User Manual: Screw Air Compressor Controller
User Manual: Screw Air Compressor Controller
MODLE: MAM-860
USER
MANUAL
Shenzhen Plot Electronic Co., Ltd specializes on the manufacture and R&D of air
compressor controller. We are devoted to win customer trust through our high quality
We try our best to ensure the completeness and correctness of the manual, but
PLOT Company shall reserve the rights for continuous research and improvement on
its products and assume no obligation for the modification and improvement on the
without notice.
Please feel free to contact our after-sale service center if you encounter any
     Please read all the operation manual before operating the set and keep this manual for further
     reference.
     Installation position shall be considered carefully in order to ensure good ventilation and reduce
     electromagnetic interference.
     Wiring shall be performed respectively according to regulations for heavy and weak current to reduce
     electromagnetic interference.
      RC snubber must be connected to the two terminals of coil (such as AC contactor ,valve, etc),which
      are controlled by relay output.
      Correct ground connection (the third ground)can help increase product capacity of resisting signal
      interference.
Features:
 ●    Chinese / English display.
 ●    Remote control/Local control.
 ●    Block mode/Independent mode.
 ●    On-off control of motor.
 ●    Prevention for air compressor reversion.
 ●    Temperature measurement, control and protection.
 ●    Voltage measurement and protection.
 ●    RS485 communication function, supporting MODBUS RTU protocol.
 ●    Protection for open phase, overload current, unbalance current, high voltage, low voltage.
 ●    High integration, high reliability, high cost performance.
                                                                                                     -1-
                                                                       Contents
1, Basic Operation .................................................................................................................................................- 3 -
      1, Button Explanation ....................................................................................................................................- 3 -
      2, Indicator Instruction...................................................................................................................................- 4 -
      3, Status Display and Operation ....................................................................................................................- 4 -
      4, Operating Parameter and Menu .................................................................................................................- 4 -
      5, User Parameter View and Modification:....................................................................................................- 5 -
      6,User Parameter Sheet and Function............................................................................................................- 6 -
      7, Factory Parameter View and Modification ................................................................................................- 8 -
      8, Factory Parameter Sheet and Function ......................................................................................................- 9 -
      9, Calibration Parameter ..............................................................................................................................- 10 -
      10, Operating Authorization and Password .................................................................................................- 11 -
2, Controller Function and Technical Parameter .................................................................................................- 12 -
3, Model and Specification ..................................................................................................................................- 13 -
      1, Model Description ...................................................................................................................................- 13 -
      2, Power consumption Table for Corresponding Motor...............................................................................- 13 -
4, Installation .......................................................................................................................................................- 14 -
      1, Mechanical Installation............................................................................................................................- 14 -
      2,Electrical Wiring Installation....................................................................................................................- 16 -
5, Control Process................................................................................................................................................- 17 -
      1, Single Machine ........................................................................................................................................- 17 -
      2, Net Work..................................................................................................................................................- 18 -
      3, Fan Operation ..........................................................................................................................................- 18 -
6, Alarm Function ................................................................................................................................................- 18 -
      1, Air Filter Alarm .......................................................................................................................................- 18 -
      2, Oil Filter Alarm .......................................................................................................................................- 18 -
      3, O/A separator Alarm................................................................................................................................- 18 -
      4、Lubricating Oil Alarm............................................................................................................................- 18 -
      5, Grease Alarm ...........................................................................................................................................- 18 -
      6, Belt Alarm................................................................................................................................................- 18 -
      7, High Discharge Air Temperature Alarm ..................................................................................................- 18 -
7, Controller Protection .......................................................................................................................................- 19 -
      1, Motor Protection......................................................................................................................................- 19 -
      2, Protection of High Discharge Air Temperature .......................................................................................- 19 -
      3, Protection of Air Compressor Non-reversing ..........................................................................................- 19 -
      4, Protection of High Pressure .....................................................................................................................- 19 -
      5, Protection of Sensor Failure ....................................................................................................................- 19 -
8, Troubleshooting ...............................................................................................................................................- 19 -
      1, This Fault Review....................................................................................................................................- 19 -
      2, Common Failures and Causes..................................................................................................................- 20 -
9, Block mode control and net work....................................................................................................................- 21 -
      1, Block mode control..................................................................................................................................- 21 -
      2. Net Work..................................................................................................................................................- 23 -
10. Schematic Diagram........................................................................................................................................- 24 -
                                                                                                                                                                       -2-
1, Basic Operation
1, Button Explanation
                                            Figure 1.1.1
        ——Start Button:
         1, When compressor is at stop status, press this button to start the compressor.
