MABNA NIROO CO.
2 ﻣﻘﺪﻣﻪ
3 ﻭﻳﮋﮔﻲ ﻫﺎﻱ ﺩﺳﺘﮕﺎﻩ AU
3 ﺁﺷﻨﺎﻳﻲ ﻛﻠﻲ ﺑﺎ ﺩﺳﺘﮕﺎﻩ AU
7 ﻣﻌﺮﻓﻲ ﻭ ﺗﺸﺮﻳﺢ ﺟﺰﺋﻴﺎﺕ ﺩﺳﺘﮕﺎﻩ AU
15 ﻧﻜﺎﺕ ﺿﺮﻭﺭﻱ
15 ﺭﻭﺵ ﻧﺼﺐ ﻭ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﺩﺳﺘﮕﺎﻩ
17 ﺟﺪﻭﻝ ﻣﺸﺨﺼﺎﺕ ﻓﻨﻲ
18 ﺗﻤﺎﺱ ﺑﺎ ﻣﺎ
AU
AU
sERIES MABNA NIROO
ﻣﻘ ﺪﻣﻪ
ﭘﻨ ﺠﺮﻩ ﺁﻻﺭ ﻡ
ﺍﻫﻤﻴـــﺖ ﻛﻨﺘـــﺮﻝ ﻭﻧﻈـــﺎﺭﺕ ﻭﭘـــﺎﻳﺶ ﺳﻴﺴـــﺘﻢ ﻫـــﺎﻱ ﺗﻮﻟﻴـــﺪ ﻭﺗﻮﺯﻳـــﻊ ﺍﻧـــﺮژﻱ
ﺍﻟﻜﺘﺮﻳﻜـــﻲ ﺩﺭ ﻣﺮﺍﻛـــﺰ ﺻـــﻨﻌﺘﻲ ﺍﻣـــﺮﻱ ﻣﻬـــﻢ ﻭ ﺣﻴـــﺎﺗﻲ ﺑـــﻪ ﺷـــﻤﺎﺭ ﺁﻣـــﺪﻩ ﻭ
ﻟــﺰﻭﻡ ﺗــﺪﺍﻭﻡ ﺍﻧــﺮژﻱ ﻭﺗــﻼﺵ ﺟﻬــﺖ ﺷﻨﺎﺳــﺎﻳﻲ ﺳــﺮﻳﻊ ﻧﻘــﺎﻁ ﺁﺳــﻴﺐ ﺩﻳــﺪﻩ ﻭ
ﺍﻧﺠـــﺎﻡ ﺍﻗـــﺪﺍﻣﺎﺕ ﺳـــﺮﻳﻊ ﺗﻌﻤﻴﺮﺍﺗـــﻲ ﻣـــﻲ ﺗﻮﺍﻧـــﺪ ﺍﺯ ﺑـــﺮﻭﺯ ﺿـــﺎﻳﻌﺎﺕ ﻓﻨـــﻲ
ﻭﺍﻗﺘﺼﺎﺩﻱ ﻣﻤﺎﻧﻌﺖ ﺑﻪ ﻋﻤﻞ ﺁﻭﺭﺩ .
ﭘﻨﺠـــﺮﻩ ﺁﻻﺭﻡ ،ﺩﺳـــﺘﮕﺎﻫﻲ ﺍﺳـــﺖ ﻛـــﻪ ﺩﺭ ﻭﺍﺣـــﺪﻫﺎ ﻭ ﻣﺮﺍﻛـــﺰ ﺻــﻨﻌﺘﻲ ﺟﻬــﺖ
ﺍﻋـــﻼﻡ ﺑـــﺮﻭﺯ ﺧﻄـــﺎ ﺩﺭ ﺳﻴﺴـــﺘﻢ ﻭ ﻧﻤـــﺎﻳﺶ ﻣﺤـــﻞ ﺁﻥ ﻭ ﺍﻫﻤﻴـــﺖ ﺣـــﻮﺯﺓ
ﺁﺳــﻴﺐ ﺩﻳــﺪﻩ ﻣــﻮﺭﺩ ﺍﺳــﺘﻔﺎﺩﻩ ﻗــﺮﺍﺭ ﮔﺮﻓﺘــﻪ ﺍﺳــﺖ؛ ﺑــﻪ ﻧﺤــﻮﻱ ﻛــﻪ ﺳــﺮﻳﻌ ًﺎ ﺑ��ﻪ
ﺍﺗــﺎﻕ ﻛﻨﺘــﺮﻝ ﻣﻨﺘﻘــﻞ ﻣــﻲ ﺷــﻮﺩ ﺗــﺎ ﻫــﻢ ﺯﻣــﺎﻥ ﺑــﺎ ﺟــﺎﻳﮕﺰﻳﻨﻲ ﺳــﺮﻳﻊ ﻓﻴــﺪﺭ
ﺁﺳــﻴﺐ ﺩﻳــﺪﻩ ﺑــﺎ ﺍﻣﻜﺎﻧــﺎﺕ ﺭﺯﺭﻭ ،ﺗﻌﻤﻴــﺮﺍﺕ ﻭ ﺭﻓــﻊ ﺍﺷــﻜﺎﻝ ﺷــﺮﻭﻉ ﮔــﺮﺩﺩ ﻭ
ﺩﺭ ﻛﻤﺘﺮﻳﻦ ﺯﻣﺎﻥ ﻣﻤﻜﻦ ،ﻭﺍﺣﺪ ﺑﻪ ﺣﺎﻟﺖ ﻋﺎﺩﻱ ﺑﺎﺯﮔﺮﺩﺍﻧﺪﻩ ﺷﻮﺩ .
ﺁﻻﺭﻡ ﻳﻮﻧﻴـــﺖ ﻫـــﺎﻱ AUﻛـــﻪ ﺑـــﺮ ﺍﺳـــﺎﺱ ﻃﺮﺍﺣـــﻲ ﻭ ﻣﻬﻨﺪﺳـــﻲ ﻧﻴﺮﻭﻫـــﺎﻱ
ﻣﺘﺨﺼـــﺺ ﺩﺍﺧﻠـــﻲ ﺗﻬﻴـــﻪ ﺷـــﺪﻩ ﺍﺳـــﺖ ،ﺑـــﺎ ﺗﺠﺮﺑـــﻪ ﻭ ﭘﻴﺸـــﻴﻨﺔ ﻃـــﻮﻻﻧﻲ ﺩﺭ
ﺍﺳـــﺘﻔﺎﺩﻩ ﺩﺭ ﭘـــﺮﻭژﻩ ﻫـــﺎﻱ ﻣﻨﺘﺨـــﺐ ﻧﻴﺮﻭﮔـــﺎﻫﻲ ﻭ ﭘﺴـــﺖ ،ﺭﺍﻩ ﺣﻠـــﻲ ﻗﺎﺑـــﻞ
ﺍﻃﻤﻴﻨــــﺎﻥ ﺟﻬــــﺖ ﺟﻤــــﻊ ﺁﻭﺭﻱ ﻭ ﻧﻤــــﺎﻳﺶ ﺍﻃﻼﻋــــﺎﺕ ﺩﺭ ﻭﺍﺣــــﺪ ﻫــــﺎﻱ
ﻣﺨﺘﻠﻒ ﻣﻲ ﺑﺎﺷﺪ .
