 11 Common Bus Inverter with DC Precharge Module
Figure 55 - PowerFlex 755TM Frame 12 Common Bus Inverter with DC Precharge Module
Notes:
N
normal operation
maintenance schedule 23
O
operating mechanism
inspection 32
T
terminals
inspection 33
test
AC input link fuses 39
DC link fuses 39
dielectric withstand voltage 34
insulation resistance 34
thermal switch (wire entry/exit bay)
install 193
remove 191
tool size
diagram 18
tool type
diagram 18
torque accuracy module
install 182
remove 180
V
visual inspection 35
W
wire entry/exit bay
kits 187
wire entry/exit bay ventilation
kits 187
Notes:
Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User https://rockwellautomation.custhelp.com/
Forums, and Product Notification Updates.
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Find the Direct Dial Code for your product. Use the code to
Direct Dial Codes route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Connected Components Workbench, PowerFlex, Rockwell Software, Rockwell Automation, and TotalFORCE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400