         2, When compressor is set as master (No.1) in block mode, press this button to start the
         compressor and activate block mode function at the same time.
        ——Stop Button:
         1, When the compressor is at running status, press this button to stop the compressor;
         2, When compressor is set as master (No.1) in block mode, press this button to stop
         compressor and block mode function as well;
         3, When compressor is at stop status, long press this button to display software edition.
2, Indicator Instruction
 Power Indicator:Indicator on when controller is energized.
 Operation indicator:Indicator is on when motor is running.
 Error indicator:Indicator is blinking when alarming; indicator on when fail to stop; indicator off when error
                  is cleared
WELCOME USING
       AIR T:78℃
       AIR P:0.60MPA                                    Main menu
       NORMAL STOP 0S
       C16      REMOTE
       RUN PARA.
       USER PARA.                                       Level 1 menu
       FACTORY PARA.
       CALBR PARA.
                                                                                                          -4-
       HISTORY FAULT
       PRODUCTION DATE、NUM.
       THIS FAULT
       COM STATUS
       Move the cursor to the corresponding menu item, press “          ” to check the specific
     parameter. Such as viewing "MOTER FAN CUR ", move the cursor to the “MOTER FAN
     CUR " menu item, press the “    ”, switch to the item of motor , fan data .
      Press the “      ” to return to the previous menu or the main menu. If no operation at the
     current menu for 120 Seconds, controller will automatically return to the main menu and
     turn off the backlight simultaneously.
          P、T SET
          SET TIME
          OPERATION MODE
          BLOCKING MODE
     Move the cursor to the "P、T SET " item, then press “      ” to switch to the following menu:
          LOAD P:00.62 MPa
          UNLOAD P:00.78MPa
          FAN START T:0080℃
          FAN STOP T:0075℃
       Move the cursor to the “LOAD P” item, then press “          ” to switch to the following
     menu which requires a user password input.
                                                                                             -5-
                   INPUT CODE
                      ****
          In the menu above, press “       ”, the first data of loading pressure starts to blink, user
     can press “      ” or “      ” to modify the present data in accordance with the above
     method .Press “        ” to move to next data bit and modify to the target data in sequence.
     When finished, press “       ” to confirm and save the data. The controller prompt sends out
     a short voice to tip the completion of parameter set.
                                                                                                       -6-
              LOAD                        Unloading in this set time after enter delta
                           0002S
              DELAY                       running
                                          When unloading continuously, compressor will
              UNLOAD
                           0600S          automatically stop and enter to standby status if
              DELAY
                                          over this set time
                                          For NORMAL STOP operation, compressor will
              STOP DELAY   0010S          stop after it continuously unloading over this set
                                          time
                                          Machine can be restarted only over this set time
              START
                           0100S          at any case(after NORMAL STOP, STANDBY or
              DELAY
                                          FAILURE STOP )
              ON/OFF
                           LOCAL/REMOTE   c
              MODE
                                          1,When set as the MANU: only when the
                                          pressure is above “unloading pressure”,
                                          compressor will unload automatically .For any
                                          other case, the Loading/Unloading function can
              LOAD
                           AUTO/MANU      only be executed by pressing “loading
              MODE
                                          /unloading ” key.