1
AU
sERIES MABNA NIROO
ﻭﻳﮋﮔﻲ ﻫﺎﻱ ﺩ ﺳﺘﮕﺎﻩ AU
ﺭﻧﺞ 24ﻭﻟﺖ ﺗﺎ 220ﻭﻟﺖ ) AC / DCﻃﺒﻖ ﺳﻔﺎﺭﺵ( . : ﺭﻧ ﺞ ﻭﻟﺘﺎژ ﺗ ﻐ ﺬﻳﻪ
. MIN / MAJ : ﻗﺎﺑﻠﻴ ﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺧﻄﺎ
ﺯﺭﺩ ﺭﻧﮓ . : ﺭﻧﮓ ﭘﻨ ﺠﺮﻩ ﻫﺎﻱ ﺁﻻﺭ ﻡ
ﺗ ﻌ ﺪﺍﺩ ﻭ ﺍﺑ ﻌﺎﺩ ﭘﻨ ﺠﺮﻩ ﺁﻻﺭ ﻡ :ﺩﺭ ﻧﻮﻉ 10ﭘﻨﺠﺮﻩ ،ﺍﺑﻌﺎﺩ ﻫﺮ ﭘﻨﺠﺮﻩ 50mm × 25mm
ﻭ ﺩﺭ ﺍﻧﻮﺍﻉ 16 ، 12ﻭ 20ﭘﻨﺠﺮﻩ ،ﺍﺑﻌﺎﺩ ﻫﺮ ﭘﻨﺠﺮﻩ 25mm× 25mmﻣﻲ ﺑﺎﺷﺪ.
3ﻛﻠﻴﺪ ) L.R ، A.Kﻭ . ( L.T : ﺗ ﻌ ﺪﺍﺩ ﻛﻠﻴ ﺪﻫﺎ
ﺁ ﺷﻨﺎﻳﻲ ﻛﻠﻲ ﺑﺎ ﺩ ﺳﺘﮕﺎﻩ AU
ﺍ ﺳﺘﺎﻧ ﺪﺍﺭﺩ ﺩ ﺳﺘﮕﺎﻩ
ﻃﺮﺍﺣﻲ ﺩﺳﺘﮕﺎﻩ ﻫﺎﻱ ﺳﺮﻱ AUﺑﺮ ﺍﺳﺎﺱ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ISA 1Aﻭ ISA 1Bﻣﻲ ﺑﺎﺷﺪ.
ﺩﺭ ﺟﺪﻭﻝ ﺷﻤﺎﺭﻩ ﻳﻚ ،ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻛﻠﻴﻪ ﺩﺳﺘﮕﺎﻩ ﻫﺎﻱ ﺁﻻﺭﻡ ﺷﺮﻛﺖ ﻣﺒﻨﺎ ﻧﻴﺮﻭ ﺍﺭﺍﺋﻪ ﺷﺪﻩ
ﺍﺳﺖ ﺗﺎ ﺍﻣﻜﺎﻥ ﻣﻘﺎﻳﺴﻪ ﺑﻴﻦ ﻣﺤﺼﻮﻻﺕ ﻣﺨﺘﻠﻒ ﻭ ﺍﻧﺘﺨﺎﺏ ﺑﻬﺘﺮﻳﻦ ﮔﺰﻳﻨﻪ ﺟﻬﺖ
ﻣﺸﺘﺮﻳﺎﻥ ﻓﺮﺍﻫﻢ ﺑﺎﺷﺪ .
ﻭﻟﺘﺎژ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﺗﻐﺬﻳﺔ ﺩﺳﺘﮕﺎﻩ ﻫﺎﻱ 110 VDC ، AUﻣﻲ ﺑﺎﺷﺪ ؛ ﻃﺒﻖ ﺳﻔﺎﺭﺵ ﻭ
ﺗﺄﻣﻴﻦ ﺩﺳﺘﮕﺎﻩ ﻫﺎﻱ AUﺑﺎ ﻭﻟﺘﺎژ ﻫﺎﻱ 48 ، 24ﻭ ، (VDC or VAC) 220ﺑﺎ
ﻫﻤﺎﻫﻨﮕﻲ ﻗﺒﻠﻲ ﺑﺎ ﺷﺮﻛﺖ ﻣﺒﻨﺎ ﻧﻴﺮﻭ ﻣﻴﺴﺮ ﻣﻲ ﺑﺎﺷﺪ .
2
AU
sERIES MABNA NIROO
TABLE 1: ISA STANDARDS
3
AU
sERIES MABNA NIROO
ﺍﺑ ﻌﺎﺩ ﻛﻠﻲ ﺩ ﺳﺘﮕﺎﻩ
ﺍﺑﻌﺎﺩ ﻧﻤﺎﻱ ﺩﺳﺘﮕﺎﻩ :
ﺍﺑﻌﺎﺩ ﻧﻤﺎﻱ ﻇﺎﻫﺮﻱ ﺩﺳﺘﮕﺎﻩ ﻛﻪ ﺷﺎﻣﻞ ﺻﻔﺤﺔ ﻧﻤﺎﻳﺶ ﻭ ﻗﺎﺏ ﻓﻠﺰﻱ ﻣﻲ ﺷﻮﺩ ﺑﺮﺍﺑﺮ
ﺑﺎ 160 ×146ﻣﻴﻠﻴﻤﺘﺮ ﻣﺮﺑﻊ ﺍﺳﺖ .
Figure1: View Dimensions
4
AU
sERIES MABNA NIROO
ﺍﺑﻌﺎﺩ ﻣﺤﻞ ﻧﺼﺐ ﺩﺳﺘﮕﺎﻩ ) ﺍﺑﻌﺎﺩ ﭘﺎﻧﭻ ﺩﺳﺘﮕﺎﻩ ( :
ﻣﺤﻞ ﻗﺮﺍﺭﮔﻴﺮﻱ ﻭ ﺍﺑﻌﺎﺩ ﺑﺮﺵ ﺟﻬﺖ ﻧﺼﺐ ﺩﺳﺘﮕﺎﻩ ﺑﺎﻳﺪ ﺑﺮﺍﺑﺮ ﺑﺎ 139.5 × 139
ﻣﻴﻠﻴﻤﺘﺮ ﺑﺎﺷﺪ ؛ ﻓﻀﺎﻱ ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺩﺭ ﭘﺸﺖ ﺩﺳﺘﮕﺎﻩ 136ﻣﻴﻠﻴﻤﺘﺮ ﺍﺳﺖ ﻛﻪ ﺑﻪ ﺍﻳﻦ
ﻣﻴﺰﺍﻥ ﺑﺎﻳﺪ ﻓﻀﺎﻱ ﻻﺯﻡ ﺟﻬﺖ ﻭﺍﻳﺮﻳﻨﮓ ﺭﺍ ﺍﺿﺎﻓﻪ ﻛﺮﺩ .