                                          2,When set as AUTO ,the loading/ unloading
OPERATION                                 function can be executed by the fluctuation of air
MODE                                      pressure automatically
PRESET                                    1,When set as PROHIBIT, the communication
                                          function is invalid.
                                          2,When set as COMP. ,compressor function as a
                            PROHIBIT
              COM MODE                    slave and is able to communicate with computer
                           /COMP./BLOCK
                                          or DCS
                                          3,When set as BLOCK, compressor can net
                                          control
                                          Set the communication ADD in block mode or
              COM
                           0001           when communicate with monitoring center. This
              ADDRESS
                                          ADD is unique for every controller in net
                                          1,When service as master in BLOCK. Master
                                          controls slave, the COM ADDRESS should be
              BLOCK
                           MASTER/SLAVE   No.1
              MODE
                                          2,When service as slave in BLOCK, slave is
                                          controlled by master
                                          When master pressure is between BLOCK LOAD
              TURN TIME    0099 Hours     P and BLOCK UNLOAD P, master determine
BLOCKING                                  slave work alternatively over this set time .
MODE
              BLK NUMER    0000           Number of air compressors in block net
SETTING
                                          In BLOCK, one compressor will start or load
              BLK MIN      00.65MPa
                                          when pressure is below this set data
                                          In BLOCK mode, one compressor will stop or
              BLK MAX      00.75MPa
                                          unload when pressure is above this set data
                                          In BLOCK mode, when master sends two
              BLK DELAY    0050S          commands continuously, second command signal
                                          delays for this set data.
                           0000H          Record total running time of oil filter, if changing
CLR    LIFE
              OIL FILTER                  new oil filter, the data should be reset by manual
TIME
                                          operation.
                           0000H          Record total running time of O/A separator. If
              O/A
                                          changing new O/A separator, the data should be
              SEPARATOR
                                          reset by manual operation
                           0000H          Record total running time of air filter .If changing
              AIR FILTER                  new air filter, the data should be reset by manual
                                          operation
                                                                                          -7-
                                     0000H                   Record total running time of lube. If changing
                   LUBE                                      lubricate ,the data should be reset by manual
                                                             operation
                                     0000H                   Record total running time of grease. If changing
                   GREASE                                    new grease, the data should be reset by manual
                                                             operation
                                     0000H                   Record total running time of belt. If changing
                   BELT                                      new belt, the data should be reset by manual
                                                             operation
                                     9999H                   1,Alarm prompts when total running time of oil
                                                             filter is above the set data.
                   OIL FILTER
                                                             2,Set this data to “0” to clear oil filter running
                                                             time
                                     9999H                   1,Alarm prompts when total running time of O/A
                   O/A                                       separator is above the set data.
                   SEPARATOR                                 2,Set this data to “0” to clear O/A separator
                                                             running time
                                     9999H                   1,Alarm prompts when total running time of air
                                                             filter is above the set data.
                   AIR FILTER
                                                             2,Set this data to “0” to clear air filter running
MAX     LIFE                                                 time
TIME PRESET                          9999H                   1,Alarm prompts when total running time of
                                                             lubricate is above the set data.
                   LUB
                                                             2, Set this data to “0” to clear lubricate running
                                                             time.
                                     9999H                   1,Alarm prompts when total running time of
                                                             grease is above the set data.
                   GREASE
                                                             2,Set this data to “0” to clear grease running
                                                             time
                                     9999H                   1,Alarm prompts when total running time of belt
                                                             is above the set data.
                   BELT
                                                             2,Set this data to “0” to clear belt running
                                                             time .