Figure2: Punching Dimensions
5
AU
sERIES MABNA NIROO
ﺭﻧﮓ ﭘﻨ ﺠﺮﻩ ﻫﺎﻱ ﺁﻻﺭ ﻡ
ﺭﻧﮓ ﭘﻨﺠﺮﻩ ﻫﺎ ﺩﺭ ﺯﻣﺎﻥ ﻓﻌﺎﻝ ﺷﺪﻥ ﺑﺮﺍﻱ ﺩﻭ ﺣﺎﻟﺖ ) Minor ( MINﻭ Major
)(MAJﺯﺭﺩ ﺭﻧﮓ ﻣﻲ ﺑﺎﺷﺪ ﻭ ﺑﺮﺍﻱ ﺗﻤﺎﻳﺰ ﺍﻳﻦ ﺣﺎﻻﺕ ﺩﻭ ﻋﺪﺩ LEDﺭﻭﻱ Front
Panelﺗﻌﺒﻴﻪ ﺷﺪﻩ ﺍﺳﺖ .
ﻣﻌﺮﻓﻲ ﻭ ﺗﺸﺮﻳﺢ ﺟﺰﺋﻴﺎﺕ ﺩﺳﺘﮕﺎﻩ AU
ﭘﻨﻞ ﺭﻭ ﺑﻪ ﺭﻭ ) ( Front Panel
ﭘﻨﺠﺮﻩ ﻫﺎﻱ ﻧﻤﺎﻳﺸﮕﺮ :
ﺳﺮﻱ ﺩﺳﺘﮕﺎﻩ ﻫﺎﻱ ﺁﻻﺭﻡ ، AUﺩﺭ ﺍﻧﻮﺍﻉ 16 ،12 ، 10ﻭ 20ﭘﻨﺠﺮﻩ ﺗﻮﻟﻴﺪ ﻣﻲ
ﺷﻮﺩ .
ﻛﻠﻴﺔ ﻋﻤﻠﻴﺎﺕ ﺩﺭﻳﺎﻓﺖ ﺧﻄﺎ reset ، set ،ﻭ ﺍﻃﻤﻴﻨﺎﻥ ﺍﺯ ﺑﺮﺩﺍﺷﺘﻪ ﺷﺪﻥ ﺧﻄﺎ ﺍﺯ ﺭﻭﻱ
ﻫﻤﺔ ﭘﻨﺠﺮﻩ ﻫﺎﻱ ﺁﻻﺭﻡ ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﺳﻪ ﻋﺪﺩ ﻛﻠﻴﺪ ﻓﺸﺎﺭﻱ ﺗﻌﺒﻴﻪ ﺷﺪﻩ ﺭﻭﻱ ﭘﻨﻞ
ﺩﺳﺘﮕﺎﻩ ﺍﻣﻜﺎﻥ ﭘﺬﻳﺮ ﻣﻲ ﺑﺎﺷﺪ.
ﺗﻮﺟﻪ :ﻃﺮﺯ ﻋﻤﻠﻜﺮﺩ ﻛﻠﻴﺪ ﻫﺎﻱ ﺭﻭﻱ ﭘﻨﻞ ﺩﺭ ﻛﻠﻴﻪ ﺩﺳﺘﮕﺎﻩ ﻫﺎﻱ ﺳﺮﻱ ، AUﻣﺸﺎﺑﻪ ﻣﻲ ﺑﺎﺷﺪ .
6
AU
sERIES MABNA NIROO
Figure3: AU10 Front Panel
: Front Panel ﺗﻮﺿﻴﺢ ﺍﺟﺰﺍﻱ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺷﺪﻩ ﺭﻭﻱ U
.1ﻧﻤﺎﻳﺸﮕﺮ ﻭﺟﻮﺩ ﻭﻟﺘﺎژ ﺗﻐﺬﻳﻪ :ﺩﺭ ﺻﻮﺭﺕ ﺍﺗﺼﺎﻝ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ،ﻻﻣﭗ
LEDﺳﺒﺰ ﺭﻧﮓ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭ ﺗﺎ ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎژ ﻭﺭﻭﺩﻱ ﺩﺳﺘﮕﺎﻩ ﻭﺻﻞ ﺑﺎﺷﺪ ،
ﺩﺭ ﻳﻜﻲ ﺍﺯ ﺣﺎﻻﺕ ﭼﺸﻤﻚ ﺯﻥ ﻳﺎ ﺛﺎﺑﺖ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ.
7
AU
sERIES MABNA NIROO
.2ﺩﺭ ﻭﺿﻌﻴﺖ ﺛﺎﺑﺖ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ﻭ ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ﺣﻀﻮﺭ ﺧﻄﺎﻱ MAJﺩﺭ
ﺳﻴﺴﺘﻢ ﺍﺳﺖ.
.3ﺩﺭ ﻭﺿﻌﻴﺖ ﺛﺎﺑﺖ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ﻭ ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ﺣﻀﻮﺭ ﺧﻄﺎﻱ MINﺩﺭ
ﺳﻴﺴﺘﻢ ﺍﺳﺖ.
.4ﻛﻠﻴﺪ ﻓﺸﺎﺭﻱ) Lamp Test ( L.Tﺑﺮﺍﻱ ﺍﻃﻤﻴﻨﺎﻥ ﺍﺯ ﺳﻼﻣﺖ ﻋﻤﻠﻜﺮﺩ ﻻﻣﭗ
ﻫﺎﻱ ﻛﻠﻴﺔ ﭘﻨﺠﺮﻩ ﻫﺎﻱ ﺁﻻﺭﻡ ﺍﺳﺖ ؛ ﺑﺎ ﻧﮕﻪ ﺩﺍﺷﺘﻦ ﺍﻳـﻦ ﻛﻠﻴﺪ ،ﺑﺎﻳﺪ ﺗﻤﺎﻣﻲ ﭘﻨــﺠﺮﻩ
ﻫـﺎ ﺑﻪ ﺣﺎﻟﺖ ﺛﺎﺑﺖ ﻳﺎ ﭼﺸﻤﻚ ﺯﻥ ﺭﻭﺷـﻦ ﺷﻮﻧﺪ ﻭ ﺑﺎ ﺭﻫﺎ ﻛﺮﺩﻥ ﺁﻥ ،ﻫﻤﻪ ﭘﻨﺠﺮﻩ
ﻫﺎ ﺧﺎﻣﻮﺵ ﮔﺮﺩﻧﺪ .
.5ﺍﺯ ﻛﻠﻴﺪ ﻓﺸﺎﺭﻱ ) ، Lamp Reset (L.Rﺟﻬﺖ ﺑﺎﺯﮔﺮﺩﺍﻧﻲ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﺣﺎﻟﺖ
ﻧﺮﻣﺎﻝ ﻭ ﺧﺎﻣﻮﺵ ﻛﺮﺩﻥ ﭘﻨﺠﺮﺓ ﺁﻻﺭﻡ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ ) .ﭘﺲ ﺍﺯ ﺭﻓﻊ ﻓﺎﻟﺖ (
.6ﻛﻠﻴﺪ ﻓﺸﺎﺭﻱ ) Acknowledge (A.Kﺑﺮﺍﻱ ﻗﻄﻊ ﺻﺪﺍﻱ Buzzerﺑﻪ
ﻛﺎﺭ ﻣﻲ ﺭﻭﺩ ﻛﻪ ﺑﻪ ﻣﻌﻨﺎﻱ ﺩﺭﻳﺎﻓﺖ ﺷﻨﻴﺪﺍﺭﻱ ﺧﻄﺎ ﻣﻲ ﺑﺎﺷﺪ .ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﭘﻨﺠﺮﻩ ﺍﻱ
ﻛﻪ ﺧﻄﺎ ﺭﺍ ﺩﺭﻳﺎﻓﺖ ﻛﺮﺩﻩ ﺍﺳﺖ ،ﺍﺯ ﺣﺎﻟﺖ ﭼﺸﻤﻚ ﺯﻥ ﺑﻪ ﺣﺎﻟﺖ ﺛﺎﺑﺖ )(Std.
ﺗﺒﺪﻳﻞ ﻣﻲ ﺷﻮﺩ .
ﺑﺮﺩ ( LED Board ) LED
ﺑﺎ ﺑﺮﺩﺍﺷﺘﻦ ﻓﺮﻳﻢ ﺟﻌﺒﻪ ﻭ ﭘﻨﻞ ﺩﺳﺘﮕﺎﻩ ،ﭘﻨﺠﺮﻩ ﻫﺎﻱ LEDﻗﺎﺑﻞ ﻣﺸﺎﻫﺪﻩ ﻫﺴﺘﻨﺪ ﻭ
ﺩﺭ ﺳﻤﺖ ﺭﺍﺳﺖ ﺁﻧﻬﺎ Dip Switchﺑﺎ ﺳﻪ ﻛﻠﻴﺪ ﻭﺟﻮﺩ ﺩﺍﺭﺩ ﻛﻪ ﺣﺎﻻﺕ ﻣﺨﺘﻠﻒ
ﺭﻭﺷﻦ ﺷﺪﻥ ﭘﻨﺠﺮﻩ ﻫﺎ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﻛﻨﺪ .
ﻋﻤﻠﻜﺮﺩ Dip Switchﺭﻭﻱ LED Boardﺩﺭ ﻛﻠﻴﻪ ﺩﺳﺘﮕﺎﻩ ﻫﺎﻱ ﺳﺮﻱ ، AUﻣﺸﺎﺑﻪ ﻣﻲ ﺑﺎﺷﺪ . ﺗﻮﺟﻪ:
)ﺗﺼﻮﻳﺮ ﺑﺮﺩ ﻭ ﺗﻮﺿﻴﺢ ﻫﺮ ﺣﺎﻟﺖ ﺭﺍ ﺩﺭ ﺻﻔﺤﺔ ﺑﻌﺪ ﻣﺸﺎﻫﺪﻩ ﻧﻤﺎﻳﻴﺪ (.
8
AU
sERIES MABNA NIROO
Figure4: LED Board
ﻋﻤﻠﻜﺮﺩ : Dip SwitchU
: RDY Fﺍﮔﺮ ﻛﻠﻴﺪ RDY Fﺩﺭ ﺣﺎﻟﺖ ONﺑﺎﺷﺪ ،ﭼﺮﺍﻍ ONﺭﻭﻱ Front Panel
ﺑﻪ ﺻﻮﺭﺕ ﺛﺎﺑﺖ ) ( Std.ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ﻭ ﺍﮔﺮ OFFﺑﺎﺷﺪ ،ﭼﺮﺍﻍ ONﺑﻪ
ﺣﺎﻟﺖ ﭼﺸﻤﻚ ﺯﻥ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ .
9
AU
sERIES MABNA NIROO
: M/Sﻛﻠﻴﺪ M/Sﺗﻌﻴﻴﻦ ﻛﻨﻨﺪﺓ ﻭﺿﻌﻴﺖ Clockﺩﺳﺘﮕﺎﻩ ﻣﻲ ﺑﺎﺷﺪ ؛ ﺑﻪ ﻃﻮﺭﻱ ﻛﻪ ﺩﺭ
ﺣﺎﻟﺖ ONﺩﺳﺘﮕﺎﻩ ) Master (Mﺷﺪﻩ ﻭ ﺍﺯ Clockﺧﻮﺩﺵ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﻛﻨﺪ ﻭ ﺩﺭ
ﺣﺎﻟﺖ ، OFFﺩﺳﺘﮕﺎﻩ ﺑﻪ ﺣﺎﻟﺖ ) Slave (Sﺭﻓﺘﻪ ﻭ ﺍﺯ Clockﺩﺳﺘﮕﺎﻩ ﺩﻳﮕﺮ ﺑﻪ
ﻋﻨﻮﺍﻥ Masterﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﻛﻨﺪ ) .ﺑﻪ ﺗﻮﺿﻴﺤﺎﺕ ﺻﻔﺤﺔ 16ﺭﺟﻮﻉ ﺷﻮﺩ ( .
: SQﺍﮔﺮ ﻛﻠﻴﺪ SQﺩﺭ ﺣﺎﻟﺖ ONﺑﺎﺷﺪ ،ﺑﺎ ﻓﺸﺮﺩﻥ ﻛﻠﻴﺪ A.Kﭘﻨﺠﺮﺓ ﻣﺘﻨﺎﻇﺮ ﺩﺭ
ﺣﺎﻟﺖ ﭼﺸﻤﻚ ﺯﻥ ﺑﺎﻗﻲ ﻣﻲ ﻣﺎﻧﺪ ﻭ ﺍﮔﺮ OFFﺑﺎﺷﺪ ،ﭘﻨﺠﺮﻩ ﺍﺯ ﺣﺎﻟﺖ ﭼﺸﻤﻚ ﺯﻥ ﺑﻪ
ﺣﺎﻟﺖ ﺛﺎﺑﺖ ﻣﻲ ﺭﻭﺩ .