                                                             1,Set to “EN” , Display in English
LANG.SEL           EN/CH             EN
                                                             2,Set to “CH” , Display in Chinese
NEW       USER ****                                          User could modify the user password by old user
                                     ****
PIN                                                          password or factory password
           INPUT CODE
              ****
Input the correct password to switch to the FACTORY PARAMETER menu as below:
   MOTOR CUR:100.0A
   FAN CUR:010.0A                                                                                          -8-
   ALARM T:0105℃
   STOP T:0110℃
     STOP P:00.90MPa
     MAX U.L.:00.85MPa
     RUN TIME:001234H
     LOAD TIME:001001H
    For more factory parameter, please check factory parameter sheet. When modify factory parameter, please
refer to customer parameter modification method, supper-password is required to set TOTAL RUN
TIME,PHASE PROT,POWER FREQ and MAX RUN TIME.
9, Calibration Parameter
    You can set relative data of controller in CALBR PARA. It is not allowed to view and modify without
   manufacturers authorization, so please verify the password before view and modification. The modification
   of CALBR PARA is similar with CUSTOMER PARA. Main function is shown as below.
    PARAMETER                  Initial Data   Function
                                              1,When calibrate the current of motor A, revise
                                              standard current data, controller calibrate the current by
                 TARGET                       figuring the current coefficient and save the data
                               0000
                 CUR                          automatically
     MOTOR
                                              2,Standard current data will return to zero after
        A                                     calibration
                                              When calibrate the current, revise coefficient. Current
                 COEF          1.000
                                              data in display=sample data*coefficient
                 CUR           ***.*A         This data is qret
                                              1,When calibrate the current of motor B, revise standard
                                              current data, controller calibrate the current by figuring
                 TARGET
                 CUR
                               0000           the current coefficient and save the data automatically
     MOTOR
                                              2,Standard current data will return to zero after
        B                                     calibration
                                              When calibrate the current, revise coefficient. Current
                 COEF          1.000
                                              data in display=sample data*coefficient
                 CUR           ***.*A         this data is qret
                                              1,When calibrate the current of motor C, revise standard
                                              current data, controller calibrate the current by figuring
                 TARGET
                 CUR
                               0000           the current coefficient and save the data automatically
     MOTOR
                                              2,Standard current data will return to zero after
        C                                     calibration
                                              When calibrate the current, revise coefficient. Current
                 COEF          1.000
                                              data in display=sample data*coefficient
                 CUR           ***.*A         this data is qret
       FAN
                 TARGET        0000           1,When calibrate the current of fan A, revise standard
        A
                 CUR                          current data, controller calibrate the current by figuring
                                                                                                    - 10 -
                                              the current coefficient and save the data automatically
                                            2,Standard current data will return to zero after
                                            calibration
                                            When calibrate the current, revise coefficient. Current
                 COEF         1.000
                                            data in display=sample data*coefficient
                 CUR          ***.*A        this data is qret
                                            1,When calibrate the current of fan B ,revise standard
                                            current data, controller calibrate the current by figuring
                 TARGET
                 CUR
                              0000          the current coefficient and save the data automatically
         FAN
                                            2,Standard current data will return to zero after
          B                                 calibration
                                            When calibrate the current, revise coefficient. Current
                 COEF         1.000
                                            data in display=sample data*coefficient
                 CUR          ***.*A        this data is qret
                                            1,When calibrate the current of fan C ,revise standard
                                            current data, controller calibrate the current by figuring
                 TARGET
                 CUR
                              0000          the current coefficient and save the data automatically
         FAN
                                            2,Standard current data will return to zero after
          C                                 calibration
                                            When calibrate the current, revise coefficient. Current
                 COEF         1.000
                                             data in display=sample data*coefficient
                 CUR          ***.*A        this data is qret
                                                                                                  - 11 -
2, Controller Function and Technical Parameter
 1, Digital input&output: 3 points of digital input ;5 points of digital relay output ;
 2, Analog input: 1 point of Pt100 temperature input ; 1 point of 4~20mA pressure signal input; two groups of
     three phases current inputs(CT provided);
 3, Input voltage of phases:380V/220V;
 4, Compressor protection of high operation voltage and low operation voltage
 5, Controller power supply: AC16-28V、50/60HZ、0.3A、5VA(recommend 10VA)
 6, Measurement:
     ①、Discharge air temperature:-50~150℃;Accuracy:±1℃.