: LTFﻛﻠﻴﺪ LTFﻭﺿﻌﻴﺖ ﺭﻭﺷﻦ ﺷﺪﻥ ﭘﻨﺠﺮﻩ ﻫﺎ ﺭﺍ ﺑﻪ ﻫﻨﮕﺎﻡ Lamp Test
ﺗﻌﻴﻴﻦ ﻣﻲ ﻛﻨﺪ .ﺑﻪ ﺍﻳﻦ ﺗﺮﺗﻴﺐ ﻛﻪ ﺩﺭ ﺣﺎﻟﺖ ، ONﺑﺎ ﻓﺸﺮﺩﻥ ﻛﻠﻴﺪ L.Tﭘﻨﺠﺮﻩ ﻫﺎ ﺑﻪ
ﺻﻮﺭﺕ ﭼﺸﻤﻚ ﺯﻥ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﻧﺪ ؛ ﺩﺭ ﺣﺎﻟﺖ OFFﭘﻨﺠﺮﻩ ﻫﺎ ﺑﻪ ﺻﻮﺭﺕ ﺛﺎﺑﺖ
) (Std.ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﻧﺪ.
10
AU
sERIES MABNA NIROO
ﭘﻨﻞ ﭘ ﺸ ﺖ ) ( Back Panel
ﻛﻠﻴﺪ ﻫﺎﻱ ﺗﻨﻈﻴﻢ)LOGIC ﭘﻨﻞ ﭘﺸﺖ ﺍﺯ ﺗﻐﺬﻳﻪ ﻛﻨﺘﺮﻟﻲ ﺩﺳﺘﮕﺎﻩ ،ﻛﺎﻧﻜﺘﻮﺭ ﻭﺭﻭﺩﻱ ﺧﻄﺎ ﻭ
(MIN, MAJ ,ﺗﺸﻜﻴﻞ ﺷﺪﻩ ﺍﺳﺖ .ﺩﺭ ﺻﻔﺤﺎﺕ ﺑﻌﺪ ﺟﺰﺋﻴﺎﺕ ﺍﻳﻦ ﭘﻨﻞ ﺑﻪ ﺗﻔﺼﻴﻞ ﺷﺮﺡ
ﺩﺍﺩﻩ ﺷﺪﻩ ﺍﺳﺖ .
Figure5 : Back Panel
11
AU
sERIES MABNA NIROO
ﺭﺍﻫﻨﻤﺎﻱ ﻛﺎﺭﻛﺮﺩ ﺍﺟﺰﺍﻱ : Back Panel U
: LOGICﻛﻨﺘﺎﻛﺖ ﻫﺎﻳﻲ ﻛﻪ ﺑﺎ ﮔﺬﺍﺷﺘﻦ ﻳﺎ ﺑﺮﺩﺍﺷﺘﻦ ﺟﺎﻣﭙﺮ ﺭﻭﻱ ﺁﻧﻬﺎ ﺑﻪ ﺗﺮﺗﻴﺐ on
ﻳﺎ offﻣﻲ ﺷﻮﻧﺪ ﻭ ﻫﺮ ﻳﻚ ﺍﺯ ﺍﻳﻦ ﻛﻨﺘﺎﻛﺖ ﻫﺎ ﺑﺎ ﻳﻚ ﻛﺎﻧﺎﻝ )ﭘﻨﺠﺮﻩ( ﺩﺳﺘﮕﺎﻩ ،ﻣﺘﻨﺎﻇﺮ
ﺍﺳﺖ .ﺩﺭ ﺣﺎﻟﺖ onﻛﻨﺘﺎﻛﺖ ﺑﺴﺘﻪ ﺍﺳﺖ ﻭ ﺩﺳﺘﮕﺎﻩ ﺩﺭ ﻣﻨﻄﻖ ﻣﺴﺘﻘﻴﻢ ﻳﺎ ﻧﺮﻣﺎﻝ ﻗﺮﺍﺭ
ﺩﺍﺭﺩ؛ ﺩﺭ ﺍﻳﻦ ﺻﻮﺭﺕ ﭘﻨﺠﺮﺓ ﻣﺘﻨﺎﻇﺮ ﺧﺎﻣﻮﺵ ﺍﺳﺖ ﻭ ﺑﻪ ﻣﺤﺾ ﺩﺭﻳﺎﻓﺖ ﻭﻟﺘﺎژ ﺧﻄﺎ
ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺷﺪ .ﺩﺭ ﺣﺎﻟﺖ ، offﻛﻨﺘﺎﻛﺖ ﺑﺎﺯ ﻣﻲ ﺑﺎﺷﺪ ﻭ ﺩﺳﺘﮕﺎﻩ ﺩﺭ ﻣﻨﻄﻖ ﻣﻌﻜﻮﺱ
ﻗﺮﺍﺭ ﻣﻲ ﮔﻴﺮﺩ ؛ ﺩﺭ ﺍﻳﻦ ﻣﻨﻄﻖ ﻫﺮ ﭘﻨﺠﺮﺓ ﻣﺘﻨﺎﻇﺮ ﺑﺎ ﻫﺮ ﭘﻴﻦ ،ﺑﻪ ﻣﺤﺾ ﺭﻭﺷﻦ ﻛﺮﺩﻥ
ﺩﺳﺘﮕﺎﻩ ،ﺑﺪﻭﻥ ﺩﺭﻳﺎﻓﺖ ﻭﻟﺘﺎژ ﺧﻄﺎ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ.
:MIN/MAJﺑﺴﺘﻪ ﺑﻪ ﻧﻴﺎﺯ ،ﺑﺎ ﻧﺼﺐ ﺟﺎﻣﭙﺮ ﺑﺮ ﺭﻭﻱ ﭘﻴﻦ ﻫﺎﻱ ﺍﻳﻦ ﻗﺴﻤﺖ ﺣﺎﻟﺖ
MINﺭﻭﻱ ﻛﺎﻧﺎﻝ ﻣﺘﻨﺎﻇﺮ ﺗﻌﺮﻳﻒ ﻣﻲ ﺷﻮﺩ ﻭ ﺑﺎ ﺑﺮﺩﺍﺷﺘﻦ ﺟﺎﻣﭙﺮ ﺣﺎﻟﺖ MAJﺑﺮ ﻛﺎﻧﺎﻝ
ﻣﺘﻨﺎﻇﺮ ﺗﻌﺮﻳﻒ ﺧﻮﺍﻫﺪ ﺷﺪ.
: X1ﻛﺎﻧﻜﺘﻮﺭ ﻭﺭﻭﺩﻱ ﺑﻪ ﻣﻨﻈﻮﺭ ﺩﺭﻳﺎﻓﺖ ﺧﻄﺎ ﺑﺎ ﺷﻤﺎﺭﻩ ﭘﻴﻦ ﻫﺎﻱ 1ﺗﺎ 20
ﺍﺳﺖ ﻛﻪ ﻣﺘﻨﺎﻇﺮ ﺑﺎ ﺗﻌﺪﺍﺩ ﭘﻨﺠﺮﻩ ﻫﺎﻱ ﺁﻻﺭﻡ ﻣﻲ ﺑﺎﺷﻨﺪ ..ﺩﺭ ﺍﻧﻮﺍﻉ 10ﭘﻨﺠﺮﻩ ﺍﺯ ﭘﻴﻦ
ﻫﺎﻱ 1ﺗﺎ ، 10ﺩﺭ ﺍﻧﻮﺍﻉ 12ﭘﻨﺠﺮﻩ ﺍﺯ 1ﺗﺎ ، 12ﺩﺭ ﺍﻧﻮﺍﻉ 16ﭘﻨﺠﺮﻩ ﺍﺯ 1ﺗﺎ 16ﻭ ﺩﺭ
ﺍﻧﻮﺍﻉ 20ﭘﻨﺠﺮﻩ ﺍﺯ ﭘﻴﻦ ﻫﺎﻱ 1ﺗﺎ 20ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ .
: X2ﻛﺎﻧﻜﺘﻮﺭ ﻭﺭﻭﺩﻱ -ﺧﺮﻭﺟﻲ ﺗﻐﺬﻳﻪ ﻭﻛﻨﺘﺮﻝ ﻛﻪ ﺩﺍﺭﺍﻱ 13ﭘﺎﻳﻪ ﺍﺳﺖ ؛ ﻋﻤﻠﻜﺮﺩ
ﻫﺮ ﻳﻚ ﺑﻪ ﺷﺮﺡ ﺯﻳﺮ ﻣﻲ ﺑﺎﺷﺪ :
: MINﭘﻴﻦ ﻫﺎی 1ﻭ ، 2ﺧﺮﻭﺟﻲ ﺩﻭ ﺳﺮ ﺭﻟﻪ ﻓﺮﻣﺎﻥ MINﻫﺴﺘﻨﺪ ﻛﻪ ﺟﻬﺖ
ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﺳﻴﺴﺘﻢ ﻫﺸﺪﺍﺭ ﺩﻫﻨﺪﻩ ﺧﺎﺭﺟﻲ ﻣﻮﺭﺩ ﺍﺳﺘﻔﺎﺩﻩ ﻗﺮﺍﺭ ﻣﻲ ﮔﻴﺮﺩ.
: A.Kﻭﺭﻭﺩﻱ ﻓﺮﻣﺎﻥ A.Kﻛﻪ ﺑﺼﻮﺭﺕ ﺧﺎﺭﺟﻲ ﺑﻪ ﺩﺳﺘﮕﺎﻩ ﺍﻋﻤﺎﻝ ﻣﻲ ﺷﻮﺩ .
) ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎژ ﻛﺎﺭ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﺑﺮ ﭼﺴﺐ ﺩﺳﺘﮕﺎﻩ ﻣﺸﺨﺺ ﻣﻲ ﺷﻮﺩ (.
12
AU
sERIES MABNA NIROO
: L.Tﻭﺭﻭﺩﻱ ﻓﺮﻣﺎﻥ L.Tﻛﻪ ﺑﻪ ﺻﻮﺭﺕ ﺧﺎﺭﺟﻲ ﺑﻪ ﺩﺳﺘﮕﺎﻩ ﺍﻋﻤﺎﻝ ﻣﻲ ﮔﺮﺩﺩ.
) ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎژ ﻛﺎﺭ ﺑﺎ ﺗﻮﺟﻪ ﺑﺮ ﭼﺴﺐ ﺩﺳﺘﮕﺎﻩ ﻣﺸﺨﺺ ﻣﻲ ﮔﺮﺩﺩ( .
: L.Rﻭﺭﻭﺩﻱ ﻓﺮﻣﺎﻥ L.Rﻛﻪ ﺑﺼﻮﺭﺕ ﺧﺎﺭﺟﻲ ﺑﻪ ﺩﺳﺘﮕﺎﻩ ﺍﻋﻤﺎﻝ ﻣﻲ ﮔﺮﺩﺩ.
)ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎژ ﻛﺎﺭ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﺑﺮ ﭼﺴﺐ ﺭﻭﻱ ﺟﻌﺒﺔ ﺩﺳﺘﮕﺎﻩ ﻣﺸﺨﺺ ﻣﻲ ﮔﺮﺩﺩ(.
ﺍﺯ L.R ، A.Kﻭ L.Tﺟﻬﺖ ﻛﻨﺘﺮﻝ ﻭ ﺍﻋﻤﺎﻝ ﺩﺳﺘﻮﺭﺍﺕ ﺍﺯ ﭘﻨﻞ ﺗﺎﺑﻠﻮ ﺟﻬﺖ ﻫﻢ ﺯﻣﺎﻧﻲ ﭼﻨﺪ ﺗﻮﺟﻪ :
ﺩﺳﺘﮕﺎﻩ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ .
: AUX SUPPLYﻭﺭﻭﺩﻱ ﺗﻐﺬﻳﻪ ﺩﺳﺘﮕﺎﻩ ﺍﺳﺖ ﻛﻪ ﺑﺴﺘﻪ ﺑﻪ ﻧﻮﻉ ﺁﻥ
، AC/DCﺩﺍﺭﺍﻱ ﭘﻼﺭﻳﺘﻪ ﻣﺮﺑﻮﻃﻪ ﻣﻲ ﺑﺎﺷﺪ .
: SYNﺟﻬﺖ ﺳﻨﻜﺮﻭﻥ ﻛﺮﺩﻥ ﺩﻭ ﻳﺎ ﭼﻨﺪ ﺩﺳﺘﮕﺎﻩ ﺑﺎ ﻳﻜﺪﻳﮕﺮ ﻣﻮﺭﺩ
ﺍﺳﺘﻔﺎﺩﻩ ﻗﺮﺍﺭ ﻣﻲ ﮔﻴﺮﺩ ) .ﺑﻪ ﺗﻮﺿﻴﺤﺎﺕ ﺻﻔﺤﻪ 16ﻣﺮﺍﺟﻌﻪ ﺷﻮﺩ (.
: SGﺧﺮﻭﺟﻲ ﺳﻴﮕﻨﺎﻝ ﭘﺎﻳﻪ ﺑﻪ ﺳﻄﺢ ﻭﻟﺘﺎژ (SYN) Clockﻣﻲ ﺑﺎﺷﺪ ﻛﻪ ﺑﺮﺍﻱ
ﺳﻨﻜﺮﻭﻥ ﻛﺮﺩﻥ ﺩﻭ ﻳﺎ ﭼﻨﺪ ﺩﺳﺘﮕﺎﻩ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ .
) ﺑﻪ ﺗﻮﺿﻴﺤﺎﺕ ﺻﻔﺤﻪ 16ﻣﺮﺍﺟﻌﻪ ﺷﻮﺩ (.