     ②、Operation time: 0~999999 hours.
     ③、Current:0~999.9A.
     ④、Pressure: 0~1.60MPa. Accuracy: ±0.01Mpa.
 7,Phase sequence protection: When compressor is at stop mode and detects wrong phase sequence, respond
 time≤1s (optional);
 8, Open phase protection: When compressor is at stop mode and detects open phase ,respond time≤1s
 9, Motor protection: This controller has the following basic protection function for main motor and overload
    protection for fan.
     ①、Open phase protection:When any phase opens, the respond time equals to set time, when phase open
          time is set above 20s,open phase protection is invalid;
    ②、Unbalance protection: when MAX-MIN >= SET*MIN/10 ,respond time is 5s;
    ③、Protection features of overload (time unit: second),please see following table(table 2.1.1),multiple
=Iactual/Iset ,motor operates with delay time according to overload multiples and operation time
         shown in following table (table 2.1.1) when motor working current is higher or equal to the set current
         from 1.2 times and 3.0 times .
               Iactual/Iset
                                ≥1.2       ≥1.3         ≥1.5        ≥1.6         ≥2.0        ≥3.0
         Time parameter
Response time(S) 60 48 24 8 5 1
 10, Temperature protection: when actual temperature measured is higher than temperature set; response
      time≤2s;
 11, Contact capacity of output relay: 250V,5A;Contact endurance : 500000 times
 12, Current error is less than 1.0%.;
 13, RS485 communication function
     1, Block mode control
     2, Communicate with-external devices as slave through MODBUS RTU, baud rate 9600BPS,1start bit,8
   data bits,1 stop bit and even parity
 14, Remote control compressor: When set as remote control mode, user can remotely control the compressor.
                                                                                                           - 12 -
3, Model and Specification
1, Model Description
                                                          860 controller
                                                          Series
                                                                                                          - 13 -
4, Installation
   1, Mechanical Installation
    ① Current transformer installation
         The CT shall be installed at a place where the current of motor cable can be measured, thus controller
    can be set according to instructions on motor nameplate, the detailed dimensions is shown as below:
Figure 4.1.1. Structure dimensions of CT1(ф36 through hole) Figure 4.1.2. Installation dimensions of CT1
          A
                  B
Figure 4.1.3. Structure dimensions of CT2 (ф10 through hole) Figure 4.1.4. Installation dimensions of CT2
                                                                                                          - 14 -
② Controller installation
  A certain room should be left around controller for wiring. The specific dimension is shown as below:
                                                                                                      - 15 -
     2, Electrical Wiring Installation
、 △
21 20 19 11 12 13 14 15 16 17 18
                                                                                                     22 23 24 25 26 27 28 29 30 31
                  C1
                           10 9 8 7 6 5 4 3 2 1
                                                  uc ub ua
                                                                                                                                     a
                                                                                                                                     b   CT2
                                                                                                                                     c
                 A                                                                                                                   A
          RS-485                                                                                                                     B   CT1
                 B
            FG
                                                                                                                                     C
                                                                                                                                               - 16 -
5, Control Process
1, Single Machine
 3, Fan Operation
     When discharge air temperature is higher than FAN START T, fan operates; when discharge air
   temperature is lower than FAN STOP T, fan stops.
6, Alarm Function
 5, Grease Alarm
     The text displays GREASE LIFE END when running time of the grease exhausts.
 6, Belt Alarm
     The text displays BELT LIFE END when running time of the belt exhausts.