: MAJﭘﻴﻦ ﻫﺎﻱ 10ﻭ ، 11ﺧﺮﻭﺟﻲ ﺩﻭ ﺳﺮ ﺭﻟﻪ ﻓﺮﻣﺎﻥ MAJﻫﺴﺘﻨﺪ ﻛﻪ
ﺟﻬﺖ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﺳﻴﺴﺘﻢ ﻫﺸﺪﺍﺭ ﺩﻫﻨﺪﻩ ﺧﺎﺭﺟﻲ ﻣﻮﺭﺩ ﺍﺳﺘﻔﺎﺩﻩ ﻗﺮﺍﺭ ﻣﻲ ﮔﻴﺮﺩ.
: SFﭘﻴﻦ ﻫﺎﻱ 12ﻭ 13ﺭﻟﺔ ﺧﺮﻭﺟﻲ ﻧﺸﺎﻥ ﺩﻫﻨﺪﺓ ﻭﺿﻌﻴﺖ ﻣﻨﺒﻊ ﺗﻐﺬﻳﺔ ﺩﺳﺘﮕﺎﻩ
ﺍﺳﺖ ﺑﻪ ﻃﻮﺭﻱ ﻛﻪ ﺍﮔﺮ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ﺗﺤﺖ ﻫﺮ ﺷﺮﺍﻳﻄﻲ ﻗﻄﻊ ﺷﻮﺩ ،ﺳﻴﺴﺘﻢ ﻫﺸﺪﺍﺭ
ﺩﻫﻨﺪﺓ ﺩﺳﺘﮕﺎﻩ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ.
ﺍﺣﺘﻴﺎﻁ !
ﺍﺯ ﺍﺗﺼﺎﻝ ﭘﻴﻦ ﻫﺎﻱ SG ، SYﺑﻪ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ
ﺑﺎ ﻫﺮ ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎژﻱ ﺧﻮﺩﺩﺍﺭﻱ ﻧﻤﺎﻳﻴﺪ .
13
AU
sERIES MABNA NIROO
ﻧﻜﺎ ﺕ ﺿﺮﻭﺭ ﻱ
! ﭘﻴﺶ ﺍﺯ ﺍﺗﺼﺎﻝ ﺑﻪ ﻭﻟﺘﺎژ ﻭ ﺗﺴﺖ ﺩﺳﺘﮕﺎﻩ ،ﻛﻠﻴﺔ ﻣﻄﺎﻟﺐ ﻣﻮﺟﻮﺩ ﺩﺭ ﻛﺎﺗﺎﻟﻮگ ﺭﺍ ﺑﺎ
ﺩﻗﺖ ﻣﻄﺎﻟﻌﻪ ﻓﺮﻣﺎﻳﻴﺪ.
! ﺩﺭ ﺻﻮﺭﺕ ﻣﻮﺍﺟﻬﻪ ﺑﺎ ﺍﺷﻜﺎﻻﺕ ﺧﺎﺹ ﺩﺭ ﺩﺳﺘﮕﺎﻩ ،ﻟﻄﻔﺎ ﺩﺭ ﺍﺳﺮﻉ ﻭﻗﺖ ﻣﺮﺍﺗﺐ ﺭﺍ
ﺑﻪ ﻭﺍﺣﺪ ﺧﺪﻣﺎﺕ ﭘﺲ ﺍﺯ ﻓﺮﻭﺵ ﺷﺮﻛﺖ ﻣﺒﻨﺎ ﻧﻴﺮﻭ ﺍﻃﻼﻉ ﺩﻫﻴﺪ .
! ﺧﺪﺷﻪ ﺩﺭ ﭘﻠﻤﭗ ﺩﺳﺘﮕﺎﻩ ﻧﺎﺷﻲ ﺍﺯ ﺑﺎﺯ ﺷﺪﮔﻲ ﺟﻌﺒﻪ ،ﻫﺮ ﮔﻮﻧﻪ ﻣﺴﺌﻮﻟﻴﺖ ﺭﺍ ﺍﺯ ﺷﺮﻛﺖ
ﻧﺎﻡ ﺑﺮﺩﻩ ﺳﻠﺐ ﺧﻮﺍﻫﺪ ﻛﺮﺩ.
! ﻛﻠﻴﻪ ﻣﻮﺍﺭﺩ ﻣﺸﻤﻮﻝ ﮔﺎﺭﺍﻧﺘﻲ ﻭ ﺧﺪﻣﺎﺕ ﭘﺲ ﺍﺯ ﻓﺮﻭﺵ ﺩﺭ ﻛﺎﺭﺕ ﮔﺎﺭﺍﻧﺘﻲ ﻣﺤﺼﻮﻝ
ﺫﻛﺮ ﺷﺪﻩ ﺍﺳﺖ.
ﺭﻭ ﺵ ﻧ ﺼ ﺐ ﻭ ﺭﺍﻩ ﺍﻧ ﺪﺍﺯﻱ ﺩ ﺳﺘﮕﺎﻩ
ﺭﻭ ﺵ ﻧ ﺼ ﺐ
- 1ﺍﺑﻌﺎﺩ ﻣﺤﻠﻲ ﺭﺍ ﻛﻪ ﺩﺳﺘﮕﺎﻩ ﺩﺭ ﺁﻥ ﻧﺼﺐ ﻣﻲ ﺷﻮﺩ ،ﻣﻄﺎﺑﻖ ﺍﺑﻌﺎﺩ ﺫﻛﺮ ﺷﺪﻩ ﺩﺭ ﺷﻜﻞ
2ﺩﺭ ﻧﻈﺮ ﺑﮕﻴﺮﻳﺪ .
- 2ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﻛﻠﻤﭗ ﻫﺎﻱ ﻧﮕﻪ ﺩﺍﺭﻧﺪﻩ ﻣﻮﺟﻮﺩ ﺩﺭ ﺟﻌﺒﻪ ﻭ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﻣﺤﻞ ﻫﺎﻱ
ﺗﻌﺒﻴﻪ ﺷﺪﻩ ﺭﻭﻱ ﺑﺪﻧﺔ ﺩﺳﺘﮕﺎﻩ ،ﻧﺴﺒﺖ ﺑﻪ ﺗﺜﺒﻴﺖ ﺩﺳﺘﮕﺎﻩ ﺩﺭ ﻣﺤﻞ ﻣﻮﺭﺩ ﻧﻈﺮ ﺍﻗﺪﺍﻡ
ﻧﻤﺎﻳﻴﺪ.
)ﺍﻧﺪﺍﺯﻩ ﻫﺎ ﻱ ﺩﻗﻴﻖ ﺩﺳﺘﮕﺎﻩ ﺭﺍ ﺩﺭ ﺷﻜﻞ ﻫﺎﻱ 1ﻭ 2ﻣﺸﺎﻫﺪﻩ ﻧﻤﺎﻳﻴﺪ (.