                                                                                                   - 18 -
7, Controller Protection
 1, Motor Protection
      MAM-860 air compressor controller provides overload, open phase, current unbalance, high voltage, low
  voltage protection for motor and overload protection for fan
    Electronic
                   Failure Display                             Reason
    failure
                                                               Overload, bearing wear and other mechanical
    Overload       Display “MOTOR/FAN OVER LOAD”
                                                               failure
                                                               Power supply, contactor and open phase of
    Open phase Display “MOTOR OPEN PHASE”
                                                               motor
                                                               Poor contact of contactor, inside open-loop of
    Unbalance      Display “MOTOR-UNBLANCE”
                                                               motor
    High
                   Display “HIGH VOLTAGE”                      High supply voltage
    voltage
    Low
                   Display “LOW VOLTAGE”                       Low supply voltage
    voltage
8, Troubleshooting
            HISTORY FAULT
            PROD DATE NO.
            THIS FAULT
            COM STATUS.
        Move cursor to THIS FAULT press “            ” to switch to the following menu:
                                                                                                               - 20 -
 9, Block mode control and net work
 1, Block mode control
    ① Block control explanation
   MAM860 controller can block operate with MAM series compressor (with communication function).16 pcs
  compressors are allowed in the net at most. The cable connection for block mode control is as below....
............
A B A B A B A B A B
 一号机
 Master                 二号机
                        Slave                     Slave                   Slave                      Slave
 No.1                   No. 2                     No. 3                   No. 4                      No. N
                                                 Picture 9.1.1
    Compressor with net communication address 0001 is master, others are slave. Any one MAM series
    compressor can be set as master or slave.
② Block mode setting
    1. Set as master:
    In main menu, press “     ” to enter select menu and choose USER PARAMETER, press “ ” and switch
 to the menu below:
        SET P,T.
        SET TIME
        OPERATION MODE
        BLOCKING MODE
Move the cursor to OPERATION MODE, press “ ” to switch to the menu below.
         ON/OFF MODE:REM
         LOAD MODE :AUTO
         COM MODE :BLOCK
         COM ADD :0001
   Set COM MODE as BLOCK,COM ADD as “0001”,return to the previous menu ,move the-cursor to
 BLOCKING MODE press “  ” to switch to the menu below
                                                                                                         - 21 -
          BLK STATE:MASTER
          ALTER TIME:0002H
          BLK NUMER.:0004
          BLK MIN:00.62MPa
          BLK MAX:00.78MPa
          BLK DELAY:0020s
   According to user requirement, set BLK STATE as MASTER, set ALTER TIME, BLK NUMER,BLK
  MIN,BLK MAX,BLK DELAY according to user’s need .After-setting ,controller-needs to be powered off and
  restarts to the setting.
2, Set as slave:
    When MAM controller serves as slave ,it is only necessary to set COM MODE as BLOCK mode, set COM
   ADD from2-16 with sequence according to the quantity of compressors, .BLK STATE set as SLAVE.
1, Start, stop block control:
   Make sure block cables connect correctly and the parameter of compressors in net set correctly. Activate master,
 master controls the compressors in net automatically according to the air pressure detected . Block control stops
 at the same time when manually stop the master so master will no longer send command to compressor in net .
        RX:—
        TX:—
     When controller receives data, RX “— ”and“*”display alternately, When sends data, TX:“— ”and“*”display
  alternately. When controller is in block control or communicates with monitoring center ,user can confirm the
     establishment of communication through this menu.
                                                                                                              - 22 -
2.Net Work
MAM860 controller supports MODBUS RTU protocol and can serve as slave when connect with other equipment
and supports 03、06、16 MODBUS command. Communication baud rate: 9600BPS, 1 start bit, 8 data bits, 1 stop
bits and even parity. For MODBUS register address, please see MODBUS communication manual.
                                                                                                   - 23 -
10.Schematic Diagram
21 20 19 11 12 13 14 15 16 17 18
                                                                                              22 23 24 25 26 27 28 29 30 31
                             C1                                                                                                   Disc T
                                    10 9 8 7 6 5 4 3 2 1
                                                           uc ub ua
                                                                                                                              a
                                                                                                                              b
                                                                                                                              c
                                A                                                                                             A
                       RS-485                                                                                                 B
                                B
                        FG
                                                                                                                              C
                                                                                                                                  AIr P