14
AU
sERIES MABNA NIROO
ﻧ ﺤﻮﺓ ﻭﺍﻳ ﺮﻳﻨﮓ ﻭ ﺭﺍﻩ ﺍﻧ ﺪﺍﺯﻱ ﺩ ﺳﺘﮕﺎﻩ
ﻛﺎﻧﻜﺘﻮﺭ ﻫﺎﻱ ﻛﻤﻜﻲ ﻣﻮﺟﻮﺩ ﺩﺭ ﺟﻌﺒﺔ ﺩﺳﺘﮕﺎﻩ ﺭﺍ ﺩﺭ ﻣﻜﺎﻥ ﺗﻌﺒﻴﻪ ﺷﺪﻩ ﺭﻭﻱ ﭘﻨﻞ
ﭘﺸﺖ )) (X1 , X2ﺷﻜﻞ ( 5ﻗﺮﺍﺭ ﺩﻫﻴﺪ .
ﻣﺘﻨﺎﺳــــﺐ ﺑﺎ ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎژ ﻧﻮﺷﺘﻪ ﺷﺪﻩ ﺭﻭﻱ ﺩﺳﺘﮕﺎﻩ ،ﺁﻥ ﺭﺍ ﺭﻭﺷﻦ ﻛﻨﻴﺪ .ﺩﺭ ﺍﻳﻦ
ﺣﺎﻟﺖ ﻻﻣﭗ ONﺑﻪ ﻧﺸﺎﻧﺔ ﺑﺮﻗﺪﺍﺭ ﺑﻮﺩﻥ ﺩﺳﺘﮕﺎﻩ ﺭﻭﺷﻦ ﻣﻲ ﮔﺮﺩﺩ .
) ﺗﻮﺿﻴﺤﺎﺕ ﺷﻜﻞ . (5
ﭘﺲ ﺍﺯ ﺍﺗﺼﺎﻝ ﺑﻪ ﺗﻐﺬﻳﻪ ﻣﻨﺎﺳﺐ ﻳﻚ ﺑﺎﺭ ﻛﻠﻴﺪ A.Kﻭ ﺳﭙﺲ ﻛﻠﻴﺪ L.Rﺭﺍ ﻓﺸﺎﺭ
ﺩﻫﻴﺪ )ﺗﻮﺿﻴﺤﺎﺕ ﺷﻜﻞ . ( 5
ﺩﺭ ﺻﻮﺭﺕ ﺍﺗﺼﺎﻝ ﺳﺮﻳﺎﻝ ﺩﻭ ﻳﺎ ﭼﻨﺪ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻣﻨﻈﻮﺭ ﻫﻢ ﺯﻣﺎﻥ ﻛﺮﺩﻥ ﺁﻧﻬﺎ ،ﭘﻴﻦ
ﻫﺎﻱ SGﺩﺭ ﻫﻤﻪ ﺩﺳﺘﮕﺎﻩ ﻫﺎ ﺭﺍ ﺑﻪ ﺻﻮﺭﺕ ﺩﻭ ﺑﻪ ﺩﻭ ﻭ ﻣﺘﻮﺍﻟﻲ ﺑﻪ ﻫﻢ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ .
ﺍﻳﻦ ﻋﻤﻠﻴﺎﺕ ﺭﺍ ﺩﺭ ﻣﻮﺭﺩ ﭘﻴﻦ ﻫﺎﻱ SYNﻧﻴﺰ ﺑﻪ ﺻﻮﺭﺕ ﻣﺸﺎﺑﻪ ﺍﻧﺠﺎﻡ ﺩﻫﻴﺪ ؛
ﺗﺬﻛﺮ :ﺍﺯ ﺍﺗﺼﺎﻝ ﭘﻴﻦ ﻫﺎﻱ SG ، SYNﺑﻪ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ﺑﺎ ﻫﺮ ﻭﻟﺘﺎژﻱ ﺧﻮﺩﺩﺍﺭﻱ ﻧﻤﺎﻳﻴﺪ .
ﻛﻠﻴﺪ ﺩﻭﻡ ) (M/Sﺍﺯ Dip Switchﺗﻌﺒﻴﻪ ﺷﺪﻩ ﺭﻭﻱ ﺑﺮﺩ LEDﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ
ﺷﺪﻩ ﺩﺭ ﺷﻜﻞ 4ﺭﺍ ﺑﺠﺰ ﺩﺭ ﻳﻜﻲ ﺍﺯ ﺩﺳﺘﮕﺎﻩ ﻫﺎ ﺩﺭ ﺣﺎﻟﺖ offﻗﺮﺍﺭ ﺩﻫﻴﺪ .ﺑﻨﺎﺑﺮﺍﻳﻦ
ﺩﺳﺘﮕﺎﻫﻲ ﻛﻪ ﺩﺭ ﺁﻥ ﻛﻠﻴﺪ M/Sﺩﺭ ﺣﺎﻟﺖ onﻗﺮﺍﺭ ﺩﺍﺭﺩ ﺩﺳﺘﮕﺎﻩ Masterﻭ ﺑﻘﻴﻪ
ﺩﺳﺘﮕﺎﻩ ﻫﺎ Slaveﻣﻲ ﺷﻮﻧﺪ .
ﺟﻬﺖ ﺍﻋﻤﺎﻝ ﻭﻟﺘﺎژ ﺧﻄﺎ ﺑﻪ ﺩﺳﺘﮕﺎﻩ ﻓﻘﻂ ﺍﺯ ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎژ ﺫﻛﺮ ﺷﺪﻩ ﺭﻭﻱ ﺑﺪﻧﺔ
ﺩﺳﺘﮕﺎﻩ ،ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﺪ .
15
AU
sERIES MABNA NIROO
ﺟ ﺪﻭﻝ ﻣ ﺸ ﺨ ﺼﺎ ﺕ ﻓﻨﻲ
Table 2: Technical Properties
16
AU
sERIES MABNA NIROO
ﺗﻤﺎ ﺱ ﺑﺎ ﻣﺎ p
ﺧﻴﺎﺑﺎﻥ ﻣﺨﺒﺮﻱ، ﺧﻴﺎﺑﺎﻥ ﺳﺮﺩﺍﺭ ﺟﻨﮕﻞ، ﺑﺰﺭﮔﺮﺍﻩ ﺷﻬﻴﺪ ﻫﻤﺖ، ﺗﻬﺮﺍﻥ : ﺁﺩﺭﺱ
. ﺷﺮﻛﺖ ﻣﺒﻨﺎ ﻧﻴﺮﻭ،111 ﭘﻼﻙ، ﻏﺮﺑﻲ
44441710 , 44444438 : ﺗﻠﻔﻦ
44419448 : ﻓﻜﺲ
Website Address : http://www.MabnaNiroo.com
U U
E-Mail Address : U Mohsen_Khalaj@yahoo.